Watlow 733 User Manual

Series 733/734
Total
Satisfaction
3 Year
Warranty
Time/Temperature
Control
Service Manual
Watlow Controls, 1241 Bundy Blvd., P.O. BOX 5580, Winona, MN 55987-5580, Phone: 507/454-5300, Fax: 507/452-4507
0600-0008-0000 Rev D November 1995
Supersedes without change: W733-XSMN Rev D00
$10.00
Made in the U.S.A.

Contents

This manual is a supplement to the Series 733/734 Program Manual. It is for configuring, servicing and calibrating your control. Use this manual in conjunc-
tion with the Series 733/734 Program Manual and Data Communications manual.
PageItem
Chapter 1
3 Install and Wire the Series 733/734 3 Dimensions 3 Panel Cutout 4 How to Wire the Series 733/734 5 Power Wiring 5 Input Wiring 8 Output 1 Wiring 9 Output 2 Wiring 10 Event Input Wiring 10 Event Output Wiring 10 Alarm Wiring 11 System Wiring Examples
Chapter 3
16 The Service Mode 17 Service Parameters 18 Service Mode Table
Chapter 4
20 Auto-Tuning 21 Manual Tuning
Chapter 5
22 The Calibration Mode 23 Calibration Parameters 24 Calibration Procedures
Chapter 2
12 The Setup Mode 12 Advancing Through the Setup Mode 12 Select or Change Setup Data Within the Mode 13 Setup Parameters 16 Setup ModeTable

Notes

˜
Informational notes alert you to important details. When you see a note icon, look for an explanation in the margin.

Safety Information

Boldface safety information protects both you and
your equipment. Please be attentive to them. Here are explanations:
ç
The CAUTION symbol (exclamation point) in the wide text column alerts you to a "CAUTION," a safety or functional hazard which could affect its performance. A full explanation is in the narrow column on the outside of the page.
your equipment
or
The WARNING symbol (lightning bolt) in the wide text column alerts you to a "WARNING," a safety hazard which could affect explanation is in the narrow column on the outside of the page.
you and the equipment
. A full
Appendix
30 Glossary 32 Index 33 Warranty/Returns 34 Specifications 35 Ordering Information 36 CE Declaration of Conformity 37 Notes 38 Notes

T echnical Assistance

If you encounter a problem with your Series 733/734 control, review all of your configuration information to verify that your selections are consistent with your application... Inputs, Outputs, Alarms, Limits, etc. If the problem persists after checking the above, you can get technical assistance by dialing: 1-507-454-5300
An Application Engineer will discuss your problem with you. Please have the following information available:
Complete model number • Revision number
All configuration information • User's manual The model and serial numbers can be found on the
outside of the case.

Your Feedback

Your comments or suggestions on the manual are welcome, please send them to: Technical Writer, Watlow Controls, 1241 Bundy Blvd., P.O. Box 5580, Winona, MN 55987-5580, or phone 507/454-5300. The Watlow Series 733/734 Service Manual and integral software are copyrighted by Watlow Winona, Inc., © 1995, with all rights reserved.
2
WATLOW Series 733/734 Service Manual
Install & Wire, Chapter 1

Chapter 1 Install and Wire the Series 733/734

Front panel mounting for ease of installation and service.
W
A
TL
W
Install
1.975
(50 mm)
(80 mm)
3.13"
2 4 6 7 9 11
1 3 5
SERIES 733
Series 733
R 0.125"
(3 mm) Max.
2.75"
(70 mm)
EVENT
10.625"
(270 mm)
LOAD 1READY
MENUS
81012
10.13"
(257 mm)
Panel Cutout
A
W
W
TL
(248 mm)
9.78"
˜
3.25"
(83 mm)
EVENT
READY LOAD 1
MENUS
1
2
3
4
5
6
8
11
3.25"
(83 mm)
9
12
7
10
SERIES 734
Series 734
10.625"
(270 mm)
Figure 1 ­Series 733 and 734 Dimensions.
Figure 2 ­Panel Cutout.
Use four #6-32 screws
Use four #6-32 screws
with press-in-nuts
with nutserts
(customer supplied)
(customer supplied)
0.27" Dia. (7 mm)
1. Make a panel cutout per the dimensions given above.
2. Drill four 0.265 (7mm) diameter holes per the dimensions given above.. See Figure 2.
3. Mount the Series 733 or 734 with four #6-32 screws using press-in-nuts, weld nuts, or equivalent…
Install & Wire, Chapter 1
WATLOW Series 733/734 Service Manual
˜
NOTE: For Series 734 orientation (verti­cal), rotate the panel cutout 90°.
3
Wiring

