Whirlpool WFM18, WFD18 Installation Instructions

80% SINGLE-STAGE MULTISPEED GAS FURNACE
INSTALLATION INSTRUCTIONS
Table of Contents
GAS FURNACE SAFETY................................................................2
INSTALLATION REQUIREMENTS................................................4
Tools and Parts ............................................................................4
Electrostatic Discharge (ESD)......................................................4
Location Requirements................................................................4
Ductwork Requirements ..............................................................8
Electrical Requirements ...............................................................8
Gas Supply Requirements...........................................................9
Venting Requirements..................................................................9
INSTALLATION INSTRUCTIONS................................................10
Inspect Shipment.......................................................................10
Plan Vent System.......................................................................10
Install Ductwork..........................................................................14
Filter Specifications....................................................................15
Make Electrical Connections .....................................................16
115-Volt Line Connection of Accessories—
Electronic Air Cleaner.................................................................18
Make Gas Connections..............................................................18
Start-Up Procedure and Adjustment.........................................22
Complete Installation..................................................................26
Furnace Shutdown.....................................................................26
SEQUENCE OF OPERATION ......................................................27
Power Up....................................................................................27
Heating Mode—Mode DIP Switch Set to 1 STG Position.........27
Heating Mode—Mode DIP Switch Set to 2 STG Position.........27
Cooling Mode.............................................................................27
Fan Only Mode...........................................................................27
OPERATIONAL CHECKS.............................................................28
Burner Flame ..............................................................................28
Auxiliary Limit Control ................................................................28
Circulator Blower Speed ............................................................28
MAINTENANCE ............................................................................31
Annual Inspection.......................................................................31
Filters ..........................................................................................31
TROUBLESHOOTING ..................................................................32
Resetting from Lockout..............................................................34
ASSISTANCE OR SERVICE.........................................................36
Accessories ................................................................................36
ATTENTION INSTALLATION PERSONNEL
As a professional installer, you have an obligation to know the product better than the customer. This includes all safety precautions and related items. Prior to actual installation, thoroughly familiarize yourself with this instruction manual. Pay special attention to all safety warnings. Often during installation or repair, it is possible to place yourself in a position which is more hazardous than when the unit is in operations.
Remember, it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use. Safety is a matter of common sense...a matter of thinking before acting. Most dealers have a list of specific good safety practices...follow them.
The precautions listed in this installation manual are intended as supplemental to existing practices. However, if there is a direct conflict between existing practices and the content of this manual, the precautions listed here take precedence.
Placeholder
Whirlpool® Model WFM18, WFD18
WPIO-359B
Whirlpool® Home Cooling and Heating
14610 Breakers Drive
Jacksonville, Florida 32258
GAS FURNACE SAFETY
Recognize this symbol as a safety precaution.
Please adhere to the following warnings and cautions when installing, adjusting, altering, servicing or operating the furnace.
WARNING
Hazards or unsafe practices could result in property damage, product damage, severe personal injury or death.
Goodman 1
CAUTION
Hazards or unsafe practices may result in property damage, product damage, personal injury or death.
IMPORTANT SAFETY INSTRUCTIONS
Use only with type of gas approved for this furnace.
Refer to the furnace rating plate. Install this furnace only in a location and position
as specified in the “Location Requirements” section of these instructions.
Provide adequate combustion and ventilation air to
the furnace space as specified in the “Venting Requirements” section of these instructions.
Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the “Venting Requirements” section of these instructions.
Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the “Make Gas Connections” section of these instructions.
Adequate clearance must be provided around the
vent-air intake terminals.
ANSI Box Install G 2009 in Goodman Folder
CAUTION
Hazards or unsafe practices may result in property or product damage.
Always install furnace to operate within the furnace’s
intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in the “Complete Installation” section of these instructions. See furnace rating plate.
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
A gas-fired furnace for installation in a residential
garage must be installed as specified in the “Location Requirements” section of these instructions.
The furnace shall be installed so the electrical
components are protected from water.
Furnaces for indoor installation on combustible flooring shall not be installed directly on carpeting, tile or other combustible material other than wood flooring.
Goodman 9
SAVE THESE INSTRUCTIONS
To the Installer
Before installing this unit, please read this manual thoroughly to familiarize yourself with specific items which must be adhered to, including but not limited to: unit maximum external static pressure, gas pressures, Btu imput rating, proper electrical connections, circulating air temperature rise, minimum or maximum CFM and motor speed connections and venting. These furnaces are designed for Category I venting only.
