8.1 MECHANICAL DATA ............................................................................................8-3
Contents
Quick Reference of Parameters
QUICK REFERENCE OF THE PARAMETERS
ParameterDescriptionAdjustable Range
P000Access to the Parameters0 to 99990rw4-4
P001Scan Cycle Time0.0 to 6553.5 ms-RO5-60
P002IN % Current0 to 999 %-RO6-3
P003True RMS Current 0.0 to 6553.5 A-RO6-3
P004Average Voltage True RMS0 to 1000 V-RO6-3
P005Line Frequency0.0 to 99.9 Hz-RO6-4
P006Relay Status (binary)bit0 = Error
P007Relay Status 2 (binary)bit0 = HMI 0 key
P008Power Factor0.00 to 1.00 -RO6-5
P009Motor Reactive Power0.0 to 6553.5 kVAr-RO6-5
P010Motor Active Power0.0 to 6553.5 kW-RO6-5
P011Motor Apparent Power0.0 to 6553.5 kVA-RO6-5
P012Digital Inputs I11 to I16 Status
(decimal)
P013Digital Outputs O1 to O4 Status
(binary)
P014Last Error0 to 200 -RO6-6
P015Second Error0 to 200 -RO6-6
P016Current Error0 to 200 -RO6-6
P020PTC Value (ohms)0 to 10000 Ω-RO6-6
P023Firmware Version (UC)0.00 to 655.35-RO6-7
P024Type of Protection (UC)0 = PTC
P026Firmware Version (UMC/UMCT)0.00 to 655.35- RO6-7
P027Firmware Version (EDU)0.00 to 655.35- RO6-7
P029Value of Addressing Switches0000h to 00FFh- RO6-7
P030L1 Phase True RMS Current0.0 to 6553.5 A-RO6-7
P031L2 Phase True RMS Current0.0 to 6553.5 A-RO6-8
P032L3 Phase True RMS Current0.0 to 6553.5 A-RO6-8
P033Line Voltage L1-L20 to 1000 V-RO6-8
P034Line Voltage L2-L30 to 1000 V-RO6-8
P035Line Voltage L3-L10 to 1000 V-RO6-8
P036Earth Leakage Percentage Current 0 to 3334 %-RO6-8
P037Earth Leakage True RMS Current0.000 to 10.000 A-RO6-9
P042Powered Relay Time0 to 65530 h-RO6-9
P043Motor Running Time0 to 65530 h-RO6-9
P044Meter kWh0.0 to 999.9 kWh-RO6-9
P045Meter MWh0 to 65535 MWh-RO6-9
P046Meter kVArh0.0 to 999.9 kVArh-RO6-10
P047Meter MVArh0 to 65535 MVArh-RO6-10
P050Motor Thermal Protection0 to 100 %-RO6-10
P051Current Imbalance Level0 to 100 %-RO6-10
P052Earth Fault Level0 to 200 %-RO6-11
P053Voltage Unbalance Level0 to 100 %-RO6-11
P060Number of Starts0 to 65535 -RO6-11
bit1 = Trip
bit2 = Alarm/Fault
bit3 = Motor On
bit4 = Remote Mode
bit1 = HMI I key
bit2 = Speed Direction/Speed
bit3 = Motor Transition
bit4 = Cooling Time
0 to 63-RO5-8
bit0 = O1
bit1 = O2
bit2 = O3
bit3 = O4
1 = ELS
2 = PTC/ELS
Factory
Setting
-RO6-4
-RO6-4
-RO6-6
- RO6-7
User
Setting
Proprieties Page
0
SRW 01 | 0-1
Quick Reference of Parameters
0
ParameterDescriptionAdjustable Range
P061Number of Overload Trips0 to 65535 -RO6-11
P062Number of Current Imbalance Trips 0 to 65535 -RO6-11
P063Number of Earth Fault Trips0 to 65535 -RO6-11
P064Number of Phase Loss (Current)
Trips
P065Number of Overcurrent Trips0 to 65535 -RO6-12
P066Number of Undercurrent Trips0 to 65535 -RO6-12
P067Number of Frequency Out of Range
Trips
P068Number of PTC Trips0 to 65535 -RO6-12
P069Number of Earth Leakage Trips0 to 65535 -RO6-12
P070Number of External Fault Trips0 to 65535 -RO6-13
P071Trip Status 1 (binary)bit0 = PTC
P072Trip Status 2 (binary)bit0 = Phase Loss (Current)
P073Trip Status 3 (binary)bit0 = Earth Leakage
P075Alarm Status 1 (binary)bit0 = PTC
P076Alarm Status 2 (binary)bit0 = Phase Loss (Current)
P077Alarm Status 3 (binary)bit0 = Earth Leakage
P078General Trip Status 20 to 65535-RO6-14
P079General Alarm Status 20 to 65535-RO6-15
P080General Trip Status0 to 65535-RO6-15
P081General Alarm Status0 to 65535-RO6-15
P082Total Number of Trips0 to 65535-RO6-15
P084Communication Protocol0 = None
P085Type of Digital Inputs UC0 = Invalid
P086Digital Inputs I5 to I10 Status
(decimal)
