Wesley BCT-6200-6SA User Manual

CURTIS INSTRUMENTS, INC.
200 Kisco Avenue Mt. Kisco, New York 10549 USA Tel. 914.666.2971 Fax 914.666.2188
www.curtisinstruments.com
1243
M O D E L
Generation 2
MultiMode™
MOTOR CONTROLLER
© 2011 CURTIS INSTRUMENTS, INC.
1243GEN2 Manual, p/n 37044
Rev. E: February 2011
CONTENTS
1. OVERVIEW ..............................................................................1
CONTENTS
2. INSTALLATION AND WIRING .............................................
Mounting the Controller .....................................................4
Connections: Low Current ..................................................6
Connections: High Current ................................................6
Wiring: Controller ..............................................................
Wiring: Throttle ..................................................................9
5k Single-ended 0–5V, current source, 3-wire pot,
and electronic throttles (“Type 2”) ......................
0–5k
Wigwag 0–5V and 3-wire pot throttles .......................
Wiring: Fault Outputs ......................................................
Wiring: Spyglass Display ...................................................
Wiring: Emergency Reverse ..............................................
Wiring: Emergency Reverse Check ...................................
Wiring: Auxiliary Driver ...................................................
Contactor, Switches, and Other Hardware .........................17
3. PROGRAMMABLE PARAMETERS ......................................
Battery Parameter ...............................................................
Battery Voltage ............................................................
Acceleration Parameters ......................................................
Drive Current Limit, M1–M4 .....................................
Acceleration Rate, M1–M4 .........................................
Quick Start ..................................................................
Current Ratio ..............................................................
Braking Parameters ............................................................
Braking Current Limit, M1–M4 .................................
Deceleration Rate, M1–M4 .........................................
Throttle Deceleration Rate ..........................................
Restraint, M1–M4 .......................................................
Braking Rate, M1–M4 ................................................
Taper Rate ...................................................................
Variable Braking ..........................................................
Interlock Braking Parameters .............................................
Interlock Braking Rate ................................................
Max. Forward Regen ...................................................
Max. Reverse Regen .....................................................
Ω–0, 2-wire potentiometer throttle (“Type 1”) ........10
11
Ω, 2-wire potentiometer throttle (“Type 3”) ........13
14 14 15 16 16 16
19 21 21 21 21 21 21 22 23 23 23 23 23 24 25 25 26 26 26 26
4
7
Curtis 1243GEN2 Manual, Rev. B
iii
CONTENTS
Min. Forward Regen ...................................................27
Min. Reverse Regen .....................................................
Max. Load Volts ..........................................................
Min. Load Volts ..........................................................
Electromagnetic Brake Parameters ......................................
Aux Type .....................................................................
EM Brake PWM .........................................................
Aux Delay ....................................................................
Interlock Brake Delay ..................................................
Speed Parameters ...............................................................
Max. Forward Speed, M1–M4 ....................................
Max. Reverse Speed, M1–M4 ......................................
Creep Speed ................................................................
Load Compensation ....................................................
Throttle Parameters ............................................................
Throttle Type ..............................................................
Throttle Deadband ......................................................
Throttle Max ...............................................................
Throttle Map ...............................................................
Pot Low Fault ..............................................................
Field Parameters .................................................................
Min. Field Current Limit ............................................
Max. Field Current Limit ............................................
Field Map Start ...........................................................
Field Map ....................................................................
Field Check .................................................................
Main Contactor Parameters ...............................................
Main Contactor Interlock ............................................
Main Contactor Open Delay .......................................
Main Contactor Diagnostics ........................................
Sequencing Fault Parameters ..............................................
Anti-Tiedown ..............................................................
High Pedal Disable (HPD) ..........................................
Static Return to Off (SRO) .........................................
Sequencing Delay ........................................................
Emergency Reverse Parameters ...........................................
Emergency Reverse Current Limit ...............................
Emergency Reverse Check ...........................................
Emergency Reverse Direction Interlock .......................
Motor Protection Parameters .............................................
Warm Speed ................................................................
Motor Warm Resistance ..............................................
Motor Hot Resistance .................................................
Motor Resistance Compensation .................................
27 27 27 28 28 28 28 28 31 31 31 31 31 32 32 32 34 36 38 38 38 38 38 39 40 40 40 40 40 41 41 41 42 42 43 43 43 43 44 44 44 44 44
iv
Curtis 1243GEN2 Manual, Rev. B
Hourmeter Parameters .......................................................45
Adjust Hours High ......................................................
Adjust Hours Middle ...................................................
Adjust Hours Low .......................................................
Set Total Hours ...........................................................
Set Traction Hours ......................................................
Total Service Hours .....................................................
Traction Service Hours ................................................
Total Disable Hours ....................................................
Traction Disable Hours ...............................................
Traction Fault Speed ....................................................
Service Total ................................................................
Service Traction ...........................................................
Hourmeter Type ..........................................................
Pump Meter ................................................................
Battery Discharge Indicator (BDI) Parameters ...................
Full Voltage .................................................................
Empty Voltage .............................................................
Reset Voltage ...............................................................
Battery Adjust ..............................................................
BDI Disable ................................................................
BDI Limit Speed .........................................................
Fault Code Parameters .......................................................
Fault Code ...................................................................
BDI Lockout ...............................................................
45 45 45 45 46 46 46 46 46 47 47 47 48 48 49 49 49 49 50 50 50 51 51 52
CONTENTS
4. INSTALLATION CHECKOUT .............................................
5. VEHICLE PERFORMANCE ADJUSTMENT ......................
Major Tuning .....................................................................
Tuning the active throttle range ...................................
Tuning the controller to the motor ..............................
Setting the unloaded vehicle top speed ........................
Equalizing loaded and unloaded vehicle speed .............
Fine Tuning ........................................................................
Response to reduced throttle .......................................
Response to increased throttle .....................................
Smoothness of direction transitions .............................
Ramp climbing ............................................................
53
55 55 55 58 60 61 62 62 63 63 64
Curtis 1243GEN2 Manual, Rev. B
v
CONTENTS
6. PROGRAMMER MENUS ......................................................65
1243 1243 1243
GEN2 Parameters Menu ..............................................65
GEN2 Monitor Menu ..................................................69
GEN2 Faults/Diagnostics Menu ...................................70
7. DIAGNOSTICS AND TROUBLESHOOTING ....................
Programmer Diagnostics ....................................................
Spyglass Diagnostics ...........................................................
Status LED Diagnostics .....................................................
Fault Output LED Diagnostics ..........................................
8. CONTROLLER MAINTENANCE ........................................
Cleaning ............................................................................
Fault History ......................................................................
APPENDIX A Vehicle Design Considerations
APPENDIX B Curtis WEEE / RoHS
APPENDIX C Programming Devices
APPENDIX D Programmable Parameters Index
APPENDIX E Specifications, 1243GEN2 Controller
71 71 71 74 75
76 76 76
vi
Curtis 1243GEN2 Manual, Rev. B
FIGURES
FIG. 1: Curtis 1243GEN2 electronic motor controller ........................... 1
FIG. 2: Mounting dimensions, Curtis 1243GEN2 controller ................ 4
FIG. 3: Basic wiring configuration, Curtis 1243GEN2 controller ........... 7
FIG. 4: Wiring for 5kΩ–0 throttle (“Type 1”) .................................... 10
FIG. 5: Wiring for 20kΩ potentiometer used as
a wigwag-style throttle (“Type 1”) ..........................................
FIG. 6: Wiring for 0–5V throttles (“Type 2”) ..................................... 11
FIG. 7: Wiring for current source throttle (“Type 2”) ........................ 12
10
FIGURES
FIG. 8: Wiring for 3-wire potentiometer throttle (“Type 2”) .............. 12
FIG. 9: Wiring for Curtis ET-XXX electronic throttle (“Type 2”) ..... 13
FIG. 10: Wiring for 0–5kΩ throttle (“Type 3”) .................................... 14
FIG. 11: Wiring for fault outputs ......................................................... 15
FIG. 12: Wiring for Curtis Spyglass display .......................................... 15
FIG. 13: Ramp restraint maps for controller with the minimum
field set at 3 amps, maximum field at 18 amps, and
braking current limit at 300 amps .........................................
FIG. 14: Electromagnetic brake parameters, in the context
of the four delay parameters ...................................................
FIG. 15: Effect of adjusting the throttle deadband parameter .............. 33
FIG. 16: Effect of adjusting the throttle max parameter ................ 34, 35
24
29
Curtis 1243GEN2 Manual, Rev. B
FIG. 17: Throttle maps for controller
with maximum speed set at 100%
and creep speed set at 0 .........................................................
FIG. 18: Throttle maps for controller
with maximum speed set at 100%
and creep speed set at 10% ...................................................
36
37
vii
TABLES
FIG. 19: Throttle maps for controller with maximum speed set at 90%
and creep speed set at 10% ...................................................
FIG. 20: Field current relative to armature current,
with field map parameter set at 50% and 20% .....................
FIG. 21: Curtis 840 Spyglass, 3-LED and 6-LED models ................... 73
37
39
TABLES
TABLE 1: Throttle wiper input (Pin 6) threshold values .......................... 9
TABLE 2: Mode selection ....................................................................... 18
TABLE 3: Configuration options: auxiliary driver .................................. 30
TABLE 4: Programmable throttle types .................................................. 32
TABLE 5: Standard battery voltages ...................................................... 49
TABLE 6: Fault categories ..................................................................... 50
TABLE 7: Troubleshooting chart ............................................................ 72
TABLE 8: Status LED fault codes .......................................................... 74
TABLE 9: Fault category codes .............................................................. 75
TABLE E-1: Specifications .....................................................................E-1
viii
Curtis 1243GEN2 Manual, Rev. B
1
Fig. 1 Curtis 1243GEN2
MultiMode™ electronic motor controller.
1 — OVERVIEW