2
WARNING
WARNING
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a
qualified installer, service agency or the gas supplier.
Goodman 42
DANGER
CARBON MONOXIDE POISONING HAZARD
Special Warning for Installation of Furnace or Air Handling Units in Enclosed Areas such as Garages, Utility Rooms or Parking Areas.
Possible property damage, personal injury or death due to fire, explosion, smoke, soot, condensation, electrical shock or carbon monoxide may result from improper installation, repair, operation or maintenance of this product.
WARNING
To prevent property damage, personal injury or death due to fire, do not install the furnace in a mobile home, trailer or recreational vehicle.
WARNING
To prevent personal injury or death due to improper installation, adjustment, alteration, refer to this manual. For additional assistance or information, consult a qualified installer, service agency or the gas supplier.
Goodman 44
service
or
maintenance,
WARNING
This product contains or produces a chemical or chemicals which may cause serious illness or death and which are known to the State of California to cause cancer, birth defects or other reproductive harm.
Goodman 45
WARNING
Carbon monoxide producing devices (such as an automobile, space heater, gas water heater, etc.) should not be operated in enclosed areas such as unventilated garages, utility rooms or parking areas because of the danger of carbon monoxide (CO) poisoning resulting from the exhaust emissions. If a furnace or air handler is installed in an enclosed area such as a garage, utility room or parking area and a carbon monoxide producing device is operated therein, there must be adequate, direct outside ventilation. This ventilation is necessary to avoid the danger of CO poisoning which can occur if a carbon monoxide producing device continues to operate in the enclosed area. Carbon monoxide emissions can be (re)circulated throughout the structure if the furnace or air handler is operating in any mode.
CO can cause serious illness including permanent brain damage or death.
Goodman 38
WARNING
Should overheating occur or the gas supply fail to shut off, turn off the manual gas shutoff valve external to the furnace before turning off the electrical supply.
Goodman 43
To prevent possible personal injury or death due to asphyxiation, this furnace must be Category I vented. Do not vent using Category III venting. Provisions must be made for venting combustion products outdoors through a proper venting system. The length of flue pipe could be a limiting factor in locating the furnace.
Goodman 66
WARNING
To prevent possible property damage, personal injury or death due to electrical shock, the furnace must be located to protect the electrical components from water.
Goodman 46
3
WARNING
Heating unit should not be utilized without reasonable, routine inspection, maintenance and supervision. If the building in which any such device is located will be vacant, care should be taken that such device is routinely inspected, maintained and monitored. In the event that the building may be exposed to freezing temperatures and will be vacant, all water-bearing pipes should be drained, the building should be properly winterized and the water source closed. In the event that the building may be exposed to freezing temperatures and will be vacant, any hydronic coil units should be drained as well, and, in such case, alternative heat sources should be utilized.
Goodman 47
INSTALLATION REQUIREMENTS
These instructions are intended as a general guide only for use by qualified persons and do not supersede any national or local codes in any way. Compliance with all local, state, or national codes pertaining to this type of equipment should be determined prior to installation.
Read this entire instruction manual, as well as the instructions supplied in separate equipment, before starting the installation.
The installation of the furnace, wiring, warm air ducts, venting, etc., must conform to the requirements of the National Fire Protection Association; the National Fuel Gas Code, ANSI Z223.1/NFPA No. 54 (latest edition) and the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States, and any state laws, local ordinances (including plumbing or wastewater codes), or local gas utility requirements.
Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.
This furnace design is certified by CSA International as a Category I furnace in compliance with the latest edition of American National Standard Z21.47/CSA Standard 2.3 for Gas­Fired Central Furnaces, for operation with Natural gas or propane. Consult the rating plate on the furnace for gas type before installing.
Tools and Parts
Gather the required tools and parts before starting installation. Read and follow the instructions provided with any tools listed here.
Too ls n eeded
Pipe wrench
Screwdriver
Tape measure
Thread sealant
Level
Parts needed
Check local codes and with gas supplier. Check existing gas supply, electrical supply, and venting, and read “Ductwork Requirements,” “Electrical Requirements,” “Gas Supply Requirements” and “Venting Requirements” before purchasing parts.
Noncorrosive leak check solution
Test g auge wi th ¹⁄₈" NPT connection
(for measuring gas supply pressure)
Allen wrench
Additional Safety Considerations
This furnace is approved for Category I venting only.
