273 Branchport Avenue
Long Branch, N.J. 07740
(800) 631-2148 Thank you for using our products.
www.cooperwheelock.com
INSTALLATION INSTRUCTIONS
CLASS A/B SPLITTER
(FOR SP40S AND SPB-160/SPB-80/4)
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
MODEL NUMBER:
109900 SP4Z-A/B
GENERAL:
The Class A/B Splitter (SP4Z-A/B) is designed to be used with Wheelock’s SP40S SAFEPATH4 panel and the SAFEPATH4 Audio Booster (SPB-160 and SPB-80/4)
panels. The SP4Z-A/B provides a means for expanding one supervised audio output zone to four Class B or two Class A zones. The SP4Z-A/B is UL Listed under
Standard 864, Control Units for Fire Protective Signaling Systems. They are for indoor use only.
One SP4Z-A/B can be connected to the SP40S panel. It is to be mounted inside the panel enclosure onto the standoffs on the SP40S board. Two SP4Z-A/B's can be
connected to the SPB-160. One SP4Z-A/B can be connected to the SPB-80/4. It is to be mounted inside the SPB-160 or SPB-80/4 panel on the Splitter Mounting
Bracket (SPMB-4Z - purchased separately) mounted over the 24VDC Power Supply (SPBPS). The SP4Z-A/B has a maximum power output per zone that cannot exceed
what is listed in Table 1.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
. All warnings are printed in bold capital letters.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF
THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY
OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Table 1: Specifications
Class A
Audio Output Voltage 25.0V 70.7V
Maximum Output Power Per Zone 40.0W 40.0W
Operating Voltage 24VDC
Standby/Alarm Current at 24VDC 15mA
Minimum Ground Fault Sensitivity 20 k Ohms
Class B Maximum Output Power Per Zone 40W 40W
WIRING INSTRUCTIONS:
NOTE: The terminal blocks on the SP4Z-A/B are removable. To remove a terminal block, pull the block straight up from the circuit board as shown in Figure 1. Attach
wires to the desired connections, then plug the terminal block back on the board being careful to match and align the pins.
Copyright 2007 Cooper Wheelock, Inc. All rights reserved.
Figure 1: Removable Terminal Block
P84205 Rev. P
Sheet 1 of 9
MOUNTING INSTRUCTIONS: (SP40S)
Figure 2 shows the mounting location of the SP4Z-A/B Splitter to the SP40S panel. Figure 3 shows the correct mounting procedure.
SP4Z - A /B
MOUNTING STUDS
Figure 2:
Mounting Location
RIGHT
SIDE
TOP
MOUNTING SCREW (4)
SP4Z-A/B COVER
COVER STANDOFFS (4)
SP4Z-A/B PC BOARD
SP4Z-A/B STANDOFFS(4)
SP40S PC BOARD
SP40S ENCLOSURE
SP4Z-A/B Mounting in SP40S Enclosure
Figure 3:
1. Install 4 standoffs through the SP40s board to the 4 mounting studs of the SP40S enclosure.
2. Position the SP4Z-A/B PC board with the terminal blocks pointing to the top of the SP40S enclosure and align the mounting holes on the PC board with the
mounting studs.
3. Screw the male end of the 4 cover standoffs through the SP4Z-A/B PC board and to the 4 standoff installed in Step 1. Tighten standoffs snug.
4. Attach wiring in accordance with the wiring section of this installation instruction.
5. Align the SP4Z-A/B cover with the holes in the cover standoffs and mount the cover using the 4 mounting screws. Tighten the screws hand tight.
P84205 Rev. P
Sheet 2 of 9
MOUNTING INSTRUCTIONS: (SPB-160 and SPB-80/4)
Figure 4 shows the mounting location of the SP4Z-A/B Splitter to the Splitter Mounting Bracket (SPMB-4Z - purchased separately). Figure 5 shows the correct
mounting procedure.
24VDC POWER
SUPPLY (SAPS)
TB2
N
OUT
POWER
TROUBLE
24VDC
CLASS B WIRING
CLASS A WIRING
+
-
-
+
+-+
AUD
Z1
IN
ZONE1ZONE2ZONE3ZONE
ZONE1ZONE
L
N
-
-
+
Z4
ZONE
4
ZONE
2
ZONE
ZONE
POWER
TROUBLE
CLASS B WIRING
+
24VDC
CLASS A WIRING
-
-
+-+
Z2
Z3 Z4
4
2
-+-
+
+
+
AUD
Z2 Z3
Z1
IN
ZONE
ZONEZONE
2 3
1
ZONE
1
SPLITTER MOUNTING
BRACKET (SPMB-4Z)
SPLITTER (SP4Z-A/B)
Figure 4 :
SP4 Z-A/B Mou n ting Lo c a tion for th e SPB -8 0 /4 and SPB -1 6 0
SPLITTER COVER
SPLITTER BOARD
(4) #6-32 SCREW
(4) HEX M/F SPACER
(4) LOCKING F S PACER
SPLITTER MTG BRKT
(4) #8-32 KEPS NUT
Figu r e 5 :
Mo u n tin g Diagr am for SP4Z-A/B Splitte r a n d S PMB-4Z Mou n tin g Brack e t
1. Mount the Splitter Mounting Bracket (SPMB-4Z) to the SPB-160 or SPB-80/4 according to installation instructions (P84252).
2. Install the 4 nylon Locking Female Spacers to the mounting bracket by pushing them into place.
3. Position the SP4Z-A/B PC board with the terminal blocks pointing to the top of the Audio Booster enclosure and align the mounting holes on the PC board with the
mounting studs.
4. Screw the male end of the 4 Hex M/F Spacers through the SP4Z-A/B PC board and to the 4 Locking Female Spacers on the SPMB-4Z. Tighten standoffs snug plus
¼ turn.
5. Attach wiring in accordance with the wiring section of this installation instruction.
6. Align the SP4Z-A/B Cover with the holes in the cover spacers and mount the cover using the 4 mounting screws. Tighten the screws hand tight.
7. Repeat Steps 2 through 6 when installing second splitter in the SPB-160 Audio Booster.
NOTE: One SPMB-4Z mounting bracket can support two SP4Z-A/B splitters.
WIRING INSTRUCTIONS:
WARNING: SHUT OFF ALL POWER BEFORE STARTING THE INSTALLATION. ELECTRICAL SHOCK CAN CAUSE DEATH OR SERIOUS
INJURY.
CAUTION: Do not move jumpers while the unit is powered on. Doing so may damage the Splitter.
Jumper Plugs J1 and J3 must be set for either Class A or Class B Wiring (Figures 6A and 6B).
NOTE: Factory setting is for Class B Wiring.
P84205 Rev. P
Sheet 3 of 9