OVERVIEW

Curtis 1243 Generation 2 MultiMode™ controllers are separately excited motor speed controllers designed for use in a variety of small industrial vehicles and in material handling equipment. These programmable controllers are simple to install, efficient, and cost effective, while offering more features than the original 1243.
Curtis 1243GEN2 Manual, Rev. B
The 1243GEN2 MultiMode™ controller provides smooth precise control of motor speed and torque. A full-bridge field control stage is combined with a half-bridge armature power stage to provide solid state motor reversing and full regenerative braking without additional relays or contactors.
The controller’s rugged IP53 housing and packaging are built to withstand shock and vibration. State-of-the-art surface mount logic board fabrication makes the 1243GEN2 controller even more reliable than the original 1243.
The 1243 programmer. In addition to configuration flexibility, the programmer provides diagnostic and test capability.
GEN2 is fully programmable through the Curtis 13XX handheld
1
1 — OVERVIEW
Like all Curtis motor controllers, the 1243GEN2 offers superior operator control of the vehicle’s motor drive speed. Features include:
Interlock braking with load sensor to meet required braking distance
without unnecessary harsh braking at light loads
Maintenance monitor responds to preset vehicle operating hours and
drive hours as programmed by the OEM
Two hourmeters—total KSI-on hours and traction hours—and the
associated maintenance timers are built into the controller
BDI calculations performed within controller
Estimates motor temperature based on field resistance and cuts back
maximum speed if the motor is overheated
Diagnostic checks for field open and field shorted faults
Supports PWM electromagnetic brake with maximum continuous
current of 2 amps
Supports Type 4 throttle
Active precharge of controller capacitor bank extends life of main
contactor
Compatibility with Curtis 1307/1311 handheld programmers for quick
and easy testing, diagnostics, and parameter adjustment
MultiMode™ allows four user-selectable vehicle operating modes
Continuous armature current control, reducing arcing and brush wear
Complete diagnostics through the handheld programmer, the built-in
Status LED, and the optional 840 Spyglass display
Two fault outputs provide diagnostics to remotely mounted displays
Regenerative braking allows shorter stopping distances, increases battery
charge, and reduces motor heating
Automatic braking when throttle is reduced provides a compression
braking feel and enhances safety
Brake/Drive Interlock meets ISO stopping distance requirements
2
Ramp restraint feature provides automatic electronic braking
that restricts vehicle movement while in neutral
Meets EEC fault detect requirements
Linear cutback of motor drive current during overtemperature
or undervoltage
Curtis 1243GEN2 Manual, Rev. B
1 — OVERVIEW
Linear cutback of regenerative braking current during overvoltage
High pedal disable (HPD) and static return to off (SRO) interlocks
prevent vehicle runaway at startup
Internal and external watchdog circuits ensure proper software operation
Fully protected inputs and short-circuit protected output drivers.
Curtis Model 840 Spyglass Display [optional]
3-wire serial interface
Sequences between hourmeter, BDI, and error displays
Single alphanumeric, non-backlit, 8 character, 5 mm LCD display for
hourmeter, BDI, and fault messages
Display updated by dedicated unidirectional serial port
Available in 52 mm round case, DIN case, and as a bare board, each
with an 8-pin Molex connector; cases feature front seal to IP65 and rear seal to IP40; shock and vibration protection to SAE J1378
Operating temperature range -10°C to 70°C; models with lower
temperature ratings available for freezer applications
Familiarity with your Curtis controller will help you install and operate it prop­erly. We encourage you to read this manual carefully. If you have questions, please contact the Curtis office nearest you.
Curtis 1243GEN2 Manual, Rev. B
3
2 — INSTALLATION & WIRING: Controller
C
L
SEPE
X
198 (7.78)
6.4 (0.25) dia., 3 plcs
68
(2.68)
114
(4.50)
173 (6.81)
17
(0.66)
7.9
(0.31)
99
(3.88)
4.8
(0.19)
7.9
(0.31)
STAT US
Status LED
TRACTION CONTROLLER
TM
INSTALLATION AND WIRING
2
Fig. 2 Mounting
dimensions, Curtis 1243GEN2 controller.

MOUNTING THE CONTROLLER

The controller can be oriented in any position, but the location should be carefully chosen to keep the controller as clean and dry as possible. If a clean, dry mounting location cannot be found, a cover must be used to shield the controller from water and contaminants.
When selecting the
mounting position, be sure to also take into consideration (1) that access is needed at the front of the controller to plug the programmer into its connec tor, and (2) that the built-in Status LED is visible only through the view port in the label on top of the controller.
The outline and mounting hole dimensions for the 1243GEN2 control­ler are shown in Figure 2. To ensure full rated power, the controller should be fastened to a clean, flat metal surface with three 6 mm (1/4") diameter screws, using the holes provided.
-
Dimensions in millimeters (and inches)
4
Curtis 1243GEN2 Manual, Rev. B
2 — INSTALLATION & WIRING: Controller
The mounting surface must be at least a 300×300×3 mm (12"×12"×1/8") aluminum plate, or its equivalent, and subjected to a minimum 3 mph airflow to meet the specified time/current ratings. Although not usually necessary, a thermal joint compound can be used to improve heat conduction from the controller heatsink to the mounting surface.
You will need to take steps during the design and development of your end product to ensure that its EMC performance complies with applicable regulations; suggestions are presented in Appendix A.
The 1243 propriate precautions in connecting, disconnecting, and handling the controller. See installation suggestions in Appendix A for protecting the controller from ESD damage.
GEN2 controller contains ESD-sensitive components. Use ap-
C A U T I O N
Working on electric vehicles is potentially dangerous. You should protect yourself against runaways, high current arcs, and outgassing from lead acid batteries:
RUNAWAYS — Some conditions could cause the vehicle to run out of
control. Disconnect the motor or jack up the vehicle and get the drive wheels off the ground before attempting any work on the motor control circuitry.
HIGH CURRENT ARCS — Electric vehicle batteries can supply very high
power, and arcs can occur if they are short circuited. Always open the battery circuit before working on the motor control circuitry. Wear safety glasses, and use properly insulated tools to prevent shorts.
LEAD ACID BATTERIES — Charging or discharging generates hydrogen
gas, which can build up in and around the batteries. Follow the battery manufacturer’s safety recommendations. Wear safety glasses
.
Curtis 1243GEN2 Manual, Rev. B
5
2 — INSTALLATION & WIRING: Controller
8 7 6 5 4 3 2 1
16 15 14 13 12 11 10 9
34
12