P087Digital Outputs O5 to O8 Status
(binary)
P100Number of Voltage Unbalance0 to 65535-RO6-16
P101Number of Phase Loss (Voltage)0 to 65535-RO6-16
P102Number of Overvoltage Trips0 to 65535-RO6-17
P103Number of Undervoltage Trips0 to 65535-RO6-17
0 to 65535 -RO6-12
0 to 65535 -RO6-12
bit1 = Out of Frequency
bit2 = Undercurrent
bit3 = Overcurrent
P104Number of Underpower0 to 65535-RO6-17
P105Number of Overpower Trips0 to 65535-RO6-17
P106Number of Power Under Factor
Trips
P107Number of Power Over Factor Trips 0 to 65535-RO6-18
P110Trip Status 4 (binary)bit0 - Voltage Unbalance
P111Trip Status 5 (binary)bit0 - Underpower
P115Alarm Status 4 (binary)bit0 - Voltage Unbalance
P116Alarm Status 5 (binary)bit0 - Underpower
P118Parameter Defined by User 11 to 1109 5Sys, rw7-3
P119Parameter Defined by User 21 to 1109 20Sys, rw7-3
P120Last Error Code0 to 200 -RO7-4
P121Phase L1 Current Last Error0.0 to 6553.5 A-RO7-4
P122Phase L2 Current Last Error0.0 to 6553.5 A-RO7-4
P123Phase L3 Current Last Error0.0 to 6553.5 A-RO7-5
P124Thermal Protection Last Error0 to 100 %-RO7-5
P125Earth Leakage Current Last Error0.000 to 10.000 A-RO7-5
P126Logical Status Last Error0 to 65535 -RO7-6
P127Voltage L1-L2 Last Error0 to 1000 V-RO7-6
P128Voltage L2-L3 Last Error0 to 1000 V-RO7-6
P129Voltage L3-L1 Last Error0 to 1000 V-RO7-7
P130Defined by User 1 Last Error0 to 65535 -RO7-7
P131Defined by User 2 Last Error0 to 65535 -RO7-7
P135Second Error Code0 to 200 -RO7-4
P136Phase L1 Current Second Error0.0 to 6553.5 A-RO7-4
P137Phase L2 Current Second Error0.0 to 6553.5 A-RO7-4
P138Phase L3 Current Second Error0.0 to 6553.5 A-RO7-5
P139Thermal Protection Second Error0 to 100 %-RO7-5
P140Earth Leakage Current Second
Error
P141Logical Status Second Error0 to 65535 -RO7-6
P142Voltage L1-L2 Second Error0 to 1000 V-RO7-6
P143Voltage L2-L3 Second Error0 to 1000 V-RO7-6
P144Voltage L3-L1 Second Error0 to 1000 V-RO7-7
P145Defined by User 1 Second Error0 to 65535 -RO7-7
P146Defined by User 2 Second Error0 to 65535 -RO7-7
P150Third Error Code0 to 200 -RO7-4
P151Phase L1 Current Third Error0.0 to 6553.5 A-RO7-4
P152Phase L2 Current Third Error0.0 to 6553.5 A-RO7-4
P153Phase L3 Current Third Error0.0 to 6553.5 A-RO7-5
P154Thermal Protection Third Error0 to 100 %-RO7-5
P155Earth Leakage Current Third Error0.000 to 10.000 A-RO7-5
P156Logical Status Third Error0 to 65535 -RO7-6
P157Voltage L1-L2 Third Error0 to 1000 V-RO7-6
P158Voltage L2-L3 Third Error0 to 1000 V-RO7-6
P159Voltage L3-L1 Third Error0 to 1000 V-RO7-7
bit1 - Overpower
bit2 - Power Under Factor
bit3 - Power Over Factor
0.000 to 10.000 A-RO7-5
Factory
Setting
-RO6-18
-RO6-18
-RO6-18
-RO6-19
User
Setting
Proprieties Page
0
SRW 01 | 0-3
Quick Reference of Parameters
0
ParameterDescriptionAdjustable Range
P160Defined by User 1 Third Error0 to 65535 -RO7-7
P161Defined by User 2 Third Error0 to 65535 -RO7-7
P165Fourth Error Code0 to 200 -RO7-4
P166Phase L1 Current Fourth Error0.0 to 6553.5 A-RO7-4
P167Phase L2 Current Fourth Error0.0 to 6553.5 A-RO7-4
P168Phase L3 Current Fourth Error0.0 to 6553.5 A-RO7-5
P169Thermal Protection Fourth Error0 to 100 %-RO7-5
P170Earth Leakage Current Fourth Error 0.000 to 10.000 A-RO7-5
P171Logical Status Fourth Error0 to 65535 -RO7-6
P172Voltage L1-L2 Fourth Error0 to 1000 V-RO7-6
P173Voltage L2-L3 Fourth Error0 to 1000 V-RO7-6
P174Voltage L3-L1 Fourth Error0 to 1000 V-RO7-7
P175Defined by User 1 Fourth Error0 to 65535 -RO7-7
P176Defined by User 2 Fourth Error0 to 65535 -RO7-7
P180Fifth Error Code0 to 200 -RO7-4
