Vogt HDD-131 Installation Manual

Page 1
Air-Cooled Condenser
Installation Instructions
Revision Date: 12/21/98
Page 2
HES Series Air-Cooled Installation Instructions
These installation guidelines must be followed to obtain reliable operation from
air-cooled ice machines. If these guidelines are not followed, the compressor
1. Use only Vogt approved condensers. Any exceptions to this policy must be obtained in writing
prior to installation and operation of the ice machine.
2. Outdoor condensers must be installed with vertical air flow. Indoor condensers used for heat
recovery may be installed with either horizontal or vertical air flow.
3. The condenser must be mounted above the ice machine, with liquid refrigerant from the
condenser outlet draining freely (1/4” per foot slope) in the direction of normal operating flow (back to the ice machine) with no traps in the liquid line.
4. Flooding head pressure controls such as Alco Headmaster are not to be used, since they cause
excessive subcooling of the returned liquid refrigerant and interfere with reliable ice harvest.
5. The discharge and liquid lines must be insulated with 1/2” thick Armaflex insulation or equal.
6. Horizontal runs in the discharge line should slope 1/4” per foot in the normal direction of flow
(away from the ice machine).
7. Traps must be installed in discharge lines at the base of all vertical risers. There should be no
intentional traps in liquid lines. Trap volume should be kept to a minimum. Typical details are shown in FIGURE-10. Long vertical runs should have traps every 20 feet.
8. Use only ACR grade copper pipe, Type L. Recommended line sizes are shown in TABLE-3.
9. Distance between ice machine and condenser must not exceed 150 equivalent feet. Refer to
Condenser Equivalent Line Size worksheet. (see TABLE-5)
10. Condensers must be provided with a cold weather valve kit per FIGURE-9A. These valves
allow one-half of the condenser to be disabled in cold weather. Running the ice machine with one half the condenser in cold weather makes it easier to maintain minimum necessary condensing pressure, particularly in windy conditions. The coil thermostat should be set to close at 35?F. for multiple fan condensers or 50?F for single fan condensers.
11. Condensers with multiple fans must be provided with a thermostat to turn off unneeded fans in
cold weather. Turning off unneeded fans reduces on-off cycling of the fan(s) and allows for a steadier condensing pressure. The fan thermostat should be set at 50?F.
12. When extreme cold conditions are expected or encountered (temperatures below 0?F and wind
greater than 15 MPH), it may be necessary to install a protective enclosure around the condenser. Other apparatuses such as louvers may be used. Contact the factory for suggestions.
! WARNING !
warranty will not be honored.
! WARNING !
2
Page 3
HES Series Air-Cooled Installation Instructions
13. After installation, the field-installed lines are to be evacuated to a vacuum of 500 microns or less
and held for at least one hour. Use ¼” access connection located on compressor discharge line and liquid return line (32). After the vacuum pump is removed, vacuum should hold at 500 microns or less for at least 5 minutes and the lines pressurized with R-22 to 25 psig minimum.
14. The volume of refrigerant supplied with the machine is sufficient to fill the condenser and
condenser lines when length of pipe (one way) is 75 feet or less. When the length of lines is longer than 75 feet, additional refrigerant must be added as noted below. Instructions for adding refrigerant are included further in these instructions.
Liquid Line Size 75 ft. 100 ft. 125 ft. 150 ft.
1/2” none None None 2 5/8” none 2 4 6 7/8” none 4 8 12
1-1/8” none 6 12 18
Pounds R-22 to Add Vs. Liquid Line Length
15. All piping must be done in accordance with applicable local and national codes. Such codes may
include “The Safety Code for Mechanical Refrigeration (ANSI B9.1), and “The Code for Refrigerant Piping” (ANSI B31.5).
16. The following installation guidelines are strongly suggested. While they do not affect the
machine warranty, they may be required for safe operation, and to comply with all applicable electrical and mechanical codes.
TABLE - 3
17. Local electrical code must be checked for wiring method.
18. The installer must provide a lockable disconnect switch(s) adjacent to the condenser. The power
is fused at the machine by a 15 amp breaker.
19. Electrical connections between the condenser and the Tube-Ice
®
machine require minimum 12
ga. wire. See FIGURE-11 &12.
20. All electrical fittings and components exposed to the weather must be suitable for outdoor
installation.
