Vulcan Hart EF3 Manuel de service

Page 1
SERVICE MANUAL
EF SERIES GAS FRYERS
MODELS
EF3 ML-52099 EF4 ML-114943 EF5 ML-114944
- NOTICE -
This manual is prepared for the use of trained Vulcan Service Technicians and should not be used by those not properly qualified. If you have attended a Vulcan Service School for this product, you may be qualified to perform all the procedures described in this manual.
This manual is not intended to be all encompassing. If you have not attended a Vulcan Service School for this product, you should read, in it's entirety, the repair procedure you wish to perform to determine if you have the necessary tools, instruments and skills required to perform the procedure. Procedures for which you do not have the necessary tools, instruments and skills should be performed by a trained Vulcan Service Technician.
Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.
For additional information on Vulcan-Hart or to locate an authorized parts
and service provider in your area, visit our website at www.vulcanhart.com
VULCAN-HART DIVISION OF ITW FOOD EQUIPMENT GROUP, LLC
WWW.VULCANHART.COM
P.O. BOX 696, LOUISVILLE, KY 40201-0696
TEL. (502) 778-2791
F-35641 (2-05)
Page 2
EF SERIES GAS FRYERS
CONTENTS
GENERAL .......................................................................................................................................... 3
INTRODUCTION ........................................................................................................................ 3
Models ................................................................................................................................ 3
INSTALLATION .......................................................................................................................... 3
OIL FILTERING .......................................................................................................................... 3
OPERATION .............................................................................................................................. 3
CLEANING ................................................................................................................................. 3
LIGHTING PILOT ....................................................................................................................... 3
SPECIFICATIONS ..................................................................................................................... 3
Gas Data ............................................................................................................................ 3
TOOLS ....................................................................................................................................... 3
Standard............................................................................................................................. 3
REMOVAL AND REPLACEMENT OF PARTS .................................................................................. 4
COVERS AND PANELS ............................................................................................................ 4
Door.................................................................................................................................... 4
Heat Shield......................................................................................................................... 4
BURNERS.................................................................................................................................. 5
THERMOSTAT ........................................................................................................................... 5
HIGH LIMIT ................................................................................................................................ 7
THERMOPILE ............................................................................................................................ 8
PILOT ORIFICE ......................................................................................................................... 9
PILOT ......................................................................................................................................... 9
COMBINATION VALVE ............................................................................................................ 10
FRY TANK .................................................................................................................................11
SERVICE PROCEDURES AND ADJUSTMENTS ........................................................................... 12
MILLIVOLT CONTROLS TEST ................................................................................................ 12
THERMOSTAT CALIBRATION ................................................................................................ 12
Calibration Steps .............................................................................................................. 12
PILOT ADJUSTMENT .............................................................................................................. 13
BURNERS, NOZZLES AND ORIFICES .................................................................................. 13
Burners ............................................................................................................................. 13
Nozzles and Orifices ........................................................................................................ 13
COMBINATION VALVE REGULATOR ADJUSTMENT............................................................ 14
ELECTRICAL OPERATION ............................................................................................................. 16
CONTROL SYSTEM DESCRIPTION ...................................................................................... 16
SYSTEM CONDITION QUICK CHECK PROCEDURES ......................................................... 17
SCHEMATIC ............................................................................................................................ 17
COMPONENT FUNCTION ...................................................................................................... 17
TROUBLESHOOTING ..................................................................................................................... 18
F35641 (02-05)
— 2 —
Page 3
GENERAL
EF SERIES GAS FRYERS
INTRODUCTION
Models
This service manual was written for: EF3, EF4 and EF5 Gas Fryers.
INSTALLATION
Generally, installations are made by the dealer or contracted by the dealer or owner. Detailed installation instructions are included in the Installation and Operation Manual, which is sent with each fryer.
OIL FILTERING
Filtering instructions are included in the Installation and Operation Manual.
4. While still holding knob in light the pilot with a taper. Continue to depress knob (approximately 30 seconds) until the pilot remains lit after the knob is released. If pilot does not remain lit, repeat steps 2, 3 & 4.