P181Phase L1 Current Fifth Error0.0 to 6553.5 A-RO7-4
P182Phase L2 Current Fifth Error0.0 to 6553.5 A-RO7-4
P183Phase L3 Current Fifth Error0.0 to 6553.5 A-RO7-5
P184Thermal Protection Fifth Error0 to 100 %-RO7-5
P185Earth Leakage Current Fifth Error0.000 to 10.000 A-RO7-5
P186Logical Status Fifth Error0 to 65535 -RO7-6
P187Voltage L1-L2 Fifth Error0 to 1000 V-RO7-6
P188Voltage L2-L3 Fifth Error0 to 1000 V-RO7-6
P189Voltage L3-L1 Fifth Error0 to 1000 V-RO7-7
P190Defined by User 1 Fifth Error0 to 65535 -RO7-7
P191Defined by User 2 Fifth Error0 to 65535 -RO7-7
P200Password Status0 = Inactive
P204Counter Reset / Factory Settings0 = No Function
1 = Reset of the Motor Running Time
2 = It resets the Protection counters and
the Number of Starts counter
3 = Resets Power Meters
4 = Reset Trip History
5 = Reset to the Factory Settings
P205Reading Parameter Selection1 = P002 (% IN Current)
0 = Digital Input I11 (NC)
1 = Digital Input I11 (NO)
1 = HMI
2 = USB/Ladder
3 = Fieldbus
0 = Retentive (Switch)
1 = Impulsive (Pushbutton)
1 = Ladder
2 = Fieldbus
3 = Alarm/Fault Signal (NO)
4 = Trip/Error Signal (NO)
5 = Trip/Error Signal (NC)
6 = Check Back Signal (NO)
7 = Trip Signal PTC (NO)
8 = Trip Signal Out of Frequency (NO)
9 = Trip Signal Undercurrent (NO)
10 = Trip Signal Overcurrent (NO)
11 = Trip Signal Phase Loss (current) (NO)
12 = Trip Signal Current Imbalance (NO)
13 = Trip Signal Earth Fault (NO)
14 = Trip Signal Overload (NO)
15 = Trip Signal Earth Leakage (NO)
16 = Trip Signal External Fault (NO)
17 = Trip Signal Trip Test (NO)
18 = Trip Signal Phase Sequence (NO)
19 = Trip Signal Voltage Unbalance (NO)
20 = Trip Signal Phase Loss (voltage) (NO)
21 = Trip Signal Overvoltage (NO)
22 = Trip Signal Undervoltage (NO)
23 = Trip Signal Underpower (NO)
24 = Trip Signal Overpower (NO)
25 = Trip Signal Power Under Factor (NO)
26 = Trip Signal Power Over Factor (NO)
1 = EDU Used
Factory
Setting
2Sys, rw5-2
0Sys, rw5-2
1Sys, CFG5-5
0 Sys, CFG5-5
3Sys, rw5-3
1Sys, CFG5-3
0Sys, CFG5-6
0Sys, CFG3-10
User
Setting
Proprieties Page
0
SRW 01 | 0-5
Quick Reference of Parameters
0
ParameterDescriptionAdjustable Range
P295Currente and/or Voltage
Measurement Unit (UMC/UMCT)
P296Number of Turns Through the UMC/
UMCT
P297Motor Type0 = Three-Phase
P298External CT Primary Current1 a 5000 A1 ASys, CFG5-27
P299External CT Secondary Current0 = 1 A
P310Configuration of the Serial Interface
Bytes
P311Action for HMI Communication Error 0 = Only Fault Indication
P312Action for EDU Communication
Error
P313Action in Case of Communication
Error
P315Action in the Local/Remote
Transition
P400Motor Nominal Voltage0 to 1000 V380 VSys, CFG5-28
P401Motor Nominal Current 10.0 to 5000.0 A0.5 ASys, CFG5-28
P402Motor Nominal Current 20.0 to 5000.0 A0.5 ASys, CFG5-29
P404Motor Rated Power0.1 to 6553.5 kW75.0 kWSys, CFG5-29
P406Service Factor1.00 to 1.50 1.15Sys, CFG5-48
P407Line Frequency0 to 99 Hz60 HzSys, CFG5-39
P408Motor Phase Sequence0 = 1-2-3
P500Parameter Upload/Download 0 = No Function
P501User Program Upload/Download0 = No Function
P601Reset Selection0 = Without Local Reset
P602Function Test/Reset Button0 = Disabled
P605Hysteresis0 to 15 %5 %Sys, rw5-33
0 = UMC0/UMCT0 (0.25 – 2.5 A)
1 = UMC1/UMCT1 (0.5 – 5 A)
2 = UMC2/UMCT2 (1.25 – 12.5 A)
3 = UMC3/UMCT3 (2.5 – 25 A)
4 = UMC4/UMCT4 (12.5 – 125 A)
5 = UMC5/UMCT5 (42 – 420 A)
6 = UMC6/UMCT6 (84 – 840 A)
7 = UMC1/UMCT1 + External CT
1 to 101Sys, CFG5-27
1 = Single-Phase
1 = 5 A
0 = 8 data bits, no parity, 1 stop bit
1 = 8 data bits, even parity, 1 stop bit