Provisions must be made for venting combustion products
outdoors through a proper venting system. The length of the flue pipe could be a limiting factor in locating the furnace.
Electrostatic Discharge (ESD)
NOTE: Discharge static electricity accumulated in the body before touching the unit. An electrostatic discharge can adversely affect electrical components.
Use the following steps during furnace installations and servicing to avoid damage to the integrated control module. By putting the furnace, the control and the person at the same electrostatic potential, these steps will help avoid exposing the integrated control module to electrostatic discharge. This procedure is applicable to both installed and non installed (ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch the
integrated control module or any wire connected to the control prior to discharging your body’s electrostatic charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the furnace
near the control. Any tools held in a person’s hand during grounding will be discharged also.
3. Service the integrated control module or connect wiring after
following the discharge process in Step 2. NOTE: Do not recharge your body with static electricity by
moving or shuffling your feet or touching ungrounded objects. Repeat Step 2 if you touch an ungrounded object.
4. Follow steps 1 through 3 before removing a new control from
its container or installing the control on a furnace. Return any old or new controls to their containers before touching any ungrounded object.
Location Requirements
This furnace is primarily designed for residential home-heating applications. It is not designed or certified for use in mobile homes, trailers or recreational vehicles. Neither is it designed or certified for outdoor applications. The furnace must be installed indoors (for example: attic space, crawl space or garage area provided the garage area is enclosed with an operating door).
4
This furnace can be used in the following non-industrial commercial applications:
Schools
Office buildings
Churches
Retail stores
Nursing homes
Hotels/motels
Common or office areas
WARNING
To prevent property damage, personal injury or death due to fire, do not install the furnace in a mobile home, trailer or recreational vehicle.
In such applications , the furnace must be installed with the following stipulations:
It must be installed according to the installation instructions
provided and according to local and national codes.
It must be installed indoors in a building constructed on site.
It must be part of a ducted system and not used in a free air
delivery application.
It must not be used as a “makeup” air unit.
All other warranty exclusions and restrictions apply.
This furnace may be used as a construction site heater only if the following conditions are met:
The vent system is permanently installed according to these
installation instructions.
A room thermostat is used to control the furnace. Fixed
jumpers that provide continuous heating cannot be used.
Return air ducts are provided and sealed to the furnace.
A return air temperature range between 60ºF (16ºC) and 80ºF
(27ºC) is maintained.
Air filters are installed in the system and maintained during
construction, replaced as appropriate during construction and, upon completion of construction, are replaced.
The input rate and temperature rise are set according to the
furnace rating plate.
100% outside air is provided for combustion air requirements
during construction. Temporary ducting can be used. NOTE: Do not connect the temporary duct directly to the
furnace. The duct must be sized according to the instructions under Section V, Combustion and Ventilation Air Requirements, Section 5.3.3.
The furnace heat exchanger, components, duct system, air
filters and evaporator coils are thoroughly cleaned following final construction cleanup.
All furnace operating conditions (including ignition, input rate,
temperature rise and venting) are verified according to these installation instructions.
NOTE: The Commonwealth of Massachusetts requires that the following additional requirements must also be met:
Gas furnaces must be installed by a licensed plumber or gas
fitter.
A T-handle gas cock must be used.
If the unit is to be installed in an attic, the passageway to and
the service area around the unit must have flooring.
To ensure proper installation and operation, thoroughly read this manual for specifics pertaining to the installation and application of this product.
To ensure proper furnace operation, install, operate and maintain the furnace in accordance with these installation and operation instructions, all local building codes and ordinances. In their absence, follow the latest edition of the National Fuel Gas Code (NFPA 54/ANSI Z223.1), and/or CAN/CSA B149 Installation Codes, local plumbing or waste water codes, and other applicable codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI Z223.1) can be obtained from any of the following:
American National Standards Institute 1430 Broadway New York, NY 10018
National Fire Protection Association 1 Batterymarch Park Quincy, MA 02269
CSA International 8501 East Pleasant Valley Cleveland, OH 44131
A copy of the CAN/CSA B149 Installation Codes can also be obtained from:
CSA International 178 Rexdale Boulevard Etobicoke, Ontario, Canada M9W 1R3
The rated heating capacity of the furnace should be greater than or equal to the total heat loss of the area to be heated. The total heat loss should be calculated by an approved method or in accordance with “ASHRAE Guide” or “Manual J-Load Calculations” published by the Air Conditioning Contractors of America.
