273 Branchport Avenue, Long Branch, NJ 07740-6899 Ph: (732) 222-6880 Fax: (732) 222-2588
Toll Free 800-631-2148 Web Site: www.wheelockinc.com
E-Mail: info@wheelockinc.com
A83637 Revision B
Intentionally Blank
Typographical Notation Conventions
Thank you for using our products. Use this product according to this instruction manual. Please keep
this instruction manual for future reference.
ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM WHEELOCK MANUALS OR
OTHER DOCUMENTS DESCRIBING THE PRODUCT FOR USE IN PROMOTIONAL OR
ADVERTISING CLAIMS, OR FOR ANY OTHER USE, INCLUDING DESCRIPTION OF THE
PRODUCT'S APPLICATION, OPERATION, INSTALLATION AND TESTING IS USED AT THE SOLE
RISK OF THE USER AND WHEELOCK WILL NOT HAVE ANY LIABILITY FOR SUCH USE.
Certain information contained in this manual has been extracted from the NFPA 72 Manual (1999 Edition)
and the Life Safety Code 101™ Manual (2000 Edition).
Notation Conventions
This manual uses the following notation conventions:
WARNING: INDICATES A POTENTIALLY HAZARDOUS SITUATION THAT, IF NOT AVOIDED,
COULD RESULT IN PROPERTY DAMAGE AND SERIOUS PERSONAL INJURY
OR DEATH TO YOU AND OR OTHERS.
CAUTION: Indicates a potentially hazardous situation that, if not avoided, could result in minor or
moderate injury. It may also be used to alert against unsafe practices.
P83636
Rev. G March 2003
Copyright 2003 Wheelock, Inc. All rights reserved.
iii
Intentionally Blank
iv
TABLE OF CONTENTS
Typographical Notation Conventions…………………………………………………………… iii
Table of Contents…………………………………………………………………………………. v
Table of Figures…………………………………………………………………………………… vii
Table of Tables……………………………………………………………………………………. ix
Section 5-2 – To Make Live Announcements………………………………………….. 5-1
Section 5-3 – To Sound Evacuation Tone……………………………………………… 5-1
Section 5-4 – To Reset Visual Appliances……………………………………………… 5-2
Section 5-5 – To Acknowledge a Trouble Condition………………………………….. 5-2
Chapter 6 – Periodic Testing and Maintenance………………………………………………. 6-1
Personnel properly qualified in the application and use of life safety equipment ("qualified personnel")
shall read this manual carefully before performing any actions to specify, apply, install, maintain and
operationally test SAFEPATH
This manual shall be kept with the SAFEPATH
manual shall be made available to all qualified personnel who operate, test, maintain, or service
SAFEPATH
®
Panel products. It is strongly recommend that such personnel read and understand the
entire manual.
Section 1-2 - Operational Safety
®
Panel products in accordance with the instructions in this manual.
®
Panel for reference during the life of the system. This
WARNING: IF SAFETY PRECAUTIONS, INSTALLATION AND TESTING INSTRUCTIONS ARE
NOT PERFORMED PROPERLY, THE
SAFEPATH
®
PANEL MAY NOT OPERATE IN
AN EMERGENCY SITUATION WHICH COULD RESULT IN PROPERTY DAMAGE
AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
WARNING: IF THE TROUBLE CONDITION PROTECTIVE SIGNALING SYSTEM SOUNDS
AND/OR FLASHES, IT IS A WARNING OF A POSSIBLE SERIOUS SITUATION AND
REQUIRES IMMEDIATE ATTENTION.
CAUTION: The SAFEPATH
delicate components mounted on a board. Discharge any static electricity from your
body by touching a grounded object, such as a metal screw, which is connected to
earth ground. Handle the board by its edges and be careful not to twist or flex it. The
SAFEPATH
attach grounded wrist straps before touching any static sensitive areas. After handling
SAFEPATH
Section 3-5 “System Checkout” of this manual to verify that the printed circuit board is
functioning properly.
®
printed circuit boards are sensitive to static electricity and have
Panel is to be installed in a static free area, and the installer is to properly
®
printed circuit boards, the panel should be tested in accordance with
This SAFEPATH® Panel will not work without power.
or 220VAC. 24VDC re-chargeable batteries provide back-up power. If both sources of power are cut off
for any reason, the SAFEPATH
®
Panel will not operate.
The SAFEPATH
DO NOT assume any installation, operation and testing details not shown in this manual.
The SAFEPATH
®
Panel shall only be operated with the dead front panel properly in place.
®
Panel is powered by 120VAC
WARNING: FOR PROPER OPERATION, THE
SAFEPATH
®
PANELSHALL BE CONNECTED TO
A LISTED COMPATIBLE AND PROPERLY OPERATING CONTROL PANEL, WHICH
CONTROLS ITS ACTIVATION. ALL EQUIPMENT SHALL BE PROPERLY
INTERCONNECTED AND OPERATING. THE INSTALLER SHALL CHECK
COMPATIBILITY OF ALL EQUIPMENT PRIOR TO INSTALLATION, OTHERWISE
THE SAFEPATH
®
PANEL AND/OR THE CONTROL PANEL MAY BE DAMAGED
AND/OR FAIL TO OPERATE IN AN EMERGENCY SITUATION.
1-1
®
Notification equipment cannot last forever. Even though SAFEPATH
years, any of its parts or components could fail before then. Therefore testing of the entire protective
signaling system, including the SAFEPATH
®
Panel, all notification equipment, as well as all messages
Panel is expected to last up to ten
and their output channel, and priority assignment, shall be conducted at least twice each year, or more
often as required by local, state and federal codes, regulations and laws, by qualified personnel. If the
notification equipment is not working properly, immediately contact the installer and have all/any problems
corrected immediately. Malfunctioning components should be replaced immediately. Do not attempt to
repair malfunctioning components. Malfunctioning components should be returned for factory repair or
replacement. In the event you cannot contact the installer, contact the manufacturer.
WARNING: CERTAIN HARDWARE FUNCTIONS ON THE SAFEPATH PANEL ARE NOT
SUPERVISED. IF ANY SUCH HARDWARE FUNCTIONS FAIL, THE SAFEPATH
PANEL MAY NOT PROVIDE THE INTENDED WARNING AND/OR NOT INDICATE A
TROUBLE CONDITION. THE FOLLOWING ARE NOT SUPERVISED:
1. THE "SHORT CIRCUIT" DETECTION CIRCUITRY FOR ANYONE OR ALL OF
THE EIGHT CONTACT INPUTS.
THE FOLLOWING HARDWARE FAILURES WOULD PREVENT THE
SAFEPATH
PANEL FROM INDICATING A TROUBLE CONDITION:
1. THE "OPEN CIRCUIT" DETECTION CIRCUITRY FOR ANY ONE OR ALL OF THE
EIGHT CONTACT INPUTS.
2. THE AUDIO SUPERVISION CIRCUITRY FOR EACH OF THE TWO OUTPUT
CHANNELS.
3.
THE STATUS CONTACT.
THESE HARDWARE FUNCTIONS SHALL BE PERIODICALLY CHECKED FOR
PROPER OPERATION.
®
Section 1-3 - Compliance with Applicable Codes, Regulations, Laws,
Standards, and Guidelines
COMPLY WITH ALL OF THE LATEST APPLICABLE CODES, REGULATIONS, LAWS, STANDARDS,
AND GUIDELINES.
WARNING: FOR EMERGENCY, HAZARDOUS, SECURITY, LIFE SAFETY, AND FIRE
PROTECTIVE SIGNALING SYSTEM APPLICATIONS USING THE SAFEPATH
PANEL INSTALLATION, TESTING AND MAINTENANCE SHALL BE PERFORMED
BY QUALIFIED PERSONNEL IN ACCORDANCE WITH ALL THE LATEST
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), UNDERWRITER’S
LABORATORY (UL), NATIONAL ELECTRIC CODE (NEC), OCCUPATIONAL
SAFETY AND HEALTH ADMINISTRATION (OSHA), STATE, COUNTY, LOCAL,
PROVINCE, DISTRICT, FEDERAL, AND OTHER APPLICABLE BUILDING AND
FIRE STANDARDS, GUIDELINES, REGULATIONS, LAWS, AND CODES
INCLUDING, BUT NOT LIMITED TO, ALL APPENDICES AND AMENDMENTS AND
REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION (AHJ).
It is recommended that the local AHJ inspect and approve the proposed placement of all the notification
appliances.
Section 1-4 - Property Insurance Recommendation
The SAFEPATH® Panel is not a substitute for insurance. All users should have adequate levels of life and
property insurance
.
1-2
Section 1-5 - Audio Output Considerations
WARNING: AUDIBLE SIGNALS MAY MASK MEDICAL EQUIPMENT MONITORING ALARMS.
WHERE MEDICAL EQUIPMENT MONITORING ALARMS ARE IN USE, DO NOT
USE AUDIBLE SIGNALS; PROVIDE VISUAL NOTIFICATION APPLIANCES IN
HIGHLY VISIBLE LOCATIONS.
CAUTION: The output of the audio system may not be heard in all cases. Sound can be blocked
or reduced by walls, doors, carpeting, wall coverings, furniture, insulation, bed
coverings, and other obstacles that may temporarily or permanently impede the output
of the audio system. Sound is also reduced by distance and masked by background
noise. The output of the audio system may not be sufficient to alert all occupants,
especially those who are asleep, those who are hearing-impaired, those who are
wearing devices that plug or cover the ears, and those who have recently used drugs
or alcohol. The output of the audio system may not be heard by an alert person if the
output device is placed in an area which is isolated by a closed door, or is located on a
different floor from the person in a hazardous situation or is placed too far away to be
heard over ambient noise such as, but not limited to, running water, traffic, air
If live microphone announcements, audible tones and/or voice messages cannot be readily heard and
understood clearly within the protected areas as intended, it will be necessary to increase the number
and/or sound output intensity of speakers within those areas so that they are heard and understood
clearly when activated
conditioners, machinery or musical appliances
.
.
Section 1-6 - RF Interference
The SAFEPATH® Panel has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the user will be
required to correct the interference at owners expense.
Section 1-7 - General
Each manufacturer's fire alarm control panel, and notification appliances operate differently and have
different features. Before specifying, installing, operating, testing, maintaining or servicing a system,
carefully read the installation, operation and testing manual for each piece of equipment and applicable
codes.
Additional copies of this manual may be obtained from:
Wheelock, Inc.
273 Branchport Ave.
Long Branch, N.J. 07740
Tel: (732) 222- 6880
Fax: (732) 222- 2588
Email: infoatwheelockinc.com
1-3
Intentionally Blank
1-4
Chapter 2 - Overview and Features
Section 2-1- Description
General
The Single Circuit SAFEPATH® Panel is a stand alone, single channel, supervised audio fire and
emergency evacuation system. Figure 2-1 on Page 2-2 illustrates the basic capabilities of the Single
Circuit SAFEPATH
The control panel that activates the Single Circuit SAFEPATH
buttons to a sophisticated computer based control panel providing dry contact closures.
The SAFEPATH
of a system that does sense such conditions. The SAFEPATH
recorded tone and/or voice message(s) to notification appliances. When used as part of a protective
signaling system, the SAFEPATH
has been approved by a nationally recognized testing laboratory ("LISTED") and to LISTED compatible
notification appliances for proper operation.
THE
SAFEPATH
TO A COMPATIBLE FIRE ALARM CONTROL PANEL TO FUNCTION IN A VOICE EVACUATION
SYSTEM.
WHEELOCK EXPRESSLY DISCLAIMS ALL LIABILITY FOR THE CONTENT, CLARITY AND
LANGUAGES OF, AND OUTPUT CHANNEL AND PRIORITY LEVEL ASSIGNED TO, ANY AND ALL
MESSAGES. IT IS ESSENTIAL THAT YOU HAVE MESSAGE CONTENT AND LANGUAGE,
SEQUENCE, OUTPUT CHANNEL AND PRIORITY ASSIGNMENTS REVIEWED AND APPROVED BY
QUALIFIED LEGAL AND SAFETY ADVISORS, QUALIFIED REPRESENTATIVE(S) OF OWNER(S)
AND USER(S), AND AUTHORITIES HAVING JURISDICTION.
Panel.
Panel can range from simple push
Panel does
PANEL MUST BE PROPERLY INSTALLED, PROGRAMMED, AND CONNECTED
not
sense an emergency condition or hazards such as fire; it is only a part
Panel must be properly connected to a compatible control panel that
Panel, when activated, provides a pre-
Standard Features
• One zone of audio and strobe NAC outputs.
• Multiple contact closure inputs
• A hand held, push-to-talk microphone (PTT) for live, emergency voice announcements and
instructions. The microphone overrides (mutes) any voice message or tones in progress.
• A multi-tone tone generator with 8 field selectable sounds for an optional evacuation signal.
• Visual NAC circuit of up to 2 amps at 24VDC. The visual NAC circuit may be selected to be
compatible with Wheelock, Inc. synchronized or non-synchronized visual notification appliances.
• Supervised Audio Amplifier module (SAA-40S, or 80S/SE) power 25, 70.7 or 100-volt speakers, or
Line Level Audio Amplifier (SALL-15S) to drive external power amplifiers and/or self-amplified
speakers.
• Digital Voice Module (MDX-2) with a Standard Message Kit (SMK) containing 8 standard messages
• Full supervision with on-board diagnostics and trouble reporting circuits for:
• Audio NAC circuit wiring open and short conditions
• Ground Fault detection
• Strobe NAC circuit wiring open and short conditions
• Self Amplified power output circuit wiring open and short conditions
• Microphone open condition
• Amplifier operation
• Selected evacuation signal
2-1
• Optional remote microphone station
• Digital Voice Module (MDX-2)
• Alarm input activation wiring
• Input voltage/low battery
• Built-in audible alert indicates any supervision loss
• Auxiliary trouble output for trouble signal connection
• Remote reporting via output contacts for system trouble or alarm activation.
• An internal 6-amp power supply/ 40Ah battery charger.
Optional Features
• Remote Microphone Station (RMS-2) for live, emergency announcements.
• Programmed Message Kit (PMK) for up to two minutes of messages tailored to customer’s needs.
• Four Zone Audio Splitter (SC-SPL).
• Auxiliary Input Module (AIM-3) used to connect three Remote Microphone Stations or two Remote
Microphone Stations and a telephone page input.
BATTERY
STANDBY
CENTRAL AMPLIFIED
(40 OR 80 WATT, SELECTABLE
25V, 70.7V, or 100V)
REMOTE
MICROPHONE
(RMS-2)
CONTROL
SYSTEM
UP TO 8 CONTACT ACTIVATIONS.
SPEAKER CIRCUIT
STROBE CIRCUIT
TROUBLE
RELAY
INPUTS
SAFEPATH
PANEL
120 VAC
8 STANDARD MESSAGES ON THE SMK OR
UP TO 2 MINUTES OF AUDIO STORAGE FOR
PERSONALIZED MESSAGES ON THE MDV-PMK.
Section 2-5 - Single Circuit SAFEPATH® Panel Basic Configuration
Each Single Circuit SAFEPATH
SCMB (Single Circuit Motherboard)
MDX-2 (Digital Voice Module)
SMK (Standard Message Kit) or optional PMK (Programmed Message Kit)
One amplifier module
DCPS (Power Supply/Battery Charger)
Optional Modules:
One SC-SPL (Single Circuit Splitter-4 Zone)
Up to eight NACIM (Notification Appliance Circuit Interface Module)
Up to three RMS-2 (Remote Microphone Station)
One AIM-3 (Auxiliary Input Module)
The module layout of the Single Circuit SAFEPATH
Panel is configured with:
®
Panel is shown in Figure 2-2 on Page 2-5.
Section 2-6 - Remote Microphone Station (RMS-2) (Optional)
The Remote Microphone Station (RMS-2) is a 4 gang switch-plate consisting of a push-to-talk (PTT),
hand-held microphone, pre-amplifier and associated LED’s and activation switches which provides a
remote live voice input. Additional Information is found in the Installation Manual.
2-3
Section 2-7 - Operation Modes
The SAFEPATH® Panel has two operation modes:
1. Standby
2. Alarm
Standby Mode
Standby is the normal mode. The SAFEPATH® Panel supervises the connections and internal
components to maintain proper operation. All strobes and speaker appliances are off.
Alarm Mode
Alarm mode occurs when an emergency signal is initiated manually, or by the FACP or control
equipment.