2 = 8 data bits, odd parity, 1 stop bit
3 = 8 data bits, no parity, 2 stop bit
4 = 8 data bits, even parity, 2 stop bit
5 = 8 data bits, odd parity, 2 stop bit
1 = The Motor is Turned Off
0 = Only Fault Indication
1 = The Motor is Turned Off
0 = Only Fault Indication
1 = The Motor is Turned Off
2 = The Motor is Turned Off and the
Commands are Reset
3 = It Changes to Local
0 = Keep Motor Status
1 = The Motor is Turned Off
1 = 3-2-1
1 = Save Bank 1
2 = Save Bank 2
3 = Save Bank 3
4 = Load Bank 1
5 = Load Bank 2
6 = Load Bank 3
1 = Save Applicative 1
2 = Save Applicative 2
3 = Save Applicative 3
4 = Load Applicative 1
5 = Load Applicative 2
6 = Load Applicative 3
1 = Front Button
2 = Reset key (HMI)
3 = Digital Input I13
4 = Digital Input I14
5 = Digital Input I15
6 = Digital Input I16
1 = Enabled
Factory
Setting
1Sys, CFG5-26
0Sys, CFG5-27
0Sys, CFG5-27
3Sys, CFG5-30
0 Sys, rw5-4
0 Sys, rw3-10
0Sys, rw5-30
0Sys, CFG5-3
0Sys, CFG5-29
0Sys, rw4-5
0Sys, rw4-6
1Sys, rw5-58
1Sys, rw5-59
User
Setting
Proprieties Page
0-6 | SRW 01
Quick Reference of Parameters
ParameterDescriptionAdjustable Range
P606External Fault Protection0 = Disabled
P607Auto-reset External Fault0 = Disabled
P608External Fault Timing0 = Disabled
P609External Fault Time1 to 99 s 1 sSys, rw5-34
P610External Fault Monitoring of
Protection
P611External Fault Signal0 = Digital Input I11
P612External Fault Signal Logic0 = Digital Input NC
P613External Fault Protection Action0 = Alarm
P614Current Imbalance 5 to 100 %40 %Sys, rw5-36
P615Current Imbalance Time 0 = Disabled
P761IP Address Config (1)0 to 255 192 Sys, rw5-30
P762IP Address Config (2)0 to 255 168 Sys, rw5-30
P763IP Address Config (3)0 to 255 0 Sys, rw5-30
P764IP Address Config (4)0 to 255 10 Sys, rw5-30
P765CIDR Subnet 0 to 31 24 Sys, rw5-30
P766Default Gateway Configuration (1)0 to 255 0 Sys, rw5-30
P767Default Gateway Configuration (2)0 to 255 0 Sys, rw5-30
P768Default Gateway Configuration (3)0 to 255 0 Sys, rw5-30
P769Default Gateway Configuration (4)0 to 255 0 Sys, rw5-30
P799UMC/UMCT Gain Adjustment0.900 to 1.1001.000Sys, rw5-27
P800Read Word #10 to 65535 680Sys, rw5-30
P801Read Word #20 to 65535 0Sys, rw5-30
P802Read Word #30 to 65535 0 Sys, rw5-30
P803Read Word #40 to 65535 0 Sys, rw5-30
P804Read Word #50 to 65535 0 Sys, rw5-30
P805Read Word #60 to 65535 0 Sys, rw5-30
P806Read Word #70 to 65535 0 Sys, rw5-30
P807Read Word #80 to 65535 0 Sys, rw5-30
P808Read Word #90 to 65535 0 Sys, rw5-30
P809Read Word #100 to 65535 0 Sys, rw5-30
P810Read Word #110 to 65535 0 Sys, rw5-30
P811Read Word #120 to 65535 0 Sys, rw5-30
P812Read Word #130 to 65535 0 Sys, rw5-30
P813Read Word #140 to 65535 0 Sys, rw5-30
P814Read Word #150 to 65535 0 Sys, rw5-30
P815Read Word #160 to 65535 0 Sys, rw5-30
P816Read Word #170 to 65535 0 Sys, rw5-30
P817Read Word #180 to 65535 0 Sys, rw5-30
P818Read Word #190 to 65535 0 Sys, rw5-30
P819Read Word #200 to 65535 0 Sys, rw5-30
P850Write Word #10 to 65535 682 Sys, rw5-31
P851Write Word #20 to 65535 0 Sys, rw5-31
P852Write Word #30 to 65535 0 Sys, rw5-31
1 to 99 s = Enabled
0 = Alarm
1 = Switch Off (Trip)
1 = Init
2 = Wait Comm
3 = Idle
4 = Data Active
5 = Error
6 = Reserved
7 = Exception
8 = Access Error
1 = 10Mbit/s, half duplex
2 = 10Mbit/s, full duplex
3 = 100Mbit/s, half duplex
4 = 100Mbit/s, full duplex
1 = DHCP
2 = DCP
Factory
Setting
0 sSys, rw5-57
1Sys, rw5-57
-RO5-30
0Sys, rw5-30
1Sys, rw5-30
User
Setting
Proprieties Page
0
SRW 01 | 0-9
Quick Reference of Parameters
0
ParameterDescriptionAdjustable Range
P853Write Word #40 to 65535 0 Sys, rw5-31
