Watts W110 User Manual

W110 LXT Downflow Softeners
IOM-WQ-W110
and SXT Filters
Installation, Operation and Maintenance Manual
W110 SXT Filter
!
WARNING
Read this Manual BEFORE using this equipment. Failure to read and follow all safety and use information
can result in death, serious personal injury, property damage, or damage to the equipment.
Keep this Manual for future reference.
!
WARNING
You are required to consult the local building and plumbing codes prior to installation. If the information in this manual is not consistent with local building or plumbing codes, the local codes should be followed. Inquire with governing authorities for additional local requirements.
!
WARNING
Need for Periodic Inspection/Maintenance: This product must be tested periodically in compliance with local codes, but at least once per year or more as service conditions warrant. All products must be retested once maintenance has been performed. Corrosive water conditions, and/or unauthorized adjustments or repair could render the product ineffective for the service intended. Regular checking and cleaning of the prod­uct’s internal components helps assure maximum life and proper product function.
W110 LXT Softener
System Specification Tables ...............................2
Safety Information .......................................4
How To Use This Manual ..................................4
Pre-Installation Considerations ...................................4
General Installation Instructions ...................................5
System Configuration ....................................6
Start-Up Instructions LXT .................................7
Timer Features LXT ......................................7
Timer Operation LXT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Start-Up Instructions SXT .................................9
Timer Features SXT ......................................9
Timer Operation SXT ....................................10
Master Programming Mode LXT ...........................11
Diagnostic Programming Mode LXT ......................13
Master Programming Mode Chart SXT ......................14
Master Programming Mode SXT ...........................15
User Programming Mode SXT .............................19
Diagnostic Programming Mode SXT ........................20
Powerhead Assembly LXT................................21
Powerhead Assembly SXT................................22
W110 Control Valve Assembly Downflow/Upflow .................. 23
3/4" Plastic Turbine Meter Assembly ........................24
Bypass Valve Assembly (Plastic) .................................24
Bypass Valve Assembly (Stainless Steel)...........................25
2310 Safety Brine Valve..................................25
Water Conditioner Flow Diagrams............................26
Troubleshooting LXT ....................................28
Troubleshooting SXT ....................................29
Job Specification Sheet..................................30
NOTES ..............................................31
System Specification Tables
NOTE: All softeners use LXT timers and all filters use SXT timers. Maximum or peak flow rates are not to be interpreted as
continuous flow capabilities.
CHART 1: W110 Series Metered Water Softeners Water With LXT Timers
MINERAL TANK BRINE TANK FLOW RATE & PRESSURE
TANK
SIZE
RESIN
FT
3
TANK
SIZE
SALT
FILL
SERVICE
(GPM)
DROP
(PSI)
BKW
(GPM)
SHIP WT.
MODEL NO.
CAPACITY
(MAX.)
PIPE SIZE
(IN.)
M3011-W110 30,000 1 9 x 48 1 18 x 40 400 12 15 2 110 M3013-W110 45,000 1 10 x 54 1.5 18 x 40 400 12 15 2.4 130 M3015-W110 60,000 1 12 x 52 2 18 x 40 400 13 15 3.5 190 M3017-W110 90,000 1 14 x 65 3 18 x 40 400 14 15 5 230
M3019-W110 120,000 1 16 x 65 4 18 x 40 400 15 15 7 310
NOTE: Brine tanks come with safety float valve.
CHART 2: W110 Series Backwashing Micro Z Filters With SXT Timers
MODEL NO. VALVE
PIPE SIZE
(IN.)
TANK
SIZE
MEDIA
(CU. FT.)
NM09-W110 W110 1 9 x 48 1 9 7 16 x 10 x 55 110
NM10-W110 W110 1 10 x 54 1.5 10 7 16 x 11 x 62 140
NM12-W110 W110 1 12 x 52 2 15 12 17 x 13 x 60 200
NM14-W110 W110 1 14 x 65 3 21 15 18 x 15 x 74 310
PEAK SERVICE
FLOW (GPM)
BACKWASH
(GPM)
FLOOR SPACE
(L x W x H).
SHIP WT.
(LBS.)
CHART 3: W110 Series Backwashing Filox Filters With SXT Timers
MODEL NO. VALVE
PIPE SIZE
(IN.)
TANK
SIZE
MEDIA
(CU. FT.)