Section 2-8 – Glossary of Terms
AHJ – Authority Having Jurisdiction
EOLR – End of Line Resistor
FACP – Fire Alarm Control Panel
NAC – Notification Appliance Circuit
NEC – National Electric Code (NFPA-70)
NFPA – National Fire Protection Association
PTT – Push to Talk (Microphone)
PCB - Printed Circuit Board
UL - Underwriters Laboratory
2-4
Digital Voice
Module MDX-2
P83412 REV ( )
U17
C50
R72
RV10
R71
R73
C46
RV9
Q2
D12
C48
R70
R69
R66
Q1
R67
D13
R68
U13
RV8
R65
C44
D10
J6
TB 3
R62
RV7
R64R63 D11
C41
RV6
R60
R59
C40
R58
R57
C39
R56
R55
RV5
C38
R54
R53
C36
RV4
R52
R43
R51
C35
R50
RV3
R49
C34
R48
R47
RV2
TB 2
TB 1
R44
C33
R46
R45
RV1
F1
R35
R34
D9
+
C27
L2
GND
EAR TH
D8
E1
C21
+
K2
J3
R32
D4
C20
C19
R25
R26
R21
R22
D3
R19
C17
J2
+
R20
R18
C16
C9
+
R8U1R6 C6
C10D2
D1
+
K1
C8
R9
R42
U7
L1
R17
R16
C15
R5R7R1C4
C5
R41
R40
C31
C30
C29
C28
U9
C25
R14
C14
C13
U3U4
R3
R4C3C1
C2C7
REV:SN:
U16
C49C47
U15
S15
C45
U14
S14
C43
U12
S12
C42
R61
J5
U11
C37
C32
R38
U10
R39
R36
R37
U8
S8
C26
C24
J4
C22
C23
R33
D7
D6
D5
R31
R29
R27
U6
U5
R30
R28
CH1 VOL
R24
R23
C18
R13
C12
J1
R10
C11R15
R12
R11
U2
R2
Power Supply/
Battery Charger
(DCPS)
MOTHER BOARD
(SCMB)
SAFEPATH P83167 REV B
T1
106
106
U3
SMP7PM
AC
AC
AC FAIL
C NC NO
BAT FAIL
NO NC C
-
DC
+
AC
SW1
SW2
J1
-
BAT
+
DC
P1
C16
D1
D2
AMBER GREEN
K2
K1
SW1 SW2 SW3
K3
U1
U2
U4
X2
X1
U5
U6
U8
U10
Amplifier
SAA-40S, 80S, 80SE
SALL-15S
F1
TB1
+
F2
-
+
-
+
-
+
TB2
-
+
-
+
TB3
-
SW4
2 3 4
1
ON
4
2 3
1
ON
SW5
E1
U9
+
-
+
-
+
-
TB5
J2
MICROPHONE
ZONE SELECT LED'S
ON
ON
OFF OFF
OFF
ZONE 1
ALL
CALL
OPERATION:
Use zone switches to select zones
for live announcements.
Use all-call to select all zones.
Zone select LED's indicate the
selected zones.
Zone active LED's indicate the
active zones.
ZONE 2
P83236 SAA-40/ 80
ON
ON
ON
TB1
+
ALL
_
OFF
OFF
ZONE 3
+
ZONE 4
PWR
_
Z
O
+
ZONE 1
AUD
N
_
E
+
Z1
A
_
C
ZONE 2
+
T
Z2
I
_
V
+
E
Z3
_
ZONE 3
L
+
E
Z4
D
_
S
ZONE 4
4 Way Splitter
(SC-SPL)
Figure 2-2.
Module Layout of a Typical Single Circuit SAFEPATH
®
Panel
2-5
Intentionally Blank
2-6
Chapter 3 - Installation and Setup
Section 3-1 - Introduction
The lives of people depend upon the safe and proper installation of the SAFEPATH® Panel. Please read,
understand and carefully follow the specific installation instructions set forth below to avoid damage to the
SAFEPATH
procedures in this manual should conduct installation.
WARNING: SHUT OFF ALL POWER BEFORE STARTING THE INSTALLATION. ELECTRICAL
WARNING: DO NOT CONNECT AC POWER OR BATTERY BACKUP POWER UNTIL SYSTEM
CAUTION: The SAFEPATH
®
Panel and equipment connected to it. Only qualified personnel in accordance with the
SHOCK CAN CAUSE DEATH OR SERIOUS INJURY.
WIRING HAS BEEN CONNECTED, MODULES HAVE BEEN INSTALLED, AND
FIELD WIRING HAS BEEN INSPECTED.
®
printed circuit boards are sensitive to static electricity and have
delicate components mounted on them. Before handling either a board or any
component on a board, discharge any static electricity from your body by touching
a grounded object such as a metal screw, which is connected to earth, ground.
Handle the board by its edges, and be careful not to twist or flex it. The
SAFEPATH
attach grounded wrist straps before touching any static sensitive areas. After
handling SAFEPATH
®
Panel is to be installed in a static free area and the user is to properly
®
printed circuit boards, verify that the printed circuit boards
are undamaged and functioning properly.
The installer, prior to installation should consult with the authorities having jurisdiction
(AHJ).
Section 3-2 - Fire Alarm Control Panel Interface Wiring Applications
The SAFEPATH® Panel can be connected to either the FACP alarm output dry contact or to the
FACP Notification Appliance Circuit (NAC). If it is connected to the NAC, then the Notification
Appliance Circuit Interface Module (NACIM) shall be used. Follow the NACIM instruction sheet
(P83478) for proper mounting and wiring.
The SAFEPATH
appliance circuit depending upon system requirements. When the SAFEPATH
a “silenceable” NAC circuit on the FACP, activating the FACP’s alarm silence switch will silence it.
The Strobe NAC circuit on the SAFEPATH
remain in alarm when the audible is silenced, the Strobe NAC circuit must be connected to a “nonsilenceable” NAC circuit on the FACP.
A SAFEPATH
FACP.
“TROUBLE”, Form C relay terminals are available for monitoring the condition of the SAFEPATH
Panel at the FACP.
®
Panel may be connected to either a “silenceable” or “non-silenceable” notification
®
Panel will also be silenced. In order for the strobes to
®
Panel connected to a “non-silenceable” NAC circuit cannot be silenced from the
SECTION 3
REMOTE MICROPHONE
STATION AND AIM-3
CONNECTIONS
Figure 3-1
Location of Plug-in Modules and Wire Connections
Section 3-3 - General Installation Instructions
Refer to Figure 3-1, which shows the location of modules and wiring connections used in the
installation of the SAFEPATH
Prepare a System Wiring Diagram
1. Using Section 3-4, prepare a complete system-wiring diagram. Keep a copy of the system-wiring
diagram with the SAFEPATH
Unpack and Check Inventory
2. Carefully unpack the SAFEPATH® Panel and make sure each item described on the packing slip
is present and undamaged.
Mounting
3. Mount the SAFEPATH® Panel and optional expansion modules in the desired locations as
described in Section 3-5.
4. Mount any additional wiring boxes or junction boxes needed to interconnect field wiring.
®
Panel.
®
Panel manual as a permanent record of the system wiring.
3-2
Connect conduit fittings or bushings as needed through the knockouts provided on the top and
5.
bottom of the SAFEPATH
®
Panel.
Field Wiring Connections
6.
Install field wiring in conduit when required, following the most current National Electrical Code
(NFPA-70) and local codes for the type of system being installed. Make all necessary
connections at any additional wiring or junction boxes.
Wire all ancillary equipment, power connections, and Fire Alarm Control Panel correctly and
7.
prepare all wires for hookup to the SAFEPATH
NAC speaker and strobe appliance wiring to the SAFEPATH
starting with Step 13 of this procedure.
Connect supplied 10K Ohm, ¼ Watt test resistors to Strobe and Audio NAC Circuit output
8.
connections on Motherboard. (If SALL-15S amplifier module is being used, connect a 10K Ohm
¼ Watt test resistor to the SPK AMP terminals also. See Figure 3-1 on Page 3-2 for location.
Figure 3-2 is an enlarged picture of the referred area.
+
ALL CALL
-
+
24V
-
+
SPK AMP
-
+
STROBE
-
+
AUDIO
TB5
-
®
Panel. Do not connect Ancillary equipment or
Panel. This will be done
SECTION 5
STROBE AND AUDIO
OUTPUT CONNECTIONS
Figure 3-2
Strobe and Audio Output Connections
CAUTION: Provide proper strain relief for all wiring not in conduit
1. Connect the SAFEPATH Panel to earth ground, following the National Electrical Code and local
codes for the type of system being installed.
Wire gauge selection of the earth ground wiring should involve consideration of all factors, including
maximum allowable wire resistance and length. The panel is tied to earth ground by connecting the
ground terminals to an earth ground. The location of the ground terminals within the panel is shown
in Figure 3-17 on Page 3-15.
CAUTION: Do not connect input voltage to any equipment until the field wiring has been tested,
inspected and approved.
1. Check the integrity of all field wiring. Confirm that the specified cable is installed, and that there is
continuity between required points (no open circuits), with no unwanted shorts to other conductors,
chassis, or earth ground.
a. Verify that the field wiring complies with the instructions of this manual and the detailed wiring
diagram prepared for this installation.
.
b. Ensure that no unwanted voltages are present on circuit conductors and ground.
c. Test all ungrounded connectors for electrical isolation from ground.
Measure and record the resistance of each NAC circuit. Conduct this test under reverse polarity
conditions.
1. Install Amplifier Module(s) (SAA-40S, 80S/SE or SALL-15S) if removed.
3-3
Initial Checkout
WARNING: TWO DIFFERENT SOURCES OF POWER MAY BE CONNECTED TO THE
SAFEPATH
®
PANEL. DISCONNECT BOTH SOURCES OF POWER BEFORE
SERVICING. FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE,
SERIOUS INJURY, OR DEATH TO YOU AND/OR OTHERS.
CAUTION: Connect the AC power source before connecting the battery backup power. Disconnect
the battery backup power before disconnecting the AC power source.
1. Conduct the Initial Checkout procedures as described in Section 3-6 System Checkout.
Final Checkout
2. Remove all EOLRs on Audio and Visual NAC Circuits.
3. Connect all Strobe and Speaker NAC Circuits to the proper connections on the SAFEPATH
Motherboard (SCMB). See Figure 3-2 on Page 3-3.
4. Connect all Optional Equipment to the SAFEPATH
®
Panel in accordance with each Installation
Sheet.
5. If the Strobe NAC Circuit is not being used connect a Wheelock, Inc. LISTED 10K Ohm, 1W EOLR to
the terminals on the Mother Board.
6. If Ground Fault Detection is required, connect and align according to Section 3-7 Ground Fault
Detection Sensitivity Adjustment.
7. Perform Final Checkout Procedures as described in Section 3-6 System Checkout.
®
8. Calculate and Install properly sized backup batteries. (Section 3-8)
Section 3-4 – Prepare a System Wiring Diagram
Wiring Guidelines
Although the SAFEPATH Panel products incorporate signal verification and noise filtering circuitry on
their inputs, induced voltages or noise on the input wiring can cause improper operation. Therefore, use
shielded twisted pair wire for all dry contact input wiring.
The shield of each cable should be connected only at one end. Each shield of each cable that
connects to the SAFEPATH
knockout locations on the chassis (see Figure 3-17 on Page 3-15).
The National Electrical Code (NFPA-70) defines two types of circuits for protective signaling systems:
power limited circuits and non-power limited circuits. The SAFEPATH
limited.
WARNING: ALL SAFEPATH
SHOULD BE ROUTED AWAY FROM ANY HIGH VOLYAGE OR HIGH CURRENT
WIRING (SUCH AS AC OR DC POWER WIRING, AUDIO POWER WIRING, AND
MOTOR OR RELAY ACTUATION WIRING). DRY CONTACT INPUT WIRING SHALL
BE INSTALLED IN SEPARATE CONDUIT. FAILURE TO DO SO MAY CAUSE
ELECTRICAL SHOCK RESULTING IN PROPERTY DAMAGE AND SERIOUS
INJURY OR DEATH TO YOU AND/OR OTHERS.
Panel is to be connected to the grounding points provided near the
®
Panel circuits are non-power
®
PANEL DRY CONTACT INPUT WIRING AND AUDIO WIRING
3-4
CAUTION: The National Electric Code limits the maximum number of conductors that can be
installed in conduit and wiring boxes depending on the size of the conduit, the volume
of the boxes, and the gauge of the wire used. Make sure that wiring used for
SAFEPATH
®
Panel installation complies with the latest NEC, NFPA, Local, State,
County or Province requirements.
Field Wiring Connections
®
All SAFEPATH
Panel wiring terminals are designed to accept #12 AWG through #22 AWG wiring (one
wire per terminal). Proper wire gage considerations for the NAC Circuit must take into account current
requirements versus length of run.
Prepare System Wiring Diagram
.
1. Prepare a system-wiring diagram to include all Notification Appliances, ancillary equipment, and
internal connections and power sources as required.
Visual Notification Appliance Output Wiring
Available alarm strobe current is a maximum of 2 Amps at 24VDC. Table 3-1 shows available strobe
current using the standard calculation for a Temporal Code 3 signal. The SAFEPATH
®
Panel does
not include any optional modules. Completecalculation information for other configurations is located
in Section 3-8 Backup Battery Calculations.
Wire gauge may vary for each visual notification appliance output circuit on the panel. Wire gauge
selection should involve consideration of all factors including, wire loop length, maximum current draw of
each appliance, number of appliances, and maximum voltage drop allowable.
• Strobe NAC has a 24VDC, 2.0 amps maximum output
• Strobe NAC meets Class B supervision requirements for notification appliance circuits.
• Each output circuit shall have a UL LISTED, 10K Ohm, 1W, EOLR installed across the last visual
notification appliance. If the output is unused, a UL LISTED, 10K Ohm, 1W, EOLR shall be
placed across the output terminals. Each amplifier module contains the required number for the
supervised outputs. If more are needed, recommend using Wheelock, Inc. End of Line Resistor
Kit (Model Number EOLK, Part# 5076), which contains Eight (8) UL LISTED 10K Ohm 1W
resistors.
Wiring Diagrams for Visual Portion of Audio/Visual Notification Appliances
STROBE
+
_
Figure 3-3
Wiring Diagram for Visual Notification Appliance Output
CAUTION: Do not loop wire under terminals. Break wire run to provide supervision of
connection.
UL LISTED 10K Ohm
1W EOLR
3-5
STROBE
_
+
+
AUDIO
CAUTION: Do not loop wire under terminals. Break wire run to provide supervision of
connection.
SPKR
AMP
_
Figure 3-4
Wiring Diagram for Combination Audio/Visual Notification
Appliances in Central Amplifier Applications
+
_
+
STROBE
_
UL LISTED 10K Ohm
1W EOLR
UL LISTED 10K Ohm
1W EOLR
UL LISTED 10K Ohm
1W EOLR
UL LISTED 10K Ohm
1W EOLR
AUDIO
+
_
UL LISTED 10K Ohm
1W EOLR
Figure 3-5
Wiring Diagram for Combination Audio/Visual Notification
Appliances in Amplified Speaker Applications
CAUTION: Do not loop wire under terminals. Break wire run to provide supervision of
connection.
Central Amplified Speaker Notification Appliance Output Wiring
The audio alarm current of the amplifier module depends on the number of speakers on the circuit, length
and gauge of wire of the audio circuit, and the audio mode in use.
When laying out each NAC circuit for the speakers, calculate the total wattage required. A good
engineering practice is to not exceed 85% of the amplifier rating that you plan to use. If your calculations
exceed this, an amplifier having increased power capacity is required or replacing the entire SAFEPATH
Panel with greater capacity.
Wire gauge may vary for each audio appliance output on the panel. When:
• Speaker (with transformer) appliances are used with supervised audio amplifier module
(central amplified outputs). Wire gauge selection should involve consideration of all
factors including, wire length, appliance power ratings, and the number of appliances.
®
3-6
• The central amplified output is either a selectable 25, 70.7 or a 100 volt audio output,
rated for 40, or 80 watts maximum, depending upon the amplifier and its configuration.
• The output meets Class B supervision requirements for notification appliance circuits.
• Each output circuit shall have a UL LISTED, 10K Ohm, 1W EOLR installed across the
last audio notification appliance. If the output is unused, it shall have a UL LISTED, 10K
Ohm, 1W EOLR across the output terminals. Each amplifier module contains the required
number for the supervised outputs. If more are needed, recommend using Wheelock, Inc.
End of Line Resistor Kit (Model Number EOLK, Part# 5076), which contains Eight (8) UL
LISTED 10K Ohm 1W resistors.
Wiring Diagrams for the Audio Portion of Audio/Visual Notification Appliances
AUDIO
+
_
UL LISTED 10K Ohm
1W EOLR
Figure 3-6
Wiring Diagram for Audio Notification Appliance Output
CAUTION: Do not loop wire under terminals. Break wire run to provide supervision of
connection.
STROBE
AUDIO
+
_
+
_
Figure 3-7
Wiring Diagram for Combination Audio/Visual Notification Appliances
in Central Amplifier Applications
CAUTION: Do not loop wire under terminals. Break wire run to provide supervision of
connection.
UL LISTED 10K Ohm
1W EOLR
UL LISTED 10K Ohm
1W EOLR
Amplified Speaker Notification Appliance Power Output Wiring
Wire gauge selection for the amplified speaker notification appliance power output should involve
consideration of all factors including wire loop length, maximum current draw of each appliance,
number of appliances, and maximum voltage drop allowable.
• The Speaker Amp (SPK AMP) output is rated for 24VDC, 2.0 amps maximum.
• The output meets Class B supervision requirements for notification appliance circuits.
• The amplified speaker output is 15 Ohms, -5dBm maximum.
