Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety
messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING.”
These words mean:
You can be killed or seriously injured if you don't immediately
DANGER
W ARNING
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can
happen if the instructions are not followed.
follow instructions.
You
can be killed or seriously injured if you don't
instructions.
follow
2
IMPORTANT SAFETY INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
■ Use this unit only in the manner intended by the
manufacturer. If you have questions, contact the
manufacturer.
■
Before servicing or cleaning the unit, switch power off at
service panel and lock the service disconnecting means to
prevent power from being switched on accidentally. When
the service disconnecting means cannot be locked,
securely fasten a prominent warning device, such as a tag,
to the service panel.
■ Installation work and electrical wiring must be done by
qualified person(s) in accordance with all applicable codes
and standards, including fire-rated construction.
■ Do not operate any fan with a damaged cord or plug.
Discard fan or return to an authorized service facility for
examination and/or repair.
■ Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel
burning equipment to prevent backdrafting. Follow the
heating equipment manufacturer's guideline and safety
standards such as those published by the National Fire
Protection Association (NFPA), the American Society for
Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
■ When cutting or drilling into wall or ceiling; do not damage
electrical wiring and other utilities.
■ Ducted fans must always be vented outdoors.CAUTION: For general ventilating use only. Do not use
to exhaust hazardous or explosive materials and vapors.
CAUTION:
air, be sure to duct air outside - do not vent exhaust air into
spaces within walls or ceilings, attics or into crawl spaces,
or garages.
WARNING: TO REDUCE THE RISK OF FIRE, USE ONLY
METAL DUCTWORK.
To reduce risk of fire and to properly exhaust
WARNING:
TO REDUCE THE RISK OF A RANGE TOP
GREASE FIRE:
■ Never leave surface units unattended at high settings.
Boilovers cause smoking and greasy spillovers that may
ignite. Heat oils slowly on low or medium settings.
■
Always turn hood ON when cooking at high heat or when
flambeing food (i.e. Crepes Suzette, Cherries Jubilee,
Peppercorn Beef Flambé).
■ Clean ventilating fans frequently. Grease should not be
allowed to accumulate on fan or filter.
■
Use proper pan size. Always use cookware appropriate for
the size of the surface element.
WARNING: TO REDUCE THE RISK OF INJURY TO
PERSONS IN THE EVENT OF A RANGE TOP GREASE
FIRE, OBSERVE THE FOLLOWING:
■ SMOTHER FLAMES with a close fitting lid, cookie sheet, or
metal tray, then turn off the burner. BE CAREFUL TO
PREVENT BURNS. If the flames do not go out
immediately, EVACUATE AND CALL THE FIRE
DEPARTMENT.
■ NEVER PICK UP A FLAMING PAN - you may be burned.
■ DO NOT USE WATER, including wet dishcloths or towels -
a violent steam explosion will result.
■ Use an extinguisher ONLY if:
– You know you have a class ABC extinguisher, and you
already know how to operate it.
– The fire is small and contained in the area where it
started.
– The fire department is being called.
– You can fight the fire with your back to an exit.
a
Based on "Kitchen Fire Safety Tips" published by NFPA.
■ WARNING: To reduce the risk of fire or electrical shock,
do not use this fan with any solid-state speed control
device.
a
READ AND SAVE THESE INSTRUCTIONS
3
INSTALLATION REQUIREMENTS
Tools and Parts
Gather the required tools and parts before starting installation.
Read and follow the instructions provided with any tools
Tools needed
LevelDrill1/8" (3 mm) drill bitPencilPliersTape measure or rulerCaulking gun and weatherproof caulking compoundPhillips screwdriverFlat-blade screwdriverSaber or keyhole sawVent clampsMetal snips
Parts needed
6" (15.2 cm) round metal vent system
For vented installations, you will need:
1 wall or roof cap
For non-vented (recirculating) installations, you will
also need:
Recirculation Kit. See the “Assistance or Service”
section to order.
Parts supplied
Remove parts from packages. Check that all parts are included.
DamperHardware package. Includes:
Installation Instructions and Use and Care Guide
2 mounting brackets
6 spacers
10 - 4.5 x 13 mm wood screws
2 - 4.2 x 15 mm machine screws
Location Requirements
IMPORTANT: Observe all governing codes and ordinances.
installer’s responsibility to comply with installation clearances
Range hood location should be away from strong draft areas,
such as windows, doors, and strong heating vents.