In the U.S.A., this furnace must be installed in accordance with the latest edition of the ANSI Z223.1 booklet entitled “National Fuel Gas Code” (NFPA 54), and the requirements or codes of the local utility or other authority having jurisdiction. In Canada, this furnace must be installed in accordance with the current CAN/ CGA-B149.1 & 2 Gas Installation Codes, local plumbing or waste water codes and other applicable codes. Additional helpful publications available from the NFPA are, NFPA 90A—Installation of Air Conditioning and Ventilating System and NFPA 90B—Warm Air Heating and Air Conditioning System.
All venting shall be in accordance with PART 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1, or applicable local building and/or air conditioning codes. These publications are available from:
National Fire Protection Association, Inc. 1 Batterymarch Park, Quincy, MA 02269
NOTE: Furnaces with NOx screens meet the California NOx emission standards and California seasonal efficiency standards. Annual inspections of the furnace and its vent system is strongly recommended.
Your unit model type determines which installation procedures must be used. For WFM18 models, you must follow instructions for horizontal left, horizontal right or upflow installations only. WFM18 furnaces are not approved for downflow installations.
WARNING
Possible property damage, personal injury or death due to fire, explosion, smoke, soot, condensation, electrical shock or carbon monoxide may result from improper installation, repair, operation or maintenance of this product.
Goodman 48
5
WARNING
To prevent possible equipment damage, property damage, personal injury or death, the following bullet points must be observed when installing the unit.
Follow the instructions listed below when selecting a furnace location. Refer also to the guidelines provided in “Combustion and Ventilation Air Requirements.”
Centrally locate the furnace with respect to the proposed or
existing air distribution system.
Check that the temperature of the return air entering the
furnace is between 55°F and 100°F (13ºC and 38ºC) when the furnace is heating.
Provide provisions for venting combustion products outdoors
through a proper venting system. Special consideration should be given to the vent/flue pipe routing and the combustion air intake pipe when applicable. Refer to “Vent/ Flue Pipe and Combustion Air Pipe—Termination Locations” for appropriate termination locations and to determine if the piping system from the furnace to the termination can be accomplished within the guidelines given.
NOTE: The length of flue and/or combustion air piping can be a limiting factor in the location of the furnace.
Check that adequate combustion air is available for the
furnace. Improper or insufficient combustion air can expose building occupants to gas combustion products that could include carbon monoxide. Refer to “Combustion and Ventilation Air Requirements.”
Set the furnace on a level floor to enable proper condensate
drainage. If the floor becomes wet or damp at times, place the furnace above the floor on a concrete base sized approximately 1¹⁄₂" (3.8 cm) larger than the base of the furnace. Refer to “Horizontal Applications and Considerations” for leveling of horizontal furnaces.
Check that the upflow or horizontal furnaces are not installed
directly on carpeting, or any other combustible material. NOTE: The only combustible material allowed is wood.
Exposure to contaminated combustion air will result in safety
and performance-related problems. NOTE: Do not install the furnace where the combustion air is
exposed to the following substances:
Chlorinated waxes or cleaners Chlorine-based swimming pool chemicals Water softening chemicals Deicing salts or chemicals Carbon tetrachloride Halogen-type refrigerants Cleaning solutions (such as perchloroethylene) Printing inks Paint removers Var nishes Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
Goodman 50
If the furnace is used in connection with a cooling unit, install
the furnace upstream or in parallel with the cooling unit. Premature heat exchanger failure will result if the cooling unit is placed ahead of the furnace.
If the furnace is installed in a residential garage, position the
furnace so that the burners and ignition source are located not less than 18" (45.7 cm) above the floor. Protect the furnace from physical damage by vehicles.
If the furnace is installed horizontally, the furnace access
doors must be vertical so that the burners fire horizontally into the heat exchanger.
NOTE: Do not install the unit with the access doors on the “up/top” or “down/bottom” side of the furnace.
Do not connect this furnace to a chimney flue that serves a
separate appliance designed to burn solid fuel.
Counterflow installation over a noncombustible floor—Before
setting the furnace over the plenum opening, check that the surface around the opening is smooth and level. A tight seal should be made between the furnace base and floor by using a silicon rubber caulking compound or cement grout.