The design total heat rejection for each Tube-Ice® machine, the recommended air-cooled condenser, and condenser physical and electrical data are shown in TABLE-2. Only the condensers shown are UL listed with the ice machines. Other condensers may be individually UL listed, but are not UL listed with the Tube-Ice® machines, and cannot be recommended by Vogt Tube-Ice. Catalog energy efficiency ratings of the ice machines are based on use of the recommended condenser.
Condensers supplied by Vogt must be utilized. The use of non-Vogt condensers will void the compressor warranty. For continuous operation at ambient above 105?F, consult the factory about using a larger condenser.
3
Page 4
HES Series Air-Cooled Installation Instructions
Ice Machine Model HE20 HE30 HE40
Recommended Condenser HDD-61 (HDD-101) HDD-101 (HDD-131) HDD-131 (HDD-191)
Note: For continuous operation at ambients above 105 °F, use larger condenser shown in parenthesis
Total Heat Rejection: BTU/hr at 60 Hz. BTU/hr at 50 Hz. Fans: Number HP, Each Total, CFM Full Load Amps:
1 ph., 208/230V, 60 Hz 3 ph., 208/230V, 60 Hz 3 ph., 460V, 60 Hz 1 ph., 200/220V, 50 Hz 3 ph., 200/220V, 50 Hz 3 ph., 400V, 50 Hz
Locked Rotor Amps:
1 ph., 208/230V, 60 Hz 3 ph., 208/230V, 60 Hz 3 ph., 460V, 60 Hz 1 ph., 200/220V, 50 Hz 3 ph., 200/220V, 50 Hz
3 ph., 400V, 50 Hz Weight, lbs.: Net Shipping Operating (maximum flooded) Condenser dimensions, inches: A (Width) B (Length) C (Height) D (Leg centerline) E (Leg centerline) F (Clearance below) Recommended Line Sizes, OD: Liquid (All lengths and orientations) Discharge Gas Vertical Up, All lengths Horizontal Or Down, < 75 ft. Horizontal Or Down, > 75 ft. Connections at Condenser: Liquid (ODC) Discharge Gas (ODC) Connections at Machine
Liquid (ODC) Discharge Gas (ODC)
28,700 23,900
1
1/3
5,000
2.5 N/A N/A
3.0 N/A N/A
7 N/A N/A
8.2 N/A N/A
150 195 167
38-7/8” 45-1/2” 36-1/8” 37-7/8”
37”
16-1/8”
1/2”
5/8” 5/8” 7/8”
1/2” 5/8”
1-1/8” 1-1/8”
TABLE - 4
Air-Cooled Condenser Data
4
44,500 37,100
2
1/2
9,800
8.0 N/A N/A
5.8 N/A N/A
15 N/A N/A
17.5 N/A N/A
250 310 276
41-3/8”
66” 36-1/8” 40-3/8”
54” 16-1/8”
5/8”
7/8” 7/8”
1-1/8”
5/8” 7/8”
1-1/8” 1-1/8”
80,400 67,000
2 (3)
1/2 (1/2)
9,800 (15,500)
8.0 (12) N/A N/A
5.8 (8.7) N/A N/A
15 (23)
N/A N/A
17.5 (27) N/A N/A
265 (370) 325 (440) 301 (405)
41-3/8” (41-3/8”)
66” (105) 36-1/8” (36-1/8”) 40-3/8” (40-3/8”)
54” (94”) 13-3/4” (13-3/4”)
7/8” (7/8”)
1-1/8” (1-1/8”) 1-1/8” (1-1/8”) 1-3/8” (1-3/8”)
7/8” (7/8”)
1-1/8” (1-3/8”)
1-1/8” 1-1/8”
Page 5
HES Series Air-Cooled Installation Instructions
Ice Machine Model HE60 / P112F HE100 / P118F P18FXT Recommended Condenser HDD-231(HDD-261) HDD-311 (HDD-361) HDD-591 (HDD-661)
Note: For continuous operation at ambients above 105 °F, use larger condenser shown in parenthesis
Total Heat Rejection: BTU/hr at 60 Hz. BTU/hr at 50 Hz. Fans: Number HP, Each Total, CFM Full Load Amps:
1 ph., 208/230V, 60 Hz 3 ph., 208/230V, 60 Hz 3 ph., 460V, 60 Hz 1 ph., 200/220V, 50 Hz 3 ph., 200/220V, 50 Hz 3 ph., 400V, 50 Hz
Locked Rotor Amps:
1 ph., 208/230V, 60 Hz 3 ph., 208/230V, 60 Hz 3 ph., 460V, 60 Hz 1 ph., 200/220V, 50 Hz 3 ph., 200/220V, 50 Hz
3 ph., 400V, 50 Hz Weight, lbs.: Net Shipping Operating (maximum flooded) Condenser dimensions, inches: A (Width) B (Length) C (Height) D (Leg centerline) E (Leg centerline) F (Clearance below) Recommended Line Sizes, OD: Liquid (All lengths and orientations) Discharge Gas Vertical Up, All lengths Horizontal Or Down, < 75 ft. Horizontal Or Down, > 75 ft. Connections at Condenser: Liquid (ODC) Discharge Gas (ODC) Connections at Machine:
Liquid (ODC) Discharge Gas (ODC)
122,000 101,700
3 (3)
1/2 (1/2)
15,000 (14,000)
N/A
6.0 (6.0)
2.7 (2.7) N/A
6.0 (6.0)
3.0 (3.0)
N/A
19.8 (19.8)
9.9 (9.9) N/A
19.8 (19.8)
9.9 (9.9)
400 (520) 475 (595) 436 (566)
41-3/8” (41-3/8”)
105” (105”) 36-1/8” (36-1/8”) 40-3/8” (40-3/8”)
94” (94”)
13-3/4” (11-3/4”)
1-1/8” (1-1/8”)
1-1/8” (1-1/8”) 1-1/8” (1-1/8”) 1-3/8” (1-3/8”)
1-1/8” (1-1/8”)
1-3/8” (1-5/8”)
1-1/8” 1-1/8”
TABLE – 4A
Air-Cooled Condenser Data
5
181,200 151,000
5 (5)
1/2 (1/2)
22,500 (22,000)
N/A
10.0 (10.0)
4.5 (4.5) N/A
10.0 (10.0)
5.0 (5.0)
N/A
33 (33)
16.5 (16.5) N/A
33 (33)
16.5 (16.5)
610 (660) 700 (770) 667 (726)
28-3/4” (28-3/4”)
180-1/8” (180-1/8”)
41-5/8” (41-5/8”)
27” (27”)
147-5/8” (147-5/8”)
14-5/8” (14-5/8”)
1-1/8” (1-1/8”)
1-3/8” (1-3/8”) 1-3/8” (1-3/8”) 1-5/8” (1-5/8”)
1-1/8” (1-5/8”) 1-5/8” (1-5/8”)
1-1/8” 1-3/8”
249,900 278,250
5 (5)
3/4 (3/4)
33,000 (32,500)
N/A
17.0 (17.0)
8.5 (8.5) N/A
17.0 (17.0)
8.5 (8.5)
N/A
60 (60) 30 (30)
N/A
60 (60) 30 (30)
1175 (1200) 1325 (1350) 1221 (1258)
57” (57”)
180-1/8” (180-1/8”)
45-5/8” (45-5/8”) 55-1/4” (55-1/4”)
147-5/8” (147-5/8”)
14-5/8” (14-5/8”)
1-3/8” (1-3/8”)
1-3/8” (1-3/8”) 1-3/8” (1-3/8”) 1-5/8” (1-5/8”)
1-3/8” (1-3/8”) 2-1/8” (2-1/8”)
1-1/8” 1-3/8”
Page 6
HES Series Air-Cooled Installation Instructions
FIGURE - 9
Condenser Dimensions (Condenser pictured: DD-101 or DD-131)
Note: Dash lines indicate customer supplied piping. The Check Valve in the return line (labeled
“Output To Machine”) is supplied with the condenser.
FIGURE – 9A
Condenser Field Piping
6
Page 7
HES Series Air-Cooled Installation Instructions
CONDENSER EQUIVALENT
LINE SIZE WORKSHEET
Discharge Gas Line O.D. _____________
Fitting Type Number Used Factor Total Globe Valve (open) Angle Valve (open)
45? Elbow 90? Elbow
Feet of Straight Copper Used
Total Fitting Factor
Total Equivalent Feet
Copper Tube O.D. Type “L”
Globe Valve (open) Angle Valve (open)
45? Elbow 90° Elbow
Fitting Factors
1/2” 5/8” 7/8” 1 1/8”
14 16 22 28
7 9 12 15
.5 1 1 1.5
1 2 2 3
TABLE - 5
FIGURE - 10
Minimum Traps for Discharge Lines
7
Page 8
HES Series Air-Cooled Installation Instructions
Refrigerant Connections to Air-Cooled Condenser.
