Introduction to the Watlow Series 988LF
Controllers
iiUsing this Manual
iiDocument Every Step
iiiNotes, Cautions and Warnings
iiiTechnical Assistance
iiiWe Value Your Feedback
Chapter 1
Hardware Setup
1.1Dip Switch Locations and Functions
Chapter 2
Installation and Wiring
2.1Panel Cutout and Dimensions
2.2Installing the Series 988LF
2.3Wiring the Series 988LF
2.3Input-to-output Isolation
2.3Power Wiring
2.3Sensor Installation Guidelines
2.4Wiring 0-20mA and 4-20mA
Process Inputs
2.5Wiring Example
2.7Input 1 Wiring
2.8Remote Set Point Option Wiring
2.9Output 1 Wiring
2.10Output 2 Wiring
Chapter 3
Front Panel and Display Loop
3.1Keys and Displays
3.2Display Loop
Chapter 4
The Setup Menus
4.1Navigating the Setup Menus
4.2Setup Prompts
Chapter 5
The Operation Menus
5.1Navigating the Operation Menus
5.2Display Prompts
Chapter 6
The Factory Menus
6.1Reaching the Diagnostics Menu
6.5Reaching the Calibration Menu
Chapter 7
Tuning, Manual Operation,
Alarms and Error Codes
7.1Auto-tuning (Heat and/or Cool)
7.2Manual Tuning
7.3Manual and Automatic Operation
7.4Using Alarms
7.5Error Code E1 and E2 Messages
7.6Error Code Actions
Appendix
A.1Warranty and Returns
A.2Glossary
A.4Index
A.6Specifications
A.7Model Number
A.8Menu Overview
A.9Declaration of Conformity
Table of Contents
Table of ContentsWATLOW Series 988LF User’s Manual
WATLOW Series 988LF User’s Manuali
Introduction
IntroductionTo The Watlow
Series 988LF Controllers
Figure Int.1 The Series 988LF
Features.
Welcome to the Watlow Series 988LF, a dual output, single input, microprocessor-based, 1/8 DIN, auto-tuning temperature control, featuring
automatic/manual capability with bumpless transfer. In the Auto mode,
the control has closed loop control with sensory feedback, while the
Manual mode has open loop control with user defined output power level.
The 988LF accepts a wide range of thermocouple sensors, along with RTD,
and process inputs. The primary output is Heating or Cooling, while the
secondary output can be Heating, Cooling, or Alarm.
With the Series 988LF, you can select either PID or ON/OFF for output 1
or Output 2. You may input a complete set of PID parameters for both
outputs, or select automatic tuning for both heat and cool from the front
panel. This includes proportional band, reset, rate, and cycle time. By
setting either output’s proportional band to zero, the Series 988LF
becomes a simple ON/OFF control with a 3°F or 1.7°C switching differential, 0.3°F or 0.17°C for 0.1° RTD.
Operator-friendly features include automatic LED indicators to aid in
monitoring and setup, as well as a calibration offset at the front panel.
The Watlow Series 988LF automatically stores all information in a nonvolatile memory.
TL
W
W
A
PROCESS
L1L2
DEV
% OUT
DISPLAY
SERIES 988LF
MODE
AUTO
MAN
Output 1
Control
Heat/Cool
Output 2
Control
Heat/Cool
Alarm
Input 1
Sensor Input
Input 2
Remote Set
Point Option
Auto-Tune
Heat/Cool
Process Deviation
from Set Point
Percent Power
iiWATLOW Series 988LF User’s Manual
Introduction
Introduction
Using this Manual
This manual provides the information you will need to install and operate
a Series 988LF controller.
If you need information about Series 988LF configurations and model
numbers, refer to the Appendix of this manual.
This manual explains the five steps of setting up a Series 988LF controller:
1. Set and document all of the DIP switches, if applicable: Chapter 1.
2. Mount the controller: Chapter 2.
3. Wire and document the controller wiring: Chapter 2.
4. Configure and document the controller software: Chapters 3-6.
5. Run, test and adjust your application. Update documentation.
The Appendix provides definitions and specifications, along with
application examples to help you optimize the safety and performance of your application. Use the Table of Contents and Index to
find specific information.
Document Every Step
The Series 988LF provides powerful control features. Carefully document
each step of the setup and any subsequent changes. This will make it
much easier to change, adjust and troubleshoot your application.
Make the configuration documentation available to engineers and technicians, on all shifts, who may need to work with the Series 988LF. We provide space in this manual to record configurations. You may prefer to
photocopy the blank forms and keep them in a separate binder. However,
you maintain your documentation; be sure to replace all old copies of the
documentation with updated versions whenever the controller configuration is changed.
NOTE:
The Menu Overview
in the Appendix
shows all of the
menus and
prompts.
NOTE:
The 12-digit number
is printed on the top
of the stickers on
each side of the
controller’s case
and on the righthand or top circuit
board.
Introduction
WATLOW Series 988LF User’s Manualiii
Introduction
Notes, Cautions and Warnings
We use note, caution and warning symbols throughout this book to draw
your attention to important operational and safety information.
A bold text “NOTE” marks a short message in the margin to alert you to
an important detail.
A bold text “CAUTION” safety alert appears with information that is
important for protecting your equipment and performance. Be especially
careful to read and follow all cautions that apply to your application.
A bold text “WARNING” safety alert appears with information that is
important for protecting you, others and equipment from damage. Pay
very close attention to all warnings that apply to your application.
The ç symbol (an exclamation point in a triangle) precedes a general
CAUTION or WARNING statement.
The Ó symbol (a lightening bolt in a triangle) precedes an electric shock
hazard CAUTION or WARNING safety statement.
Technical Assistance
If you encounter a problem with your Watlow controller, review all of your
configuration information for each step of the setup to verify that your
selections are consistent with your applications.
If the problem persists, an Application Engineer can discuss your application with you.
Before calling, please have the complete model number and user’s manual
available. You can get technical support by dialing 507/494-5656, 7 a.m.
to 7 p.m. Central Standard Time, or e-mail to wintechsupport@watlow.com.
The Watlow Series 988LF has at least one and as many as three dual inline package (DIP) switches inside the controller, depending on the model
number. They allow users to configure the controller for a variety of
input sensors, or to lockout front panel access to some functions.
To set any DIP switch:
• Remove the controller from the case by pressing firmly on the two
release tabs on one side or the top of the bezel until they unsnap. Then
firmly press the two release tabs on the opposite side or the bottom of
the control until they unsnap. You will need to gently rock the bezel
back and forth to release it from the chassis.
• Use the illustrations on the following pages to locate and set each DIP
switch.
Figure 1.1 - Press
the release tabs to
remove the controller chassis.
Release
Tabs
PROCESS
L1 L2
DEV
% OUT
SERIES 988LF
W
A
TL
DISPLAY
AUTO
MODE
MAN
W
Release
Tabs
Release
Tabs
W
A
TL
W
MODE
DSPY
PROCESS
AUTO
DEV
% OUT
L1 L2
MAN
SERIES 989LF
Release
Tabs
1.2WATLOW Series 988LF User’s Manual
Hardware Setup, Chapter 1
DIP Switches
Figure 1.2 Input DIP switches.
Input 1Input 2
(Remote Set Point)
(98_L-2___-AA__)(98_L-_2__-AA__)
RTD
thermocouple: R, S or B
thermocouple: J, K, T, N, E, C, D, Pt2
or 0-50mV (high impedance)
0-20 or 4-20mA; 0-5, 1-5 or 0-10V
❶ Set the input DIP
switches to match the sen-
sors you are using in your
application. Only controllers with model number 98_L-2___-AA__ or
98_L-_2__-AA__ have an
input DIP switch.
NOTE:
The Input 2 DIP
switch is mounted
upside down.
NOTE:
Only controllers
with the indicated
model numbers
have these DIP
switches.
Input 2 DIP
ON
Input 1 DIP
ON
Controller Chassis
Rear View
123
O
N
↑
123
O
N
↑
↑
N
O
123
↑
N
O
123
123
O
N
↑
123
O
N
↑
↑
N
O
123
↑
N
O
123
WATLOW Series 988LF User’s Manual1.3
Hardware Setup, Chapter 1
DIP Switches
Figure 1.3 Lockout DIP switch.
no hardware lockoutor
(Switch 1 has no effect.)
lockout Setup and Factory menusor
(Switch 1 has no effect.)
Control Chassis
Top View (986LF & 988LF)
Left-side View (987LF & 989LF)
Lockout
DIP
ON
OFF
❷ The lockout DIP switch
hides the Setup Menu and the
Factory Menus (Diagnostics
and Calibration). All units
have a lockout DIP switch.
ç
CAUTION:
The lockout DIP
switch makes the
Setup and Factory
menus unavailable.
Configure all the
Setup and Factory
menus before locking them out.
Failure to do so
could result in damage to equipment in
the event of a setup
error.
12
O
N
↑
12
O
N
↑
12
O
N
↑
12
O
N
↑
1.4WATLOW Series 988LF User’s Manual
Hardware Setup, Chapter 1
Notes
WATLOW Series 988LF User’s Manual2.1
Installation and Wiring, Chapter 2
Chapter 2Installation and Wiring
Figure 2.1 Series 988LF and
Series 989LF
dimensions.
NOTE:
Adjustable mounting brackets can be
side-mounted.
NOTE:
Space panel
cutouts at least 1.66
inches (42.2mm)
apart.
NOTE:
Holes can be cut in
the panel using a
Greenlee 1/8 DIN
Hydraulic Kit
#60068 (punch
#60069, die #60070).
W
A
TL
PROCESS
L1 L2
DEV
% OUT
SERIES 988LF
(55 mm)
W
2.18"
DISPLAY
AUTO
MAN
MODE
4.03"
(102mm)
W
PROCESS
L1 L2
4.03"
(102mm)
W
A
TL
DSPY
DEV
% OUT
MODE
AUTO
MAN
SERIES 989LF
2.18"
(55 mm)
Panel Cutout
Maximum Panel
Thickness
0.38" (9.65mm)
3.62" + 0.03 -0.00
(92mm + 0.8)
1.77 + 0.02 -0.00
(45mm + 0.6)
0.68"
(17 mm)
Panel
4.06"
(103 mm)
Adjustable
Mounting Bracket
2.2WATLOW Series 988LF User’s Manual
Installation and Wiring, Chapter 2
Installation
Installing the Series 988LF
Installing and mounting requires access to the back of the panel.
1. Make a panel cutout.
2. To remove the controller chassis from its case, press in firmly on the two
tabs on one side or the top of the bezel until they unsnap, then unsnap
the two tabs on the opposite side or the bottom. Pull the chassis out of
the case by gently rocking it.
3. Slide the case into the panel cutout. Check to see that the gasket is
not twisted, and is seated within the case bezel flush with the panel.
Slide the mounting collar over the back of the control.
Panel
Adjustable
Mounting Bracket
Bezel
External Gasket
Mounting Collar
Release Tabs
Top and Bottom (986LF or 988LF)
or Side (987LF or 989LF) View
Mounting Slots
Side (986LF or 988LF)
or Top and Bottom (987LF or 989LF) View
4. Loosen the mounting bracket screws enough to allow for the mounting
collar and panel thickness. Place each mounting bracket into the
mounting slots (head of the screw facing the back of the controller).
Push each bracket backward then down to secure it to the control
case. To guarantee a proper NEMA 4X seal, Series 986LF and
988LF units (vertical) must have the mounting brackets located on
either side of the unit. When installing Series 987LF and 989LF
units (horizontal) the brackets must be on the top and bottom of
the unit.
5. Make sure the case is seated properly. Tighten the installation screws
firmly against the mounting collar to secure the unit. To ensure a
NEMA 4X seal, there should be no space between the bezel and
panel. Overtightening the screws will distort the case and make it dif-
ficult to remove or replace the controller.
6. Insert the controller chassis into its case and press the bezel until all
four tabs snap. Make sure the inside gasket is seated properly and
not twisted.
7. To release the mounting brackets, loosen the mounting bracket screws
and push the brackets forward, then pull it up and out.
NOTE:
Removing the controller chassis from
its case makes
mounting easier.
Figure 2.2 Side and top view.
ç
CAUTION:
Follow the installation procedure
exactly to guarantee
a proper NEMA 4X
seal. Make sure the
gasket between the
panel and the rim of
the case is not
twisted and is seated properly. Failure
to do so could
result in damage to
equipment.
WATLOW Series 988LF User’s Manual2.3
Installation and Wiring, Chapter 2
Wiring
Wiring the Series 988LF
Wiring options depend on the model number and DIP switch settings.
