Part Number P84714 Revision D
Assembly Number A84715-001 Revision B
Copyright 2007 Printed in U.S.A. All rights reserved.
About Cooper Wheelock, Inc.: Cooper Wheelock, Inc. fulfills its mission of
Helping People Take Action by providing high
quality and advanced products and services for
the life safety, communications, and security
markets. Cooper Wheelock has served the
needs of commercial, educational, industrial,
health care, and government users for more
than eighty-five years.
Today the company continues to focus on
designing and manufacturing advanced
technological products to meet the world’s
needs for Emergency Incident Management
and Notification, Multi-Function Communications, and Mass Notification.
For more information, contact:Cooper Wheelock, Inc.
273 Branchport Avenue
Long Branch, NJ 07740-6899
Telephone: (800) 631.2148
Fax: (732) 222.2588
Web Site:
www.cooperwheelock.com
E-Mail: info@cooperwheelock.com
SP40S Multi-Function Facility Communication System Manual, Revision D
ii
Table 4-2. Digital Voice Message Tests.................................................................................... 4-20
Table 5-1. Audio Alarm Conditions and Results ......................................................................... 5-3
Table 8-1. Trouble LED Procedure Cross Reference................................................................... 8-3
SP40S Multi-Function Facility Communication System Manual, Revision D
viii
This page is left blank intentionally.
SP40S Multi-Function Facility Communication System Manual, Revision D
ix
1 Foreword
1.1 Intended Use
This manual is designed to serve the installers and operators of the SP40S Multi-Function Facility
Communication System. All operating instructions, product illustrations, troubleshooting/error
messages, and other relevant information are contained in this manual. It is the user’s
responsibility to ensure that all instructions in this manual are applied strictly.
1.2 Design Change Disclaimer
Due to design changes and product improvements, information in this manual is subject to change
without notice. Cooper Wheelock reserves the right to change product design, including
illustrations and diagrams, at any time without notice to anyone, which may subsequently affect
the contents of this manual.
Cooper Wheelock assumes no responsibility for any errors that may appear in this manual.
Cooper Wheelock will make every reasonable effort to ensure that this manual is up to date and
corresponds with the shipped Cooper Wheelock SP40S Multi-Function Facility Communication
System.
1.3 User Operation Assistance
Should you experience any difficulty in installing or operating your SP40S Multi-Function
Facility Communication System, please contact your Cooper Wheelock representative. The
Troubleshooting chapter in this manual (Chapter 8) includes a list of common system problems,
possible causes, and corrective operator actions. The information given here is general. Feel free
to contact the Technical Support department of Cooper Wheelock at 1-800-631-2148. Hours are
8:00 a.m. - 7:00 p.m. (Eastern Time), Monday through Thursday and 8:00 a.m. –
5:00 p.m. (Eastern Time) on Friday.
SP40S Multi-Function Facility Communication System Manual, Revision D
1
Foreword
1.4 Typographical Notation Conventions
Thank you for using our products. Use this product according to this instruction manual. Please
keep this instruction manual for future reference.
Any material extrapolated from this document or from Cooper Wheelock manuals or other
documents describing the product for use in promotional or advertising claims, or for any
other use, including description of the product's application, operation, installation, and
testing is used at the sole risk of the user and Cooper Wheelock will not have any liability
for such use.
Certain information contained in this manual has been extracted from the NFPA 72 Manual and
the Life Safety Code 101™ Manual.
WARNINGS
WARNING: A Warning indicates a potentially hazardous
situation that, if not avoided, could result in serious personal injury or
death to you or others. Warnings are set off in boldface type, within
boxed rules, indented, and referenced to a warning symbol.
CAUTIONS
CAUTIONS: Indicate a situation in which the equipment could be damaged or a
situation in which not following the instructions correctly could result in the
equipment not working properly. Cautions are set off with a stop sign symbol.