How to Wire the Series 733/734

The Series 733/734 wiring is illustrated by model number option. Check the terminal designation sticker on the control and compare your model number to those shown here and also the model number breakdown on the inside back cover of this manual.
When you apply power without sensor inputs on the terminal strip, the Series 733/734 display alternates parameter data and Er07 at a 3 second rate.
This error indicates an open sensor or A/D error. Remove power to the control and connect the sensor properly. All wiring and fusing must conform to the National Electric Code and to any locally applicable codes as well.
Use Figure 6 as a location reference when wiring your unit.
Figure 6 ­Series 733/734 Rear View.
9-pin
Event Input/
Output
Connector
Input/
Communications
Connector
12-pin
Output Wiring
Connector
4
WATLOW Series 733/734 Service Manual
Install & Wire, Chapter 1
1234567891011
12

Power Wiring

Wiring

Figure 7 -
ÅÅ
24V
Å (VAC) Power
ÅÅ
10
1
2
4
5
7
8
11
Wiring.
3
6
9
12
L2
Fuse
L1

Input Wiring

Use this wiring connector as a reference for terminal orientation. Each indi­vidual wiring breakdown will only show the terminals used. This connector only applies to input wiring and communications wiring.
WARNING: To avoid potential electric shock, use National Electric Code (NEC) safety practices when wiring and connect­ing this unit to a power source and to electrical sensors or peripheral devices.
Figure 8 ­Input Wiring Con­nector.
´ç
CAUTION: Input power limited to 15 watts maxi­mum. All compo­nents are rated for a maximum of 15 watts.
Install & Wire, Chapter 1
WATLOW Series 733/734 Service Manual
5
Input Wiring
˜
NOTE: Dual-zone thermo­couple units require at least one un­grounded thermocouple.
Thermocouple Input
73XX-1XXX-XXXX ˜(Dual Zone Only) 73XX-4XXX-XXXX
73XX-6XXX-XXXX 73XX-4XXX-XXXX
Zone 1 Zone 2
1
4
Figure 9 ­Thermocouple Wiring.
2
3
+
-
5
6
RTD Input
(Dual Zone Only)
73XX-2XXX-XXXX 73XX-5XXX-XXXX 73XX-5XXX-XXXX
Zone 1 Zone 2
3 Wire RTD
1
2
3 Wire RTD
4
5
+
-
Figure 10 ­2 or 3 Wire RTD Wiring.
6
WATLOW Series 733/734 Service Manual
3
1
2
3
2 Wire RTD
6
4
5
6
2 Wire RTD
Install & Wire, Chapter 1
0-5VDC or 0-10VDC Process Input
Model # 73XX-6XXX-XXXX (Dual Zone Only)
Input Wiring
Zone 2
4
5
6
+
-
0-20mA or 4-20mA Process Input
Model # 73XX-6XXX-XXXX (Dual Zone Only)
Figure 11 ­0-5VDC or 0-10VDC Process Input Wiring.
Install & Wire, Chapter 1
Zone 2
4
5
6
-
Figure 12 -
DC
I
+
WATLOW Series 733/734 Service Manual
0-20mA or 4-20mA Process Input Wiring.
7

Output 1 Wiring

AC Output Wiring - Zone 1
Figure 13 ­AC Output 1 Wiring.
Solid State Relay
with
Mechanical Relay
with
Contact Suppression Contact Suppression
Form A, 0.4 Amps Form A, 1 Amp Off state impedance: 20K max. Off state impedance: 20K min. 73XX-XBXX-XXXX 73XX-XDXX-XXXX
Solid State Relay
without
Solid State Relay
without
Contact Suppression Contact Suppression
Form A, 0.4Amps Form A, 1 Amp Off state impedance: 31M max. Off state impedance: 20k max. 73XX-XKXX-XXXX 73XX-XEXX-XXXX
10
7
8
11
9
12
L1
COM
1
2
3
4
5
6
Fuse
L2
External
Load
Figure 14 ­DC Output 1 Wiring.
DC Output Wiring - Zone 1
Switched DC (Open Collector) 4-20mA Process Output
Non-isolated Non-isolated Minimum load resistance: 500 Load impedance: 600 max. 73XX-XCXX-XXXX 73XX-XFXX-XXXX
ÅÅ
0-5V
Å (VDC) Process Output
ÅÅ
Non-isolated Load impedance: 10K min. 73XX-XHXX-XXXX
10
1
-
+
2
3
4
5
6
+
External
Load
-
7
8
11
9
12
8
WATLOW Series 733/734 Service Manual
Install & Wire, Chapter 1
AC Output Wiring - Zone 2
Output 2 Wiring
Solid State Relay
with
Mechanical Relay
with
Contact Suppression Contact Suppression
Form A, 0.4 Amps Form A, 1 Amp Off state impedance: 20K max. Off state impedance: 20K min. 73XX-XXBX-XXXX 73XX-XXDX-XXXX
Solid State Relay
without
Contact Suppression
Form A, 04 Amps Off state impedance: 31M max. 73XX-XXKX-XXXX
NO
1
2
3
External
COM
4
Load
5
6
Fuse
7
8
11
9
12
L2
L1
10
Figure 15 ­AC Output 2 Wiring.
DC Output Wiring - Zone 2
Switched DC (Open Collector) 4-20mA Process Output
Non-isolated Non-isolated Minimum load resistance: 500 Load impedance: 600 max. 73XX-XXCX-XXXX 73XX-XXFX-XXXX
ÎÎ
0-5V
Î (VDC) Process Output
ÎÎ
Non-isolated Load impedance: 10K min. 73XX-XXHX-XXXX
+
External
Load
-
+
-
10
1
2
3
4
5
6
7
8
11
9
12
Figure 16 ­DC Output 2 Wiring.
Install & Wire, Chapter 1
WATLOW Series 733/734 Service Manual
9