NF09-W110 W110 1 9 x 48 1 6 7 16 x 10 x 55 167
NF10-W110 W110 1 10 x 54 1.5 9 7 16 x 11 x 62 235
NF12-W110 W110 1 12 x 52 2 12 12 17 x 13 x 60 318
NF14-W110 W110 1 14 x 65 3 18 15 18 x 15 x 74 460
PEAK SERVICE
FLOW (GPM)
BACKWASH
(GPM)
FLOOR SPACE
(L x W x H).
SHIP WT.
(LBS.)
(LBS.)
W110 LXT Downflow Softeners and SXT Filters 2
System Specification Tables (continued)
CHART 4: W110 Series Backwashing Greensand Plus Filters With SXT Timers
MODEL NO. VALVE
PIPE SIZE
(IN.)
TANK
SIZE
MEDIA
(CU. FT.)
NGP09-W110 W110 1 9 x 48 1 3 5 16 x 21 x 55 137
NGP10-W110 W110 1 10 x 54 1.5 4 7 16 x 22 x 62 190
NGP12-W110 W110 1 12 x 52 2 5 10 17 x 24 x 60 258
NGP14-W110 W110 1 14 x 65 3 6 12 18 x 33 x 74 370
CHART 5: W110 Series Backwashing Carbon Filters With SXT Timers
MODEL NO. VALVE
PIPE SIZE
(IN.)
NC09-W110 W110 1 9 x 48 1 4 4 16 x 10 x 55 80
NC10-W110 W110 1 10 x 54 1.5 6 5 16 x 11 x 62 105
NC12-W110 W110 1 12 x 52 2 8 7 17 x 13 x 60 145
NC14-W110 W110 1 14 x 65 3 11 10 18 x 15 x 74 200
NC16-W110 W110 1 16 x 65 4 14 12 20 x 17 x 74 265
TANK
SIZE
MEDIA
(CU. FT.)
CHART 6: W110 Series Backwashing Empty Filters With SXT Timers
MODEL NO. VALVE
PIPE SIZE
(IN.)
NX09-W110 W110 1 9 x 48 1 10 5 16 x 10 x 55 53
NX10-W110 W110 1 10 x 54 1.5 10 7 16 x 11 x 62 64
NX12-W110 W110 1 12 x 52 2 20 10 17 x 13 x 60 90
NX14-W110 W110 1 14 x 65 3 40 12 18 x 15 x 74 118
NX16-W110 W110 1 16 x 65 4 50 20 20 x 17 x 74 155
TANK
SIZE
MEDIA
(CU. FT.)
PEAK SERVICE
FLOW (GPM)
PEAK SERVICE
FLOW (GPM)
PEAK SERVICE
FLOW (GPM)
BACKWASH
(GPM)
BACKWASH
(GPM)
BACKWASH
(GPM)
FLOOR SPACE
(L x W x H).
FLOOR SPACE
(L x W x H).
FLOOR SPACE
(L x W x H).
SHIP WT.
SHIP WT.
SHIP WT.
(LBS.)
(LBS.)
(LBS.)
3 W110 LXT Downflow Softeners and SXT Filters
Safety Information
This water conditioner’s control valve conforms to UL/CE Standards. Generic valves were tested and certified for compliance as verified by the agency listing.
• Please review the entire Installation and Operation Manual before installing the water conditioning system.
• As with all plumbing projects, it is recommended that a trained professional water treatment dealer install the water conditioning system. Please follow all local plumbing codes for installing this water conditioning system.
• This system will not make microbiologically unsafe water safe. Water that is unsafe must be treated separately from this conditioner.
• This water conditioning system is to be used only for potable water.
• Inspect the water conditioning system for carrier shortage or shipping damage before beginning installation.
• Use only lead-free solder and flux, as required by federal and state codes, when installing soldered copper plumbing.
• Use caution when installing soldered metal piping near the water conditioning system. Heat can adversely affect the plastic control valve and bypass valve.
• All plastic connections should be hand tightened. Teflon® tape may be used on connections that do not use an O-ring seal. Do not use pipe dope type sealants on the valve body. Do not
use pliers or pipe wrenches.
• Do not use petroleum-based lubricants such as Vaseline, oils or hydrocarbon-based lubricants. Use only 100% silicone lubricants.
• Use only the power transformer supplied with this water conditioning system.