CONNECTIONS

Low Current Connections
A 16-pin Molex low current connector in the controller provides the low cur­rent logic control connections:
Pin 1 load sensor input [optional] Pin 2 Fault 1 output / pump input Pin 3 Fault 2 output Pin 4 main contactor driver output Pin 5 throttle: 3-wire pot high Pin 6 throttle: 0–5V; pot wiper Pin 7 throttle: pot low Pin 8 auxiliary driver output (typically
used for an electromagnetic brake)
Pin 1 receive data (+5V) Pin 2 ground (B-) Pin 3 transmit data (+5V) Pin 4 +15V supply (100mA)
Pin 9 Mode Select 2 input Pin 10 emerg. reverse check output [optional] Pin 11 reverse input Pin 12 forward input Pin 13 emergency reverse input Pin 14 Mode Select 1 input Pin 15 interlock input Pin 16 keyswitch input (KSI)
The mating connector is a 16-pin Molex Mini-Fit Jr. connector p/n 39-01­2165 using type 5556 terminals.
A 4-pin low power connector is provided for the handheld programmer. A complete 1311 programmer kit, including the appropriate connecting cable, can be ordered from Curtis.
The 4-pin connector can also be used for the Spyglass display. The display is unplugged when the programmer is used.
High Current Connections
Three tin-plated solid copper bus bars are provided for high current con­nections to the battery ( fastened to the bus bars by M8 bolts. The 1243
B+ and B-) and the motor armature (M-). Cables are
GEN2 case provides the capture
6
Curtis 1243GEN2 Manual, Rev. B
2 — INSTALLATION & WIRING: Controller
S1 S2
B- M- B+
INTERLOCK
5 k
POT
THROTTLE
(TYPICAL)
EMERGENCY
REVERSE
emergency reverse wiring check (optional)
FORWARD
MAIN
CONTACTOR
COIL
POLARITY
PROTECTION
DIODE
REVERSE
MODE
SELECT
1
MODE
SELECT
2
ELECTRO-
MAGNETIC
BRAKE
KEY
SWITCH
POWER
FUSE
A
MAIN
CONTACT
OR
B+
B-
A2 A1
S2 S1
CONTROL
FUSE
1
9
8
16
nuts required for the M8 bolts. The maximum bolt insertion depth below the surface of the bus bar is 1.3 cm (1/2"). Bolt shafts exceeding this length may damage the controller. The torque applied to the bolts should not exceed
16.3 N·m (12 ft-lbs).
Two 1/4" quick connect terminals (
S1 and S2) are provided for the con-
nections to the motor field winding.
WIRING: Standard Configuration
Figure 3 shows the typical wiring configuration for most applications. For walkie applications the interlock switch is typically activated by the tiller,
and an emergency reverse switch on the tiller handle provides the emergency reverse signal.
For rider applications the interlock switch is typically a seat switch or a foot switch, and there is no emergency reverse.
Fig. 3 Standard wiring configuration, Curtis 1243GEN2 controller.
Curtis 1243GEN2 Manual, Rev. B
7
2 — INSTALLATION & WIRING: Controller
Standard Power Wiring
Motor armature wiring is straightforward, with the armature’s A1 connection going to the controller’s to the controller’s
of vehicle travel with the forward direction selected will depend on how the motor’s S1 and S2 connections are made to the controller’s two field terminals (S1 and S2) and how the motor shaft is connected to the drive wheels through
C A U T I O N
the vehicle’s drive train. will affect the operation of the emergency reverse feature. The forward and reverse switches and the the vehicle drives away from the operator when the emergency reverse button is pressed.
Standard Control Wiring
Wiring for the input switches and contactors is shown in Figure 3; the pins are identified on page 6. In the standard wiring configuration, the auxiliary driver at Pin 8 is used to drive an electromagnetic brake.
in Figure 3. The controller checks for welded or missing contactor faults and uses the main contactor coil driver output to disconnect the battery from the controller and motor when specific faults are present. If the main contactor coil is not wired to Pin 4, the controller will not be able to open the main contactor in serious fault conditions and the system will therefore not meet EEC safety requirements.
B+ bus bar and the armature’s A2 connection going
M- bus bar.
The motor’s field connections (S1 and S2) are less obvious. The direction
CAUTION: The polarity of the S1 and S2 connections
S1 and S2 connections must be configured so that
The main contactor coil must be wired directly to the controller as shown
8
Curtis 1243GEN2 Manual, Rev. B
2 — INSTALLATION & WIRING: Throttle

