SAFEPATH®4 Facility Communications System & Expansion Options
SPB-320
SPB-80/4
SPB-160
SP4-APS
SP40S
SPRM
SP4Z-A/B
SP4-TZC
SP-SVC
Description
Page
SP40S Facility Communications System 2-4
Expansion Options
SAFEPATH®4 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter 5
SAFEPATH®4 Audio Boosters 6-7
System Diagram 8-9
SAFEPATH®4 Addressable Paging Splitter and Telephone Zone Controller 10
SAFEPATH®4 Supervised Volume Control and Remote Microphone 11
Remote Microphone Expansion Module 12
S5361
151-92-E
6911-0785:157
Page 2
Description
The SP40S is a Multi-Function Supervised Paging, Messaging,
Background Music delivery and Emergency Voice Evacuation
System with 24 VDC battery backup. This single channel
system is capable of delivering 40 watts of supervised high fidelity audio power and 2 amps of supervised 24 VDC
synchronized strobe power. It comes standard with an
on-board digital voice messaging system with 8 standard
messages, a hand-held microphone, power supply/battery
charger and numerous additional features. The SAFEPATH4
system is expandable to 5280 watts utilizing the SPB-80/4 (80
watts and 4 amps of strobe power), the SPB-160 (160 watts)
or SPB-320 (320 watts) supervised audio power boosters. All
models available in 115 VAC ir 220 VAC.
Applications for the SP40S
• Multi-use applications—The system can function as an
evacuation system, an emergency messaging system,
a paging system, an employee notification system and a
background music system per NFPA 72 (2002), section
6.8.4 Combination Systems
• Fire code applications—The system is listed under UL
Standard 864, 9th edition delivering supervised audio and
voice messaging with strobes and notification appliance
circuits (NAC) for visual alerting
• Economic OSHA applications—The system is OSHA
1910.165 compliant; this means that it does not require
reliability inspections every two months, or the required
spare parts inventory
• Wide ranging applications—from small to large facilities
• Can connect to pagers for private alerting of emergency/
trouble conditions
System Activation
• Contact closure message activation
SAFEPATH
®
4
Facility Communications
SP40S
Features
Approvals & Compliance
• Approvals: UL Standard 864, 9th edition, UL Standard 1711,
California State Fire Marshal (CSFM), New York City (MEA),
FCC Part 15
• OSHA 1910.165 and ADA Compliant
• 3 Year Warranty
• Made in the USA
Background Music
• Capable of broadcasting from a supplied BGM source
• Unique supervision method allows for full system supervision
even during background music (BGM)
• Line Level input for music source
• Frequency Response 100 - 15KHz
General Paging
• Easily interfaces with most existing phone system page port, CO
port and line level signals
• Automatically mutes BGM
• Frequency Response 275 - 6.5kHz
• Night ringer or security alert connection
Voice Evacuation
• Complies to NFPA-72 requirements
• Supervised NAC speaker and strobe circuits
• Live microphone override
• 8 digitally pre-recorded voice messages
• Uses selectable pre-tones for messages
Strobe Inputs and Activation
• 2 Amps of 24 VDC supervised strobe power with built-in
Wheelock sync protocol. Power limited.
• Strobe output is selectable for control of Wheelock sync
protocol or non-sync operation
• Strobe terminals have pass thru capability for Wheelock sync
or non-sync operation
• Any of the 8 messages can be dip switch selected to activate
strobes
• Microphone activation can be dip switch selected to activate
strobes
• Auxiliary activation (Remote MIC) can be dip switch selected to
activate strobes
• 24 VDC supervised and synchronized strobe power can be
expanded to meet the requirements of the installation via
Speaker Output
• 40 watts of supervised audio power
2
• Speaker outputs: 25V or 70.7V power limited
Page 3
Audio Processing
• Volume and tone controls for general paging and BGM
• Connectability of optional speaker splitter modules
• Dual-tone tone generator with: Code 3 Tone and Slow Whoop for alerting
of system trouble
• Night ringer/security alerting capability
• Audio power can be expanded by connecting to optional audio power
boosters
-SPB-80/4 80 Watt Supervised Audio Power Booster with 4 Amp
of Synchronized Strobe Power
-SPB-160 160 Watt Supervised Audio Power Booster
-SPB-320 320 Watt Supervised Audio Power Booster
Live & Pre-recorded Message Announcement
• Supplied with 8 pre-recorded emergency messages
• Capable of in-field recording of all messages via 1/8” line level audio input
jack
• Preset audio levels for emergency messaging (prerecorded and live mic) -
system reverts back to a pre set level regardless of the volume set for BGM
or general paging
• On board Push-to-Talk Microphone
• Telephone paging input, disconnects BGM when in use
• Auxiliary input for Remote Microphone connection
Benefits and Advantages of the Multi-Function SAFEPATH4
• One System Multi-Function Facility Communications System
• Background Music (BGM) system, with patent pending supervision during BGM
operation
• Supervised Emergency/Fire Voice Evacuation System
• Interfaces with telephone system for general paging requirements
• Built in power for visual notification appliances e.g., Strobes
• Expandable for larger system requirements (with optional equipment)
Power Supply & Batteries
• 24 VDC, 33AH Max rechargeable battery back-up power circuitry
built-in
• Batteries can be housed in the enclosure (Up to two (BAT-1212),
12 volt, 12 ampere hour batteries can fit in the enclosure.