Check the terminal designation stickers on either side of the controller
and compare your model number to those shown here and with the model
number breakdown on the inside back cover of this manual.
Input-to-output Isolation
The Series 988LF uses optical isolation between the analog inputs and the
controller outputs. This isolation provides a 500V~ (ac) barrier to prevent
ground loops when using grounded sensors and/or peripheral equipment.
Here is a breakdown of the isolation barriers:
• Analog inputs 1 and 2 are grouped together.
• Outputs 1 and 2 are grouped together.
Power Wiring
100 to 240 V~ (ac), nominal (85 to 264 actual)
Vertical Package 98 8
L - _ _ _ _ - A A _ _
Horizontal Package98 9 L - _ _ _ _ - A A _ _
24 to 28 V‡‡(ac/dc), nominal (20 to 30 actual)
Vertical Package98 6
L - _ _ _ _ - A A _ _
Horizontal Package98 7 L - _ _ _ _ - A A _ _
Sensor Installation Guidelines
Thermocouple input: Extension wire for thermocouples must be of the
same alloy as the thermocouple itself to limit errors.
Using grounded thermocouples for both input 1 and remote set point
option may create ground loop problems. To correct this problem, replace
at least one of the grounded thermocouples with an ungrounded thermocouple. If the application requires grounded thermocouples, use an isolated transmitter, such as a Watlow Gordon 5702 isolated transmitter.
RTD input: Each 1Ω of lead wire resistance can cause a +2°F error when
using a two-wire RTD. A three-wire RTD sensor overcomes this problem.
All three wires must have the same electrical resistance (i.e., same gauge,
same length, multi-stranded or solid, same metal).
Process input: Maintain isolation between input 1 and input 2 to prevent
a ground loop. A ground loop may cause incorrect readings, dashes
across the upper display or the display of error codes.
fuse
22
21
earth ground
11
L2L1
+
-
∫
WARNING:
To avoid potential
electric shock, use
National Electric
Code (NEC) safety
practices when
wiring and connecting this unit to a
power source and
to electrical sensors
or peripheral
devices. Failure to
do so could result
in injury or death.
Figure 2.3 Power wiring.
ç
CAUTION:
The Series 988LF
will not function
with two grounded
thermocouple
inputs. Avoid using
a grounded thermocouple for both
input 1 and input 2.
Failure to follow this
guideline could
result in damage to
equipment.
Wiring 0-20 and 4-20mA Process Inputs
Certain “transmitters” used in process input applications are producing
internal resistor failures in the Watlow Series 988 family of controllers.
This is only apparent with the Series 988 family 1/8 DIN units with
Process Inputs selected (0-20mA or 4-20mA dc only).
We are noticing that an external resistor is required to prevent a high
in-rush current which burns out the Series 988 family controllers’ 7-ohm
internal resistor. This high in-rush current occurs initially on “power-up.”
If the transmitter turns full on for a split second during power-up, the
available current weakens or damages the internal resistor.
Example: 20V / 7 ohms = 2,857mA (too much!).
The wiring diagram example below shows an application where a customer
is using a 4-20mA dc transmitter and power supply to feed the input of a
Series 988 controller. The Rx range (100 to 400 ohms) for the external
resistor is recommended. We suggest starting with 250 ohms.
Example: Customer is using a 24VÎ (dc) power supply to power up the
4-20mA dc transmitter that inputs to the Series 988 terminals 8 (-) and 10
(+). To figure out what the internal Series 988’s handling current is for the
0-20mA or 4-20mA dc input to the Series 988 controllers, we need to
apply Ohm’s Law: The square root of Watts divided by Resistance equals
Current. Applying that formula to the example below produces the following: Square Root of (0.125 Watts / 7 ohms) = 134 mA dc (handling input
current). This is the acceptable input current for the Series 988 universal
input board.
Reminder, the input impedance of 7 ohms handles the majority of our
customer applications; the external resistor (Rx) is only for certain transducers/transmitters that spike on power-up or power-down. Please make
sure your customer’s transmitter / transducer fall within our Series 988
family (1/8 DIN) of controllers’ Process Input specification of 7 ohms input
impedance.
Figure 2.4 Process wiring
example.
2.4WATLOW Series 988LF User’s Manual
Wiring
988 Process
Input Control
4-20mA dc
Internal
Resistor
7Ω
1/8 Watt
+
—
R
100 to 400
ohms
x
Transmitter
—
+
+
24VÎ (dc)
Power Supply
—
WATLOW Series 988LF User’s Manual2.5
Installation and Wiring, Chapter 2
Wiring Example
Figure 2.5 System wiring
example.
∫
WARNING:
To avoid potential
electric shock, use
National Electric
Code (NEC) safety
practices when
wiring and connecting this unit to a
power source and
to electrical sensors or peripheral
devices. Failure to
do so could result
in injury or death.
ç
WARNING:
Install high or low
temperature limit
control protection
in systems where
an over temperature fault condition
could present a fire
hazard or other hazard. Failure to
install temperature
limit control protection where a potential hazard exists
could result in damage to equipment,
property and injury
to personnel.
ç
WARNING:
To avoid damage to
property and equipment, and/or injury
of loss of life, use
National Electric
Code (NEC) standard wiring practices to install and
operate the Series
988LF. Failure to do
so could result in
such damage,
and/or injury or
death.
L1
120 VÅ (ac)
L2
earth ground
(+)
9
10
(-)
red
120VÅ (ac)
1
2
3
4
5
6
7
8
9
10
11
12
13
high limit
mechanical
fuse
11
2221
(+)
12
(-)
13
988L-10CA-AARR
rear view
L1
1
1
12
1
process sensorlimit sensor
3
4
(+)
5
(-)
1 CR-1
8
11
17
coil
contactor
31
+
SSR-240-10A-DC1
solid state relay
-
2122
9
10
910
12
13
(+)
14
(-)
15
Series 988LF
988L-10CA-AARR
Temperature Control
12 +13 -
3
3-32VÎ (dc)
(+)
12
48-260VÅ (ac)
13
13
146D-1J1F-1100
14
Temperature Limit
10
11
5
heater
in
out
Series 146
24
4
SSR-240-10A-DC1
Solid State Relay
(-)
7
9
high temperature light
fuse
11
heater
R
18
fuse
C NO NC
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17
(+)
(-)
normally open
momentary switch
1CR
16
optional
high
temp limit
light
Series 146
limit control
146D-1J1F-1100
L2
2
2
2
2
Wiring Notes
ç
WARNING:
To avoid damage to
property and equipment, and/or injury
of loss of life, use
National Electric
Code (NEC) standard wiring practices to install and
operate the Series
988LF. Failure to do
so could result in
such damage,
and/or injury or
death.
Figure 2.6 Wiring notes.
NOTE:
Sketch in your application on this page or
a copy of it. See
wiring examples in
this chapter and in
the Appendix.
2.6WATLOW Series 988LF User’s Manual
Installation and Wiring, Chapter 2
L1L2
earth ground
11
2122
power
WATLOW Series 988LF User’s Manual2.7
Installation and Wiring, Chapter 2
Figure
2.7c — 0-5V
ÎÎ
, 1-5VÎÎor 0-10VÎÎ(dc) Process
Universal signal conditioner
98 _ L - 2 _ _ _ - A A _ _
Input impedance: 10KΩ
Figure 2.7a — Thermocouple or 0-50mV (high impedance)
Thermocouple only
98 _ L - 1 _ _ _ - A A _ _ (no DIP switches)
Universal signal conditioner
98 _ L - 2 _ _ _ - A A _ _
Input impedance: 20MΩ
Figure 2.7
b — RTD (2 or 3 Wire) 100Ω
Universal signal conditioner
98 _ L - 2 _ _ _ - A A _ _
9
10
+
-
0-50mV
Figure 2.7d — 0-20mA or 4-20mA Process
Universal signal conditioner
98 _ L - 2 _ _ _ - A A _ _
Input impedance: 7Ω
DIP Switch
Setting
R, S, B
DIP Settings
J, K, T, N, C, E, D, Pt2,
0-50mV DIP Settings
DIP Switch
Setting
DIP Switch
Setting
NOTE:
Successful installation requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch settings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).
Jumper
#9 to #10
for 2 wire
RTD
Input 1 Wiring
ç
CAUTION:
An external resistor
is required for
0-20mA and 4-20mA
process wiring to
prevent a high inrush current which
could burn out the
controller’s 7-ohm
resistor. See page
2.4 for recommendations.
123
O
N
↑
123
O
N
↑
S1
S2
O
N
↑
8
9
10
123
+
9
-
10
8
S1
9
S2
10
S3
123
O
N
↑
123
O
N
↑
9-+
10
-
8
10
+
2.8WATLOW Series 988LF User’s Manual
Installation and Wiring, Chapter 2
Figure 2.8d —
0-20mA or 4-20mA Process
Universal signal conditioner
98 _ L - _ 2 _ _ - A A _ _
Input impedance: 7Ω
Remote Set Point Option
Figure 2.8c —
0-5VÎÎ, 1-5VÎÎor 0-10VÎÎ(dc) Process
Universal signal conditioner
98 _ L - _ 2 _ _ - A A _ _
Input impedance: 10KΩ
Remote Set Point Option
Figure 2.8b — RTD (2 or 3 Wire) 100Ω
Universal signal conditioner
98 _ L - _ 2 _ _ - A A _ _
Remote Set Point Option
20
19-+
Figure 2.8a —
Thermocouple or 0-50mV (high impedance)
Universal signal conditioner
98 _ L - _ 2 _ _ - A A _ _
Input impedance: 20MΩ
Remote Set Point Option
Jumper
#19 to #20
for 2 wire
RTD
19
20
18
S2
S1
DIP Switch
Setting
R, S, B
DIP Settings
J, K, T, N, C, E, D, Pt2,
0-50mV DIP Settings
DIP Switch
Setting
19
20
18S2S1
S3
DIP Switch
Setting
NOTE:
Successful installation requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch settings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).
Input 2 Wiring
ç
CAUTION:
An external resistor
is required for
0-20mA and 4-20mA
process wiring to
prevent a high inrush current which
could burn out the
controller’s 7-ohm
resistor. See page
2.4 for recommendations.
↑
N
O
123
↑
N
O
123
↑
N
O
123
19
+
-
20
0-50mV
19
+
-
20
↑
N
O
123
↑
N
O
123
-
18
20
+
WATLOW Series 988LF User’s Manual2.9
Installation and Wiring, Chapter 2
Figure 2.9a — AC Outputs
Solid-state Relay with Contact Suppression
98 _ L - _ _ B _ - A A _ _
0.5 amps, minimum off-state impedance: 20KΩ
Electromechanical Relay with Contact Suppression
(NO and COM contacts only)
98 _ L - _ _ D _ - A A _ _
Form C, 5 amps, minimum off-state impedance: 20KΩ
Electromechanical Relay without Contact Suppression
98 _ L - _ _ E _ - A A _ _
Form C, 5 amps off-state impedance: 31MΩ
Solid-state Relay without Contact Suppression
98 _ L - _ _ K _ - A A _ _
0.5 amps, off-state impedance: 31MΩ
Output 1 Wiring
Figure 2.9b — Switched DC, Open Collector
98 _ L - _ _ C _ - A A _ _
Minimum load resistance: 500Ω
Figure 2.9d — 0-5V
ÎÎ
, 1-5VÎÎand 0-10VÎÎ(dc) Process
98 _ L - _ _ F _ - A A _ _
Minimum load impedance: 1KΩ
Figure 2.9c — 0-20mA and 4-20mA Process
98 _ L - _ _ F _ - A A _ _
Maximum load impedance: 800Ω
14
-
+
12
14
-
+
13
NOTE:
Successful installation requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch settings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).
External
Load
NO
12
13
COM
14
NC
(#14 for D & E outputs only)
Fuse
L2
L1
19 to 32VÎ (VDC)
+ VDC
790Ω
Internal Circuitry
12
13
14
12
+
External
-
13
14
Load
COM
Figure 2.10a — AC Outputs
Solid-state Relay with Contact Suppression
98 _ L - _ _ _ B
- A A _ _
0.5 amps, minimum off-state impedance: 20KΩ
Electromechanical Relay with Contact Suppression
(NO and COM contacts only)
98 _ L - _ _ _ D - A A _ _
Form C, 5 amps, minimum off-state impedance: 20KΩ
Electromechanical Relay without Contact Suppression
98 _ L - _ _ _ E - A A _ _
Form C, 5 amps off-state impedance: 31MΩ
Solid-state Relay without Contact Suppression
98 _ L - _ _ _ K - A A _ _
0.5 amps, off-state impedance: 31MΩ
2.10WATLOW Series 988LF User’s Manual
Installation and Wiring, Chapter 2
Figure 2.10b —
Switched DC, Open Collector
98 _ L - _ _ _ C - A A _ _
Minimum load resistance: 500Ω
NOTE:
Successful installation requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch settings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).