SP40S Multi-Function Facility Communication System Manual, Revision D
2
2 Safety Precautions
2.1 Read This Manual
1. Cooper Wheelock recommends that, before performing any actions to specify, apply,
install, maintain, and operationally test the SP40S Multi-Function Facility
Communication System, personnel properly qualified in the application and use of life
safety equipment read this manual carefully.
2. Keep this manual with the SP40S Multi-Function Facility Communication System for
reference during the life of the product. Make this manual available to all qualified
personnel who operate, test, maintain, or service the SP40S Multi-Function Facility
Communication System. It is strongly recommend that such personnel read and
understand the entire manual.
2.2 Operational Safety
WARNING: If safety precautions, installation, and testing
instructions are not performed properly, the SP40S Multi-Function
Facility Communication Systems may not operate in an emergency
situation, which could result in serious injury or death to you and/or
others.
WARNING: If the protective signaling system sounds and/or
flashes, it is a warning that a possible serious situation requires
immediate attention.
CAUTION: A SP40S Multi-Function Facility Communication System printed
circuit board is sensitive to static electricity and has delicate components mounted
on it.
(a) Before handling the board or any component on it, discharge any static
electricity from your body by touching a grounded object, such as a metal screw,
which is connected to earth ground.
(b) Handle the board by its edges and be careful not to twist or flex it. Install the
SP40S Multi-Function Facility Communication System in a static-free area.
(c) Attach grounded wrist straps properly before touching any static sensitive areas.
(d) After handling a SP40S Multi-Function Facility Communication System printed
circuit board, test the panel as described in section 4.6 to verify that it is functioning
properly.
SP40S Multi-Function Facility Communication System Manual, Revision D
1
Chapter 2: Safety Precautions
NOTE: In areas prone to lighting strikes, using a surge protection device is recommended.
Reference TESAN number S002-99 for recommended manufacturers of surge protection
equipment.
This TESAN (Technical Engineering Support Application Notice) is available from the Cooper
Wheelock website (www.cooperwheelock.com) and is found under the Technical Support tab.
NOTE: This SP40S Multi-Function Facility Communication System
The SP40S Multi-Function Facility Communication System is powered by 120VAC. 24VDC rechargeable batteries provide backup power, should be purchased separately. If both sources of
power are cut off for any reason, the SP40S Multi-Function Facility Communication System
not operate.
1. DO NOT assume any installation, operation, and testing details not shown in this
manual.
CAUTION: DO NOT operate the SP40S Multi-Function Facility Communication
System without the dead front panel being properly in place.
will not work without power.
will
2.2.1 Expected Equipment Lifecycle
Notification equipment cannot last forever. Even though the SP40S Multi-Function Facility
Communication System is expected to last up to ten years, any of its parts or components could
fail before then.
2.2.2 Periodic Testing
1. Cooper Wheelock recommends testing of the entire protective signaling system,
including the SP40S Multi-Function Facility Communication System, all notification
equipment, as well as all messages and their output channel, and priority assignment, at
least twice each year, or more often as required by local, state and federal codes,
regulations and laws, by qualified personnel.
2. If the notification equipment is not working properly, immediately contact the
installer and have all/any problems corrected immediately.
3. Replace any malfunctioning components immediately; do not attempt to repair
malfunctioning components. Return malfunctioning components for factory repair or
replacement. In the event you cannot contact the installer, contact the manufacturer.
WARNING: For proper operation in life safety applications,
perform the following: (a) Connect the SP40S Multi-Function Facility
Communication System to a listed compatible and properly operating
control panel, which controls its activation. (b) Ensure that all
equipment is properly interconnected and operating. (c) Make sure
the installer checks the compatibility of all equipment prior to
installation; otherwise, the SP40S Multi-Function Facility
Communication System and/or the control panel may be damaged
and/or fail to operate in an emergency situation.
SP40S Multi-Function Facility Communication System Manual, Revision D
2
Chapter 2: Safety Precautions
WARNING: Certain hardware functions on the SP40S MultiFunction Facility Communication System are not supervised. If any
such hardware functions fail, the SP40S Multi-Function Facility
Communication System may not provide the intended warning and/or
not indicate a trouble condition.