Actual battery size required will depend on speaker and/or strobe
Installation/Maintenance
• Multiple trouble LED indicators for quick system diagnostics
• Fully supervised circuitry always in effect – even during BGM and
general paging (via patent pending technology)
• Removable quick connect/disconnect terminals for ease of wiring,
accepts #12 to #22 AWG
• Power limited circuitry with Class “B” or Class “A” wiring. Class “A”
only with use of Audio Splitter
• Surge protected circuitry
Compatible Wheelock Products
All Wheelock Speaker/Strobes
All Wheelock Strobes
All Wheelock Speakers
All Cluster Speakers
Wheelock Strobe Power Supply
Inputs – Audio and Activation
Priority Ordered Inputs
Priority
Level
Type of Input
On Board Microphone1 Push to Talk (PTT) Microphone
Auxiliary2Remote Microphone or Remote Microphone Expander
Digital Message Input 13
Digital Message Input 24
Digital Message Input 35
Digital Message Input 46
Digital Message Input 57
Contact Closure activation
Digital Message Input 68
Digital Message Input 79
Digital Message Input 810
Night Ringer Input11Contact Closure input
Telephone Paging Input12Page port input
Background Music Input13Line Level Input, 600 ohm, input voltage must be less then 2.5 V peak to peak, or .3 volts RMS
Audio/Technical Specifications
Switch mode, Class D amplifier (40 Watts)
Speaker Outputs25V or 70.7V power limited
Voice: 275 Hz – 6.5 kHz
Frequency Response
BGM: 100 Hz - 15 kHz
Meets UL Voice Evacuation
Requirements of 800 - 2800 Hz
Signal to Noise Ratiobetter than 65 dB
Mechanical
Dimensions
Weight
Finish
21” H x 16” W x 6” D
(wall mount)
36 lbs.
(without batteries)
Red or black exterior
enclosure
Door LockWheelock Key-lock
Dynamic Rangebetter than 65 dB
Total Harmonic Distortion less than 2%
Stand by Current Draw140 mA
Alarm Current Draw4.7 amps
3
Page 4
Ordering Information
Model
Number
SP40S9929
SP40S-B9935Same as above but with black enclosure
SP40SE6138Same as above but with 220 VAC input
SP40SE-B6139Same as above but with 220 VAC input and black enclosure
AM-SP40S-SMK9937SP40S After Market 8 Message Standard Message Kit
AM-SP40S-PMK9938SP40S After Market 8 Message Programmed Message Kit
AM-SP40S-NBT9939SP40S After Market Narrow Band Signal Tone Kit
SP-COA9908
BATC-R5414Battery Cabinet, Red
BATC-B5413Battery Cabinet, Black
BAT-1224739112 Volt, 24Ampere Battery Cell
Order
Code
Description
Multi-Function Supervised Paging, Messaging, Background Music delivery and Emergency Voice Evacuation System with 24 VDC battery backup circuitry. Single channel system with 40 watts of supervised
audio power and 2 amps of supervised 24 VDC synchronized strobe power and 8 standard messages.
