Westermo LRW-102PP User Manual

LRW-102 Series
STATUS
N2 N1
L2 L1
PWR
CH 1
TD
FL L
RD
FL R
PKT
CH 2
LRW-100 Series
1
2
1
2
Fibre Optic industrial converter/repeater for LonWorks® TP/FT-10 point-to-point, line and redundant ring
www.westermo.com
2
6650-2260
General information
Legal information
The contents of this document are provided “as is”. Except as required by applicable law, no warranties of any kind, either express or implied, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose, are made in relation to the accuracy and reliability or contents of this document. Westermo reserves the right to revise this document or withdraw it at any time without prior notice.
Under no circumstances shall Westermo be responsible for any loss of data or income or any special, incidental, and consequential or indirect damages howsoever caused.
More information about Westermo can be found at the following Internet address:
www.westermo.com
6650-2260
3
Safety
!
! !
Before installation:
Read this manual completely and gather all information on the unit. Make sure that you understand it fully. Check that your application does not exceed the safe oper­ating specifications for this unit.
This unit should only be installed by qualified personnel. This unit should be built-in to an apparatus cabinet, or similar, where access is
restricted to service personnel only. The power supply wiring must be sufficiently fused, and if necessary it must be
possible to disconnect manually from the power supply. Ensure compliance to national installation regulations.
This unit uses convection cooling. To avoid obstructing the airflow around the unit, follow the spacing recommendations (see Cooling section).
Before mounting, using or removing this unit:
Prevent access to hazardous voltage by disconnecting the unit from power supply. Warning! Do not open connected unit. Hazardous voltage may occur within this unit when connected to power supply.
Class 1 Laser Product
Do not look directly into fibre optical fibre port or any connected fibre although this unit is designed to meet the Class 1 Laser regulations.
Care recommendations
Follow the care recommendations below to maintain full operation of unit and to fulfil the warranty obligations. This unit must not be operating with removed covers or lids.
Do not attempt to disassemble the unit. There are no user serviceable parts inside. Do not drop, knock or shake the unit, rough handling above the specification may cause
damage to internal circuit boards. Do not use harsh chemicals, cleaning solvents or strong detergents to clean the unit. Do not paint the unit. Paint can clog the unit and prevent proper operation. Do not expose the unit to any kind of liquids (rain, beverages, etc). The unit is not water-
proof. Keep the unit within the specified humidity levels. Do not use or store the unit in dusty, dirty areas, connectors as well as other mechanical
part may be damaged. If the unit is not working properly, contact the place of purchase, nearest Westermo dis-
tributor office or Westermo Tech support. Fibre connectors are supplied with plugs to avoid contamination inside the optical port. As long as no optical fibre is mounted on the connector, e.g. for storage, service or
transportation, should the plug be applied.
4
6650-2260
Note. Fibre Optic Handling
Fibre optic equipment needs special treatment. It is very sensitive to dust and dirt. If the fibre will be disconnected from the modem the protective hood on the transmitter/ receiver must be connected. The protective hood must be kept on during transportation. The fibre optic cable must also be handle the same way.
If this recommendation not will be followed it can jeopardise the warranty.
Cleaning of the optical connectors
In the event of contamination, the optical connectors should be cleaned by the use of forced nitrogen and some kind of cleaning stick.
Recommended cleaning fluids:
• Methyl-, ethyl-, isopropyl- or isobutyl-alcohol
• Hexane
• Naphtha
Maintenance
No maintenance is required, as long as the unit is used as intended within the specified conditions.
Product disposal
This symbol means that the product shall not be treated as unsorted municipal waste when disposing of it. It needs to be handed over to an applicable collection point for recy­cling electrical and electronic equipment.
6650-2260
By ensuring this product is disposed of correctly, you will help to reduce hazardous substances and prevent potential negative consequences to both environment and human health, which could be caused by inappropriate disposal.
5
Simplified EU declaration of conformity
Hereby, Westermo declares that the equipment is in compliance with applicable EU directives. The full EU declaration of conformity and other detailed information are available at the respective product page at www.westermo.com.