Counterflow installation over a combustible floor—If
installation over a combustible floor becomes necessary, use an accessory subbase (see Specification Sheet applicable to your model for details). A special accessory subbase must be used for upright counterflow unit installations over any combustible material including wood. Follow the instructions with the subbase for proper installations.
NOTES:
Do not install the furnace directly on carpeting, tile or
other combustible material other than wood flooring.
The subbase will not be required if an air conditioning coil
is installed between the supply air opening on the furnace and the floor.
Adequate combustion/ventilation air must be supplied to the
closet or enclosure.
Furnace must be completely sealed to the floor or base.
Combustion/ventilation air supply pipes must terminate 12" (30.5 cm) from the top of the closet or enclosure and 12" (30.5 cm) from the floor of the closet or enclosure.
NOTE: Do not remove the solid base plate for the side return.
Return air ducts must be completely sealed to the furnace
and terminate outside the enclosure surfaces.
6
Installation Clearances and Accessibility
D
For installations above 7,000 ft (2,133.6 m), refer to your local distributor for required kit(s).
Unobstructed front clearance of 24" (61 cm) for servicing is recommended.
Clearances to Combustibles—in. (cm)
Vent Pipe
B1-Vent Single Wall
Connector Sides Front Back Top (Plenum)
1 (2.5) 6 (15.2) 1 (2.4) 3 (7.6) 0 1 (2.5)
NOTE: Top clearance for horizontal configuration is 1" (2.5 cm).
B
A
C
Manifold Pressure
Pressure High Stage
Natural
0 to
Propane LPM-
NOTE: In Canada, gas furnaces are only certified to 4,500 ft (1,371.6 m).
Contact your local distributor for a tabular listing of appropriate manufacturer’s kits for propane gas and/or high altitude installations. The indicated kits must be used to insure proper furnace operation. All conversions must be performed by a qualified installer or service agency.
7,000 ft (2,133.6 m)
None #43 3.5"
W.C.
#55 10.0"
03B
W.C.
Low Stage
1.9" W.C.
6.0" W.C.
Switch
ChangeGas Altitude Kit Orifice
None
None
Propane Gas Conversion
WARNING
Failure to follow these instructions can result in bodily injury or death. Carefully read and follow all instructions given in this section.
Goodman 53
E
A. Top clearance—1" (2.5 cm) B. Vent pipe clearance—6" (15.2 cm)
for single wall connector, 1" (2.5 cm) for B-1 vent
C. Back clearance—0" D. Side clearance—1" (2.5 cm)
E. Front clearance—3" (7.6 cm)
High Altitude Installations
High Altitude Derate
IMPORTANT: The furnace will naturally derate itself with altitude.
Do not attempt to increase the firing rate by changing orifices or increasing the manifold pressure. This can cause poor combustion and equipment failure.
High altitude installations may require both a pressure switch and an orifice change. These changes are necessary to compensate for the natural reduction in the density of both the gas fuel and the combustion air at higher altitude.
This unit is configured for Natural gas. The appropriate manufacturer’s propane gas conversion kit must be applied for propane gas installations.
Contact your local distributor for a tabular listing of appropriate manufacturer’s kits for propane gas and/or high altitude installations. The indicated kits must be used to insure safe and proper furnace operation. All conversions must be performed by a qualified installer or service agency.
Installation Configurations
Horizontal Installation
Line contact to framing is permitted when installed in the horizontal configuration. Line contact is defined as the portion of the cabinet that is formed by the intersection of the top and side.
IMPORTANT: Accessibility clearance, where greater, should take precedence over minimum fire protection clearance.
A gas-fired furnace for installation in a residential garage must be installed so that the ignition source and burners are located not less than 18" (45.7 cm) above the floor and are protected or located to prevent physical damage by vehicles.
A gas furnace must not be installed directly on carpeting, tile, or other combustible materials other than wood flooring.
7
Furnace Suspension
If you are suspending the furnace from the rafters or joists, use a ³⁄₈" (1 cm) threaded rod and 2" x 2" x ³⁄₈" (5.1 cm x 5.1 cm x 1 cm) angle iron as shown below. The length of the rod will depend on the application and the clearances necessary.
Suspended Furnace
A
H
G
F
A.
³⁄₈
" (1 cm) diameter threaded
rod (6)
B. 8" (20.3 cm) minimum
clearance between center rod and furnace cabinet to allow for circulator blower removal.
C. Level furnace end to end, slight
forward tilt with front 0" to (1.9 cm) below back.
