1 1A79-2
Direct Immersion
WHITE-RODGERS
INST ALLA TION INSTRUCTIONS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
Hot Water Control
DESCRIPTION
This control is designed for use on hot water heating
systems.
It has a coiled element that is immersed directly into the
boiler water. This feature gives an unusual speed of
response to rapid changes of water temperature thereby
preventing thermal lag.
THIS CONTROL MUST BE INSTALLED BY A QUALIFIED INSTALLER.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical
codes and ordinances.
This control is a precision instrument, and should be
handled carefully. Rough handling or distorting components could cause the control to malfunction.
This control has been accurately calibrated at the factory.
Any attempt to calibrate this control will void the WhiteRodgers warranty.
CAUTION
!
To prevent electrical shock and/or equipment
damage, disconnect electric power to system at
main fuse or circuit breaker box until installation
is complete.
This control has single-pole, double-throw switch action,
offering terminals that have open-on-rise switch action as
well as close-on-rise switch action. It may be used as a
high limit control, low limit control, circulator control, or as
a combination low limit and circulator control.
PRECAUTIONS
Shut off main gas to heating system until installation is complete.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper
and dangerous operation.
Following installation or replacement, follow appliance manufacturer's recommended installation and/or service instructions to insure proper
operation.
Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could
cause shock or fire hazard.
If the boiler manufacturer recommends a control location,
follow such recommendations. If none is offered, the
following information gives suggested locations.
For high limit service, the control should be located in
the hottest part of the boiler. This is usually at the top of the
boiler. A high limit control should not be located in the
section of the boiler that contains the heat exchanger that
supplies domestic hot water.
For low limit or operating service, the control should be
located so that it responds to the temperature of the
section of the boiler that heats domestic hot water.
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS ROAD
ST. LOUIS, MISSOURI 63123-5398
R
When used as a circulator control, it may be located
near the boiler outlet or riser.
When used as a combination low limit and circulator
control, it should be located the same as suggested for
low limit service.
When tightening the control into the boiler, care should be
taken to apply all leverage to the hexagonal nut only to
avoid damage to the diaphragm or control mechanism.
Printed in U.S.A.
INSTALLATION
PART NO. 37-1022B
Replaces 37-1022-A
9520
NOTE
All wiring should be done according to local and
national electrical codes.
WHITE
4
3
BLUE
Open on rise
of temperature
Close on rise
of temperature
High
Limit
Ignition
Transformer
Burner
Motor
Common
RED
If the boiler or burner manufacturer recommends a wiring
diagram, then follow such recommendations. If none are
offered, the instruction sheet for the primary control (gas
valve or oil burner control) may offer some suggested
circuits.
Line Voltage
Oil Burner Control
1
T
2
T
The low limit side of the low limit/circulator control maintains domestic hot water temperature all year around.
When the room thermostat calls for heat, the burner and
This control has a single-pole, double-throw snap action
switch. The top left-hand terminal (red) is the common
terminal. The top right-hand terminal (blue) has open-onrise switch action. The bottom center terminal (white) has
close-on-rise switch action.
Limit Control: When used as either a high limit control or
a low limit control, use the open-on-rise terminals (red and
blue).
Circulator Control: When used as a circulator control,
use the close-on-rise terminals (red and white).
Combination Low Limit and Circulator Control: For
this application, all three terminals are used.
The following wiring diagram shows a typical circuit for an
oil-fired system with domestic hot water without storage
tank.
Combination
Low Limit-
Circulator
Control
R
B
W
Circulator
Thermostat
B
W
4
1
3
2
Relay
Type
809A-189
Hot
120V
Neutral
circulator operate. If boiler water temperature drops too
low, the circulator will stop until the temperature rises in
boiler.
SETTING THE CONTROL
1. Use a screwdriver in the adjusting slot (A) on the front
of the control to turn the dial so the fixed indicator (B)
points to the lowest temperature of the cycle.
2. Turn the differential adjusting screw (C) until the
movable indicator (D) points to the highest temperature of the cycle.
“B” Fixed indicator
“F” Stop tab
“A” Adjusting
slot
The movable indicator points to the temperature at which
the contacts open on high limit and low limit applica-
tions. On circulator applications, the movable indicator
points to the temperature at which the circulator will start.
On combination low limit and circulator applications,
the movable indicator points to the temperature at which
the low limit will stop the burner and permit the circulator
to run.
(cut-in point)
“C” Differential adjusting
screw
“D” Movable indicator
(cut-out point)
“E” Stop screw
CONTROLS WITH ADJUSTABLE STOPS
1. Loosen stop screw (E) with enclosed wrench.
2. Set dial to original equipment manufacturer's specification.
3. Without moving the dial, move stop tab (F) against
indicator.
4. Re-tighten stop screw (E).
Setting stop higher than control being replaced
could cause personal injury and/or property damage.
2