5. Turn gas control valve knob to ON.
6. If gas supply is interrupted, repeat steps 1-5.
SPECIFICATIONS
Gas Data
MODEL NO. TUBES BTU/HR
EF3 3 90,000 EF4 4 120,000 EF5 5 150,000
OPERATION
Detailed operation instructions are included with each fryer in the Installation and Operation Manual.
CLEANING
Detailed cleaning procedures are included in the Installation and Operation Manual.
LIGHTING PILOT
1. Turn thermostat OFF.
2. Turn gas control valve knob to OFF/PILOT. Wait 5 minutes.
3. Push the gas control valve knob in.
TOOLS
Standard
Hand tools (standard set)
VOM with AC current tester (any quality VOM with a sensitivity of at least 29,000 ohms per volt can be used)
Gas test kit
Temperature tester (thermocouple type)
Manometer
— 3 —
F35641 (02-05)
Page 4
EF SERIES GAS FRYERS
REMOVAL AND REPLACEMENT OF PARTS
COVERS AND PANELS
WARNING: SHUT OFF THE GAS BEFORE
SERVICING.
Door
1. While holding onto the door remove (2) screws securing the door hinge to the fryer bottom front flange (Figure 1).
Heat Shield
1. Remove screws holding heat shield in place (Figure 2).
Figure 1
2. Prepare to catch door assembly. Once screws and hinge are removed, the door will drop off into your hand(s).
3. Reinstall door assembly by reversing steps 1 & 2 above.
F35641 (02-05)
Figure 2
2. Remove heat shield.
— 4 —
Page 5
BURNERS
WARNING: SHUT OFF THE GAS BEFORE
SERVICING.
1. Remove heat shield as outlined under
Cover and Panels. (Optional)
2. Loosen the two mounting bolts at the top
of each burner (Figure 3).
EF SERIES GAS FRYERS
Figure 3
3. Push burner up while pulling the bottom
of the burner forward to clear the burner nozzle (Figure 4).
Figure 4
4. Reverse the procedure to install.
THERMOSTAT
WARNING: SHUT OFF THE GAS BEFORE
SERVICING.
1. Drain shortening from fry tank.
2. Remove heat shield as outlined under Covers and Panels.
3. Remove left burner as outlined under Burners.
4. Remove thermostat knob by pulling knob off thermostat shaft.
— 5 —
F35641 (02-05)
Page 6
EF SERIES GAS FRYERS
5. Remove thermostat mounting screws and remove thermostat from mounting bracket (Figure 5).
7. Loosen the packing nut and holding nut (Figure 7).
Figure 7
Figure 5
6. Remove wire leads from the rear of the thermostat, noting all connections for reassembly (Figure 6).
8. Remove the thermostat bulb from the clamp (Figure 8).
F35641 (02-05)
Figure 8
9. Pull the thermostat bulb through the underside of the fry tank and remove the thermostat assembly.
Figure 6
— 6 —
Page 7
EF SERIES GAS FRYERS
10. Reverse the procedure to install. When installing the new thermostat assembly, do not kink the thermostat capillary. Wrap threads of packing nut with Teflon tape to prevent leakage.
HIGH LIMIT
WARNING: SHUT OFF THE GAS BEFORE
SERVICING.
1. Drain shortening from fry tank.
2. Remove heat shield as outlined under Covers and Panels.
3. Remove wire leads from high limit, noting all connections for reassembly (Figure 9).
6. Loosen the packing nut and the holding nut (Figure 10).
Figure 10
Figure 9
4. Remove high limit from mounting bracket.
5. Remove left burner as outlined under Burners.
7. Remove the high limit bulb from the clamp (Figure 11).
— 7 —
Figure 11
F35641 (02-05)
Page 8
EF SERIES GAS FRYERS
8. Pull the high limit bulb through the underside of the fry tank and remove the high limit.
9. Reverse the procedure to install. When installing the new high limit assembly, do not kink the high limit capillary. Wrap threads of packing nut with Teflon tape to prevent leakage.