Output 2 Wiring
19 to 32VÎ (VDC)
+ VDC
Internal Circuitry
790Ω
15
16
17
External
NO
COM
NC
COM
Load
Fuse
+
-
15
16
17
(#17 for D & E outputs only)
15
16
17
External
Load
L2
L1
WATLOW Series 988LF User’s Manual3.1
Front Panel and Display Loop, Chapter 3
Upper Display
Indicates the actual process value,
prompt parameter value or error
code.
DEV LED
When lit, the lower display shows
the current deviation from the set
point.
% OUT LED
When lit, the lower display shows
the current percent output.
Up-arrow Key
Increases the value or changes the
parameter in the upper display
(except for set point changes in the
Display Loop, which occur in the
lower display). Hold the key down
to increase the value rapidly. New
data takes effect in five seconds or
when the Mode key or Display key
is pressed.
Up + Down Keys
Press simultaneously for three seconds to go to the Setup Menu.
Continue to press both keys for
another three seconds to go to the
Factory Menu. Access to the Setup
and Factory menus can be disabled with lockout DIP switch.
Lower Display
Indicates the set point, deviation,
percent power, temperature unit,
menu prompt name or alarm code.
L1, L2
These LED’s indicate when output
1 or 2 are active. Outputs can be
configured as:
Ot1Control
Ot2Control or Alarm
Display Key
Pressing this key enters the
Display Loop. Press the Display
key at any time to return to this
loop. The next page has more
information on the Display Loop.
Auto/Man Key
In Manual mode the lower display
shows percent output. Pressed
once, it clears a latched alarms. If
pressed again within five seconds
it will toggle between Auto and
Manual mode.
Auto/Man LED
Lit when the control is in Manual
operation. Press the Auto/Man key
twice to enter Automatic operation.
When blinking, press the Auto/Man
key to toggle between Auto and
Manual. After five seconds without
pressing the Auto/Man key, the
LED stops blinking and returns to
its previous state.
Mode Key
Enters new data and steps to
the next prompt in the current
menu.
Mode + Up-arrow Keys
Hold the Mode key then press
the Up-arrow key to move
backwards through the current menu. Scrolling stops
when you reach the top of the
menu.
Figure 3.1 Series 988LF Keys and Displays
Down-arrow Key
Decreases the value or changes
the parameter in the upper display
(except for set point changes in the
Display Loop, which occur in the
lower display). Hold the key down
to decrease the value rapidly. New
data takes effect in five seconds or
when the Mode key or Display key
is pressed.
Chapter 3Front Panel and Display Loop
Keys and Displays
W
TL
W
A
PROCESS
L1L2
DEV
% OUT
DISPLAY
AUTO
MAN
MODE
SERIES 988LF
3.2WATLOW Series 988LF User’s Manual
Front Panel and Display Loop, Chapter 3
Display Loop
Display Loop
The Display Loop is the “home” state of the Series 988LF controller. Pressing the
Display key ∂ returns the controller to the Display Loop from any prompt in any
menu. The controller automatically returns to the Display Loop from any menu
when a minute passes without any keys being pressed.
Figure 3.2 The Display Loop
NOTE:
For information on
input 1 [`In1]
ranges, refer to
Chapter 4.
DISPLAY
DISPLAY
DISPLAY
DISPLAY
[`988]
[`988]
[`988]
[`988]
[`988]
[`100]
[`988]
[``°C]
current input 1 reading
set point 1 (change with Up-arrow > or Down-arrow < key)
current input 1 reading
deviation from set point, process 1 minus set point 1 (DEV light on)
current input 1 reading
percent output (%OUT light on)
current input 1 reading
units selected (units, °F or °C)
Chapter 4The Setup Menu
TL
Navigating the Setup Menu
The Setup Menu displays the parameters that configure the Series 988LF’s
features to your application.
W
TL
W
[```0]
[`LOC]
[```1]
[`LOC]
[```2]
[`LOC]
❷ Press the Up-arrow > or the
Down-arrow < key to select one
of the prompt values
Figure 4.1 The Setup Menu
[```3]
[`LOC]
L1 L2
DEV
% OUT
SERIES 988LF
A
PROCESS
DISPLAY
AUTO
MAN
MODE
❶ To enter the Setup Menu, press the Up-arrow >
and Down-arrow < keys for three seconds. The
lower display shows the LOC [`LOC] prompt, and the
upper displays shows its current level. All keys are
inactive until you release both keys.
[`LOC]
MODE
[`In1]
MODE
[`rL1]
MODE
[`rH1]
MODE
[`rtd]
MODE
[`dEC]
MODE
[`rSp]
MODE
[`rL2]
MODE
[`rH2]
MODE
[`C_F]
MODE
[`Ot1]
MODE
[Prc1]
MODE
[`Ot2]
MODE
[`ALt]
MODE
[`Lat]
MODE
[`SIL]
Lock
Input 1
Range Low 1
Range High 1
RTD Calibration Curve
Decimal
Remote Set Point
Range Low 2
Range High 2
C or F
Output 1
Process 1
Output 2
Alarm Type
Latching
Silencing
Setup
Enter your settings,
from the controller's
upper display.
Setup Menu, Chapter 4WATLOW Series 988LF Users Manual4.1
Setup
Setup Prompts
NOTE:
Decimal points may not
always be in the
position specified
depending on the
settings in the Decimal
[`dEC] parameters in
the Setup Menu.
❸ Use the Mode key µ to advance through the
Setup Menu. You will not see every prompt in the
Setup menu; the unit’s configuration and model
number determine which prompts appear.
L1 L2
DEV
% OUT
SERIES 988LF
W
A
PROCESS
TL
DISPLAY
AUTO
MAN
MODE
W
❹ Use the Up-arrow > and Down-arrow < keys
to change the prompt setting. To move backwards
through the menu hold the Mode key µ down
and press the Up-arrow key >. Refer to the
Appendix for model number options.
L1 L2
DEV
% OUT
SERIES 988LF
W
A
PROCESS
TL
DISPLAY
AUTO
MAN
MODE
W
[`LOC]
ç
Caution:
Setting [`LOC] to
[```2] or [```3]
disables the Auto/Man
å and will force
key
the controller into
manual mode if an open
sensor occurs. Verify
that the controller is
operating in the desired
mode (auto or manual)
before setting the
lockout level. Failure to
do so could result in
damage to equipment
and/or property.
Front Panel Lockout
Sets the lockout level for the front panel. This allows you to disable
keys on the front of the controller.
• [```0] enables all keys.
• [```1] disables the Mode key µ.
• [```2] disables the Mode key µ and the Auto/Man key å.
• [```3] disables all keys.
[`LOC] This prompt always appears.
Default
↓
[```O][```1][```2][```3]
[`LOC][`LOC][`LOC][`LOC]
4.2WATLOW Series 988LF Users ManualSetup Menu, Chapter 4
Setup
[`In1]
ç
Caution:
Changing the value of
[`In1] changes most
other prompts to the
factory default values.
Verify the correct
sensor type before
making a change.
Failure to follow this
guideline could result in
damage to equipment or
property.
Input 1
Select sensor input type. This selection must match the sensor type
connected to terminals 8, 9 and 10. See Appendix for more information
about sensors.
• Changing the value of [`In1] changes all other prompts to the
factory default values, [`LOC] Lock prompt and the [`C_F] prompt
in the Setup Menu. If you change the value, the default warning
[[
[dFLt] will flash in the upper display.
[[
• Changes do not take effect automatically after five seconds; you must
press the Mode key µ to enter the selector type change and advance to
the next prompt.
Setup Menu, Chapter 4WATLOW Series 988LF Users Manual4.3
Setup
[`rL1]
[`rH1]
NOTE:
These values do not
affect the low or the high
set point limit for
process alarms.
Range Low and Range High
Select the low and high range for input 1. These prompts limit the
adjustment range for the set points. The default values are the same as
the limits of the sensor you selected by setting the input DIP switch and
selecting a value for Input [`In1].
• Process inputs are scaled by these values. Range high is the value
displayed when the maximum process signal is present at the input.
Range low is the value displayed when the minimum process signal is
present at the input.
Example:Set [`In1] to [4-20] mA.
Set [`rL1] to [`100].
Set [`rH1] to [`500].
A 4mA input will display [`100].
A 12mA input will display [`300].
A 20mA input will display [`500].
• The low and high values of each sensor type are listed on the specifications page of the Appendix.
• Choose between Fahrenheit and Celsius at the [`C_F] prompt in the
Setup Menu.
NOTE:
When high impedance
[`0-50] is selected for
Input 1, the range high
for both [``°C] and
[``°F] can be extended
to [9999]. The range
low, when [``°C] is
selected, can be extended to [-999]
[`rL1]
[`rH1]
Range Low and Range
High continued on next
page.
[`rL1][`rH1] These prompts always appear.
DefaultDefault DefaultDefault
↓↓↓↓
``°F][`°C]
[`rL1] [`rH1][`rL1] [`rH1]
[```J][``32]…[1500][```0]…`816]98_L-1__-AA__ or
[`in2][`rL1] [`rH1][`rL1] [`rH1]98_L-2__-AA__
(K)
[```H][-328]…[2500][-200]…[1371]
[```t][-328]…[`750][-200]…[`399]
[```n]``32]…[2372][```0]…[1300]
[```E][-328]…[1470][-200]…[`799]
(W5)
[```C][``32]…[4200][```0]]]…[2316]
(W3)
[```d][``32]…[4200][```0]]]…[2316]
[`Pt2][``32]…[2543[```0]]…[1395]
high impedance
[0-50][-999]…[[`999][-573]…[`573]
[```r][``32]…[3200][```0]]…[1760]98_L-2__-AA__ only
[```S][``32]…[3200][```0]…[1760]
4.4WATLOW Series 988LF Users ManualSetup Menu, Chapter 4
Setup
[`rL1]
[`rH1]
Range Low and Range
High continued from
previous page.
NOTE:
The range high [`rH1]
value for process
inputs can be extended
to [9999].
DefaultDefault DefaultDefault
↓↓↓↓
``°F][`°C]
[`rL1] [`rH1][`rL1] [`rH1]
[```b][``32]…[3300][```0]…[1816]
[`rtd][-328]…[1472][-200]…[`800]
[`r†d][-9(9]…[99(9][-7#3]…[53&7]
process
[4-20][-999]…[`999]units
[0-20][-999]…[`999]units
[`0-5][-999]…[`999]units
[`1-5][-999]…[`999]units
[0-10][-999]…[`999]units
[0-50][-999]…[`999]units
[`rtd]
RTD Calibration Curve
Select the RTD calibration curve. The RTD input uses either the
European (DIN, 0.003850 ohms/ohms/°C) or Japanese (JIS, 0.003916
ohms/ohms/°C) linearization standard.
[`rtd] This prompt appears only if you have set [`In1] to [`rtd] or
[`r†d].
Default
↓
[`din] [`J15]
[`rtd[`rtd
Setup Menu, Chapter 4WATLOW Series 988LF Users Manual4.5
Setup
[`dEC]
[`rSP]
Decimal
Select the decimal point location for process type input 1 data. This
prompt, in conjunction with the Range Low and Range High prompts,
allows you to format and limit units of measure for process 1.
• All prompts with units of measure related to input 1 will display in the
selected decimal format.
• This affects propbands, alarm set points, process set points, calibration
offsets, deadbands and ranges.
[`dEC] This prompt appears only if you have set input 1 [`In1] to a
process input or a thermocouple input set to [0-50] mV.
Default
↓
[```)] [``)0] [`)00} [)000]
[`dEC][`dEC][`dEC][`dEC]
Remote Set Point Input
[`rSP]
Remote Set Point Input
continued on next page.
Enable a remote set point signal. The remote set point input selection
switches are set to process at the factory.
[`rSP] This prompt appears only on controllers equipped with Remote Set
Point Input hardware (98 _ L-_ 2__-AA__).
Select the low and high range for Remote Set Point Input. These
prompts limit the adjustment range for the set points. The default values
are the same as the limits of the sensor you selected by setting the input 2
DIP switch and selecting a value for Input 2 [`In2].