Agency approvals and standards compliance
Type Approval / Compliance
EMC EN 61000-6-1, Immunity residential environments
EN 61000-6-2, Immunity industrial environments
EN 61000-6-3, Emission residential environments
EN 61000-6-4, Emission industrial environments
Safety EN 60950-1, IT equipment
FCC Part 15.105 Notice:
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
6
6650-2260
Type tests and environmental conditions
Electromagnetic Compatibility
Phenomena Test Description Level ESD EN 61000-4-2 Enclosure contact ± 4 kV
RF field AM modulated IEC 61000-4-3 Enclosure 10 V/m 80% AM (1 kHz), 80 – 1 000 MHz Fast transient EN 61000-4-4 Signal ports ± 1 kV
Surge Signal ports balanced ± 1 kV line to earth, ± 1 kV line to line
RF conducted EN 61000-4-6 Signal ports 10 V 80% AM (1 kHz), 0.15 – 80 MHz
Power frequency magnetic field
Pulse Magnetic field EN 61000-4-9 Enclosure 300 A/m, 6.4 / 16 µs pulse Voltage dips and
interruption
Mains freq. 50 Hz EN 61000-4-16 Signal ports 100 V 50 Hz line to earth Mains freq. 50 Hz SS 436 15 03 Signal ports 250 V 50 Hz line to line Voltage dips
and interruption
Radiated emission CISPR 16-2-3
Conducted emission CISPR 16-2-1
Dielectric strength EN 60950 Signal port to all other
Environmental
Temperature EN 60068-2-1
Humidity EN 60068-2-30 Operating 5 to 95% relative humidity
Altitude Operating 2 000 m / 70 kPa Service life Operating 10 years Vibration IEC 60068-2-6 Operating 7.5 mm, 5 – 8 Hz
Shock IEC 60068-2-27 Operating 15 g, 11 ms
Packaging
Enclosure UL 94 PC / ABS Flammability class V-1 Dimension W x H x D 35 x 121 x 119 mm Weight 0.26 kg Degree of protection IEC 529 Enclosure IP 21 Cooling Convection Mounting Horizontal on 35 mm DIN-rail
EN 61000-4-8 Enclosure 100 A/m, 50 Hz, 16.7 Hz & 0 Hz
EN 61000-4-11 AC power ports 10 & 5 000 ms, interruption
EN 61000-4-29 DC power ports 10 & 100 ms, interruption
ANSI C63.4 (FCC part 15)
ANSI C63.4 (FCC part 15b)
EN 60068-2-2
Enclosure air ± 8 kV
Power ports ± 2 kV
Power ports ± 0.5 kV line to earth, ± 0.5 kV line to line
Power ports 10 V 80% AM (1 kHz), 0.15 – 80 MHz
10 & 500 ms, 30% reduction 100 & 1 000 ms, 60% reduction
10 ms, 30% reduction 10 ms, 60% reduction
Enclosure Class B
AC power ports Class B AC power ports Class B DC power ports Class A
isolated ports Power port to other
isolated ports
Operating –40 to +70ºC LRW-102PP
Storage & Transport –40 to +70°C
Storage & Transport 5 to 95% relative humidity
+20% above & –20% below rated voltage
Class A
1.5 kVrms 50 Hz 1min
2 kVrms 50 Hz 1min
–40 to +60ºC LRW-102
2 g, 8 – 500 Hz
6650-2260
7
Description
The LRW-102 (LRW-102PP) offers an easy way to extend the distance between
LonWorks® 78 kbit/s TP/FT network segments using a fibre optic link.
The LRW-102PP is a fibre optic modem used for point-to-point applications and the LRW-102 is used for multidrop and redundant ring applications. It acts as a repeater between the two fibre optic links, and as a converter between fibre optical links and the LON TP/FT port. The maximum distance of the fibre links depends on selected transceiver and fibre types.
The LRW-102 (LRW-102PP) is designed for harsh outdoor usage, in industrial, road or railway installations. The complete transparent conversion to and from the fibre optic media facilitates the installation procedure by eliminating the need for any additional network addressing or software configuration.
Convert LON TP/FT-10 interface – optical fibre
… Multidrop, point-to-point alternatively redundant ring communication
via fibre optical network
… Small Form Factor Pluggable (SFP) transceivers
… LC fibre connectors, single or multimode
… LC-2 Multimode LC connectors, 5 km (3.1 miles)
… LC-15 Singlemode LC connectors, 15 km (9.3 miles)
… Bi-di, Multimode LC connectors, 5 km (3.1 miles)
… Bi-di, Singlemode LC connectors, 20 km (12.4 miles)
… Redundant power supply, 2 kVAC galvanic isolated to other ports
… Designed for harsh environments
… Re-timing
… Status port
LonWorks® interface
… 2-positions detachable screw terminal
… Data rate 78 kbit/s
8
6650-2260
Functional description
Converter TP/FT interface – optical fibre
The LRW-102 (LRW-102PP) is a fibre optic converter that converts between
LonWorks® TP/FT, and fibre optical link.
Repeater – optical fibre links
The LRW-102 is a fibre optic repeater that repeats received data from one fibre link out to the other link. This is useful e.g. for long distance communication, where electromagnetic interference may occur or when isolation of the electrical network is needed.
Single or multimode LC fibre connectors
The LRW-102 (LRW-102PP) uses Small Form Factor Pluggable (SFP) transceivers that are in compliance with Multi-Sourcing Agreement (MSA). A wide range of different fibre transceivers and connectors can be used.
6650-2260
9
Loading...
+ 19 hidden pages