WIRING: Throttle

Wiring for various throttles is described below. They are categorized as Type 1, 2, 3, and 4 throttles in the program menu of the handheld programmer. Note: In the text, throttles are identified by their nominal range and not by their actual active range.
Appropriate throttles for use with the 1243GEN2 controller include two­wire 5k
Ω–0 throttles (“Type 1”); 0–5V throttles, current source throttles, three-wire potentiometer throttles, and electronic throttles wired for single­ended operation (all “Type 2”); two-wire 0–5k
Ω throttles (“Type 3”), and 0–5V and three-wire potentiometer throttles wired for wigwag operation (“Type 4”). The operating specifications for these throttle types are summarized in Table
1. Refer to Section 3: Programmable Parameters, for information on the effects of the Throttle Deadband and Throttle Max parameters on the minimum and maximum throttle thresholds.
If the throttle you are planning to use is not covered, contact the Curtis
office nearest you.
Table 1 THROTTLE WIPER INPUT THRESHOLD VALUES
MAXIMUM THROTTLE HPD THROTTLE MINIMUM THROTTLE THROTTLE DEADBAND (25% throttle MAX THROTTLE TYPE PARAMETER FAULT (0% speed request) active range) (100% modulation) FAULT
1 (5kΩ–0) Wiper Voltage 5.00 V 3.80 V 2.70 V 0.20 V 0.06 V
2 (0–5V) Wiper Voltage 0.06 V 0.20 V 1.50 V 5.00 V 5.80 V
3 (0–5kΩ) Wiper Voltage 0.06 V 0.20 V 1.30 V 3.80 V 5.00 V
4 (0–5V) Wiper Voltage 0.50 V 2.50 V (fwd) * 3.10 V (fwd) 4.40 V (fwd) 4.50 V
2.50 V (rev)
Wiper Resistance 7.50 kΩ 5.50 kΩ 3.85 kΩ 0 kΩ
Wiper Resistance
Wiper Resistance 0 kΩ 1.65 kΩ 5.50 kΩ 7.50 kΩ
* 1.90 V (rev) 0.60 V (rev)
Wiper Resistance
Notes: The Throttle Deadband and Throttle Max thresholds are valid for nominal 5kΩ
potentiometers or 5V sources with the default Throttle Deadband and Throttle Max parameter settings of 0% and 100% respectively. These threshold values will change with variations in the Throttle Deadband and Throttle Max parameter settings.
The HPD thresholds are 25% of the active throttle range and therefore depen
dent on the programmed Throttle Deadband and Throttle Max settings (which define the active range).
The wiper voltage is measured with respect to B-.
The wiper resistance is measured from pot low to pot wiper. The potentiometer
must be disconnected from the controller when making this measurement.
-
* With a 0% Throttle Deadband setting, there is no neutral point
on a Type 4 throttle. A Throttle Deadband setting of at least 8% is recommended for Type 4 throttles.
Curtis 1243GEN2 Manual, Rev. B
9
2 — INSTALLATION & WIRING: Throttle
20 k
FASTERFASTER
Pot Wiper input (Pin 6)
Pot Low input (Pin 7)
5k–0
Pot Low input (Pin 7)
Pot Wiper input (Pin 6)
FASTER
5kΩ–0 Throttle (“Type 1”)
The 5kΩ–0 throttle (called a “Type 1” throttle in the programming menu of the 13XX programmer) is a 2-wire resistive throttle that connects between the Pot Wiper and Pot Low pins (Pins 6 and 7), as shown in Figure 4. It doesn’t matter which wire goes on which pin. For Type 1 throttles, zero speed corresponds to 5 kΩ measured between the two pins and full speed corresponds to 0 Ω. (Note: This wiring is also shown in the standard wiring diagram, Figure 3.)
Fig. 4 Wiring for 5k
Ω
throttle (“Type 1”).
Fig. 5 Wiring for 20k
potentiometer used as a wigwag-style throttle (“Type 1”).
Ω
–0
In addition to accommodating the basic 5kΩ–0 throttle, the Type 1 throttle is the easiest with which to implement a wigwag-style throttle. Using a 20k can be set such that the controller has 5 k
Ω potentiometer wired as shown in Figure 5, the pot wiper
Ω between Pins 6 and 7 when
the throttle is in the neutral position. The throttle mechanism can then be designed such that rotating it either forward or back decreases the resistance between Pins 6 and 7, which increases the controller output. The throttle mechanism must provide signals to the controller’s forward and reverse inputs independent of the throttle pot resistance. The controller will not sense direction from the pot resistance.
10
Broken wire protection is provided by the controller sensing the current flow from the wiper input through the potentiometer and into the Pot Low pin. If the Pot Low input current falls below 0.65 mA or its voltage below 0.06 V, a throttle fault is generated and the controller is disabled. Note: The Pot Low pin (Pin 7) must not be tied to ground (B-).
Curtis 1243GEN2 Manual, Rev. B
2 — INSTALLATION & WIRING: Throttle
+
-
B-
+
SENSOR GROUND
SENSOR OUTPUT (0–5V)
S E N S O R
Pot Low input (Pin 7)
0–5V input (Pin 6)
0–5V input (Pin 6)
Pot Low Fault setting = OFF
0–5V, Current Source, 3-Wire Potentiometer, and Electronic Throttles (“Type 2”)
With these throttles (“Type 2” in the programming menu) the controller looks for a voltage signal at the wiper input (Pin 6). Zero speed will correspond to 0 V and full speed to 5 V (measurements made relative to B-). A voltage source, current source, 3-wire potentiometer, or electronic throttle can be used with this throttle type. The wiring for each is slightly different and each has varying levels of throttle fault detection associated with it.
0–5V Throttle
Two ways of wiring the 0–5V throttle are shown in Figure 6. The active range for this throttle is from 0.2 V (at 0% Throttle Deadband) to 5.0 V (at 100% Throttle Max), measured relative to B-.
Fig. 6 Wiring for
0–5V throttles (“Type 2”).
Sensor-referenced 0–5V source Ground-referenced 0–5V source
Sensor-referenced 0–5V throttles must provide a Pot Low current greater than 0.65 mA to prevent shutdown due to pot faults. It is recommended that the maximum Pot Low current be limited to 55 mA to prevent damage to the Pot Low circuitry.