[`rL2]
[`rH2]
Range Low 2 and Range
High 2 continued on next
page.
[`rL2] [`rH2] These prompts appear only on controllers equipped with
Remote Set Point Input hardware (98 _ L-_ 2__-AA__).
• Process inputs are scaled by these values. Range high is the value
displayed when the maximum process signal is present at the input.
Range low is the value displayed when the minimum process signal is
present at the input.
Example:Set [`rSP] to [4-20]mA.
Set [`rL2] to [`100].
Set [`rH2] to [`500].
A 4mA input will display [`100].
A 12mA input will display [`300].
A 20mA input will display [`500].
• The low and high values of each sensor type are listed on the specifications page of the Appendix.
• Choose between Fahrenheit and Celsius at the [`C_F] prompt in the
Setup Menu.
[`rL2][`rH2] These prompts appear only if the controller is equipped
with Remote Set Point Input hardware and with Remote Set Point Input
[`rSP] not set to [`OFF].
DefaultDefaultDefaultDefault
↓↓↓↓
``°F][`°C]
[`rL2] [`rH2][`rL2] [`rH2]
[```J][``32]…[1500][```0]…`816]98_L-1__-AA__ or
[`in2][`rL2] [`rH2][`rL2] [`rH2]98_L-2__-AA__
Setup Menu, Chapter 4WATLOW Series 988LF Users Manual4.7
Setup
[`rL2]
[`rH2]
Range Low 2 and Range
High 2 continued from
previous page.
NOTE:
These values do not
affect the low or the high
set point limit for
process alarms.
NOTE:
When high impedance
[`0-50] is selected for
Input 1, the range high
for both [``°C] and
[``°F] can be extended
to [9999]. The range
low, when [``°C] is
selected, can be
extended to [-999]
DefaultDefaultDefault
↓↓↓↓
(K)``°F][`°C]
[```H][-328]…[2500][-200]…[1371]
[```t][-328]…[`750][-200]…[`399]
[```n]``32]…[2372][```0]…[1300]
[```E][-328]…[1470][-200]…[`799]
(W5)
[```C][``32]…[4200][```0]]]…[2316]
(W3)
[```d][``32]…[4200][```0]]]…[2316]
[`Pt2][``32]…[2543[```0]]…[1395]
high impedance
[0-50][-999]…[[`999][-573]…[`573]
[```r][``32]…[3200][```0]]…[1760]98_L-2__-AA__ only
[```S][``32]…[3200][```0]…[1760]
[```b][``32]…[3300][```0]…[1816]
[`rtd][-328]…[1472][-200]…[`800]
NOTE:
The range high [`rH2]
value for process
inputs can be extended
to [9999].
[`C_F]
[`r†d][-9(9]…[99(9][-7#3]…[53&7]
process
[4-20][-999]…[`999]units
[0-20][-999]…[`999]units
[`0-5][-999]…[`999]units
[`1-5][-999]…[`999]units
[0-10][-999]…[`999]units
[0-50][-999]…[`999]units
[0=00][-999]…[`999]units
Celsius-Fahrenheit
Select which temperature scale the controller will use.
[`C_F] This prompt appears only on controllers with either Input 1 set
to something other than a process input.
Default
↓
[``°f] [``°C]
4.8WATLOW Series 988LF Users ManualSetup Menu, Chapter 4
[`C_F][`C_F]
Setup
[`Ot1]
[Prc1]
Output 1
Set the way that output 1 will respond to a difference between the set
point and an input variable.
• [``Ht](Heat) select reverse action, so that output 1 responds when the
input signal is less than the setpoint.
• [``CL](Cool) select direct action, so that output 1 responds when the
input signal is more than the setpoint.
[`Ot1] This prompt always appears.
Default
↓
[``Ht] [``CL]
[`Ot1][`Ot1]
Process 1
Select the process range for output 1.
• [Prc1] This prompt appears only on controllers equipped with output 1
process hardware (98__-__F_-___).
[`Ot2]
Default
↓
4-20mA0-20mA0-5VÎ1-5VÎ 0-10VÎ (dc)
[4-20] [0-20][`0-5][`1-5] [0-10]
[Prc1][Prc1][Prc1][Prc1][Prc1]
Output 2
Selects the secondary output action
• [``AL] de-energizes output 2 in an alarm condition.
• [`ALn] energizes output 2 in an alarm condition.
• [``Ht](Heat) selects reverse action, so that output 2 responds when the
input signal is less than the set point.
• [``CL](Cool) selects direct action, so that output 2 responds when the
input signal is more than the set point.
[`Ot2] This prompt appears only on controllers equipped with output 2
hardware (not 98_L-___A-AA__).
Default
↓
[``no] [``AL][`Aln][``Ht] [``CL]
[`Ot2][`Ot2][`Ot2][`Ot2][`Ot2]
Setup Menu, Chapter 4WATLOW Series 988LF Users Manual4.9
Setup
[`ALt]
[`LAt]
Alarm Type
Selects the alarm type when Output 2 has been selected as an alarm.
• [``Pr] uses the process signal from input 1.
• [``de] uses a deviation from the input 1 signal.
[`ALt This prompt appears only on controllers equipped with output 2
hardware (not 98_L-___A-AA__). and with [`Ot2] set to [``AL] or [`ALn].
Default
↓
[``Pr] [``de]
[`ALt][`ALt]
Latching
Select whether alarm for output 2 will be latching or non-latching. A
latching alarm [`LAt] must be turned off manually. A non-latching alarm
[`nLA] turns off when an alarm condition no longer exists.
[`SIL]
[`LAt] This prompt appears only on controllers equipped with output 2
hardware (not 98_L-___A-AA__) and with [`Ot2] set to [``AL] or [`ALn].
Default
↓
[`nLA] [`LAt]
[`LAt][`LAt]
Silencing
Select silencing to inhibit alarm for Output 2 on startup and to allow
the operator to reset the alarm output, not the visual display.
• Silencing disables the alarm until the signal is between [A2LO] and
[`AHI].
[`AL2] This prompt appears only on controllers equipped with output 2
hardware (not 98_L-___A-AA__) and with [`Ot2] set to [``AL] or [[`ALn].
Default
↓
[`OFF] [``On]
[[`SIL][[`SIL]
4.10WATLOW Series 988LF Users ManualSetup Menu, Chapter 4
Chapter 5The Operation Menu
TL
Navigating the Operation Menus
Operations
NOTE:
Press the Display Key
∂
to return to the
Display Loop from any
point in any menu.
❷ Use the Up-arrow > or the
Down-arrow < key to select one
of the prompt values.
Figure 5.1 Navigating the
Operations Menu.
PROCESS
L1 L2
DEV
% OUT
SERIES 988LF
W
TL
A
DISPLAY
AUTO
MAN
MODE
W
❶ To reach the Operation Menus, begin in the
Display Loop and press the Mode key µ.
Depending on the controller configuration, either the
Set Point 2 prompt [`SP2], or the Proportional
Band, Output 1 prompt [`Pb1] will appear in the
lower display. You will not see every prompt in the
Operation Menu; the unit’s configuration and model
number determine which prompts appear.
Enter your settings,
from the controller's
upper display.
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
[`SP2]
[`Pb1]
[`rE1]
[`rA1]
[`Ct1]
[`Pb2]
[`rE2]
[`rA2]
[`CT2]
[``dB]
[`ALO]
[`AHI]
[`CAL]
[`AUT]
[`L-r]
Set Point 2
Proportional Band 1
Reset 1
Rate 1
Cycle Time 1
Proportional Band 2
Reset 2
Rate 2
Cycle Time 2
Deadband
Alarm Lo
Alarm Hi
Calibration Offset
Auto-tune
Local-remote
Operations Menu, Chapter 5WATLOW Series 988LF Users Manual5.1
Operations
TLTL
W
W
A
PROCESS
L1 L2
DEV
% OUT
DISPLAY
SERIES 988LF
MODE
AUTO
MAN
NOTE:
Decimal points may not
always be in the
position specified below
depending on the
settings in the Decimal
dECdEC
dEC
parameters in the
dECdEC
Setup Menu.
Display Prompts
❸ Use the Mode key µ to advance through the Operations
Menu. You will not see every prompt in the Operations
menu; the unit’s configuration and model number determine
which prompts appear.
❹ Use the Up-arrow > and Down-arrow <
keys to change the prompt setting. To move
backwards through the menu hold the Mode
key µ down and press the Up-arrow key >.
Refer to the Appendix for model number
options.
L1 L2
DEV
% OUT
SERIES 988LF
W
PROCESS
TL
A
DISPLAY
AUTO
MAN
MODE
W
[`SP2]
[`Pb1]
Set Point 2
Select a second set point that will activate output 2. This allows you
to boost the heating (reverse acting) or cooling (direct acting) action of the
output 1 device.
• The range and default settings depend on the [`In1], [`rL1], and
[`rH1] settings (Setup Menu).
[`SP2] This prompt appears only if [`Ot1] and [`Ot2] (Setup Menu) areboth set to [`Ht] or [`CL].
[`rL1]…[`rH1]
[`SP2][`SP2]
Proportional Band, Output 1
Select the proportional band for PID output 1. If set to [```0] it
functions as an on/off control with a 3°F or 1.7°C switching differential for
ranges displayed in whole degrees, and 0.3°F or 0.17°C for ranges
displayed on 0.1°. The default is 25°F/17°C.
[`Pb1] This prompt always appears.
IfDefault
↓↓
[``°F][```0] … [``25] … [9999]
[`C_F][`Pb1][`Pb1][`Pb1]
(Setup Menu)
[`r†d][``)0][[``25][99(9]
Input 1[`Pb1][`Pb1][`Pb1]
(Setup Menu)
[``°C][```0] … [``14] … [9999]
[`C_F][`Pb1][`Pb1][`Pb1]
(Setup Menu)
[`r†d][``)0] … ``14] … [99(9]
Input 1[`Pb1][`Pb1][`Pb1]
Setup Menu)
5.2WATLOW Series 988LF Users ManualOperations Menu, Chapter 5
Operations
[`rE1]
[`rA1]
Reset, Output 1
Tune the control action to eliminate the offset or droop between the
set point and the actual process value for PID output 1.
[`rE1] This prompt appears only if [`Pb1] is set to greater than [```0].
Default
↓
[`0)0] … [99(9]repeats/min.
[`rE1][`rE1]
Rate, Output 1
Tune the rate to eliminate overshoot on startup or after the set point
changes for Output 1. The rate setting will not influence the percent
power if the process value is more than twice the proportional band from
the set point.
[`RA1] This prompt appears only if [`Pb1] is set to greater than [```0].
[`Ct1]
Default
↓
[`)00] … [`(99]min.
[`rA1][`rA1]
Cycle Time, Output 1
Select the time, in seconds, of a complete on/off cycle.
[`Ct1] This prompt appears only if [`Pb1] is set to greater than [```0].
This prompt does not appear if Output 1 is a process output.
IfDefault
↓↓
mechanical[``%0] … [`1)0] … [99(9] min.
relay[`Ct1][`Ct1][`Ct1]
outputs
open collector[brSt][``)1] … [``!0]… [99(9] min.
or solid-state[`Ct1][`Ct1][`Ct1][`Ct1]
relay outputs
Operations Menu, Chapter 5WATLOW Series 988LF Users Manual5.3
Operations
[`Pb2]
Proportional Band, Output 2
Select the proportional band for PID output 2. If set to [```0] it
functions as an on/off control. If set to [```0] it functions as an on/off
control with a 3°F or 1.7°C switching differential for ranges displayed in
whole degrees, and 0.3°F or 0.17°C for ranges displayed on 0.1°. The
default is 25°F/17°C.
[`Pb2] This prompt appears if Output 2 [`Ot2] (Setup Menu) is set to
[``Ht] or [``CL].
IfDefault
↓↓
[``°F][```0] … [``25] … [9999]
[`C_F][`Pb2][`Pb2][`Pb2]
(Setup Menu)
[`r†d][``)0][[``25][99(9]
Input 1[`Pb2][`Pb2][`Pb2]
(Setup Menu)
[``°C][```0] … [``17] … [9999]
[`C_F][`Pb2][`Pb2][`Pb2]
(Setup Menu)
[`r†d][``)0] … [``17] … [99(9]
Input 1[`Pb2][`Pb2][`Pb2]
(Setup Menu)
[`rE2]
[`rA2]
Reset, Output 2
Tune the control action to eliminate the offset or droop between the
set point and the actual process value for PID output 2.