• All electrical connections must be completed according to local codes.
• The power outlet must be grounded.
• Install an appropriate grounding strap across the inlet and
outlet piping of the water conditioning system to ensure that a proper ground is maintained.
• To disconnect power, unplug the AC adapter from its power source.
• Observe drain line requirements.
• Do not support the weight of the system on the control valve
fittings, plumbing, or the bypass.
• Do not allow this water conditioning system to freeze. Damage from freezing will void this water conditioning system’s warranty.
• Operating ambient temperature: 34° to 120°F (1° to 49°C).
• Operating water temperature: 34° to 100°F (1° to 38°C).
• Operating water pressure range : 25 to 120 psi (1.38 to 8.27
bar).
• Observe all warnings that appear in this manual.
• Keep the media tank in the upright position. Do not turn upside
down or drop. Turning the tank upside down or laying the tank on its side can cause media to enter the valve.
• Use only regenerants designed for water conditioning. Do not use ice melting salt, block salt or rock salt. During cold weather it is recommended that the installer warm the valve to room temperature before operating. Teflon® is a trademark of E.I. duPont de Nemours.
How To Use This Manual
This installation manual is designed to guide the installer through the process of installing and starting up water conditioning systems featuring the ProSense controller. This manual is a reference and will not include every system installation situation. The person installing this equipment should have:
• Training on the control valve.
• Knowledge of water conditioning and how to determine proper
control settings.
• Adequate plumbing skills.
Pre-Installation Considerations
A. Water Pressure
A minimum of 25 pounds of water pressure is required for regeneration valve to operate effectively.
B. Electrical Facilities
A continuous 115 volt, 60 Hertz current supply is required. Make certain the current supply is always hot and cannot be turned off with another switch.
C. Existing Plumbing
Condition of existing plumbing should be free from lime and iron buildup. Piping that is built up heavily with lime and/or iron should be replaced. If piping is clogged with iron, a separate iron filter unit should be installed ahead of the water softener.
D. Location Of Softener And Drain
The softener should be located close to a drain.
E. Bypass Valves
Always provide for the installation of a bypass valve.
F. Valve to Tank Installation Instructions
1. Spin the valve onto the tank, ensuring the threads are not cross­threaded.
NOTICE
The main control valve and tank adaptor have right-hand threads, or clockwise, to install
2. Rotate the valve freely without using force until it comes to a stop (this position is considered zero).
3. Rotate the valve clockwise from zero, between ¼ turn and ½ turn to fully tighten. No tools are needed. Hand tight is enough. Overtightening may cause valve or tank damage.
NOTICE
If lubricant is required, a silicone compound is strongly recommended. Dow Corning® Silicone Compound (available from Watts), is recommended for best possible results. Dow Corning Release Compound is used in the manufacture of this control valve. The use of other types of lubricants may attack the control’s plastic or rubber components. Petroleum-based lubricants can cause swelling in rubber parts, including O-rings and seals.
®
7
W110 LXT Downflow Softeners and SXT Filters 4
Pre-Installation Considerations (continued)
G. Pre Installation and Loading of Media
Systems that are 13” in diameter and larger are not loaded with media. These systems must be loaded with media before placing into service. To load a system follow the below steps.
1. Cap the top open end of the distributor tube with tape and plastic sheeting to keep foreign debris from entering the distributor tube. This cap must be secure and not come off during media loading.
2. Place the distributor tube, screen end down, into the mineral tank and center it in the bottom. The top of the distributor tube should be flush with the top of the tank.
3. Make sure the plastic and tape cap is secure to the top of the distributor tube, place a funnel on the top of the tank and load first the gravel (if different sizes of gravel are used load the largest gravel first, then the smaller gravel) then the filter media/ softening resin into the tank. The cap must not come off of the distributor tube during the loading of the media.
4. Remove the plastic cap from the distributor tube. DO NOT PULL UP ON THE DISTRIBUTOR TUBE when removing the cap. The distributor tube top must remain flush with the top of the tank.
5. Clean any media from the threads and top of the mineral tank.
6. Lubricate the O-rings on the bottom of the control valve (distributor pilot O-ring and top of tank O-ring). Use non­petroleum based silicone lubricant only.