(batteries not included, 2 required) Red Enclosure
C.O. Port Adapter for the SP40S - Recommended 24 VDC Power Supply is Wheelock RPS-2406 (Order
Code 3770)
Message Capabilities
Message
and
Priority #
1
2
3FireMale
4Emergency Female
5EmergencyMale
6WeatherMale
7All ClearMale
8TestMale
Type of
Message
Fire
(do not use
elevators)
Fire
(do not use
elevators)
Voice
Type
Male
Female
Message Script
Three (3) rounds of code 3 horn (followed by): “May I have your attention please! A fire
emergency has been reported in the building. While this is being verified, please leave the
building by the nearest exit. Do not use the elevators.”
Three (3) rounds of code 3 horn (followed by): “May I have your attention please! A fire
emergency has been reported in the building. While this is being verified, please leave the
building by the nearest exit. Do not use the elevators.”
Three (3) rounds of code 3 horn (followed by): “May I have your attention please! A fire
emergency has been reported in the building. While this is being verified, please leave the
building by the nearest exit.”
Three (3) rounds of code 3 horn (followed by): “May I have your attention please! A fire
emergency has been reported in the building. While this is being verified, please leave the
building by the nearest exit.”
Three (3) rounds of code 3 horn (followed by): “May I have your attention please! A fire
emergency has been reported in the building. While this is being verified, please leave the
building and report to the designated assembly area for your group.”
Five (5) seconds of 1kHz tone (followed by): “May I have your attention please! The National
Weather Service has issued a severe weather warning for our area.”
Five (5) seconds of 1kHz tone (followed by): “May I have your attention please! The building
emergency has ended. An all clear has been given. Please resume normal activities.”
Five (5) seconds of 1kHz tone (followed by). “May I have your attention please! This is a test of
the Wheelock evacuation system, repeat, this is only a test.”
• Each message can be selected to have a code 3 pre-alert tone, a 1kHz continuous pre-alert tone, or no pre-alert tone
• Post-tones are also selectable and match the pre-tones for individual messages
• Any of the 8 messages are field programmable to record your own custom message
• Each message length is 30 seconds
• A 1/8” line level audio input jack is supplied for message recording
• A two step recording procedure is required to ensure and verify that the standard message will be permanently erased
• Factory programmed messages are available for custom messages
• Contact customer service for additional information
• Form is required and can be downloaded from www.wheelockinc.com
Note: For telephone
(C.O. Port Adapter for the SP40S) may be used to connect the SP40S to an unused C.O. port or stand-alone telephone.
Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained
and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and
in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and
testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association
(NFPA), Underwriters’ Laboratories (UL), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state,
county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not
limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ).
4
Page 5
2-Zone Class A
or
4-Zone Class B
Speaker Audio Splitter
For operation with SAFEPATH®4 Family of Products:
SP40S, SP40/2, SPB-320, SPB-160, SPB-80/4
Description:
Supervised 2-Zone Class A or 4-Zone Class B Speaker Audio
Splitter for the SP40S, SP40/2 or Audio Boosters. Enables
a single supervised speaker audio output to drive up to two
Class A supervised speaker audio outputs or four Class B
supervised speaker audio outputs.
Applications:
• Provides for expansion of one zone to up to 2 zones of supervised speaker audio output in Class A
• Provides for expansion of one zone to up to 4 zones
of supervised speaker audio output in Class B
Ordering Information:
Model
SP4Z-A/B9900
SPMB4Z9907
No te: Th e Spe aker Splitt er-M ounting Bracket
(SPMB4Z) is required when the Speaker Splitter is
used in Audio Boosters. The SPMB4Z can support
two splitters.