P854Write Word #50 to 65535 0 Sys, rw5-31
P855Write Word #60 to 65535 0 Sys, rw5-31
P856Write Word #70 to 65535 0 Sys, rw5-31
P857Write Word #80 to 65535 0 Sys, rw5-31
P858Write Word #90 to 65535 0 Sys, rw5-31
P859Write Word #100 to 65535 0 Sys, rw5-31
P860Write Word #110 to 65535 0 Sys, rw5-31
P861Write Word #120 to 65535 0 Sys, rw5-31
P862Write Word #130 to 65535 0 Sys, rw5-31
P863Write Word #140 to 65535 0 Sys, rw5-31
P864Write Word #150 to 65535 0 Sys, rw5-31
P865Write Word #160 to 65535 0 Sys, rw5-31
P866Write Word #170 to 65535 0 Sys, rw5-31
P867Write Word #180 to 65535 0 Sys, rw5-31
P868Write Word #190 to 65535 0 Sys, rw5-31
P869Write Word #200 to 65535 0 Sys, rw5-31
P899Update Ethernet Configuration 0 = Normal Operation
P1000User Program Status0 = No Program
P1001User Program Disabling0 = Executes User Program
P1010 to
P1109
User Parameters0 to 655350Us, rw5-61
1 = Update Configuration
1 = Install. Program
2 = Incompat. Program
3 = Program Stopped
4 = Program Running
1 = Stops User Program
Factory
Setting
0 Sys, CFG5-31
-RO5-61
0Sys, rw5-61
User
Setting
Proprieties Page
RO = read-only parameter.
rw = reading/writing parameter.
CFG = configuration parameter, it can only be changed with a stopped motor.
Sys = system parameter. Its value is updated when the key is pressed.
Us = User parameter. Its value is instantaneously updated by the HMI, even before pressing the key.
0-10 | SRW 01
Safety Instructions
1 SAFETY INSTRUCTIONS
This manual contains the necessary information for the correct use of the SRW 01 smart relay.
It has been developed to be used by personnel with adequate training or technical qualification to operate this
type of equipment.
1.1 SAFETY WARNINGS IN THE MANUAL
The following safety warnings are used in this manual:
DANGER!
The nonobservance of the procedures recommended in this warning can lead to death, serious injuries
and considerable material damage.
ATTENTION!
The nonobservance of the procedures recommended in this warning can lead to material damage.
NOTE!
The text intents to supply important information for the correct understanding and good operation of
the product.
1.2 PRELIMINARY RECOMMENDATIONS
DANGER!
Only qualified personnel familiar with the SRW 01 smart relay and associated equipment should plan
or implement the installation, start-up, operation and maintenance of this equipment These personnel
must follow all the safety instructions included in this Manual and/or defined by local regulations.
Failure to comply with these instructions may result in life threatening and/or equipment damage.
1
NOTE!
For the purpose of this manual, qualified personnel are those trained to be able to:
1. Install, power-up, and operate the SRW 01 according to this manual and to the effective legal safety
procedures.
2. Use protection equipment according to the established standards.
3. Provide first aid services.
DANGER!
Always disconnect the main power supply before touching any electrical device associated with the
relay.
ATTENTION!
Control, sensor and communication cables must be installed observing the minimun distance of 25 cm
away from power cables, and preferably installed in grounded metal conduits.
ATTENTION!
For digital inputs, it is recomended the use of shielded cables when the cable length exceeds 200 m
or if they are subject to electromagnetic interference.
If any further information is necessay to install the cable, refer to the cable manufacturer for the proper
installation.
SRW 01 | 1-1
Safety Instructions
NOTE!