2.3 Compliance with Applicable Codes,
Regulations, Laws, Standards, and Guidelines
Comply with all of the latest applicable codes, regulations, laws, standards, and guidelines.
WARNING: Ensure that for emergency, life safety applications
using the SP40S Multi-Function Facility Communication System,
installation, testing and maintenance always be performed by
qualified personnel in accordance with all the latest National Fire
Protection Association (NFPA), Underwriter’s Laboratory (UL),
National Electric Code (NEC), Occupational Safety and Health
Administration (OSHA), state, county, local, province, district,
federal, and other applicable building and fire standards, guidelines,
regulations, laws, and codes including, but not limited to, all
appendices and amendments and requirements of the Local Authority
Having Jurisdiction (AHJ).
It is recommended that the local Authority Having Jurisdiction (AHJ) inspect and approve the
proposed placement of all the notification appliances.
2.4 Insurance Recommendation
The SP40S Multi-Function Facility Communication System is not a substitute for insurance.
Make sure that you have adequate levels of life and property insurance.
2.5 Audio Output Considerations
WARNING: Audible signals may mask medical equipment
monitoring alarms. Where medical equipment monitoring alarms are
in use, do not use audible signals; provide visual notification
appliances in highly visible locations.
CAUTION: The output of the audio system may not be heard in all cases. Sound
can be blocked or reduced by walls, doors, carpeting, wall coverings, furniture,
insulation, bed coverings, and other obstacles that may temporarily or
permanently impede the output of the audio system. Sound is also reduced by
distance and masked by background noise.
SP40S Multi-Function Facility Communication System Manual, Revision D
3
Chapter 2: Safety Precautions
The output of the audio system may not be sufficient to alert all occupants,
especially those who are asleep, those who are hearing-impaired, those who are
wearing devices that plug or cover the ears, and those who have recently used
drugs or alcohol.
The output of the audio system may not be heard by an alert person if the output
device is placed in an area which is isolated by a closed door, or is located on a
different floor from the person in a hazardous situation or is placed too far away
to be heard over ambient noise such as, but not limited to, running water, traffic,
air conditioners, machinery or musical appliances.
If live microphone announcements, audible tones and/or voice messages cannot
be readily heard and understood clearly within the protected areas as intended,
increase the number and/or sound output intensity of speakers within those areas
so that they are heard and understood clearly when activated.
2.6 RF Interference
The SP40S Multi-Function Facility Communication System has been tested and found to comply
with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction manual, may
cause harmful interference to radio communications. Operation of this equipment in a residential
area is likely to cause harmful interference, in which case the user is required to correct the
interference at his own expense.
2.7 General
Each manufacturer's panel and notification appliances operate differently and have different
features. Before specifying, installing, operating, testing, maintaining, or servicing a system,
carefully read the installation, operation, and testing manual for each piece of equipment and
applicable codes.
Additional copies of this manual may be obtained from:
Cooper Wheelock, Inc.
273 Branchport Ave.
Long Branch, N.J. 07740
Tel: (800) 631-2148
Fax: (732) 222- 2588
E-mail: info@cooperwheelock.com
SP40S Multi-Function Facility Communication System Manual, Revision D
4
3 Overview
The SP40S Multi-Function Facility Communication System is capable of supplying the following:
• 40 Watts of audio power
• 2 Amps of strobe power
• There is an additional 0.5 Amps of auxiliary power at 28 Volts that can be used to power other Safepath
Products.
The SP40S Multi-Function Facility Communication System is used for Alarm and Non-Alarm Announcements.
3.1 Compatibility with Existing Safepath4 Products
The SP40S Multi-Function Facility Communication System is fully compatible with the SP40S, all current Audio
Splitters (SP4Z-A/B and SP4-APS), the Safepath Remote Microphone (SPRM), the Safepath Volume Control (SPSVC), the Telephone Zone Controller (SP4-TZC), and the Safepath Remote Microphone Expander (SP4-RMX).