Cabinet opening dimensions that are shown must be used.
Given dimensions provide minimum clearance. Consult your
cooktop/range manufacturer installation instructions before
making any cutouts.
This range hood is recommended for use with cooktops with a
maximum total rating of 65,000 BTUs or less.
Grounded electrical outlet is required. See the “Electrical
Requirements” section.
The range hood is factory set for vented installations through the
roof or wall. For non-vented (recirculating) installations see “Non-
the “Prepare Location” section. Recirculation Kit; See the
“Assistance or Service” section to order.
All openings in ceiling and wall where range hood will be
installed must be sealed.
For Mobile Home Installations
The installation of this range hood must conform to the
Manufactured Home Construction Safety Standards, Title 24
CFR, Part 328 (formerly the Federal Standard for Mobile Home
Construction and Safety, title 24, HUD, Part 280) or when such
standard is not applicable, the standard for Manufactured Home
Installation 1982 (Manufactured Home Sites, Communities and
Setups) ANSI A225.1/NFPA 501A, or latest edition, or with local
codes.
8 - 4.2 x 19 mm sheet metal screws
2 - 3.5 x 9.5 mm sheet metal screws
1 - 30" x 12" (76.2 cm x 30.5 cm) face panel
For 18" (45.7 cm) deep cabinets, an optional Face Panel Rear
Extension (30" [76.2 cm]) or Face Panel (36" [91.4 cm]) must
be purchased separately. See the “Assistance and Service”
section to order.
■ Vent system must terminate to the outside, except for
■ Do not terminate the vent system in an attic or other
■ Do not use a 4" (10.2 cm) laundry-type wall cap.
■ Use metal vent only. A rigid metal vent is recommended.
■ The length of the vent system and number of elbows should
For the most efficient and quiet operation:
■ Use no more than three 90° elbows.
■ Make sure there is a minimum of 24" (61.0 cm) of straight
■ Do not install two elbows together.
■ The vent system must have a damper.
■ Use clamps to seal all joints in the vent system.
■ Use caulking to seal exterior wall or roof opening
■ The size of the vent should be uniform.
G. 117/8" (30.2 cm) or
177/8" (45.4 cm)
H. 91/8" (23.1 cm)
I. 135/8" (33.7 cm)
Venting Requirements
(vented models only)
non-vented (recirculating) installations.
enclosed area.
Plastic or metal foil vent is not recommended.
be kept to a minimum to provide efcient performance.
vent between the elbows if more than one elbow is used.
aroundthecap.
5
Cold weather installations
A
B
B
A
A
D
F
G
(0.93 m)
Wall cap
An additional back draft damper should be installed to minimize
to minimize conduction of outside temperatures as part of the
vent system. The damper should be on the cold air side of the
thermal break.
The break should be as close as possible to where the vent
system enters the heated portion of the house.
Makeup air
Local building codes may require the use of makeup air systems
Venting Methods
This range hood is factory set for venting through the roof or
through the wall.
The vent system needed for installation is not included.
Roof VentingWall Venting
Example vent system: 6" (15.2 cm)
90˚ elbow
6 ft (1.8 m)
3 ft
Maximum Length = 35 ft (10.7 m)
1 - 90° elbow= 5 ft (1.5 m)
1 - wall cap= 0 ft (0 m)
9 ft (2.8 m) straight= 9 ft (2.8 m)
System length= 14 ft (4.3 m)
Non-Vented (recirculating) Installations Through the
Soffit/Cabinet
If it is not possible to vent cooking fumes and vapors to
the outside, the range hood can be used in the non-vented
Kit, See the "Assistance or Service" section to order.
A
A. 6" (15.2 cm) vent
through the roof
B. Roof cap
A. 6" (15.2 cm) vent
through the wall
B. Wall cap
Calculate Vent System Length
The recommended vent system is 6" (15.2 cm) round vent with a
maximum length of 35 ft (10.7 m). For the best performance, use
no more than three 90° elbows.
To calculate the length of the system, add the equivalent feet
(meters) for each of the vent pieces used in the system.
Vent Piece6" (15.2 cm)
45° elbow2.5 ft (0.8 m)
Through CabinetThrough Soffit
G
B
F
I
E
H
A. Ceiling
B. Vent cover
C.