7. Place the control valve on top of the tank. When doing this step, seat the top of the distributor tube inside the centered O-ring sealed port on the bottom of the valve first then press the valve down until the tank threads come in contact with the valve threads. This ensures that the distributor tube is properly seated into the bottom of the control valve. Thread the valve on to the tank clockwise. Be careful not to cross thread the valve or over tighten it. A hand tight snug fit is appropriate for the control valve torque. A wrench is not necessary. Do not use thread sealant or PTFE tape on the valve base threads.
8. The system is now ready for installation. Follow the Installation Section in the Installation, Operation and Maintenance Manual.
!
WARNING
Do not exceed water pressure of 125psi (8.6 bar). Do not exceed 110°F (43.3°C). Do not subject unit to freezing conditions.
General Installation Instructions
1. Turn off water heater(s).
2. Turn off the main water supply to the home and open an inside faucet (cold and hot) to relieve any pressure within the plumbing system.
3. Place the system in the desired installation location. Make sure that the location is level and sturdy enough to support the weight of the system once it is in operation.
4. Place the bypass valve in the bypass position.
5. Connect the cold water supply to the inlet of the water conditioning system. While constructing the supply line, install a master supply valve (user supplied) in the supply line and close it.
6. Connect the feed water line to the home to the outlet of the system.
7. Plumb the drain line to an appropriate drain abiding buy all local, city, and state codes. Use a 3/4" drain line for backwash flow rates that exceed 7 gpm or length that exceeds 20' (6 m).
8. For softening systems, connect the brine tank to the water softener control valve brine inlet port using the factory supplied fittings and tubing. Add enough water to the brine tank so that water covers the top of the air check. DO NOT ADD SALT AT THIS TIME.
9. Open the user supplied feed water valve. Check for leaks and repair as needed.
10. Allow the inside hot and cold faucet to remain open until all air has been purged from the plumbing system. Then close the faucet.
11. Locate Manual Regeneration Options in this manual and follow the steps to initiate an Immediate Manual Regeneration. Once you have read that section place the system in backwash and unplug the system from its electrical outlet once it has cycled into the backwash position. This will stall the unit in backwash so air can be purged from the tank.
12. Adjust the user supplied feed water valve to 1/4 open and place the bypass valve into the service position.
13. Air will come out of the drain line until the backwashing tank is completely purged of air. Then water will flow to drain. Allow water to flow to drain for 15 minutes or until the water to drain is clear of resin color throw.
14. Plug the system back into the electrical outlet and manually cycle it through the remaining regeneration steps until it arrives in the service position.
15. Check for leaks and repair as needed.
16. Installation is now complete and the system is ready for programming and one cycle of brine tank refill so that the correct amount of water is in the brine tank for the first regeneration cycle. The brine tank refill must be done after programming the system.
5 W110 LXT Downflow Softeners and SXT Filters
System Configuration
The chart below is for dealer use only. Use this information to configure the system to suit the application. The W110 LXT timer will use the settings to calculate cycle times.
Resin Volume
Tank Diameter
3
US (FT
) Metric (Liters)
8 0.75 20 #000 0.125
9 25 #000 0.125
9 1.00 30 #000 0.125
10 1.25 35 #00 0.125
10 1.50 40 #00 0.125
12 45 #00 0.125
12 1.75 50 #00 0.125
12 2.00 55 #0 0.25
13 60 #0 0.25
13 2.25 65 #0 0.25
14 2.50 70 #1 0.25
14 75 #1 0.25
14 2.75 80 #1 0.25
14 3.00 85 #1 0.25
14 3.25 90 #2 0.50
14 95 #2 0.50
14 3.50 100 #2 0.50
16 3.75 105 #3 0.50
16 110 #3 0.50
16 4.00 115 #3 0.50
Injector Size BLFC Size
W110 LXT Downflow Softeners and SXT Filters 6
Start-Up Instructions LXT
The water softener should be installed with the inlet, outlet, and drain connections made in accordance with the manufacturer’s recommendations, and to meet applicable plumbing codes.
1. Program the valve control according to instructions shown in this manual.
2. Start an immediate regeneration by holding the Extra Cycle button for 5 seconds. Position the valve to backwash. Ensure the drain line flow remains steady for 10 minutes or until the water runs clear.
3. Position the valve to the brine / slow rinse position. Ensure the unit is drawing water from the brine tank (this step may need to be repeated).
4. Position the valve to the rapid rinse position. Check the drain line flow, and run for 5 minutes or until the water runs clear.