Order
Code Description
Supervised 2-Zone Class A or 4-Zone
Class B Speaker Audio Splitter for the
SP40S, SP40/2 or Audio Boosters
Mounting Bracket for the SP4Z-A/B
is required when used with the Audio
Boosters
SAFEPATH®4
2-Zone Class A or 4-Zone Class B
Speaker Audio Splitter
Features:
• Approvals: UL Standard 864, 9th edition, and
California State Fire Marshal (CSFM), New York
City (MEA)
•Expands one zone to up to 2 zones of supervised
speaker audio output in Class A
•Expands one zone to up to 4 zones of supervised
speaker audio output in Class B
• Each Class A zone can accept up to 40 watts of
audio
•Each Class B zone can accept up to 40 watts of
audio
• Operates on either 25V or 70.7V RMS
• Mounts inside the enclosure of the SP40S, SP40/2
or Audio Boosters
• Power and Trouble LED’s
• Individual zone short and open LED indication
• Capable of detecting wiring faults
• Removable wiring terminals for quick connect/
disconnect accepting 12–22 AWG
• All output circuitry is Power Limited
• Space provided to allow for naming of the zones
• Powered by 24VDC, supplied by the either the
SP40S, SP40/2 or Audio Boosters
•Standby and Alarm current at 24VDC is 15mA
5
Page 6
SAFEPATH
®
4
Audio Boosters
SPB-320 320 Watt Supervised Audio Power
Booster (Four 80 watt circuits)
SPB-160 160 Watt Supervised Audio
Power Booster (Two 80 watt circuits)
SPB-80/4 80 Watt Supervised Audio
Power Booster with 4 Amps of
Supervised and Synchronizable
Strobe Power (Two 2 Amp circuits)
Description
Supervised Facility Communication and Emergency Voice
Evacuation Audio and Audio/Strobe Power Boosters, UL
Standard 1711 and UL Standard 864, 9th edition with
24VDC battery backup capabilities. Designed to provide
for additional supervised audio power for live voice, prerecorded messages or background music (BGM). Fully
supervised patent pending circuitry is always in effect even
during BGM. The SPB-80/4 also provides 4 Amps of 24 VDC
Supervised and Synchronized Strobe Power.
The SPB-320, SPB-160 and the SPB-80/4 easily connects
to the Wheelock SP40S or SP40/2. Multiple SPB-320, SPB160 and SPB-80/4 Audio Boosters can be inter-connected
to accommodate large installations with supervised audio
power and also supervised and synchronized strobe power
requirements.
The SPB-320 draws 2.4 watts of audio input power to
properly operate and provide additional supervised audio
output power. The SPB-160 and the SPB-80/4 draws 1.2
watts of audio input power to properly operate and provide
additional supervised audio output power. A maximum of
5,280 watts of supervised audio power can be achieved.
Additional strobe power can be obtained via a combination
of SPB-80/4 or Wheelock Power Supplies/Chargers.
Applications
• Provides for additional supervised audio power for
large installations
• Provides for additional supervised and synchronizable
strobe power for large installations
• Can be used in new construction as well
as in retrofit construction
SPB-320
SPB-80/4
SPB-160
Features
Approvals & Compliance
• Approvals: UL Standard 864, 9th edition, UL
Standard 1711, California State Fire Marshal
(CSFM), New York City (MEA)
• OSHA 1910.165, ADA and UFC compliant
• 3 year warranty
System Activation: Audio
• 70V or 25V input from the SP40S or SP40/2
• 1 Volt input from SP4-RMX
System Activation: Strobe (SPB-80/4)
Power Supply & Batteries
• Fully supervised patent pending circuitry always in
effect even during BGM
• Power limited circuitry
• Class D amplifiers
• Internal battery charger and power supply
• Required batteries fit inside the enclosure (sold separately)
• SPB-320 requires four 12 VDC, 12 AH batteries
• SPB-160 and SPB-80/4 require two 12 VDC, 12 AH
batteries
Outputs:
• SPB-320 has four 80 watt speaker output circuits
• SPB-160 has two 80 watt speaker output circuits
• SPB-80/4 has one 80 watt speaker output circuit and
two 2 amp strobe circuits (4 amps total)
• Supervised Audio Speaker outputs: 70V or 25V field selectable (all boosters must be either 70 V or
25 V)
• Expansion output (supervised, 24VDC at .5A in alarm
condition) used for connecting multiple boosters
• DC output (unsupervised for optional splitter power).
Each speaker circuit (four for the SPB-320, two for the
SPB-160, one for the SPB-80/4) can connect to speaker splitters
6
Page 7
SPB-80/4 Strobe Features:
• Two 24VDC 2 Amps, NAC supervised, synchronizable,
power limited, Class B strobe outputs
• Selectable outputs; Wheelock sync, pass through, or
constant DC
• Trouble LED’s for open and short output conditions
• Alarm indicator: LED’s for Strobe and Expansion Outputs
Inputs:
• Audio Speaker Inputs: 70V or 25V, field selectable
• Auxiliary in (for alarm input signal)
Mechanical:
SPB-160, SPB-80/4
• Dimensions: 21” H x 16” W x 6” D (wall mount)
• Weight: 36 lbs. (without batteries)
• Finish: Red exterior enclosure
• Door Lock: Wheelock key-lock
SPB-320
• Dimensions: 36” H x 24” W x 6” D (wall mount)
• Weight: 80 lbs. (without batteries)
• Finish: Red or black exterior enclosure
• Door Lock: Wheelock key-lock
Technical Specifications:
• 120VAC, 3.8A, 60 Hz input
• SP40SE Models 240 VAC, 2.5A, 50-60 Hz
• Standby current draw: 120mA, per amplifier board
• Alarm current draw: 9 Amps, per amplifier board
SPB-80/4 and SPB-160 have one amplifier board
SPB-320 has two amplifier boards
• System Frequency Response:
Voice 400 Hz - 6.5 kHz
• Multiple LED’s for easy indication of system diagnostic
conditions
• Signal to Noise Ratio: > 70 dB
• Dynamic Range: > 65 dB
• Total Harmonic Distortion: 2%
Note: The Speaker Splitter-Mounting Bracket
(SPMB4Z) is required when the Speaker Splitter is
used in Audio Boosters. The SPMB4Z can support
two splitters.