SP40S Multi-Function Facility Communication System Manual, Revision D
1
Chapter 3: Overview
3.2 Standard Features
Feature Description
One strobe NAC output section
40-Watt Audio Amplifier section
Digital Voice Section
• 24VDC @ 2 Amps Maximum.
• Requires separate NAC Circuit (8 to 33VDC) input or can be
programmed to operate when Digital Voice messages are played.
• Microphone (MIC) is active.
• Auxiliary (AUX) input is active and/or Digital Voice message are
played. (Each message can be programmed individually to activate
the strobe circuitry.)
• Return allows pass-through for Cooper Wheelock synchronized
strobes, remote SP40S panels, additional strobe appliances, or
EOLR.
• Synchronized output when using Cooper Wheelock’s synchronized
strobe products.
• Supervised with 10K Ohm end-of-line resistor (EOLR).
• Trouble LEDs for Open and Short conditions.
• Power limited to minimize overload condition.
• Selection of 25Vor 70V speaker output.
• Supervised with 10K Ohm EOLR.
• Trouble LEDs for Open and Short Conditions
• Power limited to avoid overload condition.
• Capable of playback and record (via 1/8” audio jack).
• Digital Voice Message Chip contains the recording program and
memory for eight message sections.
• Memory in eight sections with corresponding inputs.
o A total of four minutes of messages.
o Each message is 30 seconds in duration.
o Messages can be combined for longer durations.
• Activated by one of eight contact closure inputs (IN1 – IN8) or
manual activation on user interface.
• Each CC input (contact closure) can be supervised for an OPEN.
• Prealert tones can be chosen for each message (code 3,
continuous, or no pre-tone).
• Messages can be selected to have a post-tone that matches the
pre-tone.
• Capable of selecting the strobe NAC output for each input.
SP40S Multi-Function Facility Communication System Manual, Revision D
2
Chapter 3: Overview
Feature Description
Alarm Audio Processing Section
Non-Alarm Audio Processing
Section
• Three Priority ordered audio inputs
Hand-held, push-to-talk (PTT) microphone, and Priority 1. For live,
emergency voice announcements and instructions. The microphone
overrides (mutes) any voice message or tones in progress.
• Auxiliary Input (AUX IN, CC/NAC), Priority 2.
o CC or NAC initiates AUX IN audio
o CC is supervised. NAC is not supervised.
o For use with SAFEPATH4 – Remote Microphone Expander
o IN1, IN2, IN3, IN4, IN5, IN6, IN7, IN8 have priorities 3, 4, 5,
6, 7, 8, 9, and 10 respectively.
o IN1 – IN8 are initiated via Contact Closure.
o IN1, IN2, IN3, IN4, IN5, IN6, IN7, IN8 are supervised for an
OPEN.
o Messages can also be initiated via user interface.
• Night Ring (NR), Priority 6.
o Contact closure activated.
o Non-alarm.
o Does not operate if on Battery.
• Telephone Page (TEL), Priority 7.
o Accepts a Telephone Page Port Input.
o Will not operate if the panel is on Battery.
• Background Music (BGM), Priority 8.
o Line Level Input.
o Will mute when any other input is used.
o Will not operate if the panel is on Battery.
Ground Fault Detection Section Monitors inputs and outputs for 40K Ohms minimum in relation to
ground.
A Dual-Tone Tone Generator with
two field selectable sounds (Code
3 Tone, Slow Whoop) that sound
when there is a Digital Voice
Section Failure in alarm condition.
Full supervision with on-board
diagnostics and trouble reporting
circuits for:
Provides Code 3 tone or Slow Whoop (user selectable) in the instance
of a Digital Voice failure or system timeout.
Audio NAC circuit wiring -- open and short conditions during standby
AND active (Alarm and BGM) Ground Fault detection
Strobe NAC circuit wiring -- open and short conditions
PTT Microphone -- not installed or damaged
Amplifier -- operation
Digital Voice Section
Input voltage/low battery
Tone generator operation
SP40S Multi-Function Facility Communication System Manual, Revision D
3
Chapter 3: Overview
Feature Description
Form C relay trouble contacts for
external notification.