The incorrect selection of the Current Measurement Unit (UMC) or Current/Voltage Measurement Unit
(UMCT), by means of parameter P295 and/or lack of the setting of the motor rated current (P401 and/
or P402), may result in the incorrect communication of the value of measured current, making bit 3 of
parameter P006 – Relay Status (binary) indicate that the motor in ON, not allowing the modification of
parameters whose modification is only allowed when the motor is not energized.
In the attempt of modifying those parameters, the message “stop” will flash for three seconds on the
1
HMI and the modification will not be accepted.
In those cases, disconnect the cable that interconnects the Control Unit (UC) and the Current
Measurement Unit (UMC) or Current/Voltage Measurement Unit (UMCT). The Control Unit (UC) will
signal by means of the status led and message “E0085” on the HMI that there is no communication
with the UMC/UMCT and the current informed will be zero (0).
Set parameter P295 according to the Current Measurement Unit (UMC) or Current/Voltage Measurement
Unit (UMCT) obtained and set the motor rated current (P401 and/or P402) according to data on the
motor nameplate. After setting those parameters, reconnect the connecting cable between the UC
and the UMC/UMCT and run an error reset using the front button, and then set the other parameters
of the system.
ATTENTION!
The digital inputs and outputs functions of the Control Unit are automatically configured according to
the selection of the operating mode through parameter P202. The factory default operating mode is
the overload relay mode (P202 = 1); digital outputs O1 and O2 are used to signal Trip NO (normally
open) and Trip NC (normally closed), respectively.
ATTENTION!
The electronic boards contain components sensitive to electrostatic discharges. Do not touch
components and connectors directly.
NOTE!
Read this manual completely before installing or operating the relay.
1-2 | SRW 01
General Information
2 GENERAL INFORMATION
2.1 ABOUT THE MANUAL
This manual presents the instructions for the installation and commissioning of the Smart Relay WEG, SRW 01,
as well as its main characteristics.
In order to get information on other functions, accessories and operation conditions, refer to the following manuals:
Ladder programming manual – WLP.
Ethernet communication manual.
These manuals are they are available for download on the website: www.weg.net.
2.2 TERMS AND DEFINITIONS USED IN THE MANUAL
Amp, A: ampere is the electric current level unit of measurement.
V: volt is the voltage unit of measurement.
PC: Personal computer
PE: protective earth.
UMCT: Current/Voltage Measurement Unit.
W: watt, basic unit of real power. It is obtained by the direct product of voltage (V) by the current (I).
kW: kilowatts = 1000 (103) W.
VA: volt ampere, unit of measurement of apparent power.
kVA: kilovolt-ampere = 1000 (103) VA.
VAr: reactive volt-ampere, unit of measurement of reactive power.
kVAr: kiloVolt-ampere-reactive = 1000 (103) VA.
2
kWh: kilowatt-hour, it represents the consumed power in a time period. And the product of the load real power
(kW) by the number of hours (h) it was on.
MWh: megawatt-hour = 1,000,000 (106) W or 1000 (103) kW.
PTC: resistor whose resistance value in ohms increases proportionally to the temperature increase; used as a
temperature sensor in electric motors.
HMI: human-machine interface; It is a device that allows the motor control, as well as viewing and editing the relay
parameters. It presents keys for the motor command, navigation keys and a display.
Flash Memory: non-volatile memory that can be electronically written and erased.
Ram Memory: random access memory (volatile).
USB: universal serial bus; is a serial bus standard that allows devices to be connected using the plug and play
concept.
°C: celsius or centigrade degrees.
º F: fahrenheit.
SRW 01 | 2-1
General Information
AC: alternating current.
DC: direct current.
CV: cheval vapeur = 736 Watts (unit of power, used to indicate the mechanical power of electric motors).
hp: horse power = 746 Watts (unit of power, used to indicate the mechanical power of electric motors).
SF: service factor.
Hz: hertz.
mA: milliamp = 0.001 ampere.
min: minute.
2
ms: millisecond = 0.001 second.
rms: “root mean square”; effective value.
rpm: revolutions per minute; speed unit.
s: second.
V: volts.
Ω: ohms.
NO: normally open contact.
NC: normally closed contact.
Check Back: verification of running motor.
Trip: switching off of the motor by the action of a protection.
UC: control unit.
UMC: current measurement unit.
MC: communication module.
mm: millimeter.
in: inch.
m: meter.
ELS: earth leakage sensor.
RCD: according to IEC 60755, mechanical switching device (or device association developed to cause contacts
to open when a residual current reaches a certain value under specific conditions (Residual Current Device).
FLA: set current at full load (Full Load Amps).
EDU: Expansion Digital Unit.
2-2 | SRW 01
General Information
2.3 ABOUT THE SRW 01
The SRW 01 is a low voltage electric motor management system that presents cutting edge technology and has
network communication capabilities. For being modular, its functionalities can be extended, making it a versatile
product, and prepared for several applications.