Ordering Information
Model
SPB-3209918320 Watt Supervised Audio Power Booster (Four 80 watt circuits)
SPB-1608989 160 Watt Supervised Audio Power Booster (Two 80 watt circuits), red enclosure
SPB-160-B9930160 Watt Supervised Audio Power Booster (Two 80 watt circuits), black enclosure
SPB-80/4
SPB-80/4-B
Order
Code
9908C.O. Port Adapter for the SP40S or SP40/2 - Recommended 24 VDC Power Supply is Wheelock RPS-
9900Supervised 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter for the SP40S, SP40/2 or Audio
898880 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronized Strobe Power
993180 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronized Strobe Power
Description
Multi-Function Supervised Paging, Messaging, Background Music and Emergency Voice Evacuation
System with 24 VDC battery backup circuitry. Single channel system with 40 watts of supervised
audio power and 2 amps of supervised 24 VDC synchronized strobe power and 8 standard messages.
(batteries not included, 2 required) Red enclosure
2406 (Order Code 3770)
Boosters
(Two 2 Amp circuits), red enclosure
(Two 2 Amp circuits), black enclosure
SP4Z-A/B9900Supervised 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter for the SP40S, SP40/2, SPB-320,
SPB-160 or SPB-80/4
SPMB4Z9907 Speaker Splitter Mounting Bracket for SPB-320, SPB-160 or SPB-80/4
SP4Z-APS9920Addressable Paging Splitter
SP4-TZC9921 Telephone Zone Controller
TZC-USB9923 SP4-TZC Programming Cable
SP-SVC9926Supervised Volume Control for use with the SAFEPATH®4 System
SPRM8996
SPRM-GP9927General Paging Microphone for use with the SPB-320, SPB-160 or SPB-80/4, black plate
BATC-R5414Battery Cabinet, Red
BATC-B5413Battery Cabinet, Black
BAT-1212739012 Volt, 12 Ampere Battery Cell
BAT-1224739112 Volt, 24Ampere Battery Cell
BAT-1265739212 Volt, 65 Ampere Battery Cell
Remote Microphone for use with the SP40S, SP40/2, SPB-320, SPB-160, SPB-80/4 or SP4-RMX, red
plate
13
Page 14
Architects and Engineers Specifications
SP40S Facility Communications System
The system shall be a multi-purpose NFPA compliant, supervised, general-purpose audio, and fire/emergency evacuation system.
The system shall be a single channel voice evacuation system incorporating supervision during the broadcasting of background music
and general paging. The system shall be capable of delivering 40 watts of supervised audio power and 2 amps of supervised 24 VDC
synchronized strobe power. Minimum supervised audio power shall be 40 watts, expandable to 5280 watts, depending on system
configuration and with additional modules and power boosters. Supervised 24 VDC synchronized strobe power shall be 2 amps,
expandable to the requirements of the installation. The system shall be capable of operating from a 120 VAC power source. E models
shall be capable of operating from a 240 VAC power source. All models shall have a 24 VDC battery backup. Standard on-board system
features shall include: digital voice messaging, a hand-held push-to-talk microphone with override priority, and a power supply/battery
charger. The system shall be capable of interfacing with telephone systems for general paging announcements and will have night
ringer capabilities. Form C contacts shall be provided for system alarm and trouble conditions.
The system shall have 8 message contacts with contact closure activation. Background music input voltage shall be capable of
handling less then 2.5 V peak to peak or less then .3 volts. The system shall have thirteen priority ordered inputs, including: On Board
Microphone, Auxiliary Input (Line Level), 8 Digital Messages, Night Ringer Input, Telephone Paging Input, and Background Music Input.