5. Position the valve to the start of the brine tank fill cycle. Ensure water goes into the brine tank at the desired rate. The brine valve drive cam will hold the valve in this position to fill the brine tank for the first regeneration.
6. Replace control cover.
7. Put salt in the brine tank.
NOTICE
Do not use granulated or rock salt.
Timer Features LXT
Display Position
Program Icon
Clock
Service Indicator
• A Regeneration can be triggered immediately by pressing the Extra Cycle button for five seconds.
• During a regeneration, the display will show the cycle number followed by the time remaining in that cycle
• During regeneration, the user can force the control to advance to the next cycle step immediately by pressing the extra cycle button.
Cycle
Time
Remaining
Figure 2
B. Setting the Time of Day
1. Press and hold either the Up or Down buttons until the Time of Day icon appears.
2. Adjust the displayed time with the Up and Down buttons.
3. When the desired time is set, press the Extra Cycle button to resume normal operation. The unit will also return to normal operation after 5 seconds if no buttons are pressed.
PM
Figure 3
Flow
Indicator
Mode
Button
Time of
Time of
Backwash
Backwash
Length
MODE
Day
PM
Filter Capacity
Capacity Remaining
Resin
Extra Cycle
Button
Figure 1
A. Features of the LXT
• Power backup that continues to keep time and the passage of days for a minimum of 12 hours in the event of power failure. During a power outage, the control goes into a power-saving mode. It does not monitor water usage during a power failure, but it does store the volume remaining at the time of power failure.
• Day of the week reserve calculates a reserve for each day based on the past 4 weeks.
• The Flow Indicator flashes when outlet flow is detected.
• The Service Icon flashes if a regeneration cycle has been
queued.
C. Queueing a Regeneration
1. Press the Extra Cycle button. The service icon will flash to indicate that a regeneration is queued.
2. To cancel a queued regeneration, press the Extra Cycle button.
D. Regenerating Immediately
Press and hold the Extra Cycle button for five seconds.
7 W110 LXT Downflow Softeners and SXT Filters
Timer Operation LXT
A. Meter Delayed Control
A Meter Delayed Control measures water usage. The system regenerates at the programmed regeneration time after the calculated system capacity is depleted. The control calculates the system capacity by dividing the unit capacity by the feedwater hardness and subtracting the reserve. The reserve should be set to insure that the system delivers treated water between the time the system capacity is depleted and the actual regeneration time. A Meter Delayed control will also start a regeneration cycle at the programmed regeneration time if a number of days equal to the regeneration day override pass before water usage depletes the calculated system capacity.
B. Control Operation During Regeneration
During regeneration, the control displays a special regeneration display. In this display, the control shows the current regeneration step number the valve is advancing to, or has reached, and the time remaining in that step. The step number that displays flashes until the valve completes driving to this regeneration step position. Once all regeneration steps are complete the valve returns to service and resumes normal operation.
The meter and time clock controls will use and display cycles:
1. Backwash
2. Brine/Slow Rinse
3. Rapid Rinse
4. Brine Tank Refill The filter controls will use and display cycles:
1. Backwash
2. Rapid Rinse Pressing the Extra Cycle button during a regeneration cycle
immediately advances the valve to the next cycle step position and resumes normal step timing.
E. Control Operation During A Power Failure
The LXT includes integral power backup. In the event of power failure, the control shifts into a power-saving mode. The control stops monitoring water usage. The display and motor shut down, but it continues to keep track of the time and day for a minimum of 12 hours.
The system configuration settings are stored in a non-volatile memory and are stored indefinitely with or without line power.
If power fails while the unit is in regeneration, the control will save the current valve position before it shuts down. When power is restored, the control will resume the regeneration cycle from the point where power failed.
!
CAUTION
If power fails during a regeneration cycle, the valve will remain in it’s current position until power is restored. The valve system should include all required safety components to prevent overflows resulting from a power failure during regeneration.
The control will not start a new regeneration cycle without line power. If the valve misses a scheduled regeneration due to a power failure, it will queue a regeneration. Once power is restored, the control will initiate a regeneration cycle the next time that the Time of Day equals the programmed regeneration time. Typically, this means that the valve will regenerate one day after it was originally scheduled. If the treated water output is important and power interruptions are expected, the system should be setup with a sufficient reserve capacity to compensate for regeneration delays.