• Each output circuit shall have a UL LISTED, 10K Ohm, 1W EOLR installed across
the last appliance. All unused outputs shall have a UL LISTED, 10K Ohm, 1W EOLR
across the output terminals. Each amplifier module contains the required number for
the supervised outputs. If more are needed, recommend using Wheelock, Inc. End of
Line Resistor Kit (Model Number EOLK, Part# 5076), which contains Eight (8) UL
LISTED 10K Ohm 1W resistors.
3-7
Wiring Diagrams for Audio and SPK AMP Portions of Self-Amplified Audio/Visual Notification
Appliances
SPKR
AMP
AUDIO
+
_
+
_
UL LISTED 10K Ohm
1W EOLR
UL LISTED 10K Ohm
1W EOLR
Figure 3-8
Wiring Diagram for Audio Notification Appliances
in Amplified Speaker Applications
CAUTION: Do not loop wire under terminals. Break wire run to provide supervision of
SPKR
AMP
connection
+
_
+
STROBE
AUDIO
_
+
_
Figure 3-9
Wiring Diagram for Combination Audio/Visual Notification Appliances
in Amplified Speaker Applications
UL LISTED 10K Ohm
1W EOLR
UL LISTED 10K Ohm
1W EOLR
UL LISTED 10K Ohm
1W EOLR
Optional Equipment Connections
Remote Microphone Station (RMS-2)
See the Remote Microphone Station instruction sheet P83270 for additional information.
SECTION 3
REMOTE MICROPHONE
STATION AND AIM-3
CONNECTIONS
Figure 3-10
Wiring Connection Locations
Dry Contact Input Wiring
The dry contact inputs shall be dry contacts or open collector of a transistor. The locations of the dry
contact inputs are shown in Figure 3-10 Section 1. A magnified view of this area on the Motherboard
(SCMB) is shown in Figure 3-11 on Page 3-11.
• The dry contact input meets the requirements for non-power limited fire protective signaling
circuits as defined in the National Electrical Code. The dry contact inputs are unsupervised.
• The field wiring for the dry contact input shall not exceed 100 Ohms of resistance or 0.050 µF of
capacitance.
• IN1 through IN8 are the contact closure inputs for as many as 8 separate messages. As shown in
Figure 3-11.
3-9
Digital Voice Module
MDX-2
RV8
IN8
IN7
TB 3
RV7
D11
RV6
IN6
IN5
IN4
IN3
IN2
IN1
RV5
RV4
RV3
RV2
TB 2
RV1
Figure 3-11
Dry Contact Input Connections
ALARM STATUS OUTPUT CONTACT WIRING
Motherboard (SCMB)
+
TRB AUD
-
TRB COM
TRB NO
TRB NC
ALARM COM
ALARM NO
TB1
Figure 3-12
Alarm and Trouble Status Output Connections
The location of the Alarm Status output connections are shown in Figure 3-10 Section 2 on Page 3-
10. A magnified view of this area on the Mother Board is shown in Figure 3-12 on Page 3-11.
ALARM NC
• Wire gauge selection of the Alarm Status output contact wiring should involve consideration
of all factors including, wire loop length, maximum current capacity, and maximum voltage
drop allowable.
• The Alarm Status output contact is Form C, rated for 0.5 amps at 24VDC, resistive load.
• For terminal connection details of the Alarm Status output contact (shown and marked in
the non-alarm mode) see Figure 3-13.
3-10
TB1
6
ALARM COM
7
ALARM NO
8
ALARM NC
Figure 3-13
Alarm Relay Contacts
System Trouble Status Output Contact Wiring
The location of the Trouble Status output connections are shown in Figure 3-10 Section 2 on Page 3-
10. A magnified view of this area on the Mother Board is shown in Figure 3-12 on Page 3-11.
• Wire gauge selection of the system Trouble Status output contact wiring should involve
consideration of all factors including, wire length, maximum current capacity, and maximum
voltage drop allowable.
• The system Trouble Status output contact is Form C, rated for 0.5 amps at 24 VDC,
resistive load.
• For a detail of the system Trouble Status output contact Terminal connections (shown and
marked in the trouble condition), see Figure 3-14.
TB1
3
TRB COM
4
TRB NO
5
TRB NC
Figure 3-14
Trouble Status Relay Contacts
Trouble Audible Output Wiring
• Wire gauge selection of the System Trouble Output Contact wiring involves consideration
of all factors including wire loop length, maximum current capacity, and maximum voltage
drop allowable.
• The Trouble Audible output is rated for 24VDC, 0.1 amps maximum. The output is
unsupervised.
• Wiring diagram for the unsupervised Trouble Audible output connection – Figure 3-15
3-11
GRND
TB1
1
+
_
2
TRBL AUDIO
24VDC
Figure 3-15
Trouble Audible Connection
Ground Fault Detection Wiring
On the Mother Board, connect Earth Ground Connection (E1) as shown on Figure 3-1 on Page 3-2 to
the Chassis Ground (Figure 3-17 on Page 3-15). Make sure that chassis ground is at earth ground or
to the common ground of the FACP. Conduct the sensitivity adjustment as described in Section 3-7
Ground Fault Detection Sensitivity Adjustment.
POWER CONNECTION REQUIREMENTS
The Single Circuit SAFEPATH® Panel contains a 24VDC, 6 Amp Power Supply and a 40AH Battery
Charger for the battery backup. Connections for the input power and batteries are shown in Figure 3-16
on Page 3-14. Calculate proper backup battery requirements using Section 3-8.
WARNING: IT IS IMPORTANT THAT THE WIRING USED FOR INPUT VOLTAGE WIRING IS
LARGE ENOUGH TO CARRY THE MAXIMUM CURRENT REQUIRED BY THE
SAFEPATH
DROPS FROM AC POWER LINE LOADING AND WIRING RESISTANCE IS NOT
WITHIN THE SPECIFIED OPERATING VOLTAGE RANGE, THE SAFEPATH
PANEL WILL NOT FUNCTION PROPERLY.
PANEL WITHOUT EXCESSIVE VOLTAGE DROP. IF VOLTAGE
®
3-12
Digital Voice
Module MDX-2
P83412 REV ( )
U17
R72
RV10
R71
R73
RV9
Q2
D12
C48
R70
R69
R66
Q1
R67
D13
R68
U13
RV8
R65
C44
D10
J6
TB3
R62
RV7
R64R63 D11
C41
RV6
R60
R59
C40
R58
R57
C39
R56
R55
RV5
C38
R54
R53
C36
RV4
R52
R51
C35
R50
RV3
R49
C34
R48
R47
RV2
C33
R46
R45
TB2
RV1
F1
R35
R34
+
C27
GND
EARTH
E1
K2
J3
D4
R26
R21
R22
D3
C17
J2
+
R20
C9
+
U1
C10D2D1
+
TB1
K1
C8
REV: SN:
C50
U16
C49C47
C46
U15
S15
C45
U14
S14
C43
U12
S12
C42
R61
U11
R41
R43
C32
U10
R40
C31
C30
C29
R42
R44
C28
R39
R37
U9
U8
S8
D9
C26
U7
C25
L2
C24
C22
C23
R33
D8
C21
+
L1
R31
R29
R32
C20
C19
R19
C16
R8
R9
R27
U6
U5
R30
R28
R25
CH1 VOL
R24
R23
C18
R14
R13
C14
R17
C12
R10
R18
C11 R15
R12
R16
C15
R11
C13
U3 U4
U2
R3R4C3C1
R6 C6
R5 R7R1C4
C5
R2
C2C7
J5
C37
R38
R36
J4
D7
D6
D5
J1
10
6
6
10
SMP7PM
AC
AC
AC FAIL
C NC NO
BAT FAIL
NO NC C
-
DC
+
AC
SW2
-
BAT+
DC
SAFEPATH P83167 REV B
T1
SW1
J1
U3
P1
K1
SW1 SW2 SW3
C16
D1
AMBER GREEN
K3
X1
U5
U6
U8
U10
D2
F1
K2
TB1
U1
+
F2
-
+
U2
-
U9
TB2
TB3
SW4
4
2 3
1
ON
4
2 3
1
ON
SW5
TB5
MICROPHONE
+
-
+
-
+
-
+
-
E1
+
-
+
-
+
-
J2
U4
X2
Power Supply/
TWO BLACK LEADS
Battery Charger
DCPS
Input Power and Battery Connection Locations
TWO WHITE LEADS
120VAC
60Hz, 2.3A
Figure 3-16
-
24VDC BATTERY
BAT
CONNECTION
+
Section 3-5 - Mounting
Location
The SAFEPATH® Panel shall be mounted in a location within the environmental limits specified in the
latest UL Standard 864 for indoor control panels. The SAFEPATH
hazardous area.
CAUTION: In order to comply with the latest NFPA and UL requirements for interconnection of
fire alarm control equipment, the SAFEPATH
room, and within 20 feet of, a listed compatible fire alarm control panel. Wiring shall
be enclosed in conduit and properly connected to such control panel.
®
Panel shall not be located in a
®
Panel must be located in the same
3-13
Procedure
1. See Figure 3-17 on Page 3-15 for SAFEPATH® Panel mounting hole layout.
2. Remove Amplifier Module from the enclosure.
3. Mark and drill mounting holes for appropriate screws and anchors to ensure secure mounting to
the type of surface at the selected location.
4. Prevent dust and dirt contamination of the SAFEPATH
®
Panel during installation. This
contamination can interfere with the operation and reduce the expected life of the equipment.
5. Open the door and mount the SAFEPATH
Panel at the selected location. Use care to avoid
damage to the module PC boards during installation. Do not apply excessive pressure to any
PC board or its components, including field wiring terminals and connectors.
6. Replace Amplifier Module. Plug in Microphone.
7. For SAA-40S, 80S Amplifier Modules, set 25V/70V Switch to the correct setting for speakers. See
Figure 9-5 on Page 9-10 (SAA-40S) or Figure 9-6 on Page 9-12 (SAA-80S/SE).
14.00"
Conduit Entrances (Top and Bottom)
17.00"
Ground
Terminals
Figure 3-17
Single Circuit SAFEPATH
®
Panel Mounting
3-14
Section 3-6 System Checkout
Refer to NFPA 72 (1999 Edition) for guidelines on testing notification systems.
CAUTION: If a malfunction, or system trouble occurs during testing, STOPTESTING
the problem before you resume testing.
Insure that speaker and strobe NAC Circuits are not connected to the SAFEPATH
that 10K Ohm ¼W EOLR test resistors are connected in their place on the Mother Board.
1. Place switches on the Single Circuit Motherboard (SCMB) (Figure 3-10, Section 4 on Page 3-10
or Figure 3-18 on Page 3-17 for enlarged view) as follows:
DIP Switch SW4: TONE SEL, 3 – OFF, 2 – ON, 1 – ON, GND FLT ENB – OFF
DIP Switch SW5: RM ENABLE – OFF, SYNC – ON, DV ENABLE – ON, LAMP TEST - OFF
AUTOMATIC /MANUAL Switch: UP or “AUTOMATIC” position.
CAUTION: Connect the AC power source before connecting the battery backup power.
Disconnect the battery backup power before disconnecting the AC power source
2. Connect AC Power, then connect battery backup.
The green System Normal LED indicator on the Motherboard should be “ON” to indicate normal
operation. If the amber system trouble LED is “ON”, a trouble condition is indicated. Refer to
Chapter 7 "Troubleshooting and Servicing" to diagnose and correct the trouble condition.
Initial Checkout
3. With both AC Power and battery backup power applied observe the following indicators:
Single Circuit Motherboard (SCMB) (See Figure 9-2 )
TROUBLE / NORMAL LEDs Yellow “OFF”, Green “ON”
Digital Voice Module (MDX-2) (See Figure 9-3)
LED D5 (Green) “ON”
LED D6 (Yellow) “OFF”
LED D7 (Yellow) “OFF”
Amplifiers (SAA-40S, SAA-80S/SE, SALL-15S) SAA-40S, SAA-80S/SE (See Figure 9-5 for SAA-40S or Figure 9-6 for SAA-80S/SE)
LED D15 (STR) “OFF”
LED D10 (SPK) “OFF”
LED D6 (AMP) “OFF”.
SALL-15S (See Figure 9-7)
LED D16 (STROBE) “OFF”
LED D13 (AUDIO) “OFF”
LED D10 (PWR) “OFF”
LED D3 (AMP) “OFF”.
4. Play first message by momentarily shorting IN1 on the Digital Voice Module (MDX-2). Relay on
SCMB clicks at 1 click per second. When message ends, relay will stop clicking. Amplifier
Modules: All LEDs “OFF”.
5. Key Microphone in panel. Relay on SCMB clicks at 1 click per second. When microphone push to
talk (PTT) is released, clicking will continue until the RESET Switch is depressed (See Figure 5-1
on Page 5-3 for location). Amplifier Modules: All LEDs “OFF”.
6. Disconnect Battery Backup, then disconnect AC Power.
7. Return to Section 3-2 General Installation Instructions, Step 13.
. Correct
®
Panel, and
.
3-15
Final Checkout
CAUTION: If a malfunction, or system trouble occurs during testing, STOP TESTING. Correct
the problem before you resume testing.
CAUTION: Connect the AC power source before connecting the battery backup power.
Disconnect the battery backup power before disconnecting the AC power source.
1. Set Configuration Switches to desired settings for supervision tone. See Figure 3-18 on Page 3-17 for
switch location on the Motherboard (SCMB). See Tables 3-2 and 3-3 for switch descriptions.
NOTE: The tone selected is used to supervise the amplifiers in STANDBY condition. It is also
the tone when the AUTOMATIC/MANUAL switch is placed in the MANUAL position. The
tone will also play in ALARM if DIP Switch SW5, DV ENABLE is OFF and the input
contact closure is placed on the CH PLAY terminals on the Motherboard.
Motherboard
SCMB
SW4
4
2 3
1
ON
4
2 3
1
ON
TONE SEL
3
2
1
CND FLT ENB
RM ENABLE
SYNC
DV ENABLE
LAMP TEST
SW5
Figure 3-18
Configuration DIP Switch Location on SCMB Module
3-16
Table 3-1
SCMB DIP Switch Setting Description
DCDC DIP Switch SETTING/DESCRIPTION
SW4 Position 1
(GND FLT ENB)
GROUND FAULT ENABLE enables the ground fault detection circuit on
the Motherboard
SW4 Position 2, 3, 4
(1, 2, 3)
SW4Position 1, (LAMP
TEST)
SW5 Position 2, (DV
ENABLE)
SW5 Position 3,
(SYNC)
MULTITONE SELECT selects 1 of 8 tones used for the secondary
evacuation signal. Use chart below to select the tone.
LAMP TEST when enabled lights all the LED indicators on the
Motherboard, and the Amplifier Module.
DIGITAL VOICE ENABLE when enabled, allows the MDX-2 to transmit
messages through the SAFEPATH
®
Panel.
SYNCHRONIZED STROBES ENABLE. “ON” enables Strobe NAC
to work with Wheelock’s synchronized strobes.
Remote Microphone Station. “OFF” disables Remote Microphone Station
circuit.
Table 3-2
DIP Switch Settings for Available Tone Sounds
TONE SOUND
Horn (Continuous) ON ON ON
Bell (1560 Hz Modulated) ON OFF ON
March Time Horn (.25 Sec ON, .25 Sec OFF) OFF OFF ON
Code-3 Horn (ANSI S3.41 Temporal) ON ON OFF
Code-3 Tone 500Hz (ANSI S3.41 Temporal) OFF ON ON
Slow Whoop (500-1200Hz Sweep) OFF ON OFF
Siren (600-1200 Hz Sweep) ON OFF OFF
HI/LO (1000/800 Hz) OFF OFF OFF
SW4-2
1
SW4-3
2
SW4-4
3
2. Connect AC Power, and then connect battery backup.
3. With both AC Power and battery backup power applied observe the following indicators:
Single Circuit Motherboard (SCMB) (See Figure 9-2)
TROUBLE / NORMAL LEDs Yellow “OFF”, Green “ON”
Digital Voice Module (MDX-2) (See Figure 9-3)
LED D1 (Green) “ON”
LED D2 (Yellow) “OFF”
LED D3 (Yellow) “OFF”
Amplifiers (SAA-40S, SAA-80S/SE, SALL-15S)
SAA-40S, SAA-80S/SE (See Figure 9-5 for SAA-40S or Figure 9-6 for SAA-80S/SE) LED D15 (STR) “OFF”
LED D10 (SPK) “OFF”
LED D6 (AMP) “OFF”
SALL-15S (See Figure 9-7) LED D16 (STROBE) “OFF”
3-17
LED D13 (AUDIO) “OFF”
LED D10 (PWR) “OFF”
LED D3 (AMP) “OFF”
4. Play each messages by momentarily shorting IN1 through IN8 in turn on Digital Voice Module.
See Figure 3-11 on Page 3-11.
Relay on SCMB clicks at 1 click per second during the playing of each message.
Message will broadcast on all appliance circuits. If Strobe NAC circuits are in use, Strobes will
also flash.
5. Key Microphone in panel.
Relay closure can be heard.
Message will broadcast on all appliance circuits. If Strobe NAC circuits are in use, Strobes will
also flash.
