Whirlpool UXT2030ADW User Manual

PRODUCT MODEL NUMBERS
UXT2030AD
Electrical: A 120 volt, 60 Hz., AC only, 15-amp, fused electrical circuit is required.
30" (76.2 cm) and 36" (91.4 cm) Range Hood
Installation Clearances
Calculating Vent System Length
To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system.
Vent System Vent Piece
45° elbow 2.5 ft
(0.8 m)
90° elbow 5.0 ft
(1.5 m)
7" (17.8 cm) wall cap 0.0 ft
(0.0 m)
Maximum Recommended Length
7" (17.8 cm) Round Vent = 50 ft (15.2 m)
1 - 90° elbow = 5.0 ft (1.5 m) 1 - wall cap = 0.0 ft (0.0 m) 8 ft (2.4 m) straight = 8.0 ft (2.4 m) System length = 13.0 ft (3.9 m)
VENTING METHODS
NOTES: Flexible vent is not recommended. Flexible vent creates both
back pressure and air turbulence that greatly reduce performance.
Flexible vent is not recommended. Flexible vent creates both back pressure and air turbulence that greatly reduce performance.
The vent system is optional for this model.
Vent system can terminate either through the roof or wall. Use 7" (17.8 cm) or larger round vent with a maximum length of 50 ft (15.2 m) for vent system.
A
Because Whirlpool Corporation policy includes a continuous commitment to improve our products, we reserve the right to change materials and specifications without notice.
Dimensions are for planning purposes only. For complete details, see Installation Instructions packed with product. Specifications subject to change without notice.
PRODUCT DIMENSIONS
Ref. W10646400B
3/12/14
Top Venting Wall Venting
B
4¹⁵⁄₁₆"
(12.5 cm)
2"
(5.1 cm)
(2.5 cm)
6⁹⁄₁₆" (16.7 cm)
1"
(2.5 cm)
1"
9"
(22.9 cm)
A
A
. 7" (17.8 cm) round vent
through roof (purchased separately).
B. Roof cap with damper
(purchased separately)
A. 7" (17.8 cm) round vent out
the top and through the wall (purchased separately).
B. Wall cap with damper
(purchased separately)
B
B
29¹⁵⁄₁₆" (76.0 cm)
C
A
1¹⁄₂"
(3.8 cm)
18⁵⁄₈"
(47.3 cm)
D
Example vent system
90˚ elbow
2 ft (0.6 m)
6 ft (1.8 m)
Wall cap
E
A. 18” (45.7 cm) minimum distance from electric cooking surface.
24" (61.0 cm) minimum distance from gas cooking surface. 30" (76.2 cm) suggested maximum above the cooking surface.
B. 18" (45.7 cm) minimum clearance - upper cabinet to countertop. C. 30" (76.2 cm) minimum cabinet opening width. D. 12" (30.5 cm) cabinet depth.
E. 36" (91.4 cm) base cabinet height.