THERMOPILE
WARNING: SHUT OFF THE GAS BEFORE
SERVICING.
WARNING: ALL GAS JOINTS DISTURBED DURING SERVICING MUST BE CHECKED FOR LEAKS. CHECK WITH SOAP AND WATER SOLUTION (BUBBLES). DO NOT USE AN OPEN FLAME.
1. Remove the screw securing the Pilot/ Thermopile Assembly Bracket to the tank front. Lower the assembly away from the tank (Figure 12).
2. Disconnect thermopile lead wires as outlined under High Limit.
Figure 12
F35641 (02-05)
— 8 —
Page 9
EF SERIES GAS FRYERS
3. Remove thermopile from pilot bracket by
loosening the holding nut (Figure 13).
Figure 13
4. Reverse procedure to install.
PILOT
WARNING: SHUT OFF THE GAS BEFORE
SERVICING.
WARNING: ALL GAS JOINTS DISTURBED DURING SERVICING MUST BE CHECKED FOR LEAKS. CHECK WITH SOAP AND WATER SOLUTION (BUBBLES). DO NOT USE AN OPEN FLAME.
1. Remove the screw securing the Pilot/ Thermopile Assembly Bracket to the tank front. Lower the assembly away from the tank (Figure 12).
2. While holding assembly in the palm of your hand remove the pilot compression fitting at the bottom of the pilot and disconnect the pilot tubing (Figure 12).
3. Remove thermopile as outlined under Thermopile (set aside for reassembly).
PILOT ORIFICE
WARNING: SHUT OFF THE GAS BEFORE
SERVICING.
WARNING: ALL GAS JOINTS DISTURBED DURING SERVICING MUST BE CHECKED FOR LEAKS. CHECK WITH SOAP AND WATER SOLUTION (BUBBLES). DO NOT USE AN OPEN FLAME.
1. Remove the screw securing the Pilot/ Thermopile Assembly Bracket to the tank front. Lower the assembly away from the tank (Figure 12).
2. While holding assembly in the palm of your hand remove the pilot compression fitting at the bottom of the pilot to expose the orifice (Figure 12).
3. Replace orifice and reverse procedure to assemble.
4. Remove (2) screws holding the pilot assembly to the Pilot/Thermopile Assembly Bracket and replace the old pilot with the new assembly (Figure14).
— 9 —
Figure 14
5. Reinstall by reversing steps 1-4.
F35641 (02-05)
Page 10
EF SERIES GAS FRYERS
COMBINATION VALVE
WARNING: SHUT OFF THE GAS BEFORE
SERVICING.
WARNING: ALL GAS JOINTS DISTURBED DURING SERVICING MUST BE CHECKED FOR LEAKS. CHECK WITH SOAP AND WATER SOLUTION (BUBBLES). DO NOT USE AN OPEN FLAME.
1. Disconnect fryer from main gas supply.
2. Remove heat shield as outlined under Covers and Panels. (Optional)
3. Remove right burner as outlined under Burners.
4. Disconnect wire leads from the combination valve and mark for reconnecting.
5. Disconnect pilot tubing from combination valve (Figure 15).
6. Disconnect combination valve union and pressure fitting (Figure 16).
Figure 16
7. Remove the combination valve from the fryer.
8. Remove all pipe fittings from the old combination valve if the new valve is not supplied with fittings.
Figure 15
9. Reverse procedure to install using original pipe fittings.
F35641 (02-05)
— 10 —
Page 11
EF SERIES GAS FRYERS
FRY TANK
WARNING: SHUT OFF THE GAS BEFORE
SERVICING.
WARNING: ALL GAS JOINTS DISTURBED DURING SERVICING MUST BE CHECKED FOR LEAKS. CHECK WITH SOAP AND WATER SOLUTION (BUBBLES). DO NOT USE AN OPEN FLAME.