6. If Remote Microphone Station (RMS-2) or the AIM-3 is included, enable it by switching SW5-4
(RM ENABLE) to “ON” on the Single Circuit Motherboard (SCMB).
7. Test the Remote Microphone Station.
8. System is fully operational.
Additional system checkout should include:
Testing all Alarm and Trouble circuits.
Testing all connections to equipment that is interconnected with the SAFEPATH
®
Panel.
WARNING: ALL PROTECTIVE SIGNALING SYSTEMS REQUIRE PERIODIC TESTING. ALL
PROTECTIVE SIGNALING SYSTEM EQUIPMENT SHALL BE TESTED BY
QUALIFIED PERSONNEL AT LEAST TWICE A YEAR FOR PROPER
OPERATION, OR MORE OFTEN IF REQUIRED BY CODES, REGULATIONS
AND LAWS. FAILURE TO MAINTAIN AND TEST PROTECTIVE SIGNALING
SYSTEM EQUIPMENT CAN RESULT IN NOT DETECTING EQUIPMENT
FAILURE THAT CAN CAUSE PROPERTY DAMAGE AND SERIOUS
PERSONAL INJURY OR DEATH TO YOU AND/OR OTHERS DURING AN
EMERGENCY SITUATION.
Ground fault detection sensitivity can be adjusted for a set point between 40K Ohms and 500K Ohms.
Selecting a high resistance set point will increase the circuit sensitivity to ground fault conditions. A
high resistance may cause many false trouble conditions.
Selecting a low resistance will decrease the circuit sensitivity and will greatly reduce susceptibility to
false trouble conditions. The lower resistance allows for lower ground fault resistance before a ground
fault conditions occurs.
Before the sensitivity is adjusted, it is imperative to correct (clear) all trouble conditions.
NOTE: The ground fault detection sensitivity set-point shall be the same value as the FACP.
Adjustment Procedure
1. Place "GRND FLT ENB DIP switch in the ON position (SW4, POS 1). See Figure 3-18 on Page
3-17.
2. Disconnect the wire between earth ground and the earth ground terminal on the Mother Board.
(See Figure 9-2 on Page 9-5 for location.)
3-18
3. Rotate the shaft of the Ground Fault Detection Sensitivity potentiometer (R53) fully
counterclockwise. (See Figure 9-2 on Page 9-5 for location) The potentiometer is a 12-turn
device, there will be need to rotate the shaft repeatedly. The potentiometer produces a clicking
sound when rotated beyond its end point.
On the Mother Board (SCMB), place a resistor with the desired set-point value (40K Ohm to 500K
4.
Ohm, +/- 5% Tolerance) between the +24VDC terminal on TB4 and the earth ground terminal.
See Figure 3-10 on Page 3-10.
5. Slowly rotate the shaft of the Ground Fault Detection Sensitivity potentiometer clockwise. When
a ground fault is indicated by the trouble LED's, the sensitivity set-point is set correctly.
6. Disconnect the resistor used to set the sensitivity level.
7. Reconnect the wire between the earth ground terminal on the Mother Board and earth ground.
Section 3-8 - Battery Care and Backup Battery Calculations
Installation and Care of Sealed Lead Acid Batteries
Sealed lead acid batteries are designed to operate in standby service for approximately five years.
This is based upon a normal service condition where there is an ambient temperature of 20 degrees
C (68 degrees F) and batteries are completely discharged once every three months. LENGTH OF
SERVICE LIFE WILL BE DIRECTLY AFFECTED BY THE NUMBER OF DISCHARGE CYCLES,
DEPTH OF DISCHARGE, AND AMBIENT TEMPERATURE.
Use Guidelines:
Avoid installation and/or operation in close proximity to heat sources. While the operating
temperature range is 0 to 49 degrees C (32-120 degrees F), battery life will be maximized at an
ambient temperature of 20 degrees C (68 degrees F).
Batteries may generate ignitable gases. Because of this, batteries shall be installed in a wellventilated location, away from spark producing equipment.
Batteries shall not be installed in an atmosphere where organic solvents or adhesives may be
present. The batteries shall not be cleaned with oils, thinners, or similar substances. The
case and cover of the batteries are ABS plastic resin, which may suffer damage from these
chemicals.
Batteries shall not be installed in a heavy vibration or shock location.
Batteries shall have a minimum separation of ¼” between cells.
Insulated gloves shall always be worn when handling batteries.
WARNING: Batteries shall not be crushed, incinerated, or dismantled. The electrolyte
Batteries of different capacities, age, or manufacturer shall not be used together.
Battery Storage
Batteries which are to be stored for an extended period of time should be given a supplement charge
monthly. Batteries should never be stored in a discharged condition.
The self-discharge rate of batteries is approximately 3% per month when the storage temperature is
maintained at 20 degrees C (68 degrees F). The self-discharge rate will vary depending upon
temperature. Cooler temperatures cause the self-discharge rate to decrease. Warmer temperatures
cause the self-discharge rate to increase.
contains sulfuric acid, which can cause serious damage to eyes and skin. If
contact does occur, flush with water and seek immediate medical attention.
3-19
Calculating Backup Battery Requirements
A battery calculation worksheet is available at the back of this manual for assisting in calculating
battery backup.
It is necessary to calculate the current draw for battery backup requirements, The current
requirements depend on the system configuration and the optional modules installed. Battery Backup
current has two separate calculations that are added together. They are Standby Current and Alarm
Current.
CAUTION: The SAFEPATH
®
Power Supply generates 24VDC at a maximum of 6 Amps. The
sum of the currents from all modules, speaker circuits, and Strobe NAC circuits,
and Speaker Amp circuits (when SALL-15S are used) determine the current output
of the panel and cannot exceed 6 Amps. If the SAFEPATH
®
Panel output current
exceeds 6.0 amps, it is recommended that strobe circuits be routed through an
external power supply.
Standby Current
Standby current consumes the largest part of the storage battery capacity.
Table 3-4 represents the Standby Current of the Single Circuit SAFEPATH
signal as the supervision signal. Standby calculations can use the appropriate value from this table.
The Single Circuit SAFEPATH
®
Panel Models in this table contain the Power Supply (DCPS), Digital
Voice Module (MDX-2) and the listed amplifiers.
Standby Current from any optional module used is listed in Table 3-5. These values added to the
Panel current complete the total Standby current for the panel
Table 3-3
Standby Current for Single Circuit SAFEPATH
Model
SCSP-4RP
SCSP-8RP
SCSP-15SP
Standby Current per
UL Full Power SIN
Wave Testing
1
0.630 Amps
0.830 Amps
0.330 Amps
Standby Current when
DCDC is in Temporal
Code 3 Tone
2
0.530 Amps
0.530 Amps
0.330 Amps
®
Panel using the test
®
Panel
Standby Current when
DCDC is in HI/LO
(Worst Case Tone)
0.530 Amps
0.630 Amps
0.330 Amps
3
1
The UL Test is performed with the amplifiers out of the Panel and in a bench test condition.
2
This column uses the standard current calculation when Temporal Code 3 is selected on the
Mother Board (SCMB). This is the recommended configuration for operation.
3
This column shows the current value of the Panel with the Mother Board configured on the highest
current reading (HI/LO).
Maximum strobe current on each amplifier in the panel is 2 Amps at24VDC.
7
Maximum “SPKR AMP” current on each SALL-15S Module is 2 Amps at 24VDC.
7
0.100 0.100 0.100
Standby Current Calculating Procedure
1. From Table 3-4, select the desired value of current from the proper model.
2. From Table 3-5, select the standby current from all modules selected for the panel and add them
to the value of Step 1. (If multiple RMS-2 Modules are used, calculate the standby current for
each one.)
3. Multiply the results of Step 2 by the number of standby hours required. (i.e. 24 or 60). Record this
value as the Standby Amp-hours.
Alarm Current
Table 3-7 lists the alarm current for each amplifier.
If no strobes are installed the strobe current is zero. If strobes are installed, add the current ratings of
the strobes.
UL alarm speaker current calculations are measured with a full SIN wave input with a maximum
output are as follows:
3-21
Table 3-6
Calculations for Amplifier Alarm Current
Amplifier Module Alarm Current Calculation
SAA-40S
SAA-80S/SE
SALL-15S
1
If Strobe NAC Circuit is used, add total strobe current on that circuit to the corresponding
amplifier module calculation. A Strobe NAC Circuit cannot exceed 2 Amps of current.
2
“SPKR AMP” circuit on each amplifier module cannot exceed 2 Amps.
1
1
1, 2
[(Total wattage of connected speakers) X 55] + 0.4A
[(Total wattage of connected speakers) X 56] + 0.6A
(Sum of the “SPKR AMP” current) + 0.1A
Table 3-7
Amplifier Model
SAA-40S
SAA-80S/SE
SALL-15S
Average Current Output Measured by Wheelock, Inc.
Typical Voice
0.600 Amps
1.000 Amps
0.100 Amps +
“SPKR AMP”
current
Temporal
CODE-3 Tone
0.750 Amps
1.050 Amps
0.100 Amps +
“SPKR AMP”
current
Worst Case
Tone HI/LO
1.600 Amps
2.500 Amps
0.100 Amps +
“SPKR AMP”
current
Strobe Current
2.000 Amps
Max.
2.000 Amps
Max.
2.000 Amps
Max.
Alarm Current Calculating Procedure
1. Using Table 3-7, calculate the alarm current for each amplifier module installed.
2. Using Table 3-5, add up the alarm currents of all optional modules. If multiple Remote
Microphone Stations (RMS-2) are used, calculate the alarm current of just one
.
3. Add together the strobe current from the amplifiers NAC circuit.
4. Total the results of Steps 1 through 3.
5. Divide Step 3 results by 12 (5 minutes of alarm) or 4 (15 minutes of alarm) and record this value
as Alarm Amp-hours.
Calculating Backup Battery Requirements
Good engineering practices recommend the total Amp-hours required for backup should not
exceed 80% of the Backup Battery capacity.
Backup Battery Calculation Procedure
1. Add the total Standby Current to the total Alarm Current.
2. Multiply Step 1 by 1.25. This is the minimum Backup Battery requirement for this Panel.
3. Record results on the battery calculation worksheet at the end of this manual.
3-22
3-23
Chapter 4 - OPERATION
Section 4-1- Introduction
This chapter describes the operating characteristics of the SAFEPATH® Panel. Included is
information about the following SAFEPATH
• Amplified Speaker Notification Appliance Power Output Supervision
• Amplifier Supervision
• Remote Microphone Station Supervision (Optional RMS-3)
• Actions that Initiate Alarms
Section 4-2 - Operator’s Console
An operator’s console, which allows for manual override of the automatic message playing, is
provided. The operator’s console includes a microphone, a RESET pushbutton, a TROUBLE
ACKNOWLEDGE pushbutton, and a main AUTOMATIC/MANUAL switch. There are two LEDs to
indicate NORMAL for normal operation and TROUBLE for any Panel trouble condition. Opening the
enclosure door accesses the operator’s console.
Section 4-3 - Supervision
A trouble condition indicates that the supervisory functions have detected a malfunction in the panel.
When a trouble condition is detected, the panel may not be able to receive and/or remember
message requests from the control panel. The installer and/or user must make sure that any
message requests to the panel during a trouble condition are reactivated if necessary, when the
panel is returned to normal.
If a trouble condition is detected by any of the supervisory functions, the panel Form C status relay
(normally energized) will change state, the green NORMAL LED will turn “OFF”, and the amber
TROUBLE LED will turn “ON”. The status relay contact closure must be properly connected to and
used by the control panel to indicate a system trouble. At the same time an amber trouble location
LED will identify the location of the trouble condition. If a trouble condition is indicated, follow the
procedures in Chapter 7 "Troubleshooting”.
WARNING: DO NOT LEAVE THE PANEL IN A TROUBLE CONDITION AS, IT MAY NOT
PLAY WARNING MESSAGES WHICH COULD RESULT IN PROPERTY
DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. IF
THE PANEL INDICATES A TROUBLE CONDITION:
(1) PROVIDE UL REQUIRED ALTERNATIVE SIGNALING AND
(2) HAVE QUALIFIED SERVICE PERSONS IMMEDIATELY REPLACE
UNIT(S) THAT HAVE MALFUNCTIONED.
®
Panel features:
4-1
WARNING: MESSAGES REQUESTED BEFORE AND DURING A TROUBLE CONDITION MAY
NOT BE HEARD, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS
INJURY OR DEATH TO YOU AND/OR OTHERS. IF MESSAGES REQUESTED
BEFORE AND DURING A TROUBLE CONDITION ARE STILL NECESSARY, THEY
SHOULD BE REPEATED WHEN THE SAFEPATH
NORMAL.
The visual notification appliance output circuit is supervised for open and short circuits when the output is
de-energized. Output circuit supervision requires installation of the supplied UL LISTED, 10K Ohm EOLR
on the output circuit. Any sensed trouble will illuminate the “STR” LED on the amplifier module. See
Figure 7-1 on Page 7-2 for LED location.
The audio notification appliance output circuit is supervised for open and short circuits when the output is
de-energized. The circuit is unsupervised when the output is energized. Output circuit supervision
requires installation of the supplied UL LISTED, 10K Ohm EOLR on the output circuit. Any sensed
trouble will illuminate the “SPK” LED on the amplifier module. See Figure 7-1 on Page 7-2 for LED
location.
Amplified Speaker Notification Appliance Power Output Circuit Supervision
®
PANEL IS RETURNED TO
The amplified speaker notification appliance power output circuit supervised for open and short circuits
when the output is de-energized. Output circuit supervision requires installation of the supplied UL
LISTED, 10K Ohm EOLR on the output circuit. Any sensed trouble will illuminate the “PWR” LED on the
SALL-15S module. See Figure 7-1 on Page 7-2 for LED location.
Amplifier Supervision
A supervisory tone plays through the amplifier during standby for supervision purpose. Any sensed
trouble illuminates the “AMP” LED on the amplifier module. See Figure 7-1 on Page 7-2 for LED location.
Ground Fault Supervision
The SAFEPATH® Panel supervises for ground fault conditions on field wiring that is not electrically
isolated. The supervised wiring includes contact inputs, visual NAC circuits, audio NAC circuits, amplified
speaker NAC circuits, trouble audible output circuits, remote microphone station wiring and MDX-2 wiring.
All other wiring is electrically isolated. Ground fault supervision may be enabled and disabled by switching
the ground fault enable switch on (GND FLT ENB, SW4, POS 1). See Figure 3-18 on Page 3-17.
Remote Microphone Supervision (Optional RMS-2)
The audio circuit is supervised on the Remote Microphone Station PCB.
Section 4-4 - Actions That Initiate Alarms
Table 4-1 indicates what can initiate an alarm condition and the resulting SAFEPATH Panel actions.
NOTE: The list is arranged in order of priority (e.g., number 1 in Table 4-1 supersedes number 2
priority).
4-2
PRIORITY
OF EVENT
1. Panel microphone push-to-talk button, is
depressed.
Table 4-1 Alarm Conditions and Results
INITIATING ACTION
a. Panel microphone live voice broadcast
enabled
RESULT
b. Strobes enabled (See Note 2)
2. Automatic /Manual switch placed in
manual position.
3. Optional remote Mic key is on, and
remote Mic push-to-talk button is
depressed.
4. Optional remote Mic key is on, and
remote Mic auto/manual switch is in
a. Selected tone broadcasts
b. Strobes enabled (See Note 2)
a. Remote microphone live voice
broadcast enabled
b. Strobes enabled (See Note 2)
a. Selected tone broadcasts
b. Strobes enabled (See Note 2)
manual position.
5. Contact closure inputs a. Selected tone broadcasts
b. Strobes enabled
c. MDX-2:
1) Recorded message plays (see
note 1)
2) Strobes enabled (See Note 3)
Notes:
1. If the Digital Voice Module reports a trouble during condition 5c, the alarm condition is the selected
tone instead of the pre-recorded message.
2. The strobe circuit is a latching output. Once the strobe circuit is energized, it will stay energized until
the “RESET” switch is activated. Activating the “RESET” switch has no effect while an evacuation
signal is initiated.
3. The strobe circuit does not latch on when a digital voice message is being played from the MDX-2.
When the message ends the strobe circuit will revert back to standby mode.
4-3
Intentionally Blank
4-4
Chapter 5 - Operational Procedures
Section 5-1 - Operator Instructions
The SAFEPATH® Panel provides an operator console for manually activating the panel. The operator
console includes a microphone, a green NORMAL LED, a yellow TROUBLE LED, a “RESET” momentary
switch, a TROUBLE ACKNOWLEDGE momentary switch, and a MANUAL/AUTOMATIC switch. The
operator interface allows the operator to manually override automatically playing pre-recorded messages
with live announcements or an evacuation tone, to silence internal and external trouble audibles, and to
ascertain if the panel has detected a trouble condition. The operator instructions on the dead front panel
are shown in Figure 5-1 on Page 5-3.
The TROUBLE and NORMAL LEDs identify to the operator the condition of the SAFEPATH
yellow TROUBLE LED will be illuminated whenever there is a trouble detected by the Panel. If no
troubles are detected, the green NORMAL LED will be illuminated.