Optional Wiring

1
23
4
5
6
7
89
Event 1
Event 2
Event 3
Event 4
-
-
-
-
+
Internal +5 Volt
SSR
Customer Supplied
+
+
+
SSR
SSR
SSR
Alarm
+
-
˜
NOTE: Event Input is not available on stan­dard Series 733/734 controls. Consult factory for more information.
Event Input Wiring
2 Event Inputs Non-isolated 73XX-XXX1-XXXX
Event Input 1
4
1
5
23
7
89
Figure 17 ­Event Input Wiring.
Figure 18 ­Event Output Wiring.
Event Output Wiring
4 Event Outputs Open Collector, Non-isolated 5mA Maximum Per Event 73XX-XXX1-XXXX
6
Event Input 2
Common
Alarm Wiring
Single Alarm Mechanical Relay with Contact Suppression Form A, 1 Amp
Figure 19 -
10
Alarm Wiring.
WATLOW Series 733/734 Service Manual
73XX-XXXX-DXXX
1
2
3
4
5
6
7
8
11
9
12
COM
10
Fuse
L1
L2
External
Load
Install & Wire, Chapter 1
L1
L2 A001-0249-0001
Over
Temp
Light

System Example

73XX-1CA0-AXXX
(-)
3
(+)
2
1
2
3
69
3 2
Coil
High Limit
Mechanical
Contactor
SSR-240-10G-DC1
(+)
NO
142A-36XX-1200
UL recognized
safety limit control
NC
C
Figure 20 ­System Wiring
TC
(+)
L1
ResetL2
Normally Open
Momentary
Switch
(-)
Limit
Sensor
(-)
Example.
Process Sensor
L2
1
3
4
6
69
A001-0249-0001
2
5
4
5
6
7
1
8
1 2
9
10 11
12 13 14
1
15
Install & Wire, Chapter 1
7 8
20
(+)
11
14
(-)
1 CR-1
2 3
73XX-1CA0-AXXX
910
(+)
12 13
L1 L2
15
Reset
16
COM
17
TC (+)
18
TC (-)
COM
Series 733
32
SSR-240-10G-DC1
(-)
Series 142
142A-36XX-1200
UL recognized
safety limit control
N.O.
N.C.
Heater
R
21
Hi Temp. Light
Figure 21 ­Series 733/734 Ladder Diagram Example.
2
1CR
19
2
2
WATLOW Series 733/734 Service Manual
11
Setup
t
d
0
F
e
e
t
e
m
e
w
h
s
w
t
e
w
h
s
w
h
e
t
e
y
h
e
u
)
)
)
)
)
)
)
)
)
)
)
)
)
)

Chapter 2 The Setup Mode

Use the key sequence below to enter the Setup Mode.

Advancing Through The Setup Mode

Press the TIME key .

Select or Change Setup Data Within The Mode

Figure 22 ­Setup Mode Key Flow.
˜
NOTE: Changing the C_F, InP_, tS, rL_, rH_ parameters will default all menus.
Use the UP/DOWN keys . After 1 minute with no key activactions, the Series 733/734 reverts to the Operation mode [0)º0].
W
A
TL
SERIES 733
EVENT
C _ gb
rtd tcnP
tS SIL
LAt InP1
rL1 rH1
HyS1 AL1
A1LO A1HI
MENUS
W
LOAD 1READY
81012 1 3 5 2 4 6 7 9
( (
( (
( (
( ( ( (
( (
( (
11
Celsius_Fahrenhei Guard ban
RTD calibration curv Temperature comp. (WatCurv
Menu time selec Alarm silenc
Latching for alar Zone 1 input typ
Zone 1 range lo Zone 1 range hig
Zone 1 hysteresi Zone 1 alarm typ
Zone 1 alarm lo Zone 1 alarm hig
= Parameter may not appear depending
on control configuration
= Only appears if your unit has communications.
See the Series 733/734 data communications manual for more information.
CAL1 InP2
rL2 rH2
HyS2 AL2 A2LO
A2HI CAL2
bAUd dAtA
Prot Addr
( ) ( )
( ) ( )
( ) ( )
( ) ( ) ( ) ( )
( ) ( )
( )
00 : 0
Zone 1 calibration offse Zone 2 input typ
Zone 2 range lo Zone 2 range hig
Zone 2 hysteresi Zone 2 alarm typ Zone 2 alarm lo
Zone 2 alarm hig Zone 2 calibration offse
Baud rat Data bits and parit
Protocol type Address
Operation Men
12
WATLOW Series 733/734 Service Manual
Setup Mode, Chapter 2