Form C contact normally energized. Contacts transfer during a trouble,
an alarm trouble, or an AC trouble: 2.0 amps at 24VDC max, resistive
load. Non-Supervised.
Built-in Sounder To indicate trouble, with a trouble silence switch to silence it. If the
trouble is not corrected in 20 hours, the sounder reactivates. (Trouble
Silence Switch does not change the state of the Form C Trouble relay.)
Remote reporting via output
contacts for system trouble, alarm
AC trouble can be configured for report separately or as a system
trouble.
activation, and AC trouble.
BATTER Y
STANDBY
CENTRAL AMPLIFIED
MICROPHONE
AUX IN
TELEPHONE PAGE PORT
BACKGROUND MUSIC
CONTROL
NIGHT RING
STROBE NAC INPUT
SYSTEM
UP TO 8 CC CIRCUIT INPUTS
TROUBLE RELA Y
(8 TO 33VDC)
SP40S
PANEL
120V AC
SPEAKER CIRCUIT
STROBE CIRCUIT
STROBE RETURN
ALARM R ELEAY FORM C
DIGITAL VOICE MESSAG E CHIP ALLOWS RECORDING 8 MESSAGE
SEGMENTS AT THE PANEL. THE PANE L C O ME S W ITH 8 STANDARD
PRE-RECORDED MESSAGE. T AILORED MESSAGES CAN BE
RECORDED AT WHEELOCK.
(40 WA TT, SELECT A BLE
25V or 70.7V)
POWER LIMITED
24VDC A T 2A MAX
POWER LIMITED
FOR CINTINUATION OF
STROBE CIRCUIT OR EOLR
POWER LIMITED CONSTANT 24VDC AT 0.5A
Figure 3-1 Basic Capabilities of the SP40S Panel
SP40S Multi-Function Facility Communication System Manual, Revision D
4
Chapter 3: Overview
3.3 Enclosure and Configuration
For technical specifications, see Chapter 9.
3.4 Nominal Electrical Data
For technical specifications, see Chapter 9.
MOTHERBOARD
GROUNDING
TERMINAL
BLOCK
AC W
iring
(NON-POWER
LIMITED)
*
*
MUST BE ROUTED OUT
BOTTOM LEFT OF ENCLOSURE
Figure 3-2 Layout of SP40S Panel
Wiring to Battery
(NON-P O W E R
LIMITED)
USER INTERFACE
SP40S Multi-Function Facility Communication System Manual, Revision D
5
Chapter 3: Overview
3.5 User Interface
• The User Interface of the SP40S Multi-Function Facility Communication System displays the basic status of the
unit as well as allowing for a limited amount of user controls. Table 3-1 identifies the pushbuttons and
indicators.
Message 1
Message 2
Message 3
Message 4
Message 5
Message 6
Message 7
Message 8
Figure 3-3 SP40S User Interface
Table 3-1. SP40S User Interface Pushbuttons/Indicators
Pushbutton or Indicator Description/Function
Message 1 - 8 (there are 8 messages, 1 through 8) Button manually actives Messages 1- 8. Illuminated steady
means contact closure is on a DV input. Illuminated blinking
means DV is activated via button push.
POWER ON indicator If illuminated, indicates SP40S is powered by primary or
secondary power.
SYSTEM TROUBLE indicator If illuminated, indicates the SP40S has a trouble.
AC TROUBLE indicator If illuminated, indicates primary power is low or has failed
and SP40S is running on secondary power.
ALARM ACTIVE indicator Indicates PTT MIC (push to talk microphone), AUX
(auxiliary), or DV (digital voice) has been initiated.
STROBE ACTIVE indicator Indicates the strobe circuit has been initiated.
TROUBLE SILENCE button Temporarily silences the audible trouble indicator.
RECORD button and indicator For message recording process, see section 6.3.