The TROUBLE ACKNOWLEDGE push-button allows the operator to silence the trouble audibles, both
internal and external. When a trouble condition is detected, both the internal and external trouble
audibles are sounded. When the ACKNOWLEDGE push-button is depressed, the internal and external
trouble audibles will be silenced. The trouble audibles will resound for subsequent trouble conditions.
The Form C trouble output contact will remain in the trouble condition and the TROUBLE LED will remain
illuminated until all trouble conditions have been corrected.
The AUTOMATIC/MANUAL switch has two positions, manual (down) and automatic (up). When the
AUTOMATIC/MANUAL toggle switch is in the automatic position, pre-recorded messages may be
selected to play via dry contact inputs. When the AUTOMATIC/MANUAL switch is in the manual position,
pre-recorded messages will not play, the visual notification appliances are energized, and the evacuation
tone sounds.
Section 5-2 - To Make Live Announcements
From Panel
®
Panel. The
1. Hold the microphone within 2 inches of your mouth, press the push-to-talk switch and begin speaking.
From Optional Remote Microphone Station (RMS-2)
1. Turn the key switch from the OFF position to the ON position.
2. Hold the microphone within 2 inches of your mouth, press the push-to-talk switch and begin speaking.
See the Remote Microphone Station instruction sheet P83270 for additional information.
Section 5-3 - To Sound Evacuation Tone
From Panel
1. Slide the AUTOMATIC/MANUAL switch on the panel down to the MANUAL position. The selected
tone will play. Turn off the tone by returning the AUTOMATIC/MANUAL Switch to the UP position.
See Figure 5-1 on Page 5-3 for switch location.
From Optional Remote Microphone Station (RMS-2)
1. Turn the key switch from the “OFF” position to the “ON” position.
5-1
2. Slide the AUTOMATIC/MANUAL switch down to the MANUAL position. The selected tone will play.
Turn off the tone by returning the AUTOMATIC/MANUAL Switch to the UP position. See Figure 5-1
on Page 5-3 for switch location.
See the Remote Microphone Station instruction sheet P83270 for additional information.
Section 5-4 - To Reset Visual Appliances
1. All activation inputs must be cleared.
2. Depress the RESET momentary switch. See Figure 5-1 on Page 5-3 for switch location.
Section 5-5 - To Acknowledge a Trouble Condition
1. Depress the TROUBLE ACKNOWLEDGE momentary switch. See Figure 5-1 on Page 5-3 for switch
location.
Acknowledging a trouble condition silences the internal sounder and any external trouble
:
NOTE
signaling devices. The system will remain in the trouble condition with the yellow TROUBLE
LED “ON”. The system trouble contact will remain in the trouble position until all trouble
conditions have been corrected. Any faults, which occur after acknowledgment, will resound the
trouble circuit.
5-2
When the GREEN “NORMAL” LIGHT
Is ON, the system is functioning
Pr operly.
When the YELLOW “TROUBLE LIGHT
is ON, there is a FAULT in the
system which MUS T BE CORRECTED.
! Warning:
IF THE YELLOW “TROUBLE” LIGHT IS ON,
THIS UNIT MAY NOT BE ABLE TO PROVI DE
EMERGENCY MESSAGE ANNOUNCEMENT
CAPABI LITIES AND COULD RESULT IN PROPERTY
DAMAGE. SERI OUS INJ URY OR DEATH TO YOU
AND/ OR OTHERS. IN THE EVENT THE
“TROUBLE” LIGHT IS ON, YOU SHOULD CONTACT
YOUR SERVI CE REPRESENTATIVE IMME DIATELY.
ACKNOWLEDGEMENT
To Acknowl edge a Trouble Condition:
1. Mome ntarily slide the TROUBL E/
ACKNOWLEDGE switch down to
the ACKNOWLEDGE position.
This will only silence the internal
Sounder and any external trouble
signaling devices. The system will
rema in in a trouble condition wi th
the yellow “TROUBLE” light on and
the system trouble contact will
rema in in the trouble position until
all trouble conditions have been
corrected.
MANUAL OPERATION
To Sound Evacuation Tone:
1. Switch MANUAL /AUTOMAT IC switch
DOWN to the MAN UA L position.
MICROPHONE OPERATIONS
1. Hold the microphone within two
inches of mo uth and press
push-to-talk switch on
microphone.
2. Deliver me ssage. Activation of
the microphone will deliver the
me ssage to all circuits.
RESET
To Turn Off St robes:
1. All initiating circuits mu st be reset.
2. Mome ntarily slide the RESET
swi tch to the RESET position.
FOR ADDI TIONAL INFORMAT ION
REFER TO OPERATI ON AND
TROUBLE
AUTOMATIC
MANUAL
STATUS
NORMAL
RESET
TROUBLE
ACKNOWLEDGE
Figure 5-1
Single Circuit SAFEPATH
®
PanelOperator Console
5-3
Intentionally Blank
5-4
Chapter 6 - Periodic Testing and
Maintenance
Section 6-1 – Periodic Testing
Periodic testing of emergency notification equipment, including the SAFEPATH® Panel, all notification
equipment and all messages, including their audibility and intelligibility, content and language, sequence,
and priority assignment, must be conducted frequently, at least twice each year, or more often as
required by local, state and federal codes, regulations and laws, by qualified personnel to ensure proper
operation of all equipment. If the notification equipment is not working properly, immediately contact the
installer and have all/any problems corrected immediately. Malfunctioning units should be replaced
immediately. Do not attempt to repair malfunctioning units. Malfunctioning units should be returned for
factory repair or replacement. In the event you cannot contact the installer, contact the manufacturer.
To aid qualified personnel in performing necessary operational testing procedures, a script, listing all
messages programmed in the SAFEPATH
NOTE: As an aid to qualified personnel to perform necessary operational testing procedures,
Section 6-2 - Qualified Personnel
Qualified personnel are those who can evaluate proper equipment functionality and ensure its proper
operation and shall perform all testing procedures on the SAFEPATH
®
Panel, shall be kept with the Panel.
keep a script of all programmed messages with the SAFEPATH
®
system.
®
Panel.
WARNING: PROVIDE ALTERNATIVE SIGNALING MEANS DURING PERIODIC TESTING TO
ASSURE ADEQUATE PROTECTION OF PEOPLE AND PROPERTY. FAILURE TO
PROVIDE ALTERNATIVE SIGNALING MAY CAUSE PEOPLE TO NOT BE
WARNED OF AN EMERGENCY CONDITION WHICH COULD RESULT IN
PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR
OTHERS.
Section 6-3 - Miscellaneous Hardware Testing
In addition to testing required by relevant fire codes, regulations, and laws, the following hardware
functions shall be tested (see Table 6-1).
Table 6-1
Miscellaneous Hardware Tests
TEST/HARDWARE TEST DESCRIPTION
Short circuit detection/Contact inputs Activate (short circuit) each contact input, and
verify that proper tone sounds.
Proper operation/Status Contact Monitor the status contact, while causing the
panel to alternate between trouble and normal
states to verify proper operation.
If the panel fails to perform any of the above tests correctly, replace the malfunctioning modules and/or
panel immediately.
6-1
Intentionally Blank
6-2
Chapter 7 – Troubleshooting
Section 7-1 - Troubleshooting
WARNING: SOME ELECTRONIC COMPONENTS STORE A HIGH VOLTAGE CHARGE, EVEN
THOUGH POWER IS NOT CONNECTED, AND CAN CAUSE A DANGEROUS
SHOCK IF TOUCHED. DO NOT TOUCH EXPOSED CIRCUITRY ON THE
SAFEPATH
HOUR AND A SAFE DISCHARGE PROCEDURE IS USED.
WARNING: PROVIDE UL REQUIRED ALTERNATIVE SIGNALING MEANS DURING TROUBLE
CONDITIONS AND SERVICING TO ASSURE ADEQUATE PROTECTION OF
PEOPLE AND PROPERTY. HAVE QUALIFIED SERVICE PERSONS IMMEDIATELY
REPLACE ANY MODULES THAT HAVE MALFUNCTIONED.
CAUTION: Only qualified persons in accordance with the procedures in this manual should
conduct troubleshooting and servicing. Do not attempt to make other adjustments,
modifications, or repairs. Never use water, steam, and cleaning liquids or sprays on
the panel.
CAUTION: User servicing of the SAFEPATH
The procedures set forth in this section.
WARNING: AFTER ANY TROUBLESHOOTING PROCEDURE IS COMPLETED, PERFORM A
The panel monitors system integrity. Items monitored for integrity are:
1. Visual appliance circuit field wiring.
2. Audio appliance circuit field wiring.
3. Amplified Speaker Audio circuit field wiring.
4. Amplified Speaker Power circuit field wiring.
5. Input voltage. AC (120 VAC, 60 Hz). (220 VAC for export models) DC (Backup Battery 24VDC).
6. Battery voltage level.
7. Battery circuit field wiring.
8. Amplifier functionality.
9. Digital Voice Module functionality.
10. Internal wiring.
11. Internal fuses.
12. Optional Remote Microphone Station functionality and wiring.
System status is indicated to the operator via the NORMAL and TROUBLE LEDs. If a trouble condition is
detected, the panel will respond as follows:
1. Turn “OFF” the NORMAL (green) LED.
2. Turn “ON” the TROUBLE (yellow) LED.
3. Transfer the Form C trouble contact to the TROUBLE position.
4. Turn “ON” the internal trouble sounder.
5. Turn “ON” Remote Trouble Audible Output.
6. Turn “ON” a trouble location LED (amber), if appropriate.
If the TROUBLE ACKNOWLEDGE momentary switch is pressed, the internal trouble sounder and the
external trouble audible will be silenced. All other trouble indicators will still indicate a trouble condition.
Field-wiring changes. Follow the instructions in Chapter 3 of this manual.
COMPLETE SYSTEM CHECKOUT AS DESCRIBED IN CHAPTER 3.
®
PANEL UNLESS THE CIRCUITRY HAS DISCHARGED FOR ONE
®
Panel is limited to the following:
7-1
The internal trouble sounder and the external trouble audible will resound for subsequent trouble
conditions. When there are no trouble conditions detected, the NORMAL LED will always be “ON” and
the TROUBLE LED will always be “OFF”. When a trouble condition is detected, the NORMAL LED will
always be “OFF” and the TROUBLE LED will always be “ON”.
Figure 7-1 shows the location of all trouble location indicators within the panel. Table 7-1 crossreferences the trouble location indicators on the plug-in modules to the proper troubleshooting procedure.
Table 7-2 addresses the LEDs on the MDX-2.
If improper wiring is suspected, either from manufacture or technician replacement of a mounted module,
refer to Section 7-2 and to wiring diagram in Figure 7-4 on Page 7-13.
MDX-2 TROUBLE Digital Voice Module Trouble See Table 7-2
TROUBLE
LED
Module
LED Trouble Description
Troubleshooting
Procedure
Table 7-2
MDX-2 Trouble Procedure Cross Reference
DV Module
System Normal
LED (Green)
On Off Off Normal ----
Off Off Off Power Loss H
Off On Off DV Module Inoperative I
Off On Steady-On DV Module Inoperative J
Off On 2 Blink Pattern Message Memory Error K
Off On 4 Blink Pattern Output Channel Error L
DV Module
System Trouble
LED (Amber)
DV Module
Trouble Indicator
LED (Amber)
What it Means
Troubleshooting
Procedure
Figure 7-2 on Page 7-4 is the basic troubleshooting flowchart describing the troubleshooting procedure in
a graphic manner. The following flowchart contains the same information as described in Tables 7-1 and
7-2.
7-3
Single Circuit
Safepath Not
Operating
TROUBLE
"ON"
LED
YES
TROUBLE
LED "ON"
NORMAL
"OFF"
LED
SAA/SALL
STROBE LED
"ON"
NO
NONO
YES
NORMAL
"ON"
LED
YES
Refer to
Procedure C
Power Loss
Procedure A
Faulty Mother
Board (SCMB)
Procedure B
SAA/SALL
AUDIO LED
"ON"
NO
SALL
PWR LED
"ON"
NO
To Sheet 2
of Figure 7-2
YES
YES
Refer to
Procedure D
Refer to
Procedure E
Figure 7-2, Sheet 1 of 2
Basic Troubleshooting Flowchart
7-4
From Sheet 1
of Figure 7-2
NO
SAA/SALL
AMP LED
"ON"
NO
RMS-2
TROUBLE LED
"ON"
NO
MDX-2
NORMAL and
TROUBLE
LEDS "OFF
YES
YES
YES
"
Refer to
Procedure F
Refer to
Procedure G
Refer to
Procedure H
NO
MDX-2
TROUBLE LEDS
"ON"
Refer to
Figure 7-3
Figure 7-2, Sheet 2 of 2
Basic Troubleshooting Flowchart
7-5
From Sheet 2
of Figure 7-2
MDX-2
D6 LED
"ON"
MDX-2
D7 LED
"ON"
YES
MDX-2
D7 LED
Steady ON"
"
NO
YES
MDX-2
Inoperative
Procedure I
MDX-2
Inoperative
Procedure J
NO
MDX-2
D7 LED
"2 Blink"
NO
MDX-2
D7 LED
"4 Blink"
YES
YES
L
Message
Memory
EPROM error
Procedure K
Output Channel
Error
Procedure L
Figure 7-3
Digital Voice Module (MDX-2)
Troubleshooting Flowchart
7-6
WARNING: BEFORE PERFORMING ANY OF THE FOLLOWING TROUBLESHOOTING
PROCEDURES, THE PRELIMINARY TROUBLESHOOTING INFORMATION AT THE
BEGINNING OF THIS “TROUBLESHOOTING” SECTION ON PAGE 7-1, MUST BE
READ, UNDERSTOOD, AND FOLLOWED.
Procedure A
If the green NORMAL LED is “OFF”, the yellow TROUBLE LED is “OFF”, and no module LEDs are “ON”,
then a power loss condition has occurred. A power loss condition may be caused by:
1. Loss of AC input voltage and/or battery back-up voltage.
2. Faulty internal wiring between the Power Supply module and the Motherboard (SCMB).
3. Faulty Power Supply module.
4. Faulty Motherboard (SCMB).
Perform the following:
1. Check for 24 +/- 5VDC at TB6 on the SCMB. If voltage is not present, perform steps 2 and 3.
2. Remove Power Supply Cover. (See Figure 3-16 on Page 3-14) Observe if AC LED and DC LED are
“ON” (See Figure 9-5 on Page 9-10 for locations).
a) If both LEDs are “ON”, inspect wiring and connections between the Power Supply and
TB6 on SCMB.
b) If both LEDs are “OFF”, check 120VAC input to Power Supply. If AC is not present, check AC
source. If AC is present, replace Power Supply module.
c) If AC LED is “ON” and DC LED is “OFF”, remove AC Power and Battery Power from the
Power Supply, disconnect 24VDC wires from TB6 on SCMB and allow panel to cool for 20
minutes. Re-apply AC power. If DC LED remains “OFF”, replace Power Supply module. If DC
LED is “ON”, problem is a high current draw on the SCMB.
3. Replace the Mother Board (SCMB).
NOTE: Mark all wires before removing components. When the trouble is repaired, and before
testing, replace all wires to the proper locations and replace all covers. Figure 7-4 on Page
7-13 is the internal module wiring diagram for wire connection locations.
Procedure B
On the Single Circuit Mother Board (SCMB), if the green NORMAL LED is “ON” and the yellow TROUBLE
LED is “ON”, then a faulty Mother Board condition has occurred. A faulty Mother Board condition may be
caused by:
1. SCMB module inoperable.
2. Panel Microphone not properly plugged in.
Perform the following:
1. Replace the SCMB module.
2. Check Panel Microphone for proper plug in.
Procedure C
On the Single Circuit Mother Board (SCMB), the green NORMAL LED is “OFF”, the yellow TROUBLE
LED is “ON”, and on the SAA/SALL module the STR/STROBE LED is “ON”, then a visual notification
output wiring trouble condition
has occurred. A visual notification output wiring trouble condition might be
caused by:
1. Missing EOLR on the visual notification output.
2. The Visual Notification Output field wiring is open or shorted.
3. A fuse on the SAA/SALL module is blown.
4. A faulty SAA/SALL module.
5. A faulty Motherboard (SCMB) module.
7-7
Perform the following:
1. Check EOLR and verify that it is a UL LISTED, 10K Ohm, 5% Tolerance, 1W Resistor.
2. Check that the EOLR is properly in place.
3. Verify that the Visual Notification Output field wiring is intact.
4. Verify that all fuses on the SAA/SALL module are functioning.
5. If trouble does not clear, remove strobe appliance circuit wiring from Motherboard and place a 10K
Ohm 1/4W minimum resistor on strobe output (Figure 3-1 on Page 3-2). If STR/STROBE LED turns
“OFF”, the trouble is in the Strobe NAC Circuit. If trouble does not clear, replace the SAA/SALL
module.