³⁄₄
"
D. Tilt outward to allow for door and
E. Position as close as possible to
F. 2" x 2" x
G. Support nuts H. Hold down nuts
B
C
DE
circulator blower removal.
blower deck to allow for circulator blower removal.
1cm) angle iron (3)
³⁄₈
" (5.1 cm x 5.1 cm x
Existing Furnace Removal
NOTE: When an existing furnace is removed from a venting
system serving other appliances, the venting system may be too large to properly vent the remaining attached appliances.
The following vent testing procedure is reproduced from the American National Standard/National Standard of Canada for Gas-Fired Central Furnaces ANSI Z21.47-Latest Edition, CSA-
2.3-Latest Edition Section 1.23.1. The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation.
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal
pitch, as required by the National Fuel Gas Code, ANSI Z223.1 or the CAN/CSA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. In so far as practical, close all building doors and windows
and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Follow the lighting instructions. Place the appliance being
inspected in operation. Adjust thermostat so appliance shall operate continuously.
5. Test for draft hood equipped appliance spillage at the draft
hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
6. After it has been determined that each appliance connected
to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.
7. If improper venting is observed during any of the above tests,
the common venting system must be corrected.
Corrections must be in accordance with the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1 and/or CAN/CSA B149 Installation Codes.
If resizing is required on any portion of the venting system, use the appropriate table in Appendix G in the latest edition of the National Fuel Gas Code ANSI Z223.1 and/or CAN/CSA B149 Installation Codes.
Ductwork Requirements
Install all conditioned air plenums, ducts and air filters (if not
provided on the furnace) in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air­Conditioning Systems (latest edition).
The furnace is provided with flanges for the connection of the
plenum and ducts.
All air filters must be listed as Class 2 furnace air filters.
All ductwork must be made of materials and insulated to
meet local, state and national codes. Ductwork installed outdoors must be sealed, weatherproof and kept from physical damage. Caulking, flashing or other means of adequately providing a permanent weather seal should be used where duct penetrates a building or structure opening.
A closed return duct system must be used with the return
duct connected to the furnace.
Do not attach ductwork to the back of the furnace.
Flexible joints may be used for supply and return connections
to reduce noise transmission.
A connecting duct must be installed between the furnace and
the utility room wall to keep the blower from interfering with combustion air or draft when a central return is used.
Do not use a room, closet or alcove as a return air chamber.
For models with airflow over 1,800 CFM, install a bottom
return, 2 side returns or 1 side and 1 bottom return.
Electrical Requirements
WARNING
To avoid the risk of injury, electrical shock or death, the furnace must be electrically grounded in accordance with local codes or, in their absence, with the latest edition of the National Electric Code (NEC).
The furnace must be grounded and wired in accordance with
local codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA No. 70 (latest edition).
In all instances, other than wiring for the thermostat, the
wiring to be done and any replacement of wire shall conform with the temperature limitation for Type T wire (63°F [17ºC] rise).
8
The line voltage supply should be routed through a readily
accessible disconnect located within sight of the furnace. A junction box on the furnace side panel is provided for line voltage connections. See the Wiring Connection Diagram in the “Troubleshooting” section for specific connection information.
Proper polarity of the supply connections (“HOT” and
“NEUTRAL”) must be observed to be sure that the control system provides the damage avoidance intended.
Existing Venting Systems
When an existing furnace is removed or replaced, the original venting system may no longer be sized to properly vent the attached appliances. An improperly sized venting system can result in the spilling of flue products into the living space, the formation of condensate, leakage, etc. See the “Carbon Monoxide Poisoning Hazard” for proper test procedure.
Gas Supply Requirements
This unit is equipped for use with Natural gas. A conversion kit is required for use with propane. To order the correct conversion kit, see your local distributor.
Gas supply piping should be installed in accordance with
local, state and national codes and the regulations of the utility. Piping must be of adequate size to prevent undue pressure drop. Consult the local utility or gas supplier for complete details on special requirements for sizing gas piping.
If local codes allow the use of a flexible gas appliance
connector, use a CSA design-certified outdoor flexible stainless steel appliance connector or rigid gas supply line as needed.
Venting Requirements
WARNING
Goodman 51
To avoid property damage, personal injury or death, sufficient fresh air for proper combustion and ventilation of flue gases must be supplied. Most homes require outside air be supplied into the furnace area.