D. 6" (15.2 cm) vent
E. Range hood
F. Cabinet
G. Wall
H. 12" (30.5 cm) min.
I. 17" (43.2 cm) min.
NOTE:
B
C
D
E
90° elbow5.0 ft (1.5 m)
6
Electrical Requirements
" (85 cm)
WARNING
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death,
fire, or electrical shock.
IMPORTANT: The range hood must be electrically grounded in
accordance with local codes and ordinances, or in the absence
of local codes, with the National Electrical Code, ANSI/NFPA
70 (latest edition) or Canadian Electrical Code, CSA C22.1
No.0-M91 (latest edition).
If codes permit and a separate ground wire is used, it is
recommended that a qualied electrical installer determine that
the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
■ A 120-volt, 60 Hz, AC-only, 15- or 20-amp, fused electrical
circuit is required. A time-delay fuse or circuit breaker is also
recommended. It is recommended that a separate circuit
serving only this range hood be provided.
■ This range hood is equipped with a power supply cord
having a 3 prong grounding plug.
■ To minimize possible shock hazard, the cord must be
plugged into a mating, 3 prong, grounding-type outlet,
grounded in accordance with local codes and ordinances.
If a mating outlet is not available, it is the personal
responsibility and obligation of the customer to have the
properly grounded outlet installed by a qualied electrician.
■ The grounded 3 prong outlet is to be located inside the
cabinet above the range hood at a maximum distance of
337/16" (85.0 cm) from where the power cord exits the hood.
The grounded 3 prong outlet must be accessible after
installation of the range hood. See illustration.
33⁷⁄₁₆
GROUNDING INSTRUCTIONS
■
For a grounded, cord-connected range hood:
This range hood must be grounded. In the event of an
electrical short circuit, grounding reduces the risk of electric
shock by providing an escape wire for the electric current.
This range hood is equipped with a cord having a grounding
wire with a grounding plug. The plug must be plugged into
an outlet that is properly installed and grounded.
WARNING:Improper grounding can result in a risk of
electric shock.
Consult a qualified electrician if the grounding instructions
are not completely understood, or if doubt exists as to
whether the range hood is properly grounded.
Do not use an extension cord. If the power supply cord is too
short, have a qualified electrician install an outlet near the
range hood.
SAVE THESE INSTRUCTIONS
7
INSTALLATION INSTRUCTIONS
D
E
A
B
C
Prepare Location
■ It is recommended that the vent system be installed before
the range hood is installed.
■ Before making cutouts, make sure there is proper clearance
within the ceiling or wall for vent ttings.
■ Making the cutout to the bottom of the cabinet may be
easier to do prior to mounting the cabinet to the wall.
1. Disconnect power.
2. Determine which venting method to use: roof, wall, or
non-vented.
3. Select a at surface for assembling the range hood. Place
covering over that surface.
WARNING
Excessive Weight Hazard
Use two or more people to move and install
range hood.
Failure to do so can result in back or other injury.
4. Using two or more people, lift range hood onto covered
surface.
Range Hood Cabinet Cutout
1. Use a saber saw or keyhole saw to cut out the cabinet
bottom inside the cabinet frame.
NOTE: Frameless type cabinets require 3/4" (19 mm) front lip
in the cabinet bottom. A 3/4" (19 mm) thick ller strip (not
supplied) may be required for some types of cabinets. (See
Step 3 in the “Install Range Hood” section.)
Venting Outside Through the Roof
Measure and mark the lines as shown. Use a saber saw
or keyhole saw to cut an opening through the top of the
cabinetand the roof for the vent.
Go to Step 3.
B*
C
D
A. Cutout
B. 61/4" (15.9 cm)*
C. 73/4" (19.7 cm) centerline to cabinet front
D. Centerline
* NOTE: For 12" (30.5 cm) high cabinets, a 61/4" deep x 8" wide
(14.6 cm x 20.3 cm) rectangular opening in the cabinet top is
required for damper transition clearance.
Venting Outside Through the Wall
Install the 6" (15.2 cm) vent transition to the top of the range
hood liner using two 3.5 x 9.5 mm screws. Assemble the
vent duct that you will use over the 6" (15.2 cm) vent
transition. Measure from the bottom of the range hood liner
to the horizontal centerline of the vent opening (A).