1. Disconnect fryer from main gas supply.
2. Remove baskets, fryer basket hanger and crumb screen.
3. Drain oil from tank.
4. Remove heat shield as outlined under Covers and Panels.
5. Remove screws holding fryer tank (Figure 17).
7. Remove the manifold bracket from the tank assembly by removing the (4) bolts (Figure 18).
Figure 18
8. Remove thermostat and high limit as outlined under Thermostat and High Limit.
Figure 17
6. Remove burners as outlined under Burners.
9. Remove the screw securing the Pilot/ Thermopile Bracket Assembly (Figure 19).
Figure 19
10. Lift the fry tank up and out of cabinet. Carefully place the tank assembly on the floor (this procedure requires two people).
— 11 —
11. Remove the tank ball drain valve (Figure 18).
12. Reverse the procedure to install new tank.
F35641 (02-05)
Page 12
EF SERIES GAS FRYERS
SERVICE PROCEDURES AND ADJUSTMENTS
MILLIVOLT CONTROLS TEST
1. Verify proper gas (natural or propane) is present.
2. Check for correct wiring and secure connections.
3. Verify the pilot flame is adjusted properly as outlined in Pilot Adjustment.
4. If the pilot is not lit, light pilot as outlined under Lighting Pilot. Allow the pilot to burn for 3 to 4 minutes to stabilize.
A. If the pilot remains lit, proceed to
step 6.
B. If the pilot will not remain lit, proceed
to step 5.
5. Connect DC voltmeter to terminals TH-PG and PG of combination valve. Relight the pilot, hold the gas control valve knob in and allow the pilot to burn for 3 to 4 minutes to stabilize.
A. lf the voltage measures 450 millivolts
or greater and the pilot will not stay lit, replace the combination valve.
B. lf the voltage is less than 450 millivolts,
measure the voltage at terminals NO and C of high limit.
7. Turn gas control valve knob to ON. Turn thermostat to a setting higher than the shortening temperature.
A. If the voltage measures 150 millivolts
or more but the burners do not ignite, replace the combination valve.
B. If the voltage is less than 150 millivolts,
measure the voltage between terminals NO of the high limit and PG of the combination valve.
1) If the voltage is 200 millivolts or greater, replace the thermostat.
2) If the voltage is less than 200 millivolts, replace the combination valve.
THERMOSTAT CALIBRATION
1. Place temperature tester in the fry tank near the thermostat bulb.
2. Set the thermostat to 300°F and allow the temperature to stabilize.
3. Check the temperature tester reading against the thermostat dial reading. If there is a variance of more than ±20°F (280°F to 320°F), calibration is required.
1) If the voltage is 500 millivolts or more, replace the high limit.
2) If the voltage is less than 500 millivolts, disconnect the lead wire from terminal TH-PG of the combination valve and remeasure voltage at the high limit.
a. If the voltage is less than 500
millivolts, replace the thermopile.
b. If the voltage is 500 millivolts or
more, replace the combination valve.
6. Connect DC voltmeter to terminals PG and TH of combination valve.
F35641 (02-05)
Calibration Steps
1. Remove thermostat knob from shaft.
2. Using a small screwdriver, rotate the setscrew inside the hollow shaft counterclockwise to increase the temperature or clockwise to decrease the temperature (1/4 turn equals approx­imately 18°F).
3. Allow temperature to stabilize and recheck temperature. Repeat until the temperature falls within the limits as stated in step 3 under Thermostat Calibration.
4. Install thermostat knob and set dial to 350°
— 12 —
Page 13
5. Allow temperature to stabilize at new setting and compare temperature tester to dial setting. Recalibrate if the temperature does not fall within the range of 330°F to 370°F.
6. If the temperature does not fall within the limits at both settings, replace the thermostat.
PILOT ADJUSTMENT
EF SERIES GAS FRYERS
1. Light pilot as outlined under Lighting Pilot.
2. If the flame does not extend beyond the outer edges of the pilot shield 1/2”, or extends more than 1/2”, (Figure 20), an adjustment is necessary.
Figure 20
3. Remove the cap covering pilot adjustment screw, (Figure 21). Turn the recessed pilot adjustment screw counterclockwise to increase the size of the flame or clockwise to decrease the size of the flame.
