PLEASE READ THIS MANUAL
BEFORE INSTALLING AND
USING APPLIANCE
WARNING!
IF THE INFORMATION IN THIS
MANUAL IS NOT FOLLOWED
EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING
PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF
LIFE.
FOR YOUR SAFETY
Installation and service must
be performed by a qualified
installer, service agency or
the gas supplier.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electric switch;
do not use any phone in your
building.
• Immediately call your gas
supplier from your neighbor’s
phone. Follow the gas suppliers
instructions.
• If you cannot reach your gas
supplier call the fire department.
Direct Vent / Natural
Vent Gas Heater
Models: 2465, 2466
Homeowner’s Installation
and Operating Manual
DO NOT STORE OR USE
GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS
IN THE VICINITY OF THIS OR
ANY OTHER APPLIANCE.
This appliance may be installed in
an after market permanently located
manufactured (mobile) home where not
prohibited by local codes.
This appliance is only for use with the
type of gas indicated on the rating plate.
This appliance is not convertible for use
with other gases unless a certified kit is
used.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
30001935 1/07 Rev. 11
Dutchwest Direct Vent / Natural Vent Gas Heater
Table of Contents
PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS BEFORE USING APPLIANCE.
Thank you and congratulations on your purchase of a Dutchwest stove.
IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these
instructions may result in a possible fire hazard and will void the warranty.
The Dutchwest Direct Vent/Natural Vent Room Heater,
Model Nos. 3070, 3071, 3072 and 3073, is a vented gas
appliance listed to the ANSI standard Z21.88b-2001 and
CSA-2.33b-2001 for Vented Room Heaters, and CSA 2.17M91, Gas-Fired Appliances For Use at High Altitudes.
The installation of the Dutchwest Direct Vent/Natural
Vent Room Heater must conform with local codes, or in the
absence of local codes, with National Fuel Gas Code, ANSI
Z223.1/NFPA 54 — latest edition and CSA B-149.1 Instal
lation Code. (EXCEPTION: Do not derate this appliance
for altitude. Maintain the manifold pressure at 3.5” w.c. for
Natural Gas and 10.0” w.c. for LP gas at maximum input.)
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for
use with other gases unless a certified kit is used.
Installation and replacement of gas piping, gas utilization equipment or accessories, and repair and servicing
of equipment shall be performed only by a qualified
agency. The term “qualified agency” means any individ
ual, firm, corporation, or company that either in person
or through a representative is engaged in and is responsible for (a) installation or replacement of gas piping,
or (b), the connection, installation, repair, or servicing
of equipment, who is experienced in such work, familiar
with all precautions required, and has complied with all
the requirements of the authority having jurisdiction.
The Dutchwest Direct Vent/Natural Vent Room Heater
should be inspected before use and at least annually by
a qualified service agency. It is imperative that control
compartments, burners, and circulating air passageways of the appliance be kept clean.
The Dutchwest Direct Vent/Natural Vent Room Heater and
its individual shut-off valve must be disconnected from the
gas supply piping during any pressure testing of that system
at test pressures in excess of 1/2 psig (3.5 kPa).
The Dutchwest Direct Vent/Natural Vent Room Heater
must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure
testing of the gas supply piping system at test pressures
equal to or less than 1/2 psig.
‘Direct Vent’ describes a sealed combustion system in
which incoming outside air for combustion and outgoing
exhaust enter and exit through two separate concentric
passages within the same sealed vent system. The system
does not use room air to support combustion. The Direct
Vent system permits the gas appliance to be vented directly
to the outside atmosphere through the side of the house or
vertically through the roof. Conventional venting systems
(Natural Vent) take air from the room for combustion and
vent the exhaust vertically through the roof to the atmosphere.
This appliance is approved for bedroom installations in the
U.S. and Canada.
This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or
local codes.
30001935
-
Dutchwest Direct Vent / Natural Vent Gas Heater
WARNING: Operation of this heater when not con
nected to a properly installed and maintained venting
system can result in carbon monoxide (CO) poisoning
and possible death.
The Dutchwest Direct Vent/Natural Vent Room Heater,
when installed, must be electrically grounded in accordance
with local codes or, in the absence of local codes, with the
National Electrical Code ANSI/NFPA 70, (latest edition), or of
the current Canadian Electrical Code C22.1.
Due to high temperatures this appliance should be
located out of traffic and away from furniture and drap
eries.
WARNING: This appliance is hot while in operation.
Keep children, clothing, and furniture away. Contact
may cause burns or ignition of combustible materials.
Children and adults should be alerted to the hazards
of high surface temperatures and should stay away to
avoid burns or clothing ignition. Young children should
-
be carefully supervised when they are in the same room
as the appliance.
Clothing or other flammable materials should not be
placed on or near the appliance.