[`rE2] This prompt appears only if [`Pb2] is set to greater than [```0].
Default
↓
[`0)0] … [99(9] repeats/min.
[`rE2][`rE2]
Rate, Output 2
Tune the rate to eliminate overshoot on startup or after the set point
changes for Output 2. The rate setting will not influence the percent
power if the process value is more than twice the proportional band from
the set point.
[`RA2] This prompt appears only if [`Pb2] is set to greater than [```0].
Default
↓
[`)00] … [`(99] min.
[`rA2][`rA2]
5.4WATLOW Series 988LF Users ManualOperations Menu, Chapter 5
Operations
[`Ct2]
[``db]
Cycle Time, Output 2
Select the time, in seconds, of a complete on/off cycle.
[`Ct2] This prompt appears if Output 2 [`Ot2] (Setup Menu) is set to
[``Ht] or [``CL], and if [`Pb2] is set to greater than [```0].
IfDefault
↓↓
mechanical[``%0] … [`1)0] … [99(9] min.
relay[`Ct2][`Ct2][`Ct2]
outputs
open collector[brSt][``)1] … [``!0] … [99(9] min.
or solid-state
relay outputs
[`Ct2][`Ct2][`Ct2][`Ct2]
Dead Band
Select the width of the zone between the action of the heating
(reverse acting) output and the cooling (direct acting) output. This
shifts the cool setpoint by the dead band value entered. If you select a
positive value the heat and cool outputs cannot be energized at the same
time. If you select a negative value, both outputs can be energized at the
same time.
IfDefault
↓↓
[``°F][-999] … [```0] … [`999]
[`C_F][``db][``db][``db]
(Setup Menu)
[``°C][-555] … [```0] … [`555]
[`C_F][``db][``db][``db]
a process[-999] … [```0] … [`999] units
input is selected[``db][``db][``db]
Operations Menu, Chapter 5WATLOW Series 988LF Users Manual5.5
Operations
[`AL0
Alarm Lo
Select the low trigger value for the output 2 alarm. Represents the low
process alarm or low deviation alarm.
[`ALO] This prompt appears only if [`Ot2] parameter is set to [``AL] or
[`ALn].
IfDefault
↓↓
lowestvalue of
[`Pr1]value of … [`rL1] (or [`rL2])…[`AHI]
[`AL0]sensorin Setup Menu[`ALO]
range
[`dE1][-999]…[```0]
`AL0][`ALO][`ALO]
[`AHI]
Alarm Hi
Select the high trigger value for the output 2 alarm. Represents the
high process alarm or high deviation alarm.
[`AHI] This prompt appears only if [`Ot2] parameter is set to [``AL] or
[`ALn].
IfDefault
↓↓
[``Pr][`ALO] … [`rH1](or [`rH2]) … value of
[`AL0][`AHI]in Setup Menusensor
[``dE][```0] … [`999]…[9999]
[`AL0][[`AHI][[`AH]1[`AH1]
value ofhighest
range
5.6WATLOW Series 988LF Users ManualOperations Menu, Chapter 5
Operations
[`CAL]
[`AUt]
NOTE:
For more information on
auto-tune, see Chapter
7.
Calibration Offset
Add or subtract degrees from the input signal. This allows you to
compensate for lead resistance, sensor errors, or other factors.
[`CAL] This prompt always appears.
IfDefault
↓↓
[-999] [```0] [9999]
[`CAL][`CAL][`CAL]
[`r†d][-9(9] [```0] [99(9]
[``In][`CAL][`CAL][`CAL]
Auto-tune
Initiate an auto-tune.
[`AUt] This prompt always appears.
Default
↓
[`L-r]
[`OFF][``On]
[`CAL][`AUt]
Local-remote
Selects a local or remote set point. With [```r] selected the controller
displays the remote set point rather than the internal (local) set point, and
the set point cannot be changed with the Up-arrow > or Down-arrow <
key.
[`L-r] This prompt appears if [`rSP] (Setup Menu) is not equal to [`OFF].
Default
↓
[```L][```r]
[`L-r][`L-r]
Operations Menu, Chapter 5WATLOW Series 988LF Users Manual5.7
Operations
Notes
5.8WATLOW Series 988LF Users ManualOperations Menu, Chapter 5
Chapter 6The Factory Menus
[
Reaching the Diagnostics Menu
❶ Press the Up-arrow > and Down-arrow < keys together and hold
until the [`LOC] prompt appears in the lower display. Press and hold again
until the [Fcty] prompt appears in the lower display.
[diAg][`CAL]
[Fcty] [Fcty]
Diagnostics Calibration
MenuMenu
p. 6.1p 6.5
❷ Use the Up-arrow > key to
step from the Calibration Menu
[`CAL] to the Diagnostics Menu
[diag].
❸ Press the Mode key µ to
step through the prompts.
[``no][`YES]
[diSP] [diSP]
`OFF][out1][out2]
[tout] [tout] [tout]
❹ Press the Up-arrow key > or
the Down-arrow key < to
select one of the prompt values.
In the Diagnostics Menu only
the values of [dISP], [tout],
and [OPLP] can be changed.
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
MODE
[Diag]
[Fcty]
?
[date]
?
[SOft]
?
[Sn--]
?
[AMB]
?
[Acnt]
?
[`gnd]
?
[cnt1]
?
[cnt2]
?
[ity1]
?
[ity2]
?
[Oty1]
?
[Oty2]
?
[dISP]
?
[tout]
?
[OPLP]
Factory Prompt
Factory Ship Date
Software Revision
Serial Number
Ambient Temperature
Ambient A/D count
Ground A/D count
Input 1 A/D count
Input 2 A/D count
Input 1 Module Type
Input 2 Module Type
Output 1 Module Type
Output 2 Module Type
Test Display
Test Outputs
Open Loop
Document your settings,
from the controller's
upper display.
Figure 6.1
The Diagnostics Menu
Factory Menus, Chapter 6WATLOW Series 988LF Users Manual6.1
Factory-Diagnostics
[dAtE]
[SOFt]
[Sn--]
Factory Ship Date
Shows the date that the final factory control test was performed. The
first two digits represent the week as numbered from [01``] to [52``].
The second two digits represent the year [``97], [``98], etc…
[dAtE] This prompt always appears.
Software Revision
Shows the controller’s software revision code. This letter indicates the
software revision of your controller; [50`d].
[SOFt] This prompt always appears.
Serial Number
Shows the controller’s serial number. The first two letters in the upper
display are to indicate that the controller is in serial number mode. The
right half of the upper display shows the first two digits of the serial number. The lower display shows the last four digits of the serial number.
[AMb]
[Acnt]
[`gnd]
[Sn34]
[5678]
This is what the controller with the serial number 0988345678 would
display.
[Sn``] This prompt always appears.
Ambient Temperature
Shows the ambient temperature at the Input 1 terminals. The temperature is shown in °F in the form [00)0] regardless of the settings of
[deC1], [deC2], [`dfL], or [`C_F].
[AMb] This prompt always appears.
Factory Use Only
These prompts are used only at the factory.
[Acnt] [`gnd] [cnt1] [cnt2] These prompts always appear.
[cnt1]
[cnt2]
6.2WATLOW Series 988LF Users ManualFactory Menus, Chapter 6
Factory-Diagnostics
[ity1]
[ity2]
[Oty1]
[Oty2]
Inputs 1 and 2 Module Types
Displays which input module is installed in the controller. Please
document this value before contacting the factory for technical assistance.
Input Types
• [none] No input module
• [``tc] Thermocouple only module
• [UOFF] Universal off
• [Urtd] Universal rtd
• [Utch] Universal high-gain thermocouple
• [UtcL] Universal low-gain thermocouple
• [UMu] Universal millivolts
• [UPrc] Universal process
[ity1] [ity2] These prompts always appear.
Outputs 1 and 2 Module Types
Displays which output module is installed in the controller. Please
document this value before contacting the factory for technical assistance.
[diSP]
Output Types
• [none] no output module
• [SSr1] 0.5A solid-state relay
• [SS1S] 0.5A solid-state relay with suppression
• [``dc] switched DC output
• [rLcS] form C relay with suppression
• [Proc] process output (Output 1 only)
[Oty1] [Oty2][Oty1] [Oty2]
[Oty1] [Oty2] These prompts always appear.
[Oty1] [Oty2][Oty1] [Oty2]
Test Displays
Runs a brief test of the controller’s displays and LEDs. To run the test,
scroll through the Diagnostics Menu until [disp] is shown in the lower
display. Use the Up-arrow key > or Down-arrow key < to select[`YES] from the upper display and press the mode key µ.
The controller will run pattern tests, blink all the LEDs on and off, and
end with the model number in both displays.
[diSP] This prompt always appears.
Default
↓
[``no][`yes]
[disp][disp]
Factory Menus, Chapter 6WATLOW Series 988LF Users Manual6.3
Factory-Diagnostics
[tout]
[OPLP]
Test Outputs
This prompt tests each output. To run the test, scroll through the
Diagnostics Menu until [tout] is shown in the lower display. Use the Uparrow key > or Down-arrow key < to select an output [out1] or
[out2]. The LED for that output should light after a second or two indicating that the output has been successfully energized. Do not press the
mode key µ to activate the test; it starts automatically when anything
other than [`OFF] is selected.
If any of the LEDs fail to light contact the factory.
[tout] This prompt always appears.
Default
↓
[`OFF][out1][out2]
[tout][tout][tout]
Open Loop
Checks the control loop, consisting of the controller output, power
control, heater and sensor. With open loop enabled, the controller moni-
tors the output power level and checks for a change in the process input
value. If the output power is at maximum for a period of time equal to the
reset time and the process input has not changed by at least ±5°F, the
controller will switch to manual mode at 0% output power and [OPLP] will
be displayed in the lower display.
To clear this error, enter the Setup Menu and press the display key ∂. To
get back into auto mode, press the Auto/Man key å.
[OPLP] This prompt always appears.
Default
↓
[`OFF][``On]
[OPLP][OPLP]
6.4WATLOW Series 988LF Users ManualFactory Menus, Chapter 6
]
Factory-Calibration
t
s
[`CAL]]
Reaching the Calibration Menu
❶ Press the Up-arrow > and Down-arrow
< keys together and hold until the [`LOC]
prompt appears in the lower display. Press
and hold again until the [Fcty] prompt
appears in the lower display.
❷ Use the Up-arrow key > to select the
Calibration Menu [`CAL] in the upper
display.
[diAg][`CAL]
[Fcty] [Fcty]
Diagnostics Calibration
MenuMenu
p. 6.1p 6.5
❸ Press the Mode key µ to step through
the prompts.
[``no][`YES
[`rSt] [`rSt]
❹ Press the Up-arrow key > or the Down-
arrow key < to select one of the prompt
values.
Refer to Calibrating Watlow Process Controls
for information about the Calibration Menu.
ç
CAUTION:
Before attempting to calibrate, make sure you have the
proper equipment called for in each procedure. The
Series 988LF is calibrated and tested before it leaves
the factory. Attempting to calibrate the controller
without the proper equipment could result in damage
to property and/or equipment.
Diagnostics Prompt
[Fcty]
MODE
?
[A`50]
MODE
?
[A`00]
MODE
?
[``tc]
MODE
?
[a`0H]
MODE
?
[A`20]
MODE
?
[A`15]
MODE
?
[A380]
MODE
?
[A10U]
MODE
?
[A`0U]
MODE
?
MODE
MODE
MODE
MODE
MODE
MODE
[A20A]
?
[A`4A]
?
[A`OU]
?
[A100]
?
[b`50]
?
[b`00]
MODE
Document your set
from the controller'
upper display.
?
[[b`0H]
MODE
?
[b`20]
MODE
?
[b`15]
MODE
?
b380]
MODE
?
[b10U]
MODE
?
[b`0U
MODE
?
[b20A]
MODE
?
[b`4A]
MODE
?
[b`0U]
MODE
?
[b100]
MODE
?
[1`4`]
MODE
?
[1`20]
MODE
?
[1`0`]
MODE
?
[1`10]
MODE
?
[`rSt]
Restore
Figure 6.5 The Calibration Menu
[`rSt]
Restore
Restores the original factory calibration values. This is a simple way to
recover from a mistake made while calibrating the controller.
[`rSt] This prompt always appears.