Ground-referenced 0–5V throttles require setting the Pot Low Fault pa rameter (see Section 3, page 38) to Off; otherwise the controller will register a throttle fault and will shut down. For ground-referenced 0–5V throttles, the controller will detect open breaks in the wiper input but cannot provide full throttle fault protection. Also, the controller recognizes the voltage between the wiper input and B- as the applied throttle voltage and not the voltage from the voltage source relative to the Pot Low input.
For either throttle input, if the 0–5V throttle input (Pin 6) exceeds 5.5 V relative to B-, the controller will register a fault and shut down.
-
Curtis 1243GEN2 Manual, Rev. B
11
2 — INSTALLATION & WIRING: Throttle
1k–10k
Pot Wiper input (Pin 6)
Pot Low input (Pin 7)
Pot High output (Pin 5)
FASTER
R
throttle
B-B-
0–5V input (Pin 6)
Pot Low Fault setting = OFF
Current Sources As Throttles
A current source can also be used as a throttle input, wired as shown in Figure 7. A resistor, R age. The resistor should be sized to provide a 0–5V signal variation over the full current range.
otherwise the controller will register a throttle fault and will shut down. It is the responsibility of the vehicle manufacturer to provide appropriate throttle fault detection in applications using a current source as a throttle.
Fig. 7 Wiring for current
source throttle (“Type 2”).
, must be used to convert the current source value to a volt-
throttle
The Pot Low Fault parameter (see Section 3, page 38) must be set to Off;
Fig. 8 Wiring for 3-wire
potentiometer throttle (“Type 2”).
3-Wire Potentiometer (1kΩ–10k1Ω) Throttle
A 3-wire pot with a total resistance value anywhere between 1 k
Ω and 10 kΩ can be used, wired as shown in Figure 8. The pot is used in its voltage divider mode, with the voltage source and return being provided by the 1243
GEN2 controller.
Pot High (Pin 5) provides a current limited 5V source to the pot, and Pot Low (Pin 7) provides the return path. If a 3-wire pot is used and the Pot Low Fault parameter (see Section 3, page 38) is set to On, the controller will provide full throttle fault protection in accordance with EEC requirements. Note: the Pot Low pin (Pin 7) must not be tied to ground (B-).
12
Curtis 1243GEN2 Manual, Rev. B
Fig. 9 Wiring for Curtis
GREEN
ORANGE
BLACK
BLACK/WHITE
WHITE
WHT/BRN
B+
KEYSWITCH
connector
WHT/GRN
Reverse input (Pin 11)
KSI (Pin 16)
0–5V input (Pin 6)
Forward input (Pin 12)
Pot Low Fault setting = OFF
B-
B-
ET-XXX electronic throttle (“Type 2”).
2 — INSTALLATION & WIRING: Throttle
Curtis ET-XXX Electronic Throttle
The Curtis ET-XXX provides a 0–5V throttle and forward/reverse inputs for the 1243
GEN2 controller. Wiring for the ET-XXX is shown in Figure 9. When
an electronic throttle is used, the Pot Low Fault parameter (see Section 3, page
38) must be set to Off; otherwise the controller will register a throttle fault and will shut down.
Curtis 1243GEN2 Manual, Rev. B
There is no fault detection built into the ET-XXX, and the controller will detect only open wiper faults. It is the responsibility of the vehicle manufacturer to provide any additional throttle fault detection necessary.
The ET-XXX can be integrated into a control head to provide wigwag­style throttle control. Alternatively, a complete control head assembly is avail able from Curtis. This control head assembly—the CH series—combines the ET-XXX throttle with a variety of standard control head switch functions for use in walkie and lift truck applications.
0–5kΩ Throttle (“Type 3”)
The 0–5kΩ throttle (“Type 3” in the programming menu) is a 2-wire resistive throttle that connects between the Pot Wiper and Pot Low pins (Pins 6 and
7) as shown in Figure 10. Zero speed corresponds to 0 the two pins and full speed corresponds to 5 k
Ω measured between
Ω. This throttle type is not ap-
propriate for use in wigwag-style applications.
Broken wire protection is provided by the controller sensing the current flow from the wiper input through the potentiometer and into the Pot Low pin. If the Pot Low input current falls below 0.65 mA or its voltage below 0.06 V,
13
-
2 — INSTALLATION & WIRING: Throttle
0–5k
Pot Low input (Pin 7)
Pot Wiper input (Pin 6)
FASTER
Fig. 10 Wiring for
0–5kΩ throttle (“Type 3”).
a throttle fault is generated and the controller is disabled. Note: The Pot Low pin (Pin 7) must not be tied to ground (B-).
Wigwag-Style 0–5V Voltage Source and 3-Wire Pot Throttle (“Type 4”)
These throttles (“Type 4” in the programming menu) operate in true wigwag style. No signals to the controller’s forward and reverse inputs are required; the action is determined by the wiper input value. The interface to the controller for Type 4 devices is similar to that for Type 2 devices. The neutral point will be with the wiper at 2.5 V, measured between Pin 6 and B-.
value (Pin 6) is increased, with maximum forward speed reached at 4.5 V. The controller will provide increasing reverse speed as the wiper input value is decreased, with maximum reverse speed reached at 0.5 V. The minimum and maximum wiper voltage must not exceed the 0.5V and 4.5V fault limits.
3, page 36) is set to On, the controller provides full fault protection for Type 4 traction throttles. Any potentiometer value between 1 kΩ and 10 kΩ is sup­ported. When a voltage throttle is used, it is the responsibility of the OEM to provide appropriate throttle fault detection.
neutral switch should be wired to the forward switch input (Pin 12). The con troller will behave as though no throttle is requested when the neutral switch is high, and will use the throttle value when the neutral switch is low.
The controller will provide increasing forward speed as its wiper input
When a 3-wire pot is used and the Pot Low Fault parameter (see Section
Note: If your Type 4 throttle has an internal neutral switch, this internal
-
14