Improved construction and additional insulation in buildings have reduced heat loss by reducing air infiltration and escape around doors and windows. These changes have helped in reducing heating/cooling costs but have created a problem supplying combustion and ventilation air for gas-fired and other fuel burning appliances. Appliances that pull air out of the house (clothes dryers, exhaust fans, fireplaces, etc.) increase the problem by starving appliances for air.
House depressurization can cause back drafting or improper combustion of gas-fired appliances, thereby exposing the building occupants to gas combustion products that could include carbon monoxide.
If this furnace is to be installed in the same space with other gas appliances, such as a water heater, ensure there is an adequate supply of combustion and ventilation air for the other appliances.
Refer to the latest edition of the National Fuel Gas Code NFPA 54/ ANSI Z223.1 (Section 5.3), or CAN/CSA B149 Installation Codes (Sections 7.2, 7.3, or 7.4), or applicable provisions of the local building codes for determining the combustion air requirements for the appliances.
This furnace must use indoor air for combustion. It cannot be installed as a direct vent (for example, sealed combustion) furnace. Most homes will require outside air be supplied to the furnace area by means of ventilation grilles or ducts connecting directly to the outdoors or spaces open to the outdoors such as attics or crawl spaces.
WARNING:
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CSA B149.1, Natural Gas and Propane Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired burning appliances to their previous conditions of use.
9
INSTALLATION INSTRUCTIONS
Inspect Shipment
This furnace is shipped in one package, completely assembled and wired. The indoor thermostat and accessories are shipped in a separate carton when ordered.
Check the furnace rating plate to confirm specifications are
as ordered.
Upon receipt of the furnace, inspect it for possible shipping
damage. Examine the furnace inside the carton if the carton is damaged.
If damage is found, it should be noted on the carrier’s freight
bill. Damage claims should be filed with the carrier immediately. Claims of shortages should be filed with the seller within 5 days.
NOTE: If any damages are discovered and reported to the carrier, do not install the furnace, because your claim may be denied.
Plan Vent System
Category I Venting—Vertical Venting
WARNING
Goodman 66
To prevent possible personal injury or death due to asphyxiation, this furnace must be Category I vented. Do not vent using Category III venting. Provisions must be made for venting combustion products outdoors through a proper venting system. The length of flue pipe could be a limiting factor in locating the furnace.
The minimum vent diameter for the Category I venting system is as shown in the Minimum Vent chart.
Minimum Vent
Model Upflow Counterflow
45 4" (10.2 cm) 4" (10.2 cm)
70 4" (10.2 cm) 4" (10.2 cm)
90 4" (10.2 cm) 4" (10.2 cm)
115 5" (12.7 cm) 5" (12.7 cm)
140 5" (12.7 cm) N/A
Under some conditions, larger vents than those shown in the Minimum Vent chart may be required or allowed. When an existing furnace is removed from a venting system serving other appliances, the venting system may be too large to properly vent the remaining attached appliances.
Upflow or horizontal units are shipped with the induced draft blower discharging from the top of the furnace. (“Top” is as viewed for an upflow installation.) The induced draft blower can be rotated 90 degrees for Category I venting. For horizontal installations, a 4" (10.2 cm) single-wall pipe can be used to extend the induced draft blower outlet ¹⁄₂" (1.3 cm) beyond the furnace cabinet. This product is not designed for counterclockwise induced draft blower rotation.
Vent the furnace in accordance with the National Fuel Gas Code NFPA 54/ANSI Z223.1—latest edition. In Canada, vent the furnace in accordance with the National Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2—latest editions and amendments.
Category I Venting is venting at a non-positive pressure. A furnace vented as Category I is considered a fan-assisted appliance. The vent system does not have to be “gas tight.” NOTE: Single-stage gas furnaces with induced draft blowers draw products of combustion through a heat exchanger allowing, in some instances, common venting with natural draft appliances (for example, water heaters).
All installations must be vented in accordance with National Fuel Gas Code NFPA 54/ANSI Z223.1—latest edition. In Canada, the furnaces must be vented in accordance with the National Standard of Canada, CAN/CSA B149.1 and CAN/CSA B149.2— latest editions and amendments.
NOTE: The vertical height of the Category I venting system must be at least as great as the horizontal length of the venting system.
WARNING
To prevent possible personal injury or death, due to asphyxiation, common venting with other manufacturer's induced draft appliances is not allowed.
Goodman 67
Venting
NOTE: This furnace is not design certified to be horizontally
vented.