MACHINE FRAME ANGLE
HE20 – HE40 ONLY
ROTALOCK SPUD
HE20 – HE60 (both lines) P118 and P18XT (liquid return line) 1 1/4” – 12 Threads
P118 and P18XT (discharge line) 1 3/4” – 12 Threads
TEFLON SEAL
HE20 – HE60 (both lines) P118 and P18XT (liquid return line) PART #: 12A 2600T01 (1 1/4” – 12 Threads)
P118 and P18XT (discharge line) PART #: 12A2600T03 (1 3/4” – 12 Threads)
ROTALOCK FIELD CONNECTOR
HE20 – HE60 (both lines) P118 and P18XT (liquid return line) PART #: 12A 2396A0501 1 1/8” IDS X 1 1/4” – 12 Threads
P118 and P18XT (discharge line) PART #: 12A2396A0601 1 3/8” IDS X 1 3/4” – 12 Threads
FIGURE - 11
Field Attachment, Air Cooled Condenser Refrigerant Tubing
FOLLOW THESE PROCEDURES TO MAKE A TIGHT JOINT
1. Solder or braze condenser tubing ends to the female Rotalock connectors.
2. Remove dust caps if used, making sure that component plastic seals are intact.
3. Wipe off connector and spud threaded surfaces with a clean cloth to prevent the inclusion of dirt, or any foreign material in the system.
4. Connector coupling nut should be screwed onto Rotalock spud using the proper amount of torque (See TABLE-6).
Spud Size Amount of Torque
1/2” – 5/8” 30-40 FT LBS 7/8” 50-60 FT LBS 1 1/8” 80-100 FT LBS
TABLE – 6
Torque Ratings
8
Page 9
HES Series Air-Cooled Installation Instructions
Power
Motor (s)
Wiring Connections to Air-Cooled Condenser.
Air cooled condenser should be wired to terminals 20,21,22 and 23 (see FIGURE - 12).
Main
Main Power
Connections
Fan
Condenser
Connections
Cold Weather Package (Hot)
NOTE: All four wires must be run from the ice machine to the remote air cooled condenser.
FIGURE - 12
Ice Machine Terminal Block Connections
FIGURE - 13
Wiring For HDD-61 With Cold Weather Valve and Single Fan
9
Page 10
HES Series Air-Cooled Installation Instructions
Wiring Connections to Air-Cooled Condenser (Cont.)
FIGURE - 14
Wiring For HDD-101 & HDD-131 With Cold Weather Valve And Dual Fans
FIGURE - 15
Wiring For HDD-191, HDD-231 & HDD-261 With Cold Weather Valve And Three Fans
10
Page 11
HES Series Air-Cooled Installation Instructions
Wiring Connections to Air-Cooled Condenser (Cont.)
FIGURE - 16
Wiring For HDD-311, HDD-361, HDD-591 & HDD-661 With Cold Weather Valve And Five Fans
Condenser Description
HDD-61 5/8” N.O.
12A4200A0503 12A4199V42 12A2105C04 12A2117G05
Solenoid Valve Thermostats
Valve Valve
Rebuild Kit
Replacement
Coil
Penn (fan)
Ranco
(solenoid)
N/A
Solenoid
HDD-101 7/8” N.O.
12A4200A0704 12A4199V44 12A2105C04 12A2117G05 12A2117G06
Solenoid
HDD-131 1 1/8” N.O.
12A4200A0902 12A4199V45 12A2105C04 12A2117G05 12A2117G06
Solenoid HDD-191 HDD-231
1 3/8” N.O.
Solenoid
12A4200A1102 12A4199V45 12A2105C04 12A2117G05 12A2117G06
HDD-261 HDD-311 HDD-361 HDD-591 HDD-661
Note: Sporlan Solenoid Valves
1 5/8” N.O.
Solenoid
12A4200A1104 12A4199V47 12A2105C04 12A2117G05 12A2117G06
TABLE – 7
Kramer Cold Weather Kit Replacement Parts
11
Loading...