Any safety screen, glass or guard removed for servicing an appliance must be replaced prior to operating the
appliance.
The appliance area must be kept clear and free from
combustible materials, gasoline, and other flammable
vapors and liquids.
The flow of combustion and ventilation air must not
be obstructed. The installation must include adequate
accessibility and clearance for servicing and proper
operation.
WARNING: Do not operate the Room Heater with the
glass panel removed, cracked or broken. Replacement
of the panel should be done by a licensed or qualified
service person.
Do not use this appliance if any part has been under
water. Immediately call a qualified service technician
to inspect the appliance and to replace any part of the
control system and any gas control which has been
under water.
Do not burn wood, trash or any other material for
which this appliance was not designed. This appliance
is designed to burn either natural gas or propane only.
This gas appliance must not be connected to a chimney flue serving a separate solid-fuel burning appliance.
CAUTION: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper
and dangerous operation.
Verify proper operation after servicing.
Proposition 65 Warning: Fuels used in gas, woodburn-
ing or oil fired appliances, and the products of combustion of
such fuels, contain chemicals known to the State of California to cause cancer, birth defects and other reproductive
harm.
California Health & Safety Code Sec. 25249.6
* Aftermarket: Completion of sale, nor for purpose of resale, from
the manufacturer.
-
-
3
Dutchwest Direct Vent / Natural Vent Gas Heater
C
L
Valve Inlet
23"
(584mm)
6"
(172mm)
24"
(622mm)
C
L
Valve
Inlet
28"
(721mm)
12"
(318mm)
17"
(419mm)
4"
(111mm)
Dutchwest Direct Vent / Natural Vent Dimensions
Refer to Page 6 for Flue Collar
Centerline Dimensions
Fig. 1 Dutchwest dimensions.
Attention
The Dutchwest stove is shipped from the factory as a Direct Vent Gas Heater. This heater may be converted into a Natural Vent unit in the field. If a Natural Vent heater is desired, the Z31D00 FSDHAG Draft Hood
must be directly installed to the top of the unit according to the installation instructions. The Draft Hood
Adapter is available in the 7FSDHASK stove kit or as a separate item.
When the Dutchwest stove is converted to Natural Vent, it uses 4” vent pipe. For aesthetic purposes the
CFM direct vent system may be used up to the ceiling.
4
30001935
Dutchwest Direct Vent / Natural Vent Gas Heater
A
B
E
C
D
Installation Requirements
The installation must conform with local codes or, in
the absence of local codes, with the National Fuel Gas
Code, ANSI Z223.1/NFPA 54 - latest edition. (EXCEPTION: Do not derate this appliance for altitude. Maintain the manifold pressure at 3.5” w.c. for Natural Gas,
and 10” w.c. for Propane).
In Canada, installation must be in accordance with the
current CSA B-149.1 Installation Codes and/or local
codes.
The installation should be done by a qualified ser
vice person who is familiar with the building codes
and installation techniques appropriate for your
area to accomplish a safe and effective installation.
Your dealer or your local gas supplier will be able to
refer a qualified service person.
WARNING: Due to high temperatures, the HEATER
should be located out of traffic and away from furniture and draperies.
The surface of the Heater Is hot when it is in use.
Young children should be watched carefully when
they are in the same room when the Heater is in
use, and they should be taught to avoid the hot
surface. Keep any objects that can burn well away
from the Heater, and observe the recommended
clearances that follow.
Locating the Stove
In choosing a location for the stove, consider:
• The location of outside walls;
• Where additional heat is needed:
• Where family members gather most often;
• The vent system requirements.
NOTE: We do not recommend the use of wallpaper
next to this stove. Over time, radiant heat may cause
the wallpaper to shrink, or may adversely affect the
binders in the wallpaper adhesive.
Direct Vent System Only
-
A. Flat on corner wall D. Cross Corner
B. Room Divider E. Flat on wall
C. Island
Fig. 2 Possible stove locations.
ST207b
Clearance Requirements
Minimum Clearances to
Combustible Materials
Measure side clearances as shown in Figures 5 and 6
from the outer edge of the cast iron stove top. Measure
rear clearances from the outermost surface of the steel
rear skirt.
The Dutchwest heater is approved for installation into
an alcove constructed of combustible materials to the
dimensions and clearances shown on the next page.
The same clearances apply in a standard parallel installation.
Warning:
• Always maintain required clearances (air spaces) to nearby combustibles to
prevent fire hazard. Do not fill air spaces with
insulation. All venting components must maintain
a 1” (25mm) clearance to combustible materials.
Maintain a 6” (150mm) clearance when using a
single wall pipe.
• The gas appliance and vent system must be vented directly to the outside of the building and never
be attached to a chimney serving a separate solid
fuel or gas-burning appliance. Each direct vent
appliance must use its own separate vent system.