The SRW 01 has a modular design that allows the expansion of the relay functionalities. The Control Unit (UC)
can be mounted together with the Current Measurement Unit (UMC), forming a single unit, or separated (up to 2
meters [6.56 ft]) from it.
By using the Expansion Digital Unit (EDU), it is possible to increase the number of digital inputs and outputs in the
Control Unit (SRW01-UC), in a total of 12 digital inputs and 8 outputs.
It is possible to use a Current/Voltage Measurement Unit (UMCT) in place of a Current Measurement Unit (UMC).
Besides measuring the motor currents (like the UMC), it is possible to monitor the voltages up to 690 V, phase
sequence, power factor (cos ϕ) and all motor powers.
In order to exchange information via Ethernet communication network, the SRW 01 features two RJ45 ports with
integral switch, which enables the execution of different network topologies of the fieldbus technique.
The SRW 01 has an USB port that makes the parameterization, monitoring and programming of the relay easier
by using a PC with the WLP software. Because of the thermal memory, the relay is able to keep the motor thermal
image even when it is not energized.
2
1 - Digital input indication Led’s
2 - Digital output indication Led’s
3 - Network Led (Net) – indication according to the Table
7.1 on page 7-1
4 - Trip Led
Green – normal operation without Trip
Flashing Green – protection alarm
Flashing red – protection Trip
5 - Status Led
Green – normal operation without fault or alarm
Flashing Green – system alarm
Flashing red – system error
6 - Reset Button
7 - Current Measurement Unit (UMC) connector or
Current/ Voltage Measurement Unit (UMCT)
Figure 2.1: SRW 01 control unit identification
6
I11 I12 I13 I14 I15 I16
3
4
1
5
7
2
(a) Control Unit - SRW 01 - UC(b) HMI (vertical)(c) HMI2 (horizontal)
SRW 01 | 2-3
General Information
(d) Current Measurement Units - SRW 01 -
UMC1 (5 A), 2 (12.5 A) and 3 (25 A)
(e) Current Measurement Unit -
SRW 01 - UMC4 (125 A)
2
(f) Current Measurement Unit - SRW 01 - UMC5 (420 A)
(g) Current Measurement Unit (with busbar accessory) - SRW 01 - UMC6 (840 A)
(h) Current/Voltage Measurement Unit -
SRW 01-UMCT 1 (5 A), 2 (12.5 A) and 3 (25 A)/690 V
2-4 | SRW 01
(i) Current/Voltage Measurement Unit -
SRW 01-UMCT 4 (125 A)/690 V
General Information
(j) Current/Voltage Measurement Unit – SRW 01-UMCT 5
(l) Current/Voltage Measurement Unit – SRW 01-UMCT 6
(840 A/690 V) – with busbar accessory
2
4
3
1 - Digital input indication Led’s
2 - Digital output indication Led’s
3 - On Led
Green - Energized device
Off - Deenergized device
4 - Status Led
Green - Normal operation
Flashing green - Communication to the Control Unit (UC)
has been reestablished
Flashing red - No communication with the Control Unit (UC)
5 - Connector for the Control Unit (UC)
6 - Connector for the HMI
(n) Expansion Digital Unit – SRW 01-EDU
Figure 2.2: (a) to (n) SRW 01 components
1
3
5
2
6
4
SRW 01 | 2-5
General Information
2.4 SRW 01 IDENTIFICATION LABEL
1 - Product model
2 - WEG part number
3 - Serial number
4 - Manufacturing date
5 - Maximum ambient temperature
6 - Firmware version
7 - UC supply voltage (voltage and
frequency)
8 - Digital input voltage
9 - Connection to the input terminals
T1 and T2
1
3
7
8
9
5
11
10 -UMC/UMCT current range
11 - Protection degree
12 - UMCT voltage range
13 - Connection to the input
terminals E1 and E2
UL 508
MAX. TA: 40°C (104°F)
Voltage 600 VAC
Trip current at 125% of FLA
75°C CU wire only
Use only with SRW01-UC
See user manual for short circuit ratings
MADE IN BRAZIL HECHO EN BRASIL
FABRICADO NO BRASIL
V 1.00
47 l
6
4
10
Figure 2.3: Identification labels at the UC, UMC, EDU and UMCT laterals
There is a warning label at the top of the Control Unit (UC) and of the Expansion Digital Unit (EDU), which informs
the voltage of the digital inputs for the acquired model.
Figure 2.4: Warning labels at the UC and EDU tops
2.5 HOW TO SPECIFY THE SRW 01 MODEL
In order to specify the SRW 01 model, refer to the catalog available for download on the website: www.weg.net.
2.6 RECEIVING AND STORAGE
The SRW 01 is supplied packed in a cardboard box. There is a label outside the box describing the product main
characteristics: model, WEG part number, serial number, manufacturing date and firmware version.
