Watlow 94 Data sheet

SERIES 94
Registered Company
Winona, Minnesota USA
ISO 9001
Protection For Over-temperature Hazards
The Series 94 is a microprocessor-based control with single input, dual output.This controller is added to thermal applications to limit over-temperature conditions.The limit controller provides safety assurance against instances where a high temperature runaway condition could occur from a shorted input sensor or an output device that could fail in a closed position. A limit controller is recommended for any application where thermal runaway could affect operator safety, cause damage to capital equipment, produce large product scrap costs or create a fire hazard.
Watlow's Series 94 is a NEMA 4X (IP65) front panel (optional).This high performance controller is ideal for applications such as furnace and ovens, environmental chambers, semiconductor, food processing or anywhere an over-temperature condition could cause damage to equipment, product, create a fire hazard or pose a risk to personnel. Since the NEMA 4X front panel can be hosed or wiped down without damage to the controller it is also excellent for use where equipment needs to be cleaned frequently. The compact size of the controller allows more flexibility in applications where space is a problem.
The Series 94 also has many of the standard Watlow features, such as dual digital display, accuracy at a wide operating environment from 0 to 65˚C, at 115V~ line voltage power/0-60˚C for 230V~ power, easy setup with operator friendly prompts.
The Series 94 is manufactured by ISO 9001 registered Watlow Controls and reliably backed by a three-year warranty.
1
16 DIN temperature controller with a
±
0.1 percent of span,
Features and Benefits
Dual display
Displays limit set point and actual
Dual outputs
Provides limit/alarm capacity
NEMA 4X (IP65) certified (BSEN) (optional)
Offers water and dust resistance
Universal inputs
Offers wide range of sensor inputs
Lock-out facility
Offers high security
Output limit
Safety shut down in over-temperature condition
Flexible hi/low alarm output
Notifies of trouble
Programmable display default
Shows actual, limit or alarm default display information
percent
±0.1
Offers excellent range accuracy
accuracy
Your Authorized Watlow Distributor is:
WIN-94-109
Watlow Controls
A subsidiary of Watlow, Designer and Manufacturer of Industrial Heaters, Sensors and Controls
1241 Bundy Boulevard, Winona, Minnesota 55987-5580 USA Phone: +1 (507) 454-5300 FAX: +1 (507) 452-4507 Internet: www.watlow.com
© 1999 Watlow Electric Manufacturing Company Printed in the USA on Recycled Paper, 15% Postconsumer Waste
Specifications
Control Mode
• Microprocessor-based
• Single input, dual output
• Limit and alarm
Agency Approval
• FM approved, Class 3545, File J.I. 0D5A1.AF
Operator Interface
• Sealed membrane front panel
• Dual, 4-digit red or green displays
• Advance, Increment, Decrement, and Reset keys
Accuracy
Calibration accuracy and sensor conformity: ±0.1% of span, ±1
°C
@ 77°F ± 5°F/25°C ± 3°C ambient and rated line
voltage
• Accuracy span:1000°F/540°C minimum
• Temperature stability: ±0.2°F/°F or ±0.1°C/°C rise in ambient maximum
Voltage stability:±0.01% of span per percent of rated line voltage
Sensors/Inputs
• Thermocouple, grounded or ungrounded sensors
• RTD 2- or 3-wire, platinum, 100@ 0°C calibration to DIN curve (0.00385Ω/Ω/°C) or JIS curve (0.003916Ω/Ω/°C); user selectable
• Sensor break protection de-energizes limit output to protect system
• °F or °C display, user selectable
Input Range
Specified temperature ranges represent the controller’s operational span.
• Thermocouple
Type B 32 to 3308°F or 0 to 1820°C Type J 32 to 1382°F or 0 to 750°C Type K -328 to 2282°F or -200 to 1250°C Type N 32 to 2282°F or 0 to 1250°C Type S 32 to 2642°F or 0 to 1450°C Type T -328 to 662°F or -200 to 350°C
• RTD Resolution (DIN or JIS)
-328 to 1292°F or -200 to 700˚C
0.1° -199.9 to 999.9°F or -199.9 to 700.0˚C
Output 1 Limit