Common vents are prohibited.
• Refer to the manufacturer’s instructions included
with the venting system for complete installation
procedures.
* needed for installing DuraVent Minimum Vent Kit #2792 or CFM Corporation Minimum Vent Kit #7TFSDVSK.
Fig. 6 Dimensions and clearances to ceiling or alcove.
Hearth Requirements
The Dutchwest Heater must be installed on rigid floor
ing. When the heater is installed directly on any combustible surface other than wood flooring, a metal or
wood panel extending the full width and depth of the
unit must be used as the hearth. There are no other
hearth requirements.
6
ST101c
-
30001935
Dutchwest Direct Vent / Natural Vent Gas Heater
20
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1 2 3 4 5 6 7 8 9
10 11 12 13 14 15 16 17 18 19 20
Vertical Run (in feet)
(Measured from the appliance flue collar to the top of the vent pipe.)
The installation of your Dutchwest stove must
conform with local codes, or in the absence of local codes, with the National Fuel Gas Code ANSI
Z223.1/NFPA 54 - latest edition, or CSA B149.1
Installation code. (EXCEPTION: Do not derate this
appliance for altitude up to 4,500 feet (1,370m).
Maintain the manifold pressure at 3.5” w.c. for
Natural Gas and 10.0” w.c. for LP Gas.
Input ratings are shown in BTU per hour and are
certified without deration for elevations up to
4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA,
installations must be in accordance with the
current ANSI Z223.1/NFPA 54 and/or local codes
having jurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations at
elevations above 4,500 feet (1,370m).
WARNING: Improper installation, adjustment,
alteration, service or maintenance can cause injury or property damage. Refer to this manual for
correct installation and operational procedures.
For assistance or additional information consult
a qualified installer, service agency, or the gas
supplier.
30001935
Gas Specifications
Gas Inlet and Manifold Pressures
Dutchwest Direct Vent/Natural Vent
Certified to:
ANSI Z21.88-2005 / CSA 2.33-2005
Vented Gas Fireplace Heaters
High Elevations
Horizontal Termination -
Direct Vent ONLY
The vent must rise vertically a minimum of 24” (610mm)
off the top of the unit, before the first elbow. The horizontal run may extend up to 20’ (6m) and include a
vertical rise of up to 40’ (12m). (Fig. 7) Horizontal
termination must also meet the criteria shown in Figures
9 through 11.
• Approved vent systems must terminate above and
including the heavy line in Figure 7.
• Two 45˚ elbows may be substituted for each single
90˚ elbow.
• With a rise between 2’ - 5’, one 90˚ or two 45˚ elbows may be used.
May use up to three
90° Elbows
One 90°
Elbow
Unacceptable Venting
Configuration
ST134a
Fig. 7 Horizontal vent termination window.
7
Dutchwest Direct Vent / Natural Vent Gas Heater
20
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Vertical Run (in feet)
(Measure from the appliance flue collar to the top of the vent pipe.)
A vertical vent system must terminate no less than 8’
(2.44m) and no more than 40’ (12m) above the appliance flue collar. A 2¹⁄₄” restrictor plate (supplied) must
be used where specified in all vertically terminated vent
systems. (Fig. 8) NOTE: The restrictor plate supplied
with the vertical termination should be discarded.
Install restrictor plate supplied with stove directly at
stove outlet. A vertically terminated vent system must
also conform to the following criteria:
• No more than three 90˚ elbows may be used.
• Two 45˚ elbows may be substituted for one 90˚
elbow. No more than six elbows may be used.
• Vent must rise a minimum of 2 feet before offset is
used.
• Termination height must conform to roof clearance
as specified in Figure 9.
All Vertical Terminations in this area
Require use of the
2¹⁄₄” Restrictor Plate*
Fig. 8 Vertical vent termination window.
*The Restrictor Plate is used on Direct Vent Installations
Only
8
Vertical terminations
must be within this area
No Restrictor Plate
Unacceptable Venting
Configuration
Vent Termination Clearances
When planning the installation, consider the location
of the vent terminal and clearances. Some of the most
common clearances to keep in mind are shown in Figure 10.
Important: All vent clearances must be maintained.
Check your vent termination clearances against
Figures 9 through 11.
The vent should be placed so that people cannot be
burned by accidentally touching the vent surfaces when
the stove is operating.
The vent termination should be located where it cannot
be damaged by such things as automobile doors, lawn
mowers or snowblowers and it should be located away
from areas where it could become blocked by snow,
etc.
Some considerations are:
• Obstructions or impediments to venting.
• Nearby combustible materials that could come into
contact with combustion exhaust gases.
• Other nearby openings {within 12” (305mm)} through
which exhaust gas could reenter the building.
• All vegetation within 3’ ((76mm) that may interfere
with the draft.