C. Control Operation During Programming
The control only enters the Program Mode with the valve in service. While in the Program Mode, the control continues to operate normally monitoring water usage and keeping all displays up to date. Control programming is stored in memory permanently, and does not rely on battery backup power.
D. Manually Initiating a Regeneration
1. When timer is in service, press the Extra Cycle button for 5 seconds on the main screen.
2. The timer advances to Regeneration Cycle Step #1 (backwash), and begins programmed time count down.
3. Press the Extra Cycle button once to advance valve to Regeneration Cycle Step #2 (brine draw & slow rinse).
4. Press the Extra Cycle button once to advance valve to Regeneration Cycle Step #3 (rapid rinse).
5. Press the Extra Cycle button once to advance valve to Regeneration Cycle Step #4 (brine refill).
6. Press the Extra Cycle button once more to advance the valve back to in service.
NOTE: If the unit is a filter or upflow, the cycle step order
NOTICE
A queued regeneration can be initiated by pressing the Extra Cycle button. To clear a queued regeneration, press the Extra Cycle button again to cancel. If regeneration occurs for any reason prior to the delayed regeneration time, the manual regeneration request will be cleared.
may change.
W110 LXT Downflow Softeners and SXT Filters 8
Start-Up Instructions SXT
The water conditioner should be installed with the inlet, outlet, and drain connections made in accordance with the manufacturer’s recommendations, and to meet applicable plumbing codes.
1. Program the valve control according to instructions shown in this manual.
2. Start an immediate regeneration by holding the Extra Cycle button for 5 seconds. Position the valve to backwash. Ensure the drain line flow remains steady for 10 minutes or until the water runs clear.
3. Position the valve to the brine / slow rinse position. Ensure the unit is drawing water from the brine tank (this step may need to be repeated). Not used on SXT filter systems.
4. Position the valve to the rapid rinse position. Check the drain line flow, and run for 5 minutes or until the water runs clear.
5. Position the valve to the start of the brine tank fill cycle. Ensure water goes into the brine tank at the desired rate. The brine valve drive cam will hold the valve in this position to fill the brine tank for the first regeneration. Not used on SXT filter systems.
6. Replace control cover.
7. Put salt in the brine tank. Not used on SXT filter systems.
NOTICE
Do not use granulated or rock salt.
Timer Features SXT
NOTICE
Meter, volume, and capacity values are not displayed on SXT filter systems.
• A Regeneration can be triggered immediately by pressing the Extra Cycle button for five seconds.
• The Parameter Display displays the current Cycle Step (BW, BF, RR etc) during regeneration, and the data display counts down the time remaining for that cycle step. While the valve is transferring to a new cycle step, the display will flash. The parameter display will identify the destination cycle step (BW, BF, RR, etc) and the data display will read "------". Once the valve reaches the cycle step, the display will stop flashing and the data display will change to the time remaining. During regeneration, the user can force the control to advance to the next cycle step immediately by pressing the extra cycle button.
B. Setting the Time of Day
1. Press and hold either the Up or Down buttons until the programming icon replaces the service icon and the parameter display reads TD.
2. Adjust the displayed time with the Up and Down buttons.
3. When the desired time is set, press the Extra Cycle button to resume normal operation. The unit will also return to normal operation after 5 seconds if no buttons are pressed.
Figure 4
A. Features of the SXT
• Power backup that continues to keep time and the passage of days for a minimum of 48 hours in the event of power failure. During a power outage, the control goes into a power-saving mode. It does not monitor water usage during a power failure, but it does store the volume remaining at the time of power failure.
• Settings for both valve (basic system) and control type (method used to trigger a regeneration).
• Day-of-the-Week controls.
• While in service, the display alternates between time of day,
volume remaining or days to regeneration.
• The Flow Indicator flashes when outlet flow is detected.
• The Service Icon flashes if a regeneration cycle has been
queued.
Figure 5
C. Queueing a Regeneration
1. Press the Extra Cycle button. The service icon will flash to indicate that a regeneration is queued.
2. To cancel a queued regeneration, press the Extra Cycle button.
D. Regenerating Immediately
Press and hold the Extra Cycle button for five seconds.