The system shall have preset audio levels for emergency messaging (prerecorded and live mic). The system shall revert back to a
preset level regardless of the volume set for background music (BGM) or general paging. Background music inputs can be an AM/FM
tuner, cassette, CD, MP3, or any other remote source. The system shall be supplied with 8 pre-recorded messages and be capable of
in-field recording of customer unique messages. The system shall have a dual-tone tone generator with Code-3 Tone and Slow Whoop.
When the system is on battery power, telephone page, night ring and background music shall be disengaged.
The panel shall have power-limited circuitry with an internal battery charger and power supply. The power supply/charger section shall
be able to charge 24 VDC batteries with a maximum capacity of 33 amp hours. Up to two 12 VDC, 12 AH batteries may be housed in
the enclosure. Batteries larger than 12 Ah shall be housed in a separate enclosure such as the Cooper Wheelock BATC or equivalent.
Batteris shall be supplied separately.
The system shall have power limited circuitry and class B wiring. Wiring terminal blocks will be removable and accept #22 - #12 AWG
wire. Audio output voltage shall be selectable for 25V or 70.7V. The voice (live microphone or recorded message) frequency response
shall be 275 Hz – 6.5 kHz, background music frequency response shall be 100 Hz - 15 kHz. Stand by current draw shall be 140mA.
Alarm current draw shall be 4.7 amps. The signal to noise ratio shall be better than 65 dB, dynamic range shall be better than 65 dB,
total harmonic distortion shall be less than 2%.
The system shall be wall mountable, enclosed in a steel locking enclosure. The required batteries for 40-watt systems shall fit inside
the enclosure. The 40 watt system shall weigh no more than 36 lbs (without batteries) and its dimensions shall not exceed 21” H x 16”
W x 6” D. The system shall be made in the USA. Approvals for the system shall include: UL Standard 864, 9th edition, UL Standard
1711, FCC part 15, California State Fire Marshal (CSFM) and New York City (MEA). The system shall be OSHA 1910.165 and ADA
compliant. 3 Year Warranty.
SAFEPATH®4 Audio Boosters
The Wheelock SPB-320, SPB-160 and SPB-80/4 Audio Boosters shall be NFPA compliant supervised audio and supervised 24VDC
synchronized strobe power boosters (some models will have supervised 24VDC synchronized strobe booster capability). The booster
shall have 24VDC battery backup capabilities. The booster shall have the capability to supervise the circuitry during playback of
background music. The booster shall have the capability to be inter-connected to accommodate large installations with supervised
audio power and also supervised and synchronized strobe power requirements. Three versions of the booster shall be made available:
SPB-80/4, (80 watts of supervised audio power and 4 amps of supervised and synchronized strobe power), SPB-160 (160 watts of
supervised audio) or SPB-320 (320 watts of supervised audio).
Each booster shall use 1.2 watts of audio input power (The SPB-320 requires 2.4 watts of audio power) to properly operate and provide
additional supervised audio output power. A combination of boosters can be added together to provide for a maximum of 5,280 watts of
supervised audio power. Additional strobe power can be obtained via a combination of boosters. The audio section of the booster shall
be connected via a selectable 70V or 25V input from the Wheelock SP40S. The strobe section of the booster shall be divided into two
sections each supplying two Amps of 24VDC, NAC, supervised, synchronizable, power limited, Class B strobe outputs, with selectable
outputs offering Wheelock sync, pass through, or constant DC and can be activated via 8-33VDC NAC input or contact closure.
The internal battery charger/power supply shall be capable of charging 24 VDC batteries with a maximum capacity of 33 amp hours.
The enclosure shall be capable of housing the correct number of 12 VDC rechargeable batteries (SPB-80/4 (2), SPB-160 (2), SPB-320
(4)) with a maximum capacity of 12 Amp hours. Batteries with a larger capacity require an external battery enclosure(s) such as the
Cooper Wheelock BATC or equivalent.