Default
↓
[``no][`yes]
[`rSt][`rSt]
Factory Menus, Chapter 6WATLOW Series 988LF Users Manual6.5
Notes
6.6WATLOW Series 988LF Users ManualFactory Menus, Chapter 6
Chapter 7Tuning, Manual Operation,
Alarms and Error Codes
Auto-tuning (Heat and/or Cool)
NOTE:
A useful reference on
tuning is Tuning of
Industrial Control
Systems by Armando B.
Corripio, published by
the Instrument Society of
America.
Figure 7.1 Auto-tuning example
The Series 988LF can automatically tune the PID parameters to fit the
characteristics of your particular thermal system.
Once the auto-tune sequence has begun, all PID values for both heat and
cool are set to [```0] and the control goes into an on/off mode of control
at 90% of the established set point. The displayed set point remains
unchanged.
Auto-tuning at a set point of 200°F
200°
180°
Temperature
100°
auto-tune
begins
process
90% of
set point
Time
auto-tune
complete
set point
ç
CAUTION:
If a mechanical relay or
contactor is switching
power to the load, a
longer cycle time may
be desirable to
minimize wear on the
mechanical
components. The
typical life of a
mechanical relay is
100,000 cycles. Verify
that the cycle time
selected is appropriate
for the output device
type. Failure to do so
could result in damage
to equipment and/or
property.
When the control finishes “learning” the system, it resumes standard PID
control using the PID values established by the auto-tuning process.
Changing the set point during an auto-tune restarts the auto-tune
procedure.
During auto-tuning the process must cross the set point four times within
an 80-minute time span for the Series 988LF to successfully complete the
auto-tune. If this does not happen within the 80-minute time limit, the
Series 988LF chooses PID values based on the 80-minute tuning cycle
performed.
To start auto-tuning:
1. Press the Mode key µ to advance through the Operations menu
until the [`AUt] prompt appears in the lower display.
2. Use the Up-arrow > or Down-arrow < key to select [``On] or
[`OFF].
3. Press the Display key ¥. While the control is in the tuning mode
the lower display alternates every second between the normal
information and the [tunE] prompt.
Tuning, Manual Operation, Alarms, and Error Codes, Chapter 7WATLOW Series 988LF Users Manual7.1
T uning
4. When tuning is complete, the displays return to their previous state
and [`AUt] reverts to [`OFF]. The Series 988LF installs the PID tuning
parameters it has calculated and saves them in non-volatile memory.
To abort auto-tuning either reset the [`AUt] prompt to off, press the Auto/
Man key å twice, or cycle power off and on. In all cases, aborting autotune restores all values to their state before auto-tuning began.
Manual Tuning
For optimum control performance, tune the Series 988LF to your thermal
system. The tuning settings here are for a broad spectrum of applications;
your system may have somewhat different requirements. NOTE: This is a
slow procedure that may take hours to obtain optimum values.
NOTE:
Tune heating outputs at a set point above the ambient process value.
Tune cooling outputs at a set point below the ambient process value.
1. Apply power to the Series 988LF and enter a set point. Begin with
[``Pb] set to [```1]; [``rE] or [``It] set to [`0)0]; [``rA] or
[``dE] set to [`0)0]; [``Ct] set to [``%0]; [`CAL] set to [```0]; and
[`AUt] set to [`OFF].
2. Proportional Band Adjustment: Gradually increase [``Pb] until the
upper display process value stabilizes at a constant value. The
process value will not be right on set point because the initial reset
value is 0.00 repeats per minute. (If [``Pb] is set to [```0] then
[``rE], [``It], [``rA] and [``dE] are inoperative, and the Series 988
functions as a simple on/off control.) The [`HYS] prompt determines
the switching differential value.
3. Reset/Integral Adjustment: Gradually increase [``rE] or [``It] until
the upper display process value begins to oscillate or “hunt.” Then
slowly decrease [``rE] or [``It] until the upper display stabilizes
again near set point.
4. Cycle Time Adjustment: Set [``Ct] as required. Faster cycle times
sometimes achieve the best system control. However, if a mechanical
contactor or solenoid is switching power to the load, a longer cycle
time may be desirable to minimize wear on the mechanical compo
nents. Experiment until the cycle time is consistent with the quality of
control you want. [``Ct] will not appear on units with a process
output (98__-__F_-____ or 98__-___F-____).
5. Rate/Derivative Adjustment: Increase [``rA] or [``dE] to 0.10
minute. Then raise set point by 20° to 30°F, or 11° to 17°C. Observe
the system’s approach to the set point. If the load process value over
shoots the set point, increase [``rA] or [``dE] to 0.50 minutes.
7.2WATLOW Series 988LF Users ManualTuning, Manual Operation, Alarms, and Error Codes, Chapter 7
Tuning
Raise the set point by 20° to 30°F, or 11° to 17°C and watch the ap
proach to the new set point. If you increase [``rA] or [``dE] too
much, the approach to set point will be very sluggish. Repeat as
necessary until the system rises to the new set point without over
shooting or approaching the set point too slowly.
6. Calibration Offset Adjustment: You may want your system to control to
a process value other than the value coming from the input sensor. If
so, measure the difference between that process value (perhaps at
another point in the system) and the process value showing in the
upper display. Then enter the [`CAL] offset value you want. Calibra
tion offset adds or subtracts degrees from the value of the input signal.
Manual and Automatic Operation
To change from auto to manual operation, press the Auto/Man key å
twice.
Manual operation provides open-loop control of the outputs from a range of
-100% to 100% output. The Series 988LF allows a negative output value
only when [`Ot1] or [`Ot2] (Output Menu) is set to [``CL] (cool). Automatic operation provides closed-loop on/off or PID control. When the
operator transfers from a closed loop to an open loop, the Series 988LF
retains the power level from the closed loop control. When the Series 988LF
returns to closed-loop control, it restores the previous set-point value.
The Auto/Man LED (located on the Auto/Man key å) indicates whether
the controller is in automatic or manual operation. When the LED is lit, the
control is in manual operation. When the LED is off, it is in automatic
operation. When the LED flashes, press the key again within five seconds
to complete the change in operation.
When a sensor opens, the controller switches from automatic to manual
operation.
•If the process has stabilized at a power level less than 75% ( ± 5%) for a
two-minute period prior to the sensor break, then the Series 988LF
switches to manual operation at the last automatic power level. If these
conditions are not met, the output goes to 0% power (output disabled).
When transferring from automatic to manual operation, the control output,
or outputs, remain stable — a bumpless, or smooth, transition. When
transferring from automatic to manual operation, the output value appears
in the lower display. In automatic operation, the set point appears.
Tuning, Manual Operation, Alarms, and Error Codes, Chapter 7WATLOW Series 988LF Users Manual7.3
Alarms
NOTE:
An alarm display will
be masked by an error
condition or when the
control is in the
Calibration or Setup
menus.
Using Alarms
Output 2 of the Series 988LF can function as an alarm. This is accomplished with the [`Ot2] prompt (Setup Menu). If [``Al] is selected, the
output is energized in the non-alarm condition and de-energizes the output
in the alarm condition. Selecting [`ALn] reverses this action: de-energizing
the output in a non-alarm condition and energizing it in an alarm condition.
If the L2 LED on the front panel is lit, this indicates an alarm condition for
output 2.
Once you’ve configured [`Ot2] as an alarm, select the [`ALt] prompt. At
this prompt, you can select the type of alarm: process or deviation.
A process alarm sets an absolute temperature range or process value range.
When the temperature or process leaves the range an alarm occurs. A
process alarm is not tied to the set point.
Example: If your set point is 100°F and a process alarm high limit is set to
150°F and the low limit is set to 50°F, the high limit trips at 150°F, and the
low alarm at 50°F. If you change the set point, the process alarm limits
remain the same.
A deviation alarm alerts the operator when the process strays too far from
the set point. The operator can enter independent high and low alarm
settings. The reference for the deviation alarm is the set point. Any change
in set point causes a corresponding shift in the deviation alarm. Low
alarms are usually set at a negative deviation while high alarms are a
positive deviation.
Example: If your set point is 100°F, a deviation alarm high limit is set to
+7°F and the low limit is set to -5°F, then the high alarm trips at 107°F, and
the low alarm at 95°F. If you change the set point to 130°F, the alarms
follow the set point and trip at 137°F and 125°F.
Alarms can be latching or non-latching. When the alarm condition is
removed, a non-latching alarm automatically clears the alarm output and
alarm message, if one is present. You must manually clear a latching alarm
before it will disappear.
The alarm output is indicated by the corresponding LED on the front panel:
L2. There may be an alarm message flashing in the lower display. When an
alarm message is displayed, it alternately flashes with the current prompt at
a one-second interval in the lower display.
To clear a latching alarm, first correct the condition then press the Auto/
Man key å once.
Alarm silencing is available with all alarms. This function overrides the
alarm on initial power up. On power up, the alarm message will not appear
and the L2 LED and output will reflect a non-alarm condition. Silencing is
active until the process has entered the safe region located between the lowand high-alarm settings. Then deviation outside this safe zone triggers an
alarm. If an alarm occurs at this point, the output can be silenced by
pressing the Auto/Man key å once, but the controller still displays the
alarm message.
7.4WATLOW Series 988LF Users ManualTuning, Manual Operation, Alarms, and Error Codes, Chapter 7
NOTE:
To view the error code,
press the Auto/Man key
å
once. The upper
display shows the error
code for five seconds
before returning to the
[----][----]
[----] display.
[----][----]
Error Codes
Error Code E1 and E2 Messages
Four dashes, [----], in the upper display indicate a Series 988LF error. If
the control was operating with stable output values (less than 75% power
and less than a 5% changeover the past 2 minutes) when the error occurred, it continues to operate at those levels on a percent-power basis
([bplS]). If output values were not stable, or the percent output was
greater than 75%, the control outputs drop to 0% power (off).
[E1`1] [E2`1]: A/D underflow error
The analog-to-digital (A/D) converter of the input indicated by the first
number is under range. An open or reversed polarity sensor is the most
likely cause. Check the sensor. Make sure the input prompt is set to the
correct sensor.
W
A
TL
W
PROCESS
Figure 7.5 Error Code Display
NOTE:
An alarm display will be
masked by an error
condition or when the
control is in the Calibration or Setup menus.
L1 L2 L3 L4
DEV
DISPLAY
% OUT
AUTO
MAN
MODE
SERIES 988
[E1`2] [E2`2]: Sensor under-range error
The sensor at the input indicated by the first number generated a value
lower than that allowed for the range of the sensor, or the analog-to-digital
(A/D) converter malfunctioned. Make sure the setting for the input (Setup
Menu) matches the sensor type and that the sensor range falls within the
range of the process being controlled.
[E1`3] [E2`3]: Sensor over-range error
The sensor at the input indicated by the first number generated a value
higher than that allowed for the range of the sensor, or the analog-to-digital
(A/D) converter malfunctioned. Make sure the setting for the input (Setup
Menu) matches the sensor type and that the sensor range falls within the
range of the process being controlled.
[E1`4] [E2`4]: A/D overflow error
The analog-to-digital (A/D) converter at the input indicated by the first
number is over range. An open or reversed polarity sensor is the most
likely cause. Check the sensor. Make sure the input (Setup Menu) is set
to the correct sensor type.
The analog-to-digital (A/D) converter input voltage may be too high to
convert an A/D signal.
[`Er3]: Ambient temperature error
Tuning, Manual Operation, Alarms, and Error Codes, Chapter 7WATLOW Series 988LF Users Manual7.5
Error Codes
The ambient temperature of the Series 988LF has dropped below 32°F/0°C
or risen above 149°F/65°C. Calibration errors can also cause this error
code. Try setting [`rSt] (Calibration Menu) to [`yES].
[`Er4]: RAM verification error
An internal RAM failure has occurred. Contact the factory.
[`Er5]: Non-volatile checksum error
An EEPROM checksum error was detected. Turn the power off then back
on again. If this does not clear the error, contact the factory.
[OPLP]: Open-loop detect
This error is not available while in the on/off mode. It is only active when
[OPLP] is set to [``On] (Diagnostics Menu).
[`Er9
An incorrect module has been installed in the control. Contact the factory.
]]
]: Configuration error
]]
Error Code Actions
•All of the above error codes except [`Er4], [`Er5] and [`Er9] will
result in this condition:
•If the control was operating with stable output values (less than
75% power and less than a 5% changeover the past 2 minutes)
when the error occurred, it continues to operate at those levels on a
percent-power basis ([bplS]). If output values were not stable, or
the percent output was greater than 75%, the control outputs drop
to 0% power (off).
•To clear an error code…
•If [`Err] is set to [`nLA], the error code should clear once the
problem is corrected.