WIRING: Fault Outputs

The 1243
GEN2 has two fault signal outputs (Pins 2 and 3), which can be used
to provide diagnostic information to a display panel. These current-sinking outputs can drive LEDs or other loads requiring less than 10 mA. Since these outputs are intended to drive LEDs, each contains a dropping resistor; as a result, these outputs will not pull down to B-. Wiring is shown in Figure 11.
The Fault 1 and Fault 2 outputs can be programmed to display fault information in either of two formats: Fault Code format or Fault Category format (see Section 3, page 51).
Alternatively, Pin 2 can be used to provide a pump input signal (see pump meter parameter, Section 3, page 48); Pin 3 can be used to interface an external auxiliary enable circuit (see BDI lockout parameter, Section 3, page 52).
Curtis 1243GEN2 Manual, Rev. B
Fig. 11 Wiring for fault
B-
+
-
Fault 1 output (Pin 2)
Fault 2 output (Pin 3)
SPYGLASS 1243·GEN·2 CONTROLLER
PIN # FUNCTION PIN #
1–4 N.C.
5 +12V, +15V 4
6 receive data 3
7 N.C.
8 ground (B+) 2
58
(2.25)
44 (1.75)
8
58 (2.25)
52
(2.0)
“U” clamp for up to 6 (0.25) panel thickness
5
4 1
WIRING GUIDE
34
12
0 1
outputs, when used to drive LEDs. Alternatively, Pin 2 can be used for a pump me­ter input, and Pin 3 can be used to interface an external enable circuit.
2 — INSTALLATION & WIRING: Spyglass Display