In order to open the package:
1. Put the package on a table.
2. Open the package.
3. Take out the product.
2-6 | SRW 01
General Information
Verify if:
The identification label matches the bought model.
Damage occurred during transportation. If any problem is detected, contact the carrier immediately.
If the SRW 01 is not going to be installed soon, keep it in the closed package and store it in a clean and dry
place with temperature between - 25 °C and + 80 °C (- 13 °F and + 176 °F).
2.7 POWER FACTOR
The power factor (also called cos ϕ or cosine phi) indicates what percentage of total power supplied (kVA) is
effectively used as real power (kW). It can be defined as the relation between the apparent power (S) and the real
power (P), or also as the cosine of the displacement between the voltage and current signals.
The apparent power (S), measured in kVA, is the total power generated and transmitted to the load. The real
power (P), measured in kW, is the one that effectively performs the work, and the reactive power (Q), measured in
kVAr, is only used to create and maintain the electromagnetic fields within the motor.
Thus, while the real power is always consumed in the execution of the work, the reactive power, besides not
producing work, circulates between the loads and the power supply, taking a “space” in the electric system that
could be used to supply more real power.
The power factor is a dimensionless number between 0.00 and 1.00 and shows the efficiency level of the use of
electric systems. Therefore, when we say the power factor is 0.80, it means that 80 % of the apparent power (S)
is transformed into real power (P).
The measurement of the power factor, taking into account that the voltage is sine-shaped and the load linear (if
there are no harmonics), is obtained by observing the phase displacement between voltage and current in one of
the phases that supply the motor in the fundamental frequency. For inductive loads, as in case of asynchroous
motors (induction motors), the current signal will always be delayed in relation to the voltage signal.
According to trigonometry, the sinusoidal function can be mapped in a circumference, seeing that a full cycle of
the sinusoid is represented by 360º. As the voltage and current signals have the same period, the displacement
between signals is easily obtained.
Voltage [V]
Current [A]
ϕ
360º
2
Time [s]
Figure 2.5: Displacement between voltage and current signals
After obtaining the displacement (ϕ) between the voltage and current signals, the power factor is calculated by
means of equation 01.
Power Factor = cos (ϕ)
Equation 01: Calculation of the power factor
SRW 01 | 2-7
General Information
From the power factor value, in the case of sine-shaped waves, the real (P), reactive (Q) and apparent (S) powers
can be represented by vectors that form a right triangle, also known as power triangle, as shown in Figure 2.6 on
page 2-8 from which the power relations can be obtained.
Reactive
power
Apparent power (kVA)
ϕ
(kVAr)
Real power (kW)
Figure 2.6: Power triangle
2
2-8 | SRW 01
Installation and Connection
3 INSTALLATION AND CONNECTION
This chapter describes the procedures for the electrical and mechanical installation of the SRW 01. The orientations
and suggestions shall be followed in order to guarantee personnel and equipment safety, as well as the proper
operation of the relay.
3.1 MECHANICAL INSTALLATION
3.1.1 Environmental Conditions
Avoid:
Exposure to direct sunlight, rain, high humidity, or sea-air.
Explosive or corrosive gases or liquids.
Excessive Vibration.
Dust, metallic particles or oil mist in the air.
Closeness to strong magnetic fields or high-current cables.
Allowed environmental conditions for operation:
3
Temperature: According IEC: 0 °C to 55 °C (32 °F to 131 °F).
According UL: 0 °C to 40 °C (32 °F to 104 °F).
Humidity: 5 % to 90 % non-condensing.
Pollution degree: 2 (according to UL508) with non-conductive pollution. Condensation shall not originate
conduction through the accumulated residues.
Maximum altitude: 2000 m (6.600 ft) above sea level - nominal conditions. For applications at higher altitudes,
contact WEG.
NOTE!
In order to prevent overheating, the ventilation openings must not be blocked. It is recommended to
provide a side clearance of at least 10 mm (± 0.39 in), and a top and bottom clearance of at least 30
mm (±1.18 in) so as to allow a good air circulation and better cooling.
3.1.2 Mounting
The Control Unit (UC), Current Measurement Unit (UMC1, 2, 3 and 4), the Expansion Digital Unit (EDU) and
Current/Voltage Measurement Unit (UMCT1, 2, 3 and 4) can be installed in any position.
They can be mounted on a 35 mm (1.38 in) DIN rail or through the fixing adapter (PLMP) with M4 screws.
SRW 01 | 3-1
Installation and Connection
3
(a) 35 mm (1.38 in) DIN rail mounting(b) Secured with screws
Figure 3.1: (a) and (b) UC, UMC, EDU and UMCT mounting
NOTE!
The Control Unit (UC) can be mounted together with the Current Measurement Unit (UMC), making a
single unit, or separately (up to 2 meters). The Current/Voltage Measurement Unit (UMCT) only allows
the mounting separate from the Control Unit (UC).
3-2 | SRW 01
Loading...
+ 118 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.