A
C
B
A. Bottom of cabinet cutout
B. Bottom must be cut ush to the inside walls of the cabinet.
C. 107/8" (27.6 cm) min. from the inside of the cabinet front face
D. 3/4" (19 mm) thick front face required for cabinet bottom.
E. Front of cabinet
2. Complete cabinet preparation following the instructions for
your type of venting. Determine venting cutout locations and
cut out vent openings in the cabinets, walls, and/or soft.
Remove the vent duct from the range hood liner.
A. Measurement A
B. Horizontal centerline of vent opening
C. Range hood liner
A
8
Transfer measurement A to the cabinet back wall. Measure
A
A
from the underside of the cabinet. Mark the cutout as shown.
Use a saber saw or keyhole saw to cut a round opening
through the back of the cabinet and the exterior wall for
Measure and mark the centerline location for the cutout in
the cabinet top. Use a saber saw or keyhole saw to cut an
opening for the vent.
Go to Step 3.
A
B
A. Measurement A
B. Centerline
1
C. 6
/4" (15.9 cm) round cutout
C
Non-Vented (recirculating) Installation Through
the Soffit/Cabinet
Measure and mark the centerline of the cabinet to the
Measure from the bottom of the cabinet to the centerline of
location and use a saber saw or keyhole saw to cut a 53/4"
(14.6 cm) hole for the vent cover.
B
B*
C
D
A. Cutout
B. *See chart below.
3
C. 7
/4" (19.7 cm) centerline to cabinet front
D. Centerline
Cabinet HeightHole Shape and Size
1
12" (30.5 cm)A 6
/4" deep x 8" wide (15.9 cm x
20.3 cm) rectangular opening in the
cabinet top is required for damper
transition clearance.
15" (38.1 cm) cabinet
A 61/4" (15.9 cm) diameter
18" (45.7 cm) or A 53/4" (14.6 cm) diameter round
opening is required.
For non-vented (recirculating) installations only, the range
hood can be vented indoors through the top of the cabinet.
are necessary. See the “Range Hood Care” section for
Recirculation Kit. See the “Assistance or Service” section
to order.
A. Vent cover
B. Centerline
9
Complete Preparation
D
D
D
B
A
1. If not yet attached, install the 6" (15.2 cm) vent transition the
top of the range hood liner using two 3.5 x 9.5 mm screws.
2. Locate side mounting bracket ush to the bottom of the
cabinet side and against the inside of the front cabinet face.
Orient the bracket depending on the width of your cabinet
as depicted in the diagrams below. Drill 1/8" (3 mm) pilot
holes in six places, attach a bracket using three 4.5 x 13 mm
screws to each side of the cabinet, and tighten. Additional
washers in hardware package are supplied as spacers for
cabinet walls thinner than 1/2" (13 mm).
Bracket Orientation for 30" (76.2 cm) Cabinet
3. Install the vent system according to the method needed.
Usecaulking to seal the exterior wall or roof opening.
Install Range Hood
WARNING
Excessive Weight Hazard
Use two or more people to move and install
range hood.
Failure to do so can result in back or other injury.
1. Using two or more people, lift the hood liner into its mounted
location. Attach with four 4.2 x 19 mm screws into the
slotted openings. Do not tighten screws.
B
A
A. 30" (76.2 cm) cabinet
B. Screws: 4.5 x 13 mm (6)
C. Washers (optional)
D. Mounting bracket (2) (position for 30" [76.2 cm] cabinet)
Bracket Orientation for 36" (91.4 cm) cabinet
C
A
B
C
A. Cabinet
B. Hood liner canopy assembly
2. If needed, insert spacers between each side of the canopy
and the mounting plate to space and center the canopy
inthe cabinet. Align the bottom of the canopy with the
bottom of the cabinet. Install four 4.2 x 19 mm screws into
the round mounting plate openings and tighten all eight
mounting screws.
3. (For some installations):
A ller strip may be required for some cabinets.
Install a ller strip and secure with two 4.5 x 13 mm screws
from inside the front of the hood liner assembly.
C. Screws: 4.2 x 19 mm (8)
D. Spacer: optional
C
A
B
A. 36" (91.4 cm) cabinet
B. Screws: 4.5 x 13 mm (6)
C. Washers (optional)
D. Mounting bracket (2) (position for 36" [91.4 cm] cabinet)
10
A. Screws: 4.5 x 13 mm
B. Filler strip
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.