The boosters shall have power-limited circuitry and be a class D amplifier with an internal battery charger and power supply. The required
batteries (purchased separately) shall fit inside the enclosure (two 12VDC, 12 AH for the SPB-80/4 or SPB-160 and four 12 VDC, 12 AH
for the SPB-320). The booster shall operate on 120VAC, 3.8A, 50 – 60 Hz input. E model boosters shall operate on 240 VAC, 2.5A, 50
– 60 Hz input. The SPB-80/4 or SPB-160 standby current draw shall be 120mA and alarm current draw shall be 9 Amps. The SPB-320
consists of two SPB-160’s. Each SPB-160 shall have its own power supply and battery charger. The voice frequency response shall
be 400 Hz – 6.5 kHz +/- 3 dB, the BGM frequency response shall be 275 Hz - 15 kHz +/- 3 dB. Removable quick connect/disconnect
terminals that accept 12 -22 AWG shall be used. Multiple LED’s for easy indication of system diagnostic conditions shall be present
on the PC board. The Signal to Noise Ratio shall be > 70 dB, the dynamic range shall be > 65 dB, the Total Harmonic Distortion spec
shall be 2%.
The booster shall be wall mountable, enclosed in a steel locking enclosure, with a red finish. The booster shall be made in the USA.
Approvals for the booster shall include; UL Standard 864, 9th edition, UL Standard 1711, CSFM and MEA. The booster shall be OSHA
1910.165 and ADA compliant. The booster shall carry a 3 year warranty.
14
Page 15
Architects and Engineers Specifications
4 Zone Class B Speaker Splitter
The Wheelock SP4Z-A/B shall be UL Standard 864, 9th edition, California State Fire Marshal (CSFM) and New York City (MEA)
approved, 2-Zone Class A or 4-Zone Class B Speaker Splitter for operation with the Wheelock, SP40S, SP40/2, SPB-80/4, SPB160 and SPB-320. The SP4Z-A/B shall enable a single supervised speaker audio output to drive up to two Class A supervised
speaker audio outputs or four Class B supervised speaker audio outputs. Each Class A zone shall be capable of accepting up to
40 watts and operate on either 25 or 70.7V RMS of audio input. Each Class B zone shall be capable of accepting up to 40 watts of
audio and operate on either 25 or 70.7V RMS of audio input. The SP4Z-A/B shall be capable of supporting live microphone paging,
prerecorded emergency voice evacuation messages, supervised background music and general paging announcements.
The SP4Z-A/B shall mount inside the enclosure of the SP40S, SP40/2, SPB-80/4, SPB-160 and SPB-320 and shall have power and
trouble LED’s with individual zone short and open LED indication. The SP4Z-A/B shall be capable of detecting wiring faults. The
SP4Z-A/B shall be powered by 24VDC, which is to be supplied by the SP40S, SP40/2, SPB-80/4, SPB-160 or SPB-320. Standby
and Alarm current at 24VDC shall be 15mA. Removable wiring terminals for quick connect/disconnect accepting 12–22 AWG shall
be incorporated. All output circuitry shall be power limited. Space shall be provided to allow for naming of the zones.
Addressable Paging Splitter and Telephone Zone Controller
The Wheelock Addressable Paging Splitter (SP4-APS) and Telephone Zone Controller (SP4-TZC) shall be used to control and
direct telephone paging and background music zones connected to the SAFEPATH4 Multi-Function Facility Communication System
using an RS485 connection.
The Addressable Paging Splitter (SP4-APS) shall be UL Standard 864, 9th edition and California State Fire Marshal (CSFM)
approved, addressable and supervised 2-zone Class A or 4-zone Class B Speaker splitter. The SP4-APS shall be used with
Wheelock’s SP40S or SP40/2 panel and the Audio Booster (SPB-160, SPB-80/4, and SPB-320) panels. Each SP4-APS shall have
a single audio input capable of 25 Vrms or 70.7 Vrms at a maximum of 80 Watts. The input audio power shall be distributed to the
zone connections with the total not exceeding the input and no zone exceeding 40 Watts. When audio boosters are connected,
each audio booster module shall consume 1.2 Watts from the total input power of the SP4-APS. The splitter shall be mounted
inside the SP40S, SP40/2 or Audio Booster that it is associated with, and it shall operate on 24VDC supplied
module. The SP4-APS shall contain 16 LED indicators used to monitor and troubleshoot the module.