1. Disconnect electrical power from the furnace.
2. Disconnect the induced draft blower power leads, flue pipe
and pressure switch tubing.
3. Remove the round cutout from the right-hand side of the
wrapper.
4. Remove and save the 4 screws that fasten the induced draft
blower to the flue collector box.
5. Remove and save the 3 screws that hold the chimney
assembly to the induced draft blower.
6. Remove and save the 4 screws that fasten the chimney top to
the chimney bottom.
7. Remove the chimney transition bottom from the transition
bottom kit.
8. Install the chimney top with the 4 screws retained from Step
6 onto the new chimney transition bottom from the transition bottom kit.
9. Install the chimney assembly with the 3 screws retained from
Step 5 onto the induced draft blower.
10. Reinstall the induced draft blower rotating it 90 degrees
clockwise from the original upflow configuration using the 4 screws retained in Step 3. Ensure the gasket located between the induced draft blower and the collector box is rotated accordingly.
10
11. Reconnect the induced draft blower power leads.
C
D E
F
G
H
I
J
K
NOTE: If the wires are not long enough, pull extra wire from the wire bundle in the blower compartment.
12. Reconnect the flue pipe and the pressure switch tubing.
Ensure that all wires and the pressure switch tubing are at least 1" (2.5 cm) from the flue pipe, or any other hot surface.
13. Reconnect electrical power to the furnace. Counterflow units are shipped with the inducted draft blower
discharging from the top (as viewed for a counterflow installation) of the furnace.
Vent the furnace in accordance with the National Fuel Gas Code NFPA 54/ANSI Z223.1—latest edition. In Canada, vent the furnace in accordance with the National Standard of Canada, CAN/CSA B149.1 AND CAN/CSA B149.2—latest editions and amendments.
AB
R
Q P
WARNING
Never allow the products of combustion, including carbon monoxide, to enter the return ductwork or circulation air supply.
Goodman 68
Category I Furnaces Only—Exterior Masonry Chimneys
An exterior masonry chimney is defined as a “Masonry chimney exposed to the outdoors on one or more sides below the roof line.” The ability to use a clay-lined masonry chimney depends on a parameter not associated with interior chimneys. This variable is the geographic location of the installation. Researchers have discovered that the winter design temperatures have a direct impact on the suitability of this type of venting. In most situations, the existing masonry chimneys will require a properly-sized metallic liner.
WARNING
Possiblility of property damage, personal injury or death. Damaging condensation can occur inside masonry chimneys when a single fan-assisted Category I appliance (80% AFUE furnace) is vented without adequate dilution air. Do not connect an 80% furnace to a masonry chimney unless the furnace is common vented with a draft hood equipped appliance or the chimney is lined with a metal liner or Type B metal vent. All installations using masonry chimneys must be sized in accordance with the appropriate venting tables. If an 80% furnace is common vented with a draft hood equipped appliance, the potential for condensation damage may still exist with extremely cold conditons, long vent connectors, exterior chimneys or any combination of these conditions. The risk of condensation damage is best avoided by using the masonry chimney as a pathway for properly-sized metal liner or Type B metal vent.
Goodman 69
O
N
L
M
A. Crown B. Wash C. Roof line D. Clay tile size: 8" x 8" x
12" (24.3 cm x 24.3 cm x 30.5 cm) (each x 24" [61 cm] length)
E. Attic floor
F.
¹⁄₂
" to 1 " (1.3 cm to
2.5 cm) air space
G. Second floor H. First floor
I. Water heater vent
connector
J. Natural draft water
heater
K. Basement floor
L. Fan-assisted
forced air furnace
M. Forced air furnace
vent connector N. Clean out O. Breech P. D am p e r Q. Throat R. Clay tile size:
generally 12" x 12"
(30.5 cm x 30.5 cm)
(24" [61 cm] length)
Checklist Summary
This checklist serves as a summary of the items to be checked before venting an 80+ furnace into a masonry chimney. In addition, we recommend that a qualified serviceman use this checklist to perform a yearly inspection of the furnace venting system.
This checklist is only a summary. For detailed information on each of the procedures mentioned, see the paragraph referenced with each item.
This inspection is based upon a draft topical report, “Masonry Chimney Inspection and Relining,” issued by the Gas Research Institute. While not yet finalized, we believe this report represents the best information on this subject which is currently available.
11
Loading...
+ 25 hidden pages