6. Replace the Motherboard (SCMB).
Procedure D
On the Single Circuit Mother Board (SCMB), the green NORMAL LED is “OFF”, the yellow TROUBLE
LED is “ON”, and on the SAA/SALL module, the SPK/AUDIO LED is “ON”, then an audio output wiring
trouble condition has occurred. An audio output wiring trouble condition might be caused by:
1. Missing end-of-line resistor on the audio output.
2. The audio output field wiring is open or shorted.
3. A faulty SAA/SALL module.
4. A faulty Motherboard (SCMB).
Perform the following:
1. Check EOLR and verify that it is a UL LISTED 10K Ohm, 5% Tolerance, 1W Resistor.
2. Verify that the EOLR is properly in place.
3. Verify that the audio output field wiring is intact.
4. If trouble does not clear, remove audio appliance circuit wiring from Motherboard and place a 10K
Ohm 1/4W minimum resistor on audio output (Figure 3-1 on Page 3-2). If SPK/AUDIO LED turns
“OFF”, the trouble is in the Audio NAC Circuit. If trouble does not clear, replace the SAA/SALL
module.
5. Replace the Motherboard (SCMB).
Procedure E
On the Single Circuit Mother Board (SCMB), the green NORMAL LED is “OFF”, the yellow TROUBLE
LED is “ON”, and on the SALL-15S module the PWR LED is “ON”, then an amplified speaker power
output wiring trouble condition has occurred. An amplified speaker power output wiring trouble condition
might be caused by:
1. Missing EOLR on the amplified speaker power output.
2. The Amplified Speaker Power Output field wiring is open or shorted.
3. A fuse on the SALL-15S module is blown.
4. A faulty SALL-15S module.
5. A faulty Motherboard (SCMB).
Perform the following:
1. Check EOLR and verify that it is a UL LISTED 10K Ohm, 5% Tolerance, 1W Resistor.
2. Verify that the end-of-line resistor is properly in place.
3. Verify that the Amplified Speaker Power Output field wiring is intact.
4. Verify that all fuses on the SALL-15S module are intact. (See Figure 9-8 on Page 9-15 for locations)
5. If trouble does not clear, remove SPKR AMP appliance circuit wiring from Motherboard and place a
10K Ohm 1/4W minimum resistor on the output (Figure 3-1 on Page 3-2). If PWR LED turns “OFF”,
the trouble is in the Speaker Power NAC Circuit. If trouble does not clear, replace the SALL-15S
module.
6. Replace the Motherboard (SCMB).
7-8
Procedure F
On the Single Circuit Mother Board (SCMB), the green NORMAL LED is “OFF”, the yellow TROUBLE
LED is “ON”, and the AMP LED on the SAA/SALL module is “ON”, then an amplifier trouble condition has
occurred. An amplifier trouble condition may be caused by:
1. A faulty SAA/SALL module.
2. A faulty Motherboard (SCMB).
Perform the following:
1. Replace the SAA/SALL module.
2. Replace the Motherboard (SCMB).
Procedure G
On the Single Circuit Mother Board (SCMB), the green NORMAL LED is “OFF”, the yellow TROUBLE
LED is “ON”, and on the Remote Microphone Station (RMS-2) TROUBLE LED is “ON”, then a faulty
Remote Microphone Station condition has occurred. A faulty Remote Microphone Station condition may
be caused by:
1. Improperly configured panel.
2. Faulty wiring between the panel and the remote microphone station.
3. Faulty REM MIC fuse (F1) on the SCMB module.
4. Faulty Remote Microphone Station.
Perform the following:
1. If the system does not have a remote microphone attached then switch the Remote Microphone DIP
switch (RM) OFF. (See Figure 3-18 on Page 3-17 for switch location)
2. Verify field wiring between the panel and the remote microphone station. (See Appendix B)
3. Replace F1 on the SCMB module. (See Figure 9-3 on Page 9-7 for fuse location)
4. Replace the Remote Microphone Station.
Procedure H
On the Single Circuit Mother Board (SCMB), the green NORMAL LED is “OFF”, the yellow TROUBLE
LED is “ON”, and the Digital Voice Module NORMAL LED,SYSTEM TROUBLELED,and TROUBLE
LED are “OFF”, then the Digital Voice Module (MDX-2) may be completely inoperative due to power loss.
This condition is caused by:
1. Input voltage is not within proper range or polarity is incorrect.
2. Blown fuse (F2) on the MDX-2.
3. One or more LED's are broken.
4. Faulty Motherboard (SCMB)
Perform the following:
1. Verify the Voltage at TB6 on the Motherboard (DCMB) is within proper range and that polarity is
correct.
a. Check appropriate fuse on MDX-2.
b. Replace Motherboard.
If, after the above procedure is completed, the trouble condition persists, the trouble condition is caused
by broken LED's on the MDX-2 Module. The LED's on the MDX-2 module are not field replaceable.
Digital voice modules with broken LED's shall be replaced immediately, following the “SAFEPATH
®
Module Replacement Procedure”, set forth at the end of this section.
7-9
Procedure I
On the Single Circuit Mother Board (SCMB), the green NORMAL LED is “OFF”, the yellow TROUBLE
LED is “ON”, and the MDX-2 SYSTEM NORMAL LED is “OFF”, SYSTEM TROUBLE LED is “ON”, and
the TROUBLE LED is “OFF”, then the digital voice module may be completely inoperative. This condition
is caused by:
1. Too low input voltage on the digital voice module.
2. Missing or improperly installed program memory EPROM.
3. Broken TROUBLE LED (digital voice module is operative if this is the cause).
4. Failed circuitry on the digital voice module.
Perform the following:
1. Verify that the input voltage exceeds the minimum operating voltage.
2. Verify that the program memory EPROM is present and inserted into slot S15 properly.
3. Attempt to play a message file. If the file plays then the digital voice module trouble indicator LED is
broken.
If, after the above procedure is completed, the trouble condition persists, the trouble condition is caused
by failed circuitry on the Digital Voice Module. There are no field correctable failed circuitry problems on
the digital voice module. Digital Voice Modules with failed circuitry shall be replaced immediately,
following the “SAFEPATH
®
Module Replacement Procedure”, set forth at the end of this section.
Procedure J
On the Single Circuit Mother Board (SCMB), the green NORMAL LED is “OFF”, the yellow TROUBLE
LED is “ON”, and the MDX-2 SYSTEM NORMAL LED is “OFF”, SYSTEM TROUBLE LED is “ON”, and
the TROUBLE LED is “STEADY
ON”, then the digital voice module is partially or completely inoperative.
The Digital Voice Module can be rendered inoperative by:
1. Too low input voltage on the Digital Voice Module.
2. Failed audio channel on the Digital Voice Module.
3. Failed Message Kit (SMK or PMK)
4. Other failed circuitry on the Series MDX-2 or Output Channel Module (MDV-OCM).
If the error was either due to the first or third cause, the Digital Voice Module will not play
messages. If the error was due to the second cause, the Digital Voice Module might play
messages.
When the digital voice module is rendered inoperative, perform the following:
1. Verify that the input voltage is 24 ± 5VDC.
2. Attempt to play messages on all installed audio channels.
3. Remove Message Kit (SMK or PMK). If the “TROUBLE” LED on the MDX-2 goes to a 2 Blink pattern,
then the Message Kit is in error. Replace Message Kit.
There are no field correctable failed circuitry problems. Digital Voice Modules with failed circuitry shall be
replaced immediately, following the “SAFEPATH
®
Module Replacement Procedure”, set forth at the end
of this section.
Procedure K
On the Single Circuit Mother Board (SCMB), the green NORMAL LED is “OFF”, the yellow TROUBLE
LED is “ON”, and the MDX-2 SYSTEM NORMAL LED is “OFF”, SYSTEM TROUBLE LED is “ON”, and
the TROUBLE LED flashes a “2-blink pattern”, then a message memory EPROM error has occurred on
the MDX-2 module. A message memory EPROM error may be caused by:
1. Pre-programmed message memory EPROM's not installed into Series MDX-2 in proper order.
2. No messages programmed into message memory EPROM's.
7-10
3. Missing or improperly installed message memory EPROM's.
4. One or more of the messages were not programmed completely.
5. Failed circuitry on the MDX-2.
If the error was due to one of the first four causes, the trouble will clear automatically when the cause is
corrected. The first four causes should only occur when power is first turned on to the Series MDX-2.
When a message memory error is indicated, perform the following:
1. Verify that the preprogrammed message memory EPROM's were installed in the correct sockets on
the Series MDX-2. See Figure 9-3 on Page 9-7 for proper chip location. An EPROM must always be
installed in socket S14. If between one and two minutes of message memory is required, the first
EPROM must be installed into socket S14 and the second EPROM into socket S12.
2. Verify, at least one message is programmed into the message memory EPROM's.
3. Verify that all message memory EPROM's are inserted into their sockets properly.
4. Verify that there are no partially programmed messages on the message memory EPROM's. This can
only be done using commands on the serial port, which is located on the optional Ground Fault
Detection/Computer Interface
Module.
If, after the above procedure is completed, the trouble condition persists, the trouble condition is caused
by failed circuitry on the Series MDX-2. There are no field correctable failed circuitry problems on the
Series MDX-2. Series MDX-2's with failed circuitry shall be replaced immediately, following the
Replacement Procedure, set forth at the end of this section.
Procedure L
On the Single Circuit Mother Board (SCMB), the green NORMAL LED is “OFF”, the yellow TROUBLE
LED is “ON”, and the MDX-2 SYSTEM NORMAL LED is “OFF”, SYSTEM TROUBLE LED is “ON”, and
the TROUBLE LED flashes a “4-blink pattern”, then an audio channel error has occurred. An audio
channel error may be caused by:
1. Too low an audio level while playing a message.
2. Pause in message while playing a message that lasts longer than 3 seconds.
If the error occurs while playing a file, then the error was due to the first cause. If the error occurs
immediately after turning on power to the Series MDX-2, the error was due to the second cause.
If the error was due to either cause while playing a message, the trouble will clear automatically when
audio is again detected while a message is playing. If the error is due to the third cause, the trouble will
clear automatically when the output is no longer loaded down while a message is playing. If the error was
due to the fourth cause, the trouble will clear automatically when the module is properly installed and
input power is cycled off and on.
When an audio channel error is indicated, perform the following:
1. Have the message re-recorded, shortening duration of the pause.
Return any modules that are malfunctioning, after all troubleshooting operations have been performed, for
factory repair or replacement. If it is necessary to return a Single Circuit SAFEPATH
the malfunctioning modules immediately in the following manner:
1. Disconnect battery backup power from the Single Circuit SAFEPATH
2. Disconnect AC input power from the Single Circuit SAFEPATH
®
Panel.
®
Panel.
3. Identify all wiring connections to make sure they will be reconnected identically on the replacement.
4. Disconnect all wiring connections.
®
Module, replace
7-11
5. Remove the malfunctioning module(s) and install the replacement module(s). Perform all checkout
procedures described in the “Installation” section of this manual to make sure the replacement
module(s) is (is) operating properly.
Figure 7-4 on Page 7-13 illustrates the Single Circuit SAFEPATH
the wires are color-coded. If major modules have been replaced or improper wiring is suspected, use this
wiring diagram to trace the proper wiring routes.
®
ModuleWiring between modules. Note
7-12
24V+
24V-
LINE IN +
CH PLAY +
DV POWER +
BLUE
BLACK
RED
LINE OUT +
DV POWER -
DV STATUS +
TB2
TB4
SCMB
WHITE
YELLOW
ORANGE
A83413
TB3
1
7
2
MDX-2
8
TB1
7
8
12
10
Module Wiring Diagram
PATH
BLACK
BLACK
Figure 7-4
Single-Circuit SAFE
RED
BLACK
BLACK
RED
-
AC
AC
POWER
4102 6
XFMR
WHITE
BLACK
120VAC
INPUT
2 6410
XFMR
AC
FAIL
J2
WHITE
BLACK
Resistor
10K Ohm 1/4W
SUPPLY
BAT
FAIL
J1
+
BAT
BLACK
WHITE
DC+
DC-
7-13
Intentionally Blank
7-14
Chapter 8 Technical Data
Section 8-1- Mechanical
Dimensions (H x W x D) 21 x 16 x 6 in.
Weight 40 lb.
Finish Red
Enclosure Construction Type 0.050” steel
Mounting Indoor surface mount
Wiring Entry Top and bottom knockouts (3/4”, 1”)
Door Lock Standard Wheelock key-lock
PC Boards 1 Mother Board (SCDC)
1 Power Supply (DCPS)
1 Digital Voice Module (MDX-2)
1 Amplifier Module
Section 8-2 – Environmental
Operating Temperature 0 to 49 °C (32 to 120 °F)
Storage Temperature -20 to 70 °C (-4 to 158 °F)
Humidity, Non-condensing
85±5% at 30±2 °C (86 ± 4 °F)
Section 8-3 – Electrical
Input
Input Voltage 120VAC, 2.50A, 60Hz
220VAC, 1.25A, 50Hz for Export
Models
Battery Current Calculations
The current draw of the Single Circuit SAFEPATH® Panel is determined by the configuration being
utilized. Section 3-7 Battery Care and Battery Backup Calculation will assist you in developing the current
requirements.
Automatic Activation
Dry contact inputs or use of NACIM to activate from a NAC.
8-1
Outputs
Visual Notification Appliance
Output
Central Amplified Audio Output 1 output circuit.
Amplified Speaker Audio
Output
Amplified Speaker Power
Output
Trouble Audible Output
Status Contact
Alarm Contact
Table 8-1 Outputs
1 output circuit. 2.0 amps at 24VDC
per zone. Supervised.
Selectable 25, 70.7 volt output at
40W or 80W max, or 100 volt
(export) at 80W. (Depending on
amplifier configuration). Supervised.
1 output circuit, 15 Ohms,
-5dBm output max (when
configured with a SALL-15S).
Supervised
1 output circuit. 2.0 amps at 24VDC
(when configured with a SALL-15S).
Supervised.
0.100 amps at 24VDC. NonSupervised.
Form C contact normally energized.
Contacts transfer during trouble: 0.5
amps at 24VDC max, resistive load.
Non-Supervised.
Form C contact normally deenergized. Contact transfers during
alarm: 0.5 amps at 24VDC max,
resistive load. Non-Supervised.
WARNING: DO NOT EXCEED THE RATINGS OF ANY STATUS CONTACT. EXCEEDING THE
RATINGS MAY CAUSE THE RELAY TO FAIL AND PREVENT A TROUBLE
CONDITION FROM BEING INDICATED.
DO NOT EXCEED THE RATINGS OF THE ALARM CONTACT. EXCEEDING THE
RATING MAY CAUSE THE RELAY TO FAIL AND PREVENT MESSAGES FROM
BEING PLAYED.
Wiring Connections
Screw terminals Accept #12 to #22 AWG
8-2
End-of-Line Resistor
Visual Notification Appliance
Outputs
Audio Notification Appliance
Outputs
Amplified Speaker Appliance
Power Outputs
UL LISTED 10K Ohm, 1/8W Minimum
±5%
UL LISTED 10K Ohm, 1W Minimum
±5%
UL LISTED 10K Ohm, 1W Minimum
±5%
NOTE:A package of 8 UL LISTED 10K Ohm, 1W resistors are available through Wheelock, Inc.
Model Number EOLK (Part# 5076).
8-3
Intentionally Blank
8-4
Chapter 9 - Module Descriptions
Section 9-1 - Introduction
There are ten modules in the Single Circuit SAFEPATH® Panel product line.
The ten modules are:
1. Single Circuit Mother Board (SCMB)
2. Digital Voice Module (MDX-2)
3. Power Supply / Battery Charger (DCPS)
4. Supervised Audio System Amplifier/Signal Circuit Module (SAA-40S)
5. Supervised Audio System Amplifier/Signal Circuit Module (SAA-80S/SE*)
The interior view of the Single Circuit SAFEPATH Panel with the modules is shown in Figure 9-1. The
amplifier modules may be used in any
Figure 9-1 shows the locations of the MDX-2, Power Supply, Amplifier Module, and the SC-SPL. The
Power Supply is mounted under the Digital Voice Module (MDX-2). The SC-SPL is mounted on the dead
front panel.
combination by installing into slots 1 and 2 in the DCMB. Also
Digital Voice
Module MDX-2
P83412 REV ( )
U17
C50
R72
RV10
R71
R73
C46
RV9
Q2
D12
C48
R70
R69
R66
Q1
R67
D13
R68
U13
RV8
R65
C44
D10
J6
TB 3
R62
RV7
R64R63 D11
C41
RV6
R60
R59
C40
R58
R57
C39
R56
R55
RV5
C38
R54
R53
C36
RV4
R52
R43
R51
C35
R50
RV3
R49
C34
R48
R47
RV2
R44
C33
R46
R45
TB 2
RV1
F1
R35
R34
D9
+
C27
L2
GND
EAR TH
D8
E1
C21
+
K2
J3
R32
D4
C20
C19
R25
R26
R21
R22
D3
R19
C17
J2
+
R20
R18
C16
U4
C9
+
U1
R8
C10D2
D1
+
TB 1
K1
C8R9
C31
R42
U7
C25
L1
C14
R17
R16
C15
R4C3C1
R6 C6
R5R7R1C4
C5
REV:SN:
U16
C49C47
U15
S15
C45
U14
S14
C43
U12
S12
C42
R61
J5
U11
C37
R41
C32
R38
U10
R40
C30
C29
C28
R39
R36
R37
U9
U8
S8
C26
C24
J4
C22
C23
R33
D7
D6
D5
R31
R29
R27
U6
U5
R30
R28
CH1 VOL
R24
R23
C18
R14
R13
C12
J1
R10
C11R15
R12
R11
C13
U3
U2
R3
R2
C2C7
Power Supply/
Battery Charger
Mother Board
(SCMB)
10
6
6
10
SMP7PM
AC
AC
AC FAIL
C NC NO
BAT FAIL
NO NC C
-
DC
+
AC
SW1
SW2
-
BAT+
DC
Amplifiers
SAA-40S, 80S/SE
SALL-15S
D1
SAFEPATH P83167 REV B
T1
U3
C16
J1
P1
D2
AMBER GREEN
K2
K1
SW1 SW2 SW3
K3
U1
U2
U4
X2
X1
U5
U6
U8
U9
U10
F1
TB1
F2
TB2
TB3
SW4
SW5
TB5
MICROPHONE
4
1 2 3
ON
4
2 3
1
ON
P83236 SAA-40/80
+
-
+
-
+
-
+
-
+
-
+
-
E1
+
-
+
-
+
-
J2
ZONE SELECT LED'S
ON
ON
OFF OFF
OFF
ZONE 1
ALL
CALL
OPERATION:
Use zone switches to select zones
for live announcements.