WIRING: Spyglass Display

The Curtis 840 Spyglass features an 8-character LCD display that sequences between hourmeter, BDI %, and fault messages. Depending on the model, either three or six indicator LEDs are also located on the face of the gauge. See Section 7 (Diagnostics and Troubleshooting) for more information on the Spyglass displays.
The mating 8-pin connector is Molex 39-01-2085, with 39-00-0039 (18–24 AWG) pins.
Fig. 12 Wiring guide and
mounting dimensions for Curtis Spyglass (6-LED model shown; dimensions and wiring are identical for the 3-LED model).
Curtis 1243GEN2 Manual, Rev. B
Dimensions in millimeters (and inches)
15
2 — INSTALLATION & WIRING: Emerg. Reverse and Aux Driver

WIRING: Emergency Reverse

To implement the emergency reverse feature, Pin 13 (the emergency reverse input) must be connected to battery voltage as shown in the standard wiring diagram, Figure 3.
The controller provides maximum braking torque as soon as the emer gency reverse switch is closed. The vehicle will then be automatically driven in the reverse direction at the programmed emergency reverse current limit until the emergency reverse switch is released.
C A U T I O N
CAUTION: The polarity of the S1 and S2 connections will affect the op-
eration of the emergency reverse feature. The forward and reverse switches and the S1 and S2 connections must be configured so that the vehicle drives away from the operator when the emergency reverse button is pressed.

WIRING: Emergency Reverse Check

An optional wire connected directly to the emergency reverse switch provides for broken wire detection when that feature is programmed On (see Section 3, page 43). The emergency reverse check output wire periodically pulses the emergency reverse circuit to check for continuity in the wiring. If there is no con tinuity, the controller output is inhibited until the wiring fault is corrected.
The emergency reverse check wire is connected to Pin 10 as shown by the dotted line in the standard wiring diagram, Figure 3. If the option is selected and the check wire is not connected, the vehicle will not operate. If the op tion is not selected and the check wire is connected, no harm will occur—but continuity will not be checked.
-
-
-
16

WIRING: Auxiliary Driver

The 1243 designed to energize an electromagnetic brake coil, as shown in the standard wiring diagram (Figure 3). The output is rated at 2 amps and is overcurrent protected. A coil suppression diode is provided internally to protect the driver from inductive spikes generated at turn-off. The recommended wiring is shown in the standard wiring diagram, Figure 3. The contactor coil or driver load should not be connected directly to B+, which would cause the controller to be always biased On via a path through the coil suppression diode to the KSI input.
can be used to drive a pump contactor or hydraulic steering assist in applica­tions not requiring an EM brake.
programmable parameters related to this driver are described in the electro­magnetic brake parameter group; see page 28.
GEN2 provides an auxiliary driver at Pin 8. This low side driver is
Although it is typically used to drive an EM brake, the auxiliary driver
Note: Because the auxiliary driver is typically used for an EM brake, the
Curtis 1243GEN2 Manual, Rev. B
2 — INSTALLATION & WIRING: Main Contactor & Switches, etc.
CONTACTOR, SWITCHES, and OTHER HARDWARE
Main Contactor
A main contactor should be used with any 1243GEN2 controller; otherwise the controller’s fault detects will not be able to fully protect the controller and mo tor drive system from damage in a fault condition. The main contactor allows the controller and motor to be disconnected from the battery. This provides a significant safety feature in that the battery power can be removed from the drive system if a controller or wiring fault results in full battery power being applied to the motor. If the Contactor Diagnostics parameter (see Section 3, page 40) is On, the controller will conduct a missing contactor check and a welded contactor check each time the main contactor is requested to close and will not proceed with the request if a fault is found.
A single-pole, single-throw (SPST) contactor with silver-alloy contacts, such as an Albright SW80 or SW180—available from Curtis—is recommended for use as the main contactor. The contactor coils should be specified with a continuous rating at the nominal battery pack voltage.
The main contactor coil driver output (Pin 4) is rated at 2 amps, is over­current protected, and is checked for open coil faults. A built-in coil suppres sion diode is connected between the main contactor coil driver output and the keyswitch input. This protects the main contactor coil driver from failure due to inductive voltage kickback spikes when the contactor is turned off.
-
-
Keyswitch and Interlock Switch
The vehicle should have a master on/off switch to turn the system off when not in use. The keyswitch input provides logic power for the controller.
The interlock switch—which is typically implemented as a tiller switch, deadman footswitch, or seatswitch—provides a safety interlock for the system.
The keyswitch and interlock switch provide current to drive the main contactor coil and all other output driver loads as well as the controller’s internal logic circuitry and must be rated to carry these currents.
Forward, Reverse, Mode Select, and Emergency Reverse Switches
These input switches can be any type of single-pole, single-throw (SPST) switch capable of switching the battery voltage at 10 mA. Typically the emergency reverse switch is a momentary switch, active only while it is being pressed.
Reverse Polarity Protection Diode
For reverse polarity protection, a diode should be added in series between the battery and KSI. This diode will prohibit main contactor operation and cur rent flow if the battery pack is accidentally wired with the B+ and B- terminals exchanged. It should be sized appropriately for the maximum contactor coil and fault diode currents required from the control circuit. The reverse polarity protection diode should be wired as shown in the standard wiring diagram, Figure 3 (page 7).
-
Curtis 1243GEN2 Manual, Rev. B
17
2 — INSTALLATION & WIRING: Switches, etc.
Circuitry Protection Devices
To protect the control circuitry from accidental shorts, a low current fuse (appropriate for the maximum current draw) should be connected in series between the battery and KSI. Additionally, a high current fuse should be wired in series with the main contactor to protect the motor, controller, and batter­ies from accidental shorts in the power system. The appropriate fuse for each application should be selected with the help of a reputable fuse manufacturer or dealer. The standard wiring diagram, Figure 3, shows the recommended location for each fuse.
Mode Select Switch Operation
The two mode select switches (Mode Select 1 and Mode Select 2) together define the four operating modes. The switch combinations are shown in Table 2.
MODE MODE
OPERATING MODE SELECT SELECT
MultiMode™ 1 OPEN OPEN
Table 2 MODE SELECTION
SWITCH 1 SWITCH 2
MultiMode™ 2 CLOSED OPEN
MultiMode™ 3 OPEN CLOSED
MultiMode™ 4 CLOSED CLOSED
Load Sensor [optional]
The 1243GEN2 provides a load sensor input at Pin 1. The controller can be programmed to vary the strength of regen braking depending on the load sensor input. The load sensor, if one is used, should be sized to handle your application’s maximum expected load without exceeding 5 V.
18
Curtis 1243GEN2 Manual, Rev. B
3 — PROGRAMMABLE PARAMETERS