•If [`Err] is set to [`LAt], correct the problem and cycle power. You
can also clear the error by pressing both the Up-arrow > and
Down-arrow < keys to enter the Setup Menu, then press the
Display key ¥.
•Error codes [`Er4], [`Er5] and [`Er9] will result in these conditions:
•The control is in automatic operation with both control outputs off.
•The alarm outputs are in their alarm state (de-energized with the
LED lit).
NOTE:
An alarm display will be
masked by an error
condition or when the
control is in the Calibration or Setup menus.
7.6WATLOW Series 988LF Users ManualTuning, Manual Operation, Alarms, and Error Codes, Chapter 7
•The lower display is blank.
•The upper display indicates the error code.
•All keys are inactive.
•With [`Er5], all Setup Menu prompts return to default values.
Cycle power to the control. If the error is still present contact the factory.
Notes
Tuning, Manual Operation, Alarms, and Error Codes, Chapter 7WATLOW Series 988LF Users Manual7.7
Notes
7.8WATLOW Series 988LF Users ManualTuning, Manual Operation, Alarms, and Error Codes, Chapter 7
Appendix
Warranty and ReturnsA.1
GlossaryA.2
IndexA.4
Warranty/Returns
SpecificationsA.6
Model NumberA.7
Menu OverviewA.8
Declaration of ConformityA.9
Total
Customer
Satisfaction
Warranty
The Watlow Series 988LF is warranted to be free of
defects in material and workmanship for 36 months
after delivery to the first purchaser for use, providing
that the units have not been misapplied. Since Watlow
has no control over their use, and sometimes misuse,
we cannot guarantee against failure. Watlow's
obligations hereunder, at Watlow's option, are limited to
replacement, repair or refund of purchase price, and
parts which upon examination prove to be defective
within the warranty period specified. This warranty
does not apply to damage resulting from transportation,
alteration, misuse or abuse.
Watlow Controls
Returns
1. Call Watlow Customer Service, (507) 454-5300, for
a Return Material Authorization (RMA) number
before returning any item for repair. We need this
information:
• Ship to address• Bill to address
• Contact name• Phone number
• Ship via• Your P.O. number
• Symptoms and/or special instructions
• Name and phone number of person returning
the material.
NOTE: All unit model number stemming from this
user’s manual end in “-INT,” which indicates a CE
compliant product.
2. Prior approval and an RMA number, from the
Customer Service Department, is needed when
returning any unused product for credit. Make sure
the RMA number is on the outside of the carton,
and on all paperwork returned. Ship on a Freight
Prepaid basis.
3. After we receive your return, we will examine it and
determine the cause for your action.
Watlow Controls is a division of Watlow Electric
Manufacturing Company, St. Louis, Missouri, a
manufacturer of industrial electric heating products
since 1922. Watlow begins with a full set of
specifications and completes an industrial product that
is manufactured totally in-house, in the U.S.A. Watlow
products include electric heaters, sensors, controls and
switching devices. The Winona operation has been
designing solid state electronic control devices since
1962, and has earned the reputation as an excellent
supplier to original equipment manufacturers. These
OEMs depend upon Watlow Controls to provide
compatibly engineered controls which they can
incorporate into their products with confidence. Watlow
Controls resides in a 100,000-square-foot marketing,
engineering and manufacturing facility in Winona,
Minnesota.
AppendixWATLOW Series 988LF Users ManualA.1
4. In cases of manufacturing defect, we will enter a
repair order, replacement order, or issue credit for
material. A 20-percent restocking charge is applied
for all returned stock controls and accessories.
5. If the unit is unrepairable, it will be returned to you
with a letter of explanation. Repair costs will not
exceed 50 percent of the original cost.
Shipping Claims
When you receive your Watlow control, examine the
package for any signs of external damage it may have
sustained enroute. If there is apparent damage either
outside the box or to its contents, make a claim with the
shipper immediately. Save the original shipping carton
and packing material.
Glossary
annunciator — A visual display that uses pilot lights to
indicate the former or existing condition of several items in a
system.
bumpless transfer — A smooth transition from auto (closed
loop) to manual (open loop) operation. The control output(s)
does not change during the transfer.
burst fire — A power control method that repeatedly turns on
and off full AC cycles. Also called zero-cross fire, it switches
close to the zero-voltage point of the AC sine wave. Variabletime-base burst fire selectively holds or transits AC cycles to
achieve the desired power level.
calibration offset — An adjustment to eliminate the difference between the indicated value and the actual process
value.
cascade — Control algorithm in which the output of one
control loop provides the set point for another loop. The
second loop, in turn, determines the control action.
closed loop — A control system that uses a sensor to measure
a process variable and makes decisions based on that
feedback.
cold junction — See junction, cold.
cold junction compensation — Electronic means to compen-
sate for the effective temperature at the cold junction.
current transformer — A transformer designed for measuring
electrical current.
dead band — The range through which a variation of the
input produces no noticeable change in the output. In the
dead band, specific conditions can be placed on control output
actions. Operators select the dead band. It is usually above
the heating proportional band and below the cooling proportional band.
default parameters — The programmed instructions that are
permanently stored in the microprocessor software.
derivative — The rate of change in a process variable. Also
known as rate. See PID.
DIN (Deutsche Industrial Norm) — A set of technical,
scientific and dimensional standards developed in Germany.
Many DIN standards have worldwide recognition.
DIN-a-mite — Watlow family of SCR power controls.
droop — In proportional controllers, the difference between
set point and actual value after the system stabilizes.
duty cycle — The percentage of a cycle time in which the
output is on.
external signal conditioner power supply — A dc voltage
source that powers external devices.
filter —
digital filter (DF) — A filter that slows the response
of a system when inputs change unrealistically or too fast.
Equivalent to a standard resistor-capacitor (RC) filter.
frequency input signal noise (noise spikes).
digital adaptive filter — A filter that rejects high
heat/cool output filter — A filter that slows the
change in the response of the heat or cool output. The output
responds to a step change by going to approximately 2/3 its
final value within the number of scans that are set.
form A — A single-pole, single-throw relay that uses only the
normally open (NO) and common contacts. These contacts
close when the relay coil is energized. They open when power
is removed from the coil.
form B — A single-pole, single-throw relay that uses only the
normally closed (NC) and common contacts. These contacts
open when the relay coil is energized. They close when power
is removed from the coil.
form C — A single-pole, double-throw relay that uses the
normally open (NO), normally closed (NC) and common
contacts. The operator can choose to wire for a Form A or
Form B contact.
hunting — Oscillation of process temperature between the set
point and the process variable.
hysteresis — A change in the process variable required to reenergize the control or alarm output. Sometimes called
switching differential.
integral — Control action that automatically eliminates offset,
or droop, between set point and actual process temperature.
See reset, automatic.
isolation — Electrical separation of sensor from high voltage
circuitry. Allows use of grounded or ungrounded sensing
element.
JIS(Joint Industrial Standards) — A Japanese agency that
establishes and maintains standards for equipment and
components. Also known as JISC (Japanese Industrial
Standards Committee), its function is similar to Germany’s
Deutsche Industrial Norm (DIN).
junction — The point where two dissimilar metal conductors
join to form a thermocouple.
cold junction — Connection point between thermocouple metals and the electronic instrument. See reference
junction.
grounded junction — Type of thermocouple probe in
which the hot, or measuring junction, is an integral part of the
sheath material. No electrical isolation is provided.
isolated junction — A form of thermocouple probe
construction in which the measuring junction is fully enclosed
in a protective sheath and electrically isolated from it.
Commonly called an ungrounded junction.
reference junction — The junction in a thermocouple circuit held at a stable, known temperature (cold
junction). Standard reference temperature is 32°F (0°C).
thermocouple junction — The point where the two
dissimilar metal conductors join. In a typical thermocouple
circuit, there is a measuring junction and a reference junction. See reference junction.
ungrounded junction — See isolated junction.
linearization, square root — The extraction of a linear signal
from a nonlinear signal corresponding to the measured flow
from a flow transmitter. Also called square root extraction.
A.2WATLOW Series 988LF Users ManualAppendix
Glossary
NEMA 4X — A NEMA specification for determining resistance
to moisture infiltration. This rating certifies the controller as
washable and corrosion resistant.
on/off — A method of control that turns the output full on
until set point is reached, and then off until the process error
exceeds the hysteresis.
open loop — A control system with no sensory feedback.
output — Control signal action in response to the difference
between set point and process variable.
overshoot — The amount by which a process variable exceeds
the set point before it stabilizes.
P control — Proportioning control.
PD control — Proportioning control with derivative (rate)
action.
PDR control — Proportional derivative control with manual
reset, used in fast responding systems where the reset causes
instabilities. With PDR control, an operator can enter a
manual reset value that eliminates droop in the system.
PI control — Proportioning control with integral (automatic
reset) action.
PID — Proportional, integral, derivative. A control mode with
three functions: proportional action dampens the system
response, integral corrects for droop, and derivative prevents
overshoot and undershoot.
controls that does not recognize power outage as a limit
automatic power reset — A feature in latching limit
condition. When power is restored, the output is re-energized
automatically, as long as the temperature is within limits.
manual reset — 1) A feature on a limit control that
requires human intervention to return the limit to normal
operation after a limit condition has occurred. 2) The adjustment of a proportional control to raise the proportional band
to compensate for droop.
no key reset — A method for resetting the
controller’s memory (for instance, after an EPROM change).
resistance temperature detector (RTD) — A sensor that
uses the resistance temperature characteristic to measure
temperature. There are two basic types of RTDs: the wire
RTD, which is usually made of platinum, and the thermistor,
which is made of a semiconductor material. The wire RTD is a
positive temperature coefficient sensor only, while the
thermistor can have either a negative or positive temperature
coefficient.
retransmit output — An analog output signal that may be
scaled to represent the process value or set point value.
RTD — See resistance temperature detector.
slidewire feedback — A method of controlling the position of
a valve. It uses a potentiometer to vary resistance ( ) and
indicate position of the valve.
switching sensitivity — In on/off control, the temperature
change necessary to change the output from full on to full off.
See hysteresis.
process variable — The parameter that is controlled or
measured. Typical examples are temperature, relative humidity, pressure, flow, fluid level, events, etc. The high process
variable is the highest value of the process range, expressed in
engineering units. The low process variable is the lowest value
of the process range.
proportional band (PB) — A range in which the proportioning
function of the control is active. Expressed in units, degrees or
percent of span. See PID.
proportional control — A control using only the P (proportional) value of PID control.
rate band — A range in which the rate function of a controller
is active. Expressed in multiples of the proportional band. See
PID.
ratio — A method by which the controller measures the flow
of an uncontrolled variable and uses a proportion of it to
control the flow of a second variable.
reference junction — See junction.
reset — Control action that automatically eliminates offset, or
droop, between set point and actual process temperature. Also
see integral.
automatic reset — The integral function of a PI or
PID temperature controller that adjusts the process temperature to the set point after the system stabilizes. The inverse of
integral.
thermal system — A regulated environment that consists of a
heat source, heat transfer medium or load, sensing device and
a control instrument.
thermocouple (t/c) — A temperature sensing device made by
joining two dissimilar metals. This junction produces an
electrical voltage in proportion to the difference in temperature
between the hot junction (sensing junction) and the leadwire
connection to the instrument (cold junction).
thermocouple break protection — The ability of a control to
detect a break in the thermocouple circuit and take a predetermined action.
three-mode control — Proportioning control with integral
(reset) and derivative (rate). Also see PID.
time proportioning control — A method of controlling power
by varying the on/off duty cycle of an output. This variance is
proportional to the difference between the set point and the
actual process temperature.
zero cross — Action that provides output switching only at or
near the zero-voltage crossing points of the AC sine wave. See
burst fire.
zero switching — See zero cross.