The Telephone Zone Controller Module (SP4-TZC) shall be used to address the output zones on the SP4-APS. The SP4-TZC shall
be capable of supporting 17 SP4-APS speaker splitter modules and shall be capable of addressing all zones at once (“All Call”), a
maximum of 68 separate zones, 17 fixed zone groups and 9 programmed logical zone groups. This shall be accomplished using
two digit DTMF tones from a page port, an unused CO port, or a stand alone telephone with a loop start circuit. Also, the SP4TZC shall be able to select zones for background music. The SP4-TZC has the following inputs: Power, USB port, Background
Music (BGM), Page Audio in. The outputs are: Audio out and RS485 Digital Control. The basic operating parameters of the SP4APS shall be pre-programmed. Customized programming shall be accomplished using a USB cable and programming computer
software. The SP4-TZC shall be powered using a 24VDC filtered and regulated power supply such as the Wheelock RPS-2406.
The Controller Module assembly is mounted in a metal enclosure measuring 13”L x 7 5/8”W x 2”D.
by the supported
Supervised Volume Control
The Wheelock SP-SVC shall be UL Standard 864, 9th edition approved, supervised volume control for use with the SAPEPATH®4
Facility Communications System.
The SP-SVC shall provide for manual volume setting for telephone paging and background music for a specific speaker or speaker
zone. The selected adjustment will not affect the volume setting of emergency prerecorded messages or live microphone usage.
The SP-SVC shall be capable of handling up to 35 watts of audio power @ 70.7 volts or 4 watts audio power @ 25 volts and shall
operate on either 70.7 or 25 volt input from an SP40S or Audio Booster. The SP-SVC shall be capable of operating in Class B or
Class A wiring configurations (for Class A, the SP4-APS is required). The SP-SVC shall receive operating power from an Audio
Booster, SP40S or SP40/2. Volume adjustment settings shall be off, 1 – 10, in 3dB increments. The SP-SVC shall be supplied
with a stainless steel mounting plate with a black knob and require a double gang, 3½” deep back box for mounting.
Remote Microphone
The Wheelock SPRM shall be UL Standard 864, 9th edition and California State Fire Marshal (CSFM) approved, Remote
Microphone for use with the SAPEPATH®4 Facility Communications System.
The SPRM shall be a supervised hand held push to talk microphone and a key shall be required to enable remote microphone
use. (Same key as SP40S or SP40/2) Removable wiring terminals for quick connect/disconnect accepting 12 – 22 AWG shall be
incorporated. All output circuitry shall be power limited. Individual front panel LED’s shall be provided for indication of System
Normal, System Trouble and Alarm. Multiple on board diagnostic LED’s shall be provided. When used with the SP40S or SP40/2,
the priority level shall be number two. Remote microphone usage shall disengage background music and general paging.
Voice frequency response shall be 275 Hz - 6.5 kHz +/- 2.4 dB. Power requirements shall be 24VDC and will be supplied by the
SP40S or SP40/2. Input current for Standby shall be 26mA and for Alarm 38mA. Audio output level shall be 1.05V RMA. There
shall be a 6-wire connection to the SP40S or SP40/2. The mounting plate shall be red and measure, 8 3/4” x 5 ¼”, and shall fit
into a 4 gang back box.
15
Page 16
Remote Microphone Expansion Module
The Wheelock SP4-RMX Remote Microphone Expansion Module shall be UL Standard 864, 9th edition and California State Fire Marshal
(CSFM) approved for use with the SAPEPATH®4 SP40S Facility Communications System.
The SP4-RMX shall be a supervised outboard expansion module for use with the SAPEPATH®4 system. It shall be used to expand
the number of optional supervised Remote Microphone (SPRM) modules up to three. Two SP4-RMX Remote Microphone Expansion
Modules can be connected to the SP40S or SP40/2 and shall have the capability of providing the SP40S or SP40/2 with up to six system
wide “All Call” Remote Microphone (SPRM) modules*. The SP4-RMX can be programmed to provide either priority override for each
SPRM module input or First In First Out. First In First Out allows the active SPRM to complete its communication before another SPRM
can be used. All output circuitry shall be power limited. Multiple on board diagnostic LED indicators shall be provided. All wiring shall be
connected to the module using quick connect/disconnect wiring terminals, capable of accepting 12 – 22 AWG wiring.
The SP4-RMX PCB assembly is mounted in a metal enclosure measuring 13”L x 7 5/8”W x 2”D. The SP4-RMX can support each SPRM
at a range up to 2000 feet.
*The SP4-RMX can also be connected to Audio Booster for general (non-alarm) paging with use of SPRM-GP.
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in
accordance with Wheelock Inc. standard terms and conditions.
Note: Refer to the products Installation Instructions for proper installation, wiring procedures and any additional specifications.