SP40S Multi-Function Facility Communication System Manual, Revision D
6
Chapter 3: Overview
3.5.1 Basic Operation of User Interface
When a Message button is pressed, the user interface microcontroller processes the signal and outputs it to the
Digital Voice microcontroller which plays the corresponding message. The user interface illuminates the
corresponding message LED when a button is pressed or a message activation contact closure is received. The LED
blinks if the activation was a button press and the LED remains ON constantly when a contact closure is present. If
a button is pressed, the message LED remains blinking and the message remains active until the button is pressed
again.
SP40S Multi-Function Facility Communication System Manual, Revision D
7
Chapter 3: Overview
3.6 Additional Drawings
J2
DV Record
1/8" Audio
Jack
TB1
Alarm
Connections
TB2
System Trouble
Connections
TB3
AC Trouble
Connections
TB4
Audio Output
Connections
(Aux iliar y 2 4 V DC OUT,
SPB AC Trouble
Monitoring Connections)
TB5
Night Ringer,
T elephone Page,
Background Music
Connections
TB6
Auxiliary Input and
24VDC Output
Connections
TB7
Internal Digital V o ic e
Module Input
Connections
TB8
Interna l Digital Voice
Module Input
Connections
TB9
Primary Power
Connections
(120VAC)
TB10
Secondaty Power
Connections
(Battery)
Figure 3-4 SP40S Terminal Blocks
SP40S Multi-Function Facility Communication System Manual, Revision D
8
TB12
Strobe Connections
Chapter 3: Overview
JP3
2 Wire/4 Wire Mode
(For connection
to Audio Boosters)
JP5
DV
Record
J6
User
Display
Interface
Connection
J1
Audio
Output Select
JP4
Contact
Closure Supervision
J4
AUX IN
Select
J5
FACP In te rfa c e
(for future u s e )
Figure 3-5 SP40S Jumpers
SP40S Multi-Function Facility Communication System Manual, Revision D
9
SW3
Strobe
Activation
Chapter 3: Overview
SW2
AC Trouble Settings
Booster Connection
Settings
SW4
T one Types
SW6
NAC/Contact
Closure Select
SW5
Pretone/
Postone Enable
Figure 3-6 SP40S Switches
SW7
DV IN
Sup e rv is io n
and Auxiliary
Timeout
SW9
Sync/
Nonsync
Strobe
Settings
SP40S Multi-Function Facility Communication System Manual, Revision D
10
Chapter 3: Overview
D29
(Red) Audio
Peak/Overload
D47
Interfa c e
Trouble
D1
Audio Circuit
D2
Audio Circuit
Open
Short
D4
PTT MIC Missing
or Inoperable
D3
DV
Digital
Vo ic e Section
MIC
D5
AMP
Amp lifie r S ection
Trouble
D6
SPB
Supervision Open
D8
Batteries
Missing or Low
D44
AUX IN,
CC Open,
RMX or
Remote MIC
Trouble
D55
- DV1 - IN1 OPEN
D62
- DV2 - IN2 OPEN
D67
GF
Ground
Fault
Trouble
F2
AC
Line Fuse
(250V 10A)
D93
Battery
Charger Trouble
D100
(Green)
Power is Present
(AC and/or BAT)
Figure 3-7 Diagnostic LEDs/Fuses
F1
Battery Fuse
(125V 8A)
D58
- DV3 - IN3 OPEN
D65
- DV4 - IN4 OPEN
D75
- DV5 - IN5 OPEN
D78
- DV7 - IN7 OPEN
D87
- DV8 - IN8 OPEN
D84
- DV6 - IN6 OPEN
D97
Strobe Open
D96
Strobe Circuit
Short
D109
(Green)
AC Power is Present
SP40S Multi-Function Facility Communication System Manual, Revision D
11
Chapter 3: Overview
R73
Digital
Voice Volume
Control
R81
Digital
Voice Tone
Volume Control
R40
T elephone
Page Volume
Control
R92
Background
Music V olum e
Control
R93
T one
Control Treble
R94
T one
Control Bass
R100
AUX IN
Volume
Control
Figure 3-8 SP40S Potentiometers
SP40S Multi-Function Facility Communication System Manual, Revision D
12