PROGRAMMABLE PARAMETERS

3
The 1243GEN2 controller has a number of parameters that can be programmed using a Curtis programming device. These programmable parameters allow the vehicle’s performance characteristics to be customized to fit the needs of individual vehicles or vehicle applications.
The OEM can specify the default value for each parameter and can also designate whether a parameter will have User or OEM access rights. Accordingly, programmers are available in User and OEM versions. The User programmer can adjust only those parameters with User access rights, whereas the OEM programmer can adjust all the parameters. For information about Curtis pro gramming devices, see Appendix C.
The MultiMode™ feature of the 1243 four distinct modes. These modes can be programmed to provide four different sets of operating characteristics, which can be useful for operating in different conditions, such as slow precise indoor maneuvering in Mode 1; faster, long distance, outdoor travel in Mode 4; and application-specific special conditions in Modes 2 and 3. Eight parameters can be configured independently in each of the four modes:
— acceleration rate (M1–M4)
— braking current limit (M1–M4)
— braking rate (M1–M4)
— deceleration rate (M1–M4)
— drive current limit (M1–M4)
— maximum forward speed (M1–M4)
— maximum reverse speed (M1–M4)
— restraint (M1–M4).
GEN2 controller allows operation in
-
Curtis 1243GEN2 Manual, Rev. B
To better describe their interrelationships, the individual parameters are grouped into categories as follows:
Battery Parameters
Acceleration Parameters
Braking Parameters
Interlock Braking Parameters
Electromagnetic Brake Parameters
Speed Parameters
Throttle Parameters
Field Parameters
Contactor Parameters
Sequencing Fault Parameters
Emergency Reverse Parameters
Motor Protection Parameters
Hourmeter Parameters
BDI Parameters
Fault Code Parameters
19
3 — PROGRAMMABLE PARAMETERS
Battery Parameter ..................... p.21
Battery Voltage
Acceleration Parameters ........... p.21
Drive Current Limit, M1–M4 Acceleration Rate, M1–M4 Quick Start Current Ratio
Braking Parameters ................... p.23
Braking Current Limit, M1–M4 Deceleration Rate, M1–M4 Throttle Deceleration Rate Restraint, M1–M4 Braking Rate, M1–M4 Taper Rate Variable Braking
Interlock Braking
Parameters .................................. p.26
Interlock Braking Rate Max. Forward Regen Max. Reverse Regen Min. Forward Regen Min. Reverse Regen Max. Load Volts Min. Load Volts
Electromagnetic Brake
Parameters .................................. p.28
Auxiliary Driver Type Electromagnetic Brake PWM Auxiliary Driver Delay Interlock Brake Delay
Field Parameters ........................ p.38
Min. Field Current Limit Max. Field Current Limit Field Map Start Field Map Field Check
Main Contactor Parameters .... p.40
Main Contactor Interlock Main Contactor Open Delay Main Contactor Diagnostics
Sequencing Fault Parameters .. p.41
Anti-Tiedown High Pedal Disable (HPD) Static Return to Off (SRO) Sequencing Delay
Emergency Reverse
Parameters .................................. p.43
Emerg. Reverse Current Limit Emerg. Reverse Check Emerg. Reverse Direction Interlock
Motor Protection Parameters .. p.44
Warm Speed Motor Warm Resistance Motor Hot Resistance Motor Resistance Compensation
Hourmeter
Parameters ................... p. 45
Adjust Hours High Adjust Hours Middle Adjust Hours Low Set Total Hours Set Traction Hours Total Service Hours Traction Service Hours Total Disable Hours Traction Disable Hours Traction Fault Speed Service Total Service Traction Hourmeter Type Pump Meter
BDI Parameters ...........p.49
Full Voltage Empty Voltage Reset Voltage Battery Adjust BDI Disable BDI Limit Speed
Fault Code
Parameters ....................p.51
Fault Code BDI Lockout
Speed Parameters ....................... p.31
Max. Forward Speed, M1–M4 Max. Reverse Speed, M1–M4 Creep Speed Load Compensation
Throttle Parameters .................. p.32
Throttle Type Throttle Deadband Throttle Max Throttle Map Pot Low Fault
20
Individual parameters are described in the following text in the order they are listed on this page. They are listed by the abbreviated names that are displayed by the program ming device. Not all of these parameters are displayed on all controllers; the list for any given controller depends on its specifications.
The programmer displays the parameters in a different order. For a list of the individual parameters in the order in which they are displayed, see Section 6: Programmer Menus.
Curtis 1243GEN2 Manual, Rev. B
-
Loading...
+ 64 hidden pages