Use all-call to select all zones.
Zone select LED's indicate the
selected zones.
Zone active LED's indicate the
active zones.
ON
ON
ON
TB1
+
ALL
_
OFF
OFF
ZONE 2
ZONE 3
+
ZONE 4
PWR
_
Z
O
+
ZONE 1
AUD
N
_
E
+
Z1
A
_
C
ZONE 2
+
T
Z2
I
_
V
+
E
Z3
_
ZONE 3
L
+
E
Z4
D
_
S
ZONE 4
(DCPS)
4 Way Splitter
(SC-SPL)
Figure 9-1
Location of Plug-in Modules
9-2
Section 9-2 - Single Circuit Mother Board (SCMB)
Wheelock, Inc. Part Number 108974
The Single Circuit Mother Board provides all signal handling capabilities between itself and the amplifier
modules, terminal blocks for output wiring, and connectors for handling signals from the digital voice
module.
The Single Circuit Mother Board is illustrated in Figure 9-2 on Page 9-5.
A single amplifier module is connected to the SCMB.
A single channel from the Digital Voice Module (MDX-2) is connected to the SCMB. The digital voice
module is mounted on the power supply cover and wired to the Mother Board. The digital voice module
channel will play through the amplifier module installed.
The microphone input is located in the lower right corner of the board and is used for live voice
announcements.
Form C contacts are available for remote monitoring of Alarm Status and Trouble Status. Also remote
trouble power is available at 24VDC, 0.100 Amps, that is non-supervised.
Single Circuit Mother Board supervises the Digital Voice Module (MDX-2), Power Supply, and the
amplifier module (SAA-40S, SAA-80S/SE, or SALL-15S) for proper operation. The microphone is
supervised for connection.
The channel play contacts from the digital voice module (MDX-2) are monitored to determine their status
(e.g. active or inactive). If the channel play contact is inactive, the control module routes a supervision
tone to the amplifier circuit module and monitors the amplifier for functionality. If the channel playing
contact is active, the control module routes the audio from that MDX-2 line output to the amplifier circuit
module. Wiring used to monitor the channel play contacts and to route the line output from the Digital
Voice Module is supervised for open and short circuit conditions.
The Power Supply module is supervised for two conditions: low AC input power, and low battery voltage.
The wiring between the controller module and the battery charger is supervised for open and short circuit
conditions.
The amplifier module is supervised for two failure conditions: field wiring trouble conditions and amplifier
audio output trouble conditions. The SCMB only supervises the audio output during standby conditions.
When either a message is playing from the Digital Voice Module or a live announcement is being made
from the microphone, the field wiring and audio output are not supervised.
The strobe NAC circuit can be used with standard non-synchronized strobes or the circuit can be place in
the SYNC mode for synchronizing Wheelock, Inc. synchronized strobes. Synchronization is accomplished
by turning “ON” DIP Switch SW5, Position 3 (SYNC) on the SAMB.
The strobe NAC circuit on the amplifier module is also supervised in the standby mode for field wiring
trouble conditions.
If at any time a trouble condition is detected, the SCMB will energize the internal audible, the external
trouble audible circuit, and transfer the Form C trouble contact to the trouble position, turn “OFF” the
NORMAL LED, and turn “ON” the TROUBLE LED.
There are two fuses on the Mother Board. F1 is the fuse for the external trouble audible circuit, and F2 is
the fuse for the Remote Microphone Station power. Both fuses are rated at 0.5A. See Figure 9-2 on
Page 9-5 for fuse location.
Fuse Rating
F1 0.5A
F2 0.5A
9-3
Nominal Specifications:
Input Voltage Range 20 to 28VDC
Supply Current (Idle) at 24VDC 75mA
Supply Current (Full Load) at 24VDC 150mA
Operating Temperature Range 0 to 49 Degrees C (32-120 Degrees F)
Humidity Range 0 to 85%, Non-condensing
9-4
J1
SAFEPATH P83167 REV B
T1
U3
C16
U8
P1
D1
AMBERGREEN
K1
D2
K2
SW1SW2SW3
K3
U1
U2
U4
X1
X2
U5
U6
R53
GROUND
FAULT
ADJUST
U10
U9
F1
F2
SW5
TB5
TB1
TB2
TB3
SW4
4
2 3
1
ON
4
2 3
1
ON
+
TRB AUD
-
TRB COM
TRB NO
TRB NC
ALARM COM
ALARM NO
ALARM NC
+
DV POWER
-
+
DV STATUS
-
+
CH PLAY
-
+
LINE OUT
-
+
LINE IN
-
+
RM AUDIO
-
RM TXD
RM RXD
+
RM POWER
-
TONE SEL
3
2
1
GND FLT ENB
RM ENABLE
SYNC
DV ENABLE
LAMP TEST
E1
+
ALL CALL
-
+
24V
-
+
SPK AMP
-
+
STROBE
-
+
AUDIO
-
J2
F1 TROUBLE AUDIO
F2 REMOTE
MICROPHONE
STATION POWER
GROUND
CONNECTION
R53 GROUND
FAULT ADJUST
MICROPHONE
Figure 9-2
Single Circuit SAFEPATH
®
Mother Board
9-5
Section 9-3 - Digital Voice Module (MDX-2)
Wheelock, Inc. Part Number: 105094
The Digital Voice Module (MDX-2) provides playback capability of pre-recorded messages. The MDX-2,
when activated, provides a pre-recorded tone and/or message to the Single Circuit SAFEPATH
which then broadcasts it through the amplifiers and to the audio appliances.
The MDX-2 can have up to 8 pre-recorded messages that can be initiated by dry contact closure or open
collector for each one. Figure 9-3 on Page 9-7 shows the location of these inputs. Up to 2 minutes of
audio storage are recorded on UV-erasable EPROM memory chips. Any dry contact closure or open
collector can include Acknowledgment of the playing file and Reset initiation. (The reset switch is required
to be in a locked enclosure.)
The memory chips are normally recorded at Wheelock, Inc. The Standard Message Kit (SMK), which has
8 common messages and tones, is programmed for a single channel output. The Programmed Message
Kit (PMK) is tailor made to the customer’s desires. The location of these kits are shown on Figure 9-3 on
Page 9-7.
Fuse F1 fuses the 24VDC power input.
Figure 9-3 shows the MDX-2 as it is mounted in the panel.
®
Panel
9-6
Dry Contacts Inputs
(IN1 Through IN8)
P83412 REV ( )
U17
C50
R72
RV10
R71
R73
RV9
Q2
R69
Q1
R68
RV8
TB 3
RV7
R64R63D11
RV6
RV5
RV4
RV3
RV2
TB 2
RV1
F1
J3
J2
+
C10D2
D1
TB 1
K1
C46
D12
C48
R70
R66
R67
D13
U13
R65
C44
D10
J6
R62
C41
R60
R59
C40
R58
R57
C39
R56
R55
C38
R54
R53
C36
C9
R52
R43
R51
C35
R50
R49
C34
R48
R47
R44
C33
R46
R45
R35
R34
D9
+
C27
GND
R22
D3
L2
EA R TH
D8
E1
C21
+
K2
R32
D4
C20
C19
R25
R26
R21
R19
C17
R20
R18
C16
U4
+
U1
R8
R41
R40
C31
R42
U9
U7
C25
L1
R14
C14
R17
R16
C15
U3
R4
R6C6
C3
+
R5R7
C4
C5
C7
C8
R9
C13
C2
REV:SN :
U16
C49C47
U15
S15
C45
U14
S14
C43
U12
S12
1st Chip
SMK or PMK
Location
2nd Chip
C42
R61
J5
U11
C37
C32
R38
U10
C30
C29
C28
C22
R33
C12
C11R15
R3
C1
R2
R39
R36
R37
U8
S8
C26
C24
R31
U6
U5
R13
R1
J4
C23
D7
D6
D5
R29
R27
R30
R28
CH1 VOL
R24
R23
C18
J1
R10
R12
R11
U2
Figure 9-3
Digital Voice Module (MDX-2)
NOTE: The MDX-2 Module is mounted upside down in the Single Circuit SAFEPATH
access to the terminal blocks. Figure 9-3 shows this module as it is mounted.
®
Panel to allow
9-7
Section 9-4 - Power Supply / Battery Charger (DCPS)
Wheelock, Inc. Part Number: 107378
The Power Supply / Battery Charger (Figure 9-4) provides the Single Circuit SAFEPATH
power supply/battery charger with an output of 24VDC with a maximum current of 6 Amps. The battery
charger section is capable of charging a 40 AH battery in 48 hours.
The Power Supply is protected with short circuit protection and thermal shutdown. It also contains Form C
contacts for external monitoring of AC Failure and Battery Failure. “AC FAIL” is indicated with a minimum
of (6) hour delay. LOW BATTERY is indicated on the “BAT FAIL” contacts when the battery voltage drops
below 20VDC. NO BATTERY PRESENT is indicated on “BAT FAIL” terminals within 2 minutes.
The AC LED indicates that AC is applied to the Power Supply. The DC LED indicates that the DCPS
output is 24VDC.
®
Panel with a
AC INPUT SUPERVISION
BATTERY SUPERVISION
24 VDC, 6 AMP OUTPUT
TO MOTHER BOARD
SMP7PM
AC
AC
AC
AC FAIL
C NC NO
BAT FAIL
NO NC C
SW1
SW2
28 VOLT AC INPUT FROM
TRANSFORMER
GREEN LED - INDICATES AC
VOLTAGE IS APPLIED TO
THIS BOARD
-
DC
+
24 VDC BACKUP
BATTERY INPUT
RED LED - INDICATES POWER SUPPLY
OUTPUT VOLTAGE IS AVAILABLE
DC
-
BAT
+
BATTERY INPUT
FUSE
Figure 9-4
Power Supply / Battery Charger (DCPS)
9-8
Section 9-5 - Supervised Audio System Amplifier/Signal Circuit
Module, 40 Watts (SAA-40S)
Wheelock, Inc. Part Number: 105493
The supervised audio system amplifier/signal circuit module, 40 watts (SAA) provides audio amplification
for the SAFEPATH
The amplifier contains a switch mode power supply, a linear amplifier, and supervision circuitry.
The switching power supply is used to provide a constant DC voltage to the amplifier while the input
voltage is allowed to fluctuate over its operating range. The amplifier amplifies the low-level 600-ohm
audio to 40 watts output at either 25V or 70.7V. The supervision circuit monitors field speaker wiring
integrity, field strobe wiring integrity, and amplifier functionality.
The module can be field configured for either 25V or 70.7V output. The configuration is done using a twoposition slide switch (S1) on the printed circuit board. One position (down) configures the amplifier to
have a 25V output and the other position (up) configures the amplifier to have a 70.7V output. See Figure
9-5 on Page 9-10 for switch location.
The amplifier supervises both the strobe field wiring and the speaker field wiring with a DC current. The
strobe field wiring is supervised with a reverse polarity technique, which applies a DC voltage with one
polarity to supervise the wiring and then reverses the polarity to energize the strobes. The speaker field
wiring is supervised with a DC current, which is removed when audio is being played. Both field-wiring
circuits are only supervised in the standby state. The amplifier is supervised by monitoring the amplifier
output for audio. The state of each of the three supervision features is indicated via three LEDs on the
module. See Figure 9-5 on Page 9-10 for LED locations.
There are two fuses on the printed circuit board, F1 and F2. Fuse F1 is the main fuse for the entire
board. F2 is the fuse for the strobe power. See Figure 9-5 on Page 9-10 for fuse locations.
Two UL LISTED 10K Ohm, 1W, End of Line Resistors are included with this module.
Fuse Rating
F1 10A
F2 3A
Nominal Specifications:
Rated Output at 1kHz 40 Watts
Input Sensitivity 1Vrms
S/N Ratio 72dB
Frequency Response 275Hz to 6kHz
Input Voltage Range 24VDC
Supply Current (Standby) at 24VDC 400mA
Supply Current (Full Load) at 24VDC 3.6A
(Including 2.0A Strobe Current)
Operating Temperature Range 0 to 49 Degrees C (32-120
Degrees F)
Humidity Range 0 to 85%, Non-condensing
®
system. The amplifier can be selected to have either a 25V or a 70.7V audio output.
9-9
Strobe Trouble LED
Audio Trouble LED
Amplifier Trouble LED
Switch S1 - 25V / 70.7 V
Speaker Selector Switch
P83253
SAA-40S Only
Fuse F2 - Strobe
Power. 3 Amp.
Fuse F1 - Main Amplifier
Fuse. 10 Amp.
P83236 SAA- 40/80
Figure 9-5
Supervised Audio System Amplifier/Signal Circuit Module, 40 Watts
(SAA-40S)
9-10
Section 9-6 - Supervised Audio System Amplifier/Signal Circuit
Module, 80 Watts (SAA-80S/SE)
Wheelock, Inc. Part Number: SAA-80S 105495, SAA-80SE 105496
The supervised audio system amplifier/signal circuit module, 80 watts (SAA) provides audio amplification
for the SAFEPATH
The SAA-80SE (European version) is 100V audio output only. The amplifier contains a switch mode
power supply, a linear amplifier, and supervision circuitry.
The switching power supply is used to provide a constant DC voltage to the amplifier while the input
voltage is allowed to fluctuate over its operating range. The amplifier amplifies the low-level 600-ohm
audio to 80 watts output. The supervision circuit monitors field speaker wiring integrity, field strobe wiring
integrity, and amplifier functionality.
The SAA-80S module can be field configured for either 25V or 70.7V output. The configuration is done
using a two-position slide switch (S1) on the printed circuit board. One position (down) configures the
amplifier to have a 25V output and the other position (up) configures the amplifier to have a 70.7V output.
See Figure 9-6 on Page 9-12 for switch location.
The SAA-80SE module is configured for a 100V output only. The two-position slide switch is removed.
The amplifier supervises both the strobe field wiring and the speaker field wiring with a DC current. The
strobe field wiring is supervised with a reverse polarity technique, which applies a DC voltage with one
polarity to supervise the wiring and then reverses the polarity to energize the strobes. The speaker field
wiring is supervised with a DC current, which is removed when audio is being played. Both field-wiring
circuits are only supervised in the standby state. The amplifier is supervised by monitoring the amplifier
output for audio. The state of each of the three supervision features is indicated via three LEDs on the
printed circuit board. See Figure 9-6 on Page 9-12 for LED locations.
There are two fuses on the printed circuit board, F1 and F2. Fuse F1 is the main fuse for the entire
board. F2 is the fuse for the strobe power. See Figure 9-6 on Page 9-12 for fuse locations.
Two UL LISTED, 10K Ohm, 1W, End of Line Resistors are included with this module.
Fuse Rating
F1 10A
F2 3A
Nominal Specifications:
Rated Output at 1kHz 80 Watts
Input Sensitivity 1Vrms
S/N Ratio 72dB
Frequency Response 275Hz to 6kHz
Input Voltage Range 24VDC
Supply Current (Standby) at 24VDC 600mA
Supply Current (Full Load) at 24VDC
(Including 2.0A Strobe Current) 4.5A
Operating Temperature Range 0 to 49 Degrees C (32-120
Degrees F)
®
system. The amplifier can be selected to have either a 25V or a 70.7V audio output.
9-11
Strobe Trouble LED
Audio Trouble LED
Amplifier Trouble LED
Switch S1 - 25V / 70.7 V
Speaker Selector Switch
(SAA-80S Only)
SAA-80SE Switch is Removed.
(100 V Only)
P83254
SAA-80S / SE Only
Fuse F2 - Strobe
Power. 3 Amp.
Fuse F1 - Main Amplifier
Fuse. 10 Amp.