9 W110 LXT Downflow Softeners and SXT Filters
Timer Operation SXT
A. Meter Immediate Control
(Not used on SXT filter systems.) A Meter Immediate control measures water usage and regenerates
the system as soon as the calculated system capacity is depleted. The control calculates the system capacity by dividing the unit capacity (typically expressed in grains/unit volume) by the feedwater hardness and subtracting the reserve. Meter Immediate systems generally do not use a reserve volume. The control will also start a regeneration cycle at the programmed regeneration time if a number of days equal to the regeneratio day override pass before water usage depletes the calculated system capacity.
B. Meter Delayed Control
(Not used on SXT filter systems.) A Meter Delayed Control measures water usage. The system
regenerates at the programmed regeneration time after the calculated system capacity is depleted. As with Meter Immediate systems, the control calculates the system capacity by dividing the unit capacity by the feedwater hardness and subtracting the reserve. The reserve should be set to insure that the system delivers treated water between the time the system capacity is depleted and the actual regeneration time. A Meter Delayed control will also start a regeneration cycle at the programmed regeneration time if a number of days equal to the regeneration day override pass before water usage depletes the calculated system capacity.
C. Time Clock Delayed Control
A Time Clock Delayed Control regenerates the system on a timed interval. The control will initiate a regeneration cycle at the programmed regeneration time when the number of days since the last regeneration equals the regeneration day override value.
D. Day of the Week Control
This control regenerates the system on a weekly schedule. The schedule is defined in Master programming by setting each day to either "off" or "on". The control will initiate a regeneration cycle on days that have been set to "on" at the specified regeneration time.
E. Control Operation During Regeneration
During regeneration, the control displays a special regeneration display. In this display, the control shows the current regeneration step number the valve is advancing to, or has reached, and the time remaining in that step. The step number that displays flashes until the valve completes driving to this regeneration step position. Once all regeneration steps are complete the valve returns to service and resumes normal operation.
Pressing the Extra Cycle button during a regeneration cycle immediately advances the valve to the next cycle step position and resumes normal step timing.
F. Control Operation During Programming
The control only enters the Program Mode with the valve in service. While in the Program Mode, the control continues to operate normally monitoring water usage and keeping all displays up to date. Control programming is stored in memory permanently.
G. Manually Initiating a Regeneration
1. When timer is in service, press the Extra Cycle button for 5 seconds on the main screen.
2. The timer advances to Regeneration Cycle Step #1 (backwash), and begins programmed time count down.
3. Press the Extra Cycle button once to advance valve to Regeneration Cycle Step #2 (brine draw & slow rinse). Not used on SXT filter systems).
4. Press the Extra Cycle button once to advance valve to Regeneration Cycle Step #3 (rapid rinse).
5. Press the Extra Cycle button once to advance valve to Regeneration Cycle Step #4 (brine refill). Not used on SXT filter systems.
6. Press the Extra Cycle button once more to advance the valve back to in service.
NOTE: If the unit is a filter or upflow, the cycle step order
may change.
NOTICE
A queued regeneration can be initiated by pressing the Extra Cycle button. To clear a queued regeneration, press the Extra Cycle button again to cancel. If regeneration occurs for any reason prior to the delayed regeneration time, the manual regeneration request will be cleared
H. Control Operation During a Power Failure
The SXT includes integral power backup. In the event of power failure, the control shifts into a power-saving mode. The control stops monitoring water usage. The display and motor shut down, but it continues to keep track of the time and day for a minimum of 12 hours.
The system configuration settings are stored in a non-volatile memory and are stored indefinitely with or without power. The Time of Day flashes when there has been a power failure. Press any button to stop the Time of Day from flashing.
If power fails while the unit is in regeneration, the control will save the current valve position before it shuts down. When power is restored, the control will resume the regeneration cycle from the point where power failed.
!
CAUTION
If power fails during a regeneration cycle, the valve will remain in it’s current position until power is restored. The valve system should include all required safety components to prevent overflows resulting from a power failure during regeneration.
The control will not start a new regeneration cycle without power. If the valve misses a scheduled regeneration due to a power failure, it will queue a regeneration. Once power is restored, the control will initiate a regeneration cycle the next time that the Time of Day equals the programmed regeneration time. Typically, this means that the valve will regenerate one day after it was originally scheduled. If the treated water output is important and power interruptions are expected, the system should be setup with a sufficient reserve capacity to compensate for regeneration delays.
W110 LXT Downflow Softeners and SXT Filters 10
Loading...
+ 22 hidden pages