AppendixWATLOW Series 988LF Users ManualA.3
Index
%OUT LED 3.1
0-5VÎ (dc) process wiring
input 1 2.7
remote set point option 2.8
output 1 2.9
0-10VÎ (dc) process wiring
input 1 2.7
remote set point option 2.8
output 1 2.9
0-20mA process wiring
input 1 2.7
remote set point option 2.8
output 1 2.9
0-50mV (high impedance) wiring
input 1 2.7
remote set point option 2.8
1-5VÎ (dc) process wiring
input 1 2.7
remote set point option 2.8
output 1 2.9
4-20mA process wiring
input 1 2.7
remote set point option 2.8
output 1 2.9
P control A.3
panel back access 2.2
panel cutouts 2.1 - 2.2
Panel Lockout Menu 4.2
PD control A.3
PDR control A.3
PI control A.3
PID control A.3
power wiring 2.3
process variable A.3
process alarm 7.4
proportional band A.3
output 1 5.2
proportioning control A.3
A.4WATLOW Series 988LF Users ManualAppendix
Index / Prompts
Q, R
range high 1 4.4 - 4.5
range high 2 4.7 - 4.8
range low 1 4.4 - 4.5
range low 2 4.7 - 4.8
rate
output 1 5.3
output 2 5.4
rate band A.3
reference junction A.2
relay, mechanical 7.1
release tabs 1.1, 2.2
remote set point 4.6
removing controller chassis 1.1, 2.2
reset
• CE: 89/336/EEC Electromagnetic Compatibility
Directive.
EN 50081-2: 1994 Emissions.
EN 50082-2: 1995 Immunity.
• 73/23/EEC Low-Voltage Directive.
EN 61010-1: 1993 Safety.
• NEMA 4X
Terminals
• #6 compression universal head screws (tighten
to 5 inch/pounds maximum), accepts 20-14
gauge wire.
Accuracy
• Calibration accuracy and sensor conformity:
±0.1% of span, ±1 LSD, 77°F ±5°F (25°C ±3°C)
ambient and rated line #voltage ±10%
• Accuracy span: 1000°F (540°C) minimum
• Temperature stability: ±0.2°F/°F (0.1°C/°C)
change in ambient
Mechanical
• 1⁄8 DIN panel mount, NEMA 4X (IP65
equivalent) front panel
• Overall width x height x depth
• Horizontal; 4.03" x 2.18" x 4.74", (102 mm x 55
mm x 120 mm)
• Vertical; 2.18" x 4.03" x 4.74", (55 mm x 102
mm x 120 mm)
• Depth behind panel; 4.06"(103 mm)
• Weight less than or equal to 14.0 oz (0.40kg)
Input Range
Specified temperature ranges represent the
controller's operational span.
Thermocouple
(Available with basic or universal signal
conditioner)
Type C
Type D
Type E-328to1470°For -200to799°C
Type J32to1500°For0to816°C
Type K-328to2500°For -200to1371°C
Type N32to2372°For0to1300°C
Type T-328to750°For -200to399°C
Pt 2
2
32to4200°For0to2316°C
2
32to4200°For0to2316°C
2
32to2543°For0to1395°C
(Available with universal signal conditioner)
Type B1598to3300°For870to1816°C
Type R32to3200°For0to1760°C
Type S32to3200°For0to 1760°C
RTD Resolution (DIN or JIS) (Avail. w/universal signal conditioner)
Process (Available with universal signal conditioner)
0-50mVÎ(dc) -999 to 9999 units
0-5VÎ(dc)-999to9999 units
1-5VÎ(dc)-999to9999 units
0-10VÎ(dc)-999to9999 units
0-20mAÎ(dc)-999to9999 units
4-20mAÎ(dc)-999to9999 units
Output Options
• Solid state relay, 0.5A @ 24V~ (ac) min., 253V~
(ac) max., opto isolated, burst fire. With or
without contact suppression.
• Open collector, switched dc signal provides a
minimum turn-on voltage of 3VÎ(dc) into a
minimum 500 load; maximum on voltage not
greater than 32VÎ(dc) into an infinite load,
isolated.
• Electromechanical relay1, Form C, 5A @ 120/
240~ (ac), 6A @ 28VÎ(dc), 1/8 hp. @ 120V~ (ac)
or 125VA @ 120V~ (ac). With or without contact
suppression. Off-state output impedance with
RC suppression is 20k .
• Process, 0-20mA (dc), 4-20mA (dc) into 800
maximum, 0-5VÎ(dc), 1-5VÎ(dc), or 0-10VÎ(dc)
into 1k minimum1, reverse acting, isolated.
1
Electromechanical relays are warranted for 100,000
closures only. Solid-state switching devices are
recommended for applications requiring fast cycle times or
extended service life.
2
Not an ANSI symbol.
A.6WATLOW Series 988LF Users ManualAppendix
1
Electromechanical relays
warranted for 100,000
closures only. Solid state
switching devices recommended for applications
requiring fast cycle times
or extended service life.
Model Number
Ordering Information–(1319)
To order, complete the code number to the right with the information below:
9 8 _ L - _ _ _ _ - A A _ _
Series 988LF = Single channel 1⁄8 DIN temperature
/process controller, vertical or horizontal mount
(excludes tc types B, R, and S, RTD, Process inputs)
2= Universal signal conditioner
(All inputs included - see Range Information)
#2 Input
0= None
2= Universal signal conditioner (Remote Set Point)
#1 Output
B= Solid state relay, Form A, 0.5A, with RC suppression
C= Switched dc or open collector, isolated
D= Electromechanical relay1, Form C, 5A, with RC suppression
E= Electromechanical relay1, Form C, 5A,
K= Solid state relay, Form A, 0.5A, without RC suppression
#2 Output
A= None
B= Solid state relay, Form A, 0.5A, with RC suppression
C= Switched dc or open collector, isolated
D= Electromechanical relay1, Form C, 5A, with RC suppression
E= Electromechanical relay1, Form C, 5A, without contact
suppression
K= Solid state relay, Form A, 0.5A, without contact suppression
NOTE: User documentation may be available in French, German, Spanish, Italian and
Dutch, as well as English. Check Watlow’ s website (www .watlow .com/) for availability.
Specify language at time of order.
AppendixWATLOW Series 988LF Users ManualA.7
e
2
Menu Overview
Figure A.8The Series 988LF Map
NOTE:
This is a complete
listing of all Series
988LF prompts.
Not all prompts will
appear on your
control. They are
dependent on your
configuration and
model number.
To Navigate:
Press ∂ to return to the
Display Loop from any
location and to advance
through the Display Loop.
Press > or < to move
between the menus.
Display Loop
(Lower Display)
Operation
Menu
SP2
Pb1
rE1
rA1
µ
Ct1
Pb2
rE2
rA2
Ct2
db
ALO
AHI
CAL
AUt
L-r
Factory Menus
Press µ to exit
any menu and
reach the Display
Loop at any time.
Press µ to
advance to the
7550°F0
Set point
or Remote
set point
Setup Menu
Operation Menu.
(Operation)
( )
Set point 2
( )
Proportional band 1
( )
Reset 1
( )
Rate 1
( )
Cycle time 1
( )
Proportional band
( )
Reset 2
( )
Rate 2
( )
Cycle time 2
( )
Deadband
( )
Alarm Lo
( )
Alarm Hi
( )
Calibration offset
( )
Auto-tune
( )
Local-remote
µ
At the Setup Menu, press > and < another
3 seconds to enter the Factory Menus.
( )
Fcty
Factory
% OUT LED onDEV LED onProcess units
Press > and < for
3 seconds to enter the
Setup Menu.
(Setup)
LOC
( )
Lock
In1
( )
Input 1
( )
rL1
rH1
rtd
dEC
rSP
rL2
rH2
C_F
Ot1
Ot2
ALt
LAt
SIL
Range low 1
( )
Range high 1
( )
RTD calibration curve
( )
Decimal
( )
Remote set point
( )
Range low 2
( )
Range high 2
( )
C or F
( )
Output 1
( )
Output 2
( )
Alarm type
( )
Latching
( )
Silencing
Press µ to advance
through a menu.
Hold µ while pressing
> to move backwards
through the menus.
Press > or < to
select prompt values.
µ
(diAg)
( )
dAtE
( )
SOFt
Sn
( )
( )
AMb
Acnt
( )
gnd
( )
cnt1
( )
( )
cnt2
( )
ity1
( )
ity2
( )
Oty1
( )
Oty2
( )
dISP
( )
tout
OPLP ( )
(Diagnostics)
Factory ship date
Software revision
Serial number
Ambient temperatur
Ambient A/D count
Ground A/D count
Input 1 A/D count
Input 2 A/D count
Input 1 module
Input 2 module
Output 1 module
Output 2 module
Test displays
Test output
Open loop
WATLOW CONTROLS
1241 Bundy Boulevard
Winona, Minnesota 55987 USA
Declares that the following product:
Designation:Series 986, 987, 988, 989
Model Number(s):9 8 (6, 7, 8 or 9) (Any letter) - (1 or 2) (0 1 2 3 4 or 5)
Classification:Control, Installation Category II, Polution Degree II
Rated Voltage:100 to 240V~
Rated Frequency:50/60 Hz
Rated Power Consumption: 16VA maximum
Meets the essential requirements of the following European Union Directive(s)
using the relevant section(s) of the normalized standards and related documents
shown:
EN 50082-2:1995 EMC Generic immunity standard, Part 2: Industrial
EN 61000-4-2: 1995 Electrostatic discharge
EN 61000-4-4: 1995 Electical fast transients
EN 61000-4-3: 1996 Radiated immunity
EN 61000-4-6: 1996 Conducted immunity
ENV 50204:1995 Cellular phone
EN 50081-2:1994 EMC Generic emission standard, Part 2: Industrial
EN 55011:1991 Limits and methods of measurement of radio disturbance
EN 61000-3-2: 1995 Limits for harmonic current emissions
EN 61000-3-3: 1995 Limitations of voltage fluctuations and flicker
EN 61010-1:1993 Safety requirements for electrical equipment for
Déclare que le produit suivant :
Désignation :Série 986, 987, 988, 989
Numéro(s) de modèle(s) :98 (6, 7, 8 ou 9) (lettre quelconque) - (1 ou 2) (0, 1, 2,
Classification :Commande, installation catégorie II, degré de
T ension nominale :100 à 240 V ~
Fréquence nominale :50/60 Hz
Consommation
d’alimentation nominale :16 VA maximum
Conforme aux exigences de la (ou des) directive(s) suivantes de l’Union
Européenne figurant aux sections correspondantes des normes et documents
associés ci-dessous :
89/336/EEC Directive de compatibilité électromagnétique
EN 50082-2 : 1995 Norme générique d’insensibilité électromagnétique,
EN 61000-4-2 : 1995 Décharge électrostatique
EN 61000-4-4 : 1995 Courants électriques transitoires rapides
EN 61000-4-3: 1996 Insensibilité à l’énergie rayonnée
EN 61000-4-6: 1996 Insensibilité à l’énergie par conduction
ENV 50204 :1995 Téléphone cellulaire
EN 50081-2 : 1994 Norme générique sur les émissions électromagnétiques,
EN 55011 :1991 Limites et méthodes de mesure des caractéristiques
EN 61000-3-2 : 1995 Limites d’émission d’harmoniques
EN 61000-3-3 : 1995 Limitations d’écarts de tension et de papillotement
73/23/EEC Directive liée aux basses tensions
EN 61010-1 : 1993 Exigences de sécurité pour le matériel électrique de
(1230)
(B C D E F or K) (A B C D E F K or T) - (A B C J K M
N or T) (A B C D E K R S or T) (Any two letters)
or
24 to 28V‡
environment
environment
characteristics of industrial, scientific and medical radiofrequency equipment (Group 1, Class A)
73/23/EEC Low-Voltage Directive
measurement, control, and laboratory use, Part 1:
General requirements
3, 4 ou 5) (B, C, D, E, F ou K) (A, B, C, D, E, F, K ou
T) - (A, B, C, J, K, M, N ou T) (A, B, C, D, E, K, R, S,
ou T) (deux lettres quelconques)
pollution II
Partie 2 : Environnement industriel
Partie 2 : Environnement industriel
d’interférences du matériel radiofréquence industriel,
scientifique et médical (Groupe 1, Classe A)
mesure, commande et de laboratoire, Partie 1 :
Exigences générales
ou
24 à 28 V ‡
96
English
Français
Erklärt, daß das folgende Produkt:
Beschreibung:Serie 986, 987, 988, 989
Modellnummer(n):9 8 (6 7 8 oder 9) (beliebiger Buchstabe) - (1 oder 2)
Klassifikation:Regelsystem, Installationskategorie II, Emissionsgrad II
Nennspannung:100 bis 240 V~
Nennfrequenz:50/60 Hz
Stromverbrauch:Max. 16 VA
Erfüllt die wichtigsten Normen der folgenden Anweisung(en) der Europäischen
Union unter Verwendung der untenstehenden einschlägigen Dokumente:
(0 1 2 3 4 oder 5) (B C D E F oder K) (A B C D E F K
oder T) - (A B C J K M N oder T) (A B C D E K R S
oder T) (2 beliebige Buchstaben)