Figure 21
BURNERS, NOZZLES
AND ORIFICES
WARNING: SHUT OFF THE GAS BEFORE
SERVICING.
Burners
If the burner ports become clogged, the fryer will not operate properly. If the burner is cracked, it must be replaced.
1. Remove burner(s) as outlined under Burners.
2. Check burner(s) for cracks and clogged ports.
3. If the ports are clogged, wash burner(s) in warm, soapy water. If this does not remove obstructions, a #37 drill bit can be used (do not use in an electric drill; hand-turn only).
Nozzles and Orifices
— 13 —
1. Remove the burners as outlined under Burners.
F35641 (02-05)
Page 14
EF SERIES GAS FRYERS
2. Hold the burner nozzle with channel locks and remove the orifice, (Figure 22). Check the orifice for obstructions or damage.
Figure 22
1. Turn the gas control valve knob to OFF (Figure 23).
Figure 23
2. Remove the plug from the submanifold and install pressure gauge at this point (Figure 24).
3. If the orifice is clogged, wash the orifice in warm, soapy water. If this does not remove obstructions, a #37 drill bit can be used (do not use in an electric drill; hand-turn only).
4. With channel locks, remove the burner nozzle (Figure 22).
5. Reverse procedure to install new burner nozzle and orifice.
COMBINATION VALVE
REGULATOR ADJUSTMENT
WARNING: SHUT OFF THE GAS BEFORE
SERVICING.
Accurate gas pressure adjustments can only be made with the gas on and the burner lit. If the incoming line pressure to the valve is less than the minimum stated, then the pressure cannot be set correctly.
Figure 24
3. Turn on the gas and light the pilot as outlined under Lighting Pilot.
4. Turn the gas control valve knob to ON.
5. Set the thermostat so the burners will come on.
The combination valve is preadjusted for natural or propane gas as specified on the rating plate. The natural gas rating is 4” W.C., and the propane rating is 10" W.C.
F35641 (02-05)
— 14 —
Page 15
6. Read the pressure gauge. The manifold pressure reading should match the pressure rating on the data plate.
A. To adjust, remove the cap covering
the manifold pressure adjustment screw (Figure 25). Turn the recessed manifold pressure adjustment screw counterclockwise to decrease pressure or clockwise to increase pressure.
EF SERIES GAS FRYERS
Figure 25
7. Install the cap and check for proper operation.
— 15 —
F35641 (02-05)
Page 16
EF SERIES GAS FRYERS
ELECTRICAL OPERATION
CONTROL SYSTEM
DESCRIPTION
1. The thermopile (PG) provides the total control voltage for this system.
A. One side of the thermopile is
connected to the common (C) of the high limit (HL).
B. The other side of the thermopile is
connected to the normally open (NO) contacts of the high limit.
C. The common of the high limit (below
the high limit trip temp.) is connected through the normally closed (NC) contacts of the high limit, through wire 3 to the combination valve pilot connection common.
D. The other side of the pilot valve is
connected through wire 4 to wire 1 to the high limit normally open contacts which hold the pilot valve open.
C. When the thermostat calls for heat
(closed circuit) power from the thermopile is then connected to the other combination valve thermostat connection through wire 2.
D. If the high limit trips, the thermopile is
connected across zero ohms, the output voltage of the thermopile drops to 0.0 millivolts, and the thermostat coil of the combination valve drops out, shutting the thermostat valve.
3. Total Shutdown.
A. When the high limit trips, 0.0 millivolts
will read across both coils of the combination valve, causing both valves to close.
B. Pilot relight cannot be accomplished
until oil cools sufficiently to allow high limit to close.
C If any wire in the system is cut or
broken, the system will shut down.
1) If the high limit trips, connection is made from the common to the normally open contacts, turning off pilot valve voltage. The gas valve closes.
2. Thermostat Control.
A. One side of the millivolt supply is
connected through the high limit system, as described above, to the thermostat common (wire 3) of the combination valve.