P83236 SAA- 40/80
Figure 9-6
Supervised Audio System Amplifier/Signal Circuit Module, 80 Watts
(SAA-80S/SE)
9-12
Section 9-7 - Supervised Audio Line Level Module (SALL-15S)
Wheelock, Inc. Part Number: 105497
The Supervised Audio Line Level Module (SALL-15S) provides audio output for the SAFEPATH
The circuit module has a 0.5Vrms, 15 ohm audio NAC circuit, a 24VDC, 2A speaker amplifier power
output, and a 24VDC, 2A strobe NAC Circuit. The circuit module contains a linear amplifier and
supervision circuitry.
The module supervises the strobe NAC circuit field wiring, the speaker amplifier audio field wiring, the
speaker amplifier power NAC circuit field wiring, and the amplifier. The strobe NAC circuit field wiring and
the speaker amplifier power wiring are supervised with a reverse polarity technique, which applies a DC
voltage with one polarity to supervise the wiring and then reverses the polarity to energize the strobe NAC
circuit. The speaker amplifier audio NAC circuit field wiring is supervised with a DC current, which is
removed when audio is being played. Both field-wiring circuits are only supervised in the standby
condition. The amplifier is supervised by monitoring the amplifier output for audio. The state of each of
the four supervision features is indicated via four LEDs on the printed circuit board. See Figure 9-7 on
Page 9-14 for LED locations.
There are three fuses on the printed circuit board, F1 and F2, and F3. Fuse F1 is the fuse for the strobe
NAC circuit. F2 is the fuse for the speaker amplifier power. F3 is the main fuse for the entire board. See
Figure 9-7 on Page 9-14 for fuse locations.
Fuse
Rating
F1 3A
F2 3A
F3 6A
Nominal Specifications:
Rated Output at 1kHz 500m Vrms, 30 ohm load
Input Sensitivity 1Vrms
S/N Ratio -75dB
Frequency Response 275Hz to 4kHz
Input Voltage 24VDC
Supply Current (Idle) at 24VDC 50mA
Supply Current (Full Load) at 24VDC 135mA
Operating Temperature Range 0 to 49 Degrees C (32-120 Degrees F)
The Notification Appliance Circuit Interface Module (NACIM) in Figure 9-8 is used to convert the
Notification Appliance Circuit (NAC) of a Fire Alarm Control Panel (FACP) to an open collector circuit to
operate the inputs of the Digital Voice Module. The NACIM can be connected to either a 12-volt or a 24volt NAC circuit. An End-Of-Line Resistor (EOLR) that is UL LISTED for use with the FACP shall be
installed across the two terminals of the TB2 on the NACIM. See Figure 9-8.
Additional Information is available on the NACIM Installation Instruction Sheet P83487.
P83480
EOLR
TB-2
TB-1
+
INPUT
_
+
OUTPUT
_
COM
NO
TRBL
Figure 9-8
Notification Appliance Circuit Interface Module
(NACIM)
9-15
Section 9-9 - FOUR ZONE SPLITTER (SC-SPL)
Wheelock, Inc. Part Number: SC-SPL-B (Black) 107367, SC-SPL-R (Red) 107368
The Four Zone Splitter (SC-SPL) in Figure 9-9 is designed to be used with Wheelock’s Single Circuit
SAFEPATH
®
Panels and provides a means for expanding a supervised audio output zone from one to
four sub zones. The Four Zone Splitters are UL Listed under UL Standard 864, Control Units for Fire
Protective Signaling Systems. They are listed for indoor use only. Only 1 Four Zone Splitter can be
connected to the Single Circuit SAFEPATH
®
Panel. The splitter works with all Wheelock amplifier
modules. If the splitter is used with a power amplifier, the maximum power per sub zone cannot exceed
what is listed in table below. See Figure 9-9.
Additional Information is available on the SC-SPL Installation Instruction Sheet P83270.
SPECIFICATIONS:
SAA-40S/80S/80SE SALL-15S
Audio Output Voltage 25.0V 70.7V 100.0V 1.0V
Maximum Output Power Per Zone 25.0W 70.0W 100.0W 150 Speaker Inputs
ZONE SELECT LED'S
ON
ON
ON
ON
ON
OFFOFF
OFF
ZONE 1
ALL
CALL
OPERATION:
Use zone switches to select zones
for live announcements.
Use all-call to select all zones.
Zone select LED's indicat e the
selected zones.
Zone active LED's indicate the
active zones.
ZONE 2
OFF
ZONE 3
OFF
ZONE 4
Z
O
N
E
A
C
T
I
V
E
L
E
D
S
ZONE 1
ZONE 2
ZONE 3
ZONE 4
Figure 9-9
4-Zone Splitter Module (SC-SPL
TB1
+
ALL
_
+
PWR
_
+
AUD
_
+
Z1
_
+
Z2
_
+
Z3
_
+
Z4
_
)
9-16
Section 9-10 - Auxiliary Input Module (AIM-3)
Wheelock, Inc. Part Number: 107387
The Auxiliary Input Module (AIM-3) is an outboard module for use with the SAFEPATH
the number of optional Remote Microphone Stations from one to three. It also has the capability of using
one of the Remote Microphone Inputs to connect to a telephone system page port. See Figure 9-10 on
Page 9-18.
Additional information is available on the AIM-3 Installation Instruction Sheet P83667.
Electrical
Input Voltage 24VDC
Input Current 100 mA Telephone Page
60 mA RMS Page
40 mA Standby
Audio Input 1Vrms
Dimensions (H x W x D
13.0” x 7.6” x 2.15” (33cm x 19.4cm x 5.4cm)
)
®
Panels to expand
9-17
A83640
.1 AMP
AIM-3
P83639 REV. B
+
_
TXD
RXD
+
_
+
_
TXD
RXD
+
_
AUDIO
POWER
AUDIO
POWER
AUDIO INPUT MODULE
TRB
4
PHONE
SEL3
2 3
SEL2
1
SEL1
ON
ON
OFF
SW1
F1
+
AUDIO
F3
_
TXD
RXD
+
_
+
_
TXD
RXD/CC
+
POWER/CC
_
.1 AMP
SW4
TAL K
BATT
1
POWER
AUDIO
2
PEAK
F2
.1 AMP
2
1
RM
SW2
PHONE
R58
VOLUME
Figure 9-10
Auxiliary Input Module (AIM-3)
9-18
Section 9-11 - Remote Microphone Station (RMS-2)
Wheelock, Inc. Part Number: RMS-2R (Red) 105475
The Remote Microphone Station (RMS-2) is designed to used with the Single Circuit SAFEPATH
It provides a means of emergency voice announcements from a remote location. Only 1 Remote
Microphone Station connection is available on the SAFEPATH
®
Panel. A single RMS-2 module can be
connected, or an Auxiliary Input Module (AIM-3) can be connected, allowing as many as three RMS-2
modules to be used.
Additional Information is available on the RMS-2 Installation Instructions P83270.
Specifications:
Power Input Voltage: 20-31VDC
Audio Output Level: 1.05Vrms
Output Impedance: 600 Ohms
Input Current: 50 mA
REMOTE MICROPHONE
SYSTEM STATUS
NORMAL
TROUBLE
STATUS
®
Panel.
AUTO
MANUAL
OPERATING INSTRUCTIONS:
1. Turn key to ON position
2. Select zones
3. Press microphone button
and speak into microphone
Figure 9-11
Remote Microphone Station (RMS-2)
OFF
ON
9-19
Intentionally Blank
9-20
Chapter 10 - MEA and Warranty
Recommendations - That the above units be accepted on condition that all uses, configurations, arrangements and
functions, locations and installations comply with the New York City Building Code, specifically Subchapter 17 and
with the Referenced Standard RS 17-3 through 17-3C including the NFPA as appropriate, the UL Listing, the
manufacturer’s instructions, the Fire Department Rules and the Electrical Code of the City of New York, and on
further condition that:
(a) The use, installation and application of the SAFEPATH® System shall be restricted exclusively to connection
with an BSA/MEA approved compatible Class E, Class J or Class C Fire Command Station.
(b) The Fire Command Station shall have the capability of overriding any function of the SAFEPATH
(c) Prior to the installation of any SAFEPATH® System, a specific approval for a specific installation must be
obtained from the Fire Department.
(d) A priority voice message matrix must be submitted to the Fir Department for approval before the installation is
performed and shall include the following information:
1. The duration of each message.
2. The content of each message.
3. The duration of the audible and visual alarm signals prior to the initiation of the subsequent prerecorded
message transmission.
4. The interval between the cessation of the audible and visual alarm signals and the generation of
prerecorded message.
(e) The SAFEPATH
Command Station. The wiring between the SAFEPATH
must be enclosed in conduit.
(f) Power supply wiring to the SAFEPATH
input and output wiring.
(g) When used with central office communicator or transmitter, the installation and operation of the equipment and
devices listed herein shall comply with Fire Department Rule #3 - RCNY 17-01, NFPA 71, and shall have the
capability of transmitting separate and distinct signals to indicate manual pull station alarm, automatic
smoke/heat detection alarm, sprinkler waterflow alarm, supervisory signal indications and trouble indications.
(h) The connection of security/burglar devices and equipment to that submitted for acceptance for fire alarm usage
under this MEA application is prohibited within New York City and such equipment and devices shall be so
permanently labeled.
All shipments and deliveries of such equipment shall be provided with a metal tag suitably placed, certifying that the
equipment shipped or delivered is equivalent to that tested and accepted for use, as provided for in Section 27-131 of
the Building Code.
®
Panel must be located in the room as, and within 20 feet of a BSA/MEA approved Fire
®
Panel Control Unit shall be installed in the same conduit containing the
®
Panel Control Unit and the Fire Command Station
®
System.
10-1
Wheelock products must be used within their published specifications and must be PROPERLY specified,
applied, installed, operated, maintained and operationally tested in accordance with these instructions at the
time of installation and at least twice a year or more often and in accordance with local, state and federal
codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must
be performed by qualified personnel for proper operation in accordance with all of the latest National Fire
Protection Association (NFPA), Underwriters' Laboratories (UL), Underwriters’ Laboratories of Canada (ULC),
National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county,
province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and
codes including, but not limited to, all appendices and amendments and the requirements of the local
authority having jurisdiction (AHJ). Wheelock products when properly specified, applied, installed, operated,
maintained and operationally tested as provided above are warranted against mechanical and electrical
defects for a period of three years from date of manufacture (as determined by date code. Correction of
defects by repair or replacement shall be at Wheelock's sole discretion and shall constitute fulfillment of all
obligations under this warranty.
IN THE EVENT ANY PART NOT FURNISHED BY WHEELOCK IS INSTALLED IN THE PRODUCT. THE
FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES ANY SOFTWARE REQUIRED FOR THE
OPERATION OF OR INCLUDED IN A PRODUCT. WHEELOCK MAKES NO REPRESENTATION OR
WARRANTY OF ANY OTHER KIND, EXPRESS, IMPLIED OR STATUTORY WHETHER AS TO
MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR ANY OTHER MATTER.
USERS ARE SOLELY RESPONSIBLE FOR DETERMINING WHETHER A PRODUCT IS SUITABLE FOR THE
USER'S PURPOSES, OR WHETHER IT WILL ACHIEVE THE USER'S INTENDED RESULTS. THERE IS NO
WARRANTY AGAINST DAMAGE RESULTING FROM MISAPPLICATION, IMPROPER SPECIFICATION, ABUSE,
ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK'S CONTROL.
SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE. WITH RESPECT TO THOSE PRODUCTS,
WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE
UNINTERRUPTED OR ERROR-FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF
PERFORMANCE, OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE
USER'S REQUIREMENTS. WHEELOCK SHALL NOT BE LIABLE FOR ANY DELAYS, BREAKDOWNS,
INTERRUPTIONS, LOSS, DESTRUCTION, ALTERATION, OR OTHER PROBLEMS IN THE USE OF A
PRODUCT ARISING OUT OF OR CAUSED BY THE SOFTWARE.
THE LIABILITY OF WHEELOCK ARISING OUT OF THE SUPPLYING OF A PRODUCT, OR ITS USE, WHETHER
ON WARRANTIES, NEGLIGENCE, OR OTHERWISE, SHALL NOT IN ANY CASE EXCEED THE COST OF
CORRECTING DEFECTS AS STATED IN THE LIMITED WARRANTY AND UPON EXPIRATION OF THE
WARRANTY PERIOD ALL SUCH LIABILITY SHALL TERMINATE. WHEELOCK IS NOT LIABLE FOR LABOR
COSTS INCURRED IN REMOVAL, REINSTALLATION OR REPAIR OF THE PRODUCT BY ANYONE OTHER
THAN WHEELOCK OR FOR DAMAGE OF ANY TYPE WHATSOEVER, INCLUDING BUT NOT LIMITED TO,
LOSS OF PROFIT OR INCIDENTAL OR CONSEQUENTIAL DAMAGES. THE FOREGOING SHALL
CONSTITUTE THE SOLE REMEDY OF THE PURCHASER AND THE EXCLUSIVE LIABILITY OF WHEELOCK.
IN NO CASE WILL WHEELOCK'S LIABILITY EXCEED THE PURCHASE PRICE PAID FOR A PRODUCT.
WHEELOCK'S LIABILITY ON ANY CLAIM OF ANY KIND, INCLUDING NEGLIGENCE AND BREACH OF
WARRANTY, FOR ANY LOSS OR DAMAGE RESULTING FROM, ARISING OUT OF, OR CONNECTED WITH
THIS CONTRACT, OR FROM THE MANUFACTURE, SALE, DELIVERY, RESALE, REPAIR OR USE OF ANY
PRODUCT COVERED BY THIS ORDER SHALL BE LIMITED TO THE PRICE APPLICABLE TO THE PRODUCT
OR PART THEREOF WHICH GIVES RISE TO THE CLAIM. WHEELOCK'S LIABILITY ON ANY CLAIM OF ANY
KIND SHALL CEASE IMMEDIATELY UPON THE INSTALLATION IN THE PRODUCT OF ANY PART NOT
FURNISHED BY WHEELOCK. IN NO EVENT SHALL WHEELOCK BE LIABLE FOR ANY CLAIM OF ANY KIND
UNLESS IT IS PROVEN THAT OUR PRODUCT WAS A DIRECT CAUSE OF SUCH CLAIM. FURTHER, IN NO
EVENT, INCLUDING IN THE CASE OF A CLAIM OF NEGLIGENCE, SHALL WHEELOCK BE LIABLE FOR
INCIDENTAL OR CONSEQUENTIAL DAMAGES. SOME STATES DO NOT ALLOW THE EXCLUSION OR
LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE PRECEEDING LIMITATION MAY
NOT APPLY TO ALL PURCHASERS.
Limited Warranty
THE FOREGOING LIMITED WARRANTY SHALL IMMEDIATELY TERMINATE
Limitation of Liability
10-2
y
BATTERY BACKUP CALCULATION WORKSHEET
Tables for thisworksheet are in Section 3-5 of this manual.
STANDBY CURRENT CALCULATIONS
1. Select and record Standby Current for Model from Table 3-4.
2. Select Standby Current for Optional Modules from Table 3-5.
List them in Table 1.
Table 1
Standby Qty X
Module Qt
3. Calculate total Standby Current from Table 1.
4. Add Standby Current from Step 1 and Step 3.
5. Multiply results of Step 3 by the number of hours of Standby required.
CurrentStandby Current
24 Hours - Multiply By 24
60 Hours - Multiply By 60
TOTAL STANDBY CURRENT IN AMP HOURS.
ALARM CURRENT CALCULATIONS
NOTE: DO NOT EXCEED THE WATTAGE VALUE OF THE AMPLIFIER.
Good engineering practices call for amplifier to operate at 85% Max wattage.
1. In Table 2 list the speaker and strobe requirements for each amplifier used.
Table 2
NOTFICATIONSPEAKER STROBE"SPKR AMP"
APPLIANCEWATTAGECURRENT CURRENT
SAA OnlySALL Only
1
C
f
2. Using Table 2, calculate total
3. For SAA Series Amplifier Modules, use Table 2 and calculate
total
SPEAKER WATTAGE
STROBE CURRENT
.
.
4. For SALL-15S Module, use Table 2 and calculate total "
current.
5. SAA Series Modules,calculate the Alarm Current
Module using the total
Table 3-7 in this manual.
6. In Table 3, using Table 3-5, list all alarm currents of Modules installed.
Module Qty CurrentAlarm Current
SCSP-PS10.1500.150
MDX-210.0900.090
7.
alculate the
8. Add Steps 2, 4, 5, and 7 together as appropriate.
NOTE: THE MAXIMUM CURRENT OUTPUT IN ALARM CONDITION IS 6 AMPS.
9. Divide Step 8 by the appropriate value for Alarm Time in Amp Hours.
Total Alarm Current
SPEAKER WATTAGE
Table 3
Alarm Total
in Table 3.
from Step 3 and
SPKR AMP
"
5 minutes of Alarm - divide Step 8 by 12
15 minutes of Alarm - divide Step 8 by 4
TOTAL ALARM CURRENT IN AMP HOURS
BACKUP BATTERY REQUIREMENT
1. Enter results from
2. Enter results
3. Add Steps 1 and 2 together, enter total
4. Multiply Step 3 by 1.25 for Minimum Backup Battery requirement.
Standby Current
rom
Alarm Current
section.
section.
Ampere Hours
2
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.