• Electromechanical relay
Output 2 Alarm
• Electromechanical relay
• Switched dc
• Solid state relay
Output Specifications
• Electromechanical relay or 30VÎ(dc) maximum, rated resistive load, without contact suppression.
• Switched dc signal provides a non-isolated minimum turn on voltage of 3VÎ(dc) into a minimum 500Ω load, maximum on voltage not greater than 12VÎ(dc) into an infinite load.
• Solid state relay 265V~ max. Opto-isolated, without contact suppression. Off state output impedance is 31MΩ.
Output Configurations
Output 1 selections: Limit Control
• Limit output
Output 2 selections:
• Process with flashing alarm message
• Process without alarm message
• Alarm with separate high and low set points
• Hysteresis: 1 to 9999°C/°F
United States Sales Offices: Atlanta/Greenville, (770)908-9164 • Austin, (512)249-1900 • Charlotte/Columbia, (704)541-3896 •
Chicago, (847)458-1500 • Cincinnati, (513)398-5500 • Cleveland, (330)467-1423 • Dallas, (972)422-4988 • Denver, (303)798-7778 • Detroit, (248)651-0500 • Houston, (281)355-6015 • Indianapolis, (317)575-8932 • Kansas City, (913)897-3973 • Los Ang eles, (714)935-2999 • Maryland/Virginia, (410)840-8034 • Minneapolis, (612)431-5700 • Nashville, (615)264-6148 • New England, (603)882-1330 • New Y ork/New Jersey/Philadelphia, (215)345-8130 • New Y ork, Upstate, (716)438-0454 • Orlando, (407)351-0737 • Phoenix, (602)708-1995 • Pittsburgh, (412)323-0548 • Portland, (503)245-9037 • St. Louis, (314)878-4600 • Sacramento, (707)425-1155 • San Diego, (760)728-9188 • San Francisco, (408)980-9355 • Seattle, (425)222-4090 • Tampa/St.Petersburg, (813)926-3600 • Tulsa, (918)496-2826 • Winston Salem/Raleigh, (336)766-9659 • Wisconsin, (414)723-5990
Asian Sales Offices: Australia, +61 (3) 9335-6449 • China, +86 (21) 6229-8917 • Japan, +81 (03) 5403-4688 • Korea, +82 (02) 563-5777 •
Singapore, +65 777-5488 • Taiwan, +886 (0) 7-261-8397 European Sales Offices: France, +33 (01) 3073-2425 • Germany, +49 (0) 7253-9400-0 • Italy, +39 (02) 458-8841 • United Kingdom, +44 (0) 115-964-0777 Latin American Sales Office: Mexico, +52 (42) 17-6235
For other product information, call Watlow’s FAX REPLY: United States +1 (800) 367-0430 • Outside the United States +1 (732) 885-6344
c
, Form C, 5A @ 120/240V~
c
, Form A, 0.5A @ 24V~ min. to
Line V oltage/Po wer
• 100-240V~ (85-264V~); 50/60Hz ±5%
• 12-24Vı(ac/dc) (10-26ı[ac/dc]); 50/60Hz ±5%
• Power consumption 7VA (12 to 24 12VA (100-240
• Data retention upon power failure via non-volatile memory
Operating Environment
• 32 to 149°F/0 to 65°C at 115
• 32 to 140°
• 0 to 90% RH, non-condensing
• Storage temperature: -40° to 185°F/-40° to 70°C
Terminals
• Size 6 universal head screw terminals accepts 20-14 gauge wire
Dimensions
Height 2.1" 53 mm Width 2.1" 53 mm Overall Depth 4.7" 119 mm Behind panel depth 4.1" 104 mm Weight 0.5 lb 0.2 kg
V~)
F/0 to 60°C at 230V~ line voltage power
Vı[ac/dc])
V~ line voltage power

Ordering Information

9 4 - 1 - 0 0
Series 94
Microprocessor-based
1
⁄16DIN, single input, dual output
4-digit displays
NEMA 4X (IP65)b Option
A = Without NEMA 4X (IP65) Rating B = With NEMA 4X (IP65) Rating
CE Option
A = Non CE Compliant B = CE Compliant
Output 1 (Limit)
D = Electromechanical relay, Form C, 5A,
without contact suppression
Output 2 (Alarm)
A = None
Switched dc output, non-isolated
C= D = Electromechanical relay, Form C, 5A,
without contact suppression
K = Solid state relay, Form A, 0.5A, without
contact suppression
Line V oltage/P ower
100-240V~ (high voltage)
0= 1=
12-24Vı(ac/dc)
(low voltage)
Display
Upper/Lower RR = Red/Red RG = Red/Green GR = Green/Red GG= Green/Green
a Electromechanical relays are not recommended for PID
control.They are warranted only for 100,000 contact closures.
b To effect NEMA 4X (IP65) rating requires a minimum
mounting panel thickness of 0.06 inch (1.5 mm) and surface finish not rougher than 0.000032 inch (0.000812 mm).
c Switching inductive loads (relay coils, etc.) requires using an
RC suppressor.
ac