B. The other side of the thermopile is
connected from the normally open contacts of the high limit to the thermostat through wire 1.
F35641 (02-05)
— 16 —
Page 17
EF SERIES GAS FRYERS
SYSTEM CONDITION QUICK
CHECK PROCEDURES
1. Use the Pilot Lighting procedure and check millivolts (mV) at wires 3 and 4.
A. lf the pilot lights, then pilot combination
valve and high limit are good.
B. If the pilot will not stay lit, check high
limit and open the thermopile circuit. It should read 300 mV; if there are Ø volts, check high limit. If the high limit is good, replace combination valve.
C. Check for voltage at disconnected
thermopile. It should read 300 mV; if there are Ø volts, replace thermopile. Check high limit. If the high limit is good, replace combination valve.
2. Turn on thermostat; burners should light.
A. lf the burner does not light, check the
following:
SCHEMATIC
1) Voltage at combination valve at wires 2 and 4.
2) If correct voltage is present, then check combination valve.
3) If there are Ø volts, check voltage between wire 3 of combination valve and wire 1 of thermostat. If correct voltage is present, then check resistance of the thermostat contacts and continuity of wires 3 & 2.
Figure 26
COMPONENT FUNCTION
Thermostat - Millivolt type with capillary bulb, single-throw break on temperature rise. Temperature range of 200°F to 400° F.
Thermopile - Millivolt control with 24" capillary. Rated to generate 500 millivolts.
Combination Valve - Regulates gas flow to burner and pilot. Provides pilot safety.
High Limit - Prevents overheating of fryer in the event of thermostat failure. Opens at 465°F and automatically resets at 415°F.
— 17 —
F35641 (02-05)
Page 18
EF SERIES GAS FRYERS
TROUBLESHOOTING
SYMPTOM
The temperature of the shortening drops, or excessive recovery time is required.
Pilot won’t stay lit. Fryer shuts off.
Rapid shortening breakdown, crumbs and specks in frying compound.
CAUSE
Insufficient gas supply to unit.
Ventilation system pulling heat out of heat exchanger and flue box.
Overloading fryer capacity. Malfunctioning thermopile
or loose/dirty connection in thermopile.
Malfunctioning shutoff valve.
Pilot burner orifice and air openings need cleaning.
Excessive temperature settings (over 375° F).
Shortening not being filtered regularly.
REMEDY
Adjust gas supply at gas combination valve.
Relocate fryer.
Adjust loads accordingly. Check thermopile function and
connections. Adjust or replace as required.
Replace shutoff valve.
Clean burner orifice and air openings as required.
Adjust temperature setting.
Adjust filtering schedule.
Incorrect preparation of breaded food.
Do not use salt.
Allow breading time to adhere to food.
Do not allow loose flour to fall into shortening from hands.
Do not add strainings or drippings from meat fats to shortening.
Use correct shortening and follow temperature recommendations.
Take out 10% to 15% of the shortening.
Check thermostat settings with thermometer periodically.
F35641 (02-05)
— 18 —
Page 19
EF SERIES GAS FRYERS
SYMPTOM
Leaking tank.
Pilot burner flames adjusted properly, but fluctuates to very low and blows out easily.
CAUSE
Foam-over by depleted shortening permits oil to drip from the tank surface, giving appearance of leaking.
Careless draining procedures.
Carbon buildup causes rapid attack on tank by promoting acid formulation.
Gas pressure too low.
Gas pressure too low at submanifold.
REMEDY
Replace shortening.
Gas control valve knob should be in PILOT or OFF position before draining oil. Burners heating an empty tank will damage tank joints.
Clean tank surfaces.
Check gas pressure on submanifold fitting when fryer is in operation.
Check other equipment attached to same gas line.
Adjust gas pressure at submanifold to not less than 4.0” W.C. (natural and mixed gas) or 10.0” W.C. for propane gas.
— 19 —
F35641 (02-05)
Page 20
F35641 (02-05)
PRINTED IN U.S.A.
Loading...