Other factors that influence where the installation will
be sited include the location of outside walls, where
additional heat may be desired in the home, where the
family members gather most regularly, and perhaps
most importantly, the distance limitations of the venting
system.
IMPORTANT
Direct Vent Only
• The horizontal termination must not be recessed
into the exterior wall or siding.
• Horizontal vent runs must be level toward the vent
termination.
• Clearances around the vent termination must be
maintained.
• For installations using Simpson DuraVent pipe,
parallel installations with minimum wall clearance
have restricted access for connecting the Horizontal Vent Cap straps to the vent pipe. See the
maker’s instructions for recommended installation
procedures.
ST132a
30001935
Dutchwest Direct Vent / Natural Vent Gas Heater
Venting Termination Clearances
Your stove is approved to be vented either through the
side wall, or vertical through the roof.
• This unit does not require any opening for in-
spection of vent pipe.
• Only CFM Corporation and Simpson DuraVent
venting components specifically approved and
labelled for this stove may be used.
• Minimum clearances between vent pipes and
combustible materials is one (1”) inch (25 mm),
except where stated otherwise.
• Venting terminals shall not be recessed into a wall or
siding.
• Horizontal venting must be installed on a level plane
without an inclining or declining slope.
There must not be any obstruction such as bushes,
garden sheds, fences, decks or utility buildings within
24” from the front of the termination hood.
Do not locate termination hood where excessive snow
or ice build up may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow
blowers, make sure snow is not directed towards vent
termination area.
Location of Vent Termination
It is imperative the vent termination be located observing the minimum clearances as shown on this page.
30001935
9
Dutchwest Direct Vent / Natural Vent Gas Heater
V
V
V
V
V
V
V
X
X
X
D
E
B
B
B
C
B
M
B
A
J
K
F
L
VENT TERMINATION AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
H
I
Operable
Operable
Fixed
Closed
V
B
INSIDE
CORNER DETAIL
V
A
G
N
N
CFM145a
General Venting Information - Termination Location
deck, or balcony
B = Clearance to window or door that may be 6” (15cm) for appliances 6” (15cm) for appliances opened < 10,000Btuh (3kW), 12” (30cm) < 10,000 Btuh (3kW), 9” for appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000
< 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh
for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for appliances > 50,000 Btuh (15kW)
C = Clearance to permanently closed window 12” (305mm) recommended to 12” (305mm) recommended to
prevent window condensation prevent window condensation
D = Vertical clearance to ventilated soffit located above the terminal within a horizontal 18” (458mm) 18” (458mm) distance of 2 feet (610mm) from the center line of the terminal
E = Clearance to unventilated soffit 12” (305mm) 12” (305mm)
F = Clearance to outside corner see next page see next page
G = Clearance to inside corner (see next page) see next page see next page
H = Clearance to each inside of center line 3’ (91cm) within a height of 15’ (5m) 3’ (91cm) within a height of 15’
extended above meter/regulator assembly above the meter/regulator assembly (5m) above the meter/regulator
assy
I = Clearance to service regulator vent outlet 3’ (91cm) 3’ (91cm)
J = Clearance to nonmechanical air supply inlet 6” (15cm) for appliances < 10,000 6” (15cm) for appliances to building or the combustion air inlet to any Btuh (3kW), 12” (30cm) for < 10,000 Btuh (3kW), 9” other appliances appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000
< 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh
for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for appliances > 50,000 Btuh (15kW)
K = Clearance to a mechanical air supply inlet 6’ (1.83m) 3’ (91cm) above if within 10’
(3m) horizontally
L = Clearance above paved sidewalk or paved 7’ (2.13m)† 7’ (2.13m)† driveway located on public property
M = Clearance under veranda, porch, deck or 12” (30cm)‡ 12” (30cm)‡ balcony
N = Clearance above a roof shall extend a minimum of 24” (610mm) above the highest point when it passes through the roof
surface, and any other obstruction within a horizontal distance of 18” (450mm).
1 In accordance with the current CSA-B149 Installation Codes
2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes
† A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
‡ only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor:
NOTE: 1. Local codes or regulations may require different clearances.
2. The special venting system used on Direct Vent appliances are certified as part of the appliance, with clearances tested and
approved by the listing agency.
3. CFM Corporation assumes no responsibility for the improper performance of the appliance when the venting system does not
meet these requirements.
Fig. 9 Vent termination clearances.
10
30001935
Venting Runs
Horizontal Run (in feet)
Vertical Run (in feet)
(Measured from top of the unit before any elbow)
A: Vertical installations up to 36 feet (12m) in
height. Up to an 18 ft. horizontal vent run can be
installed within the vent system using a
maximum of two 90-degree elbows or four
45-degree elbows.
B: Vertical installations up to 36 feet (12m) in
height. Up to a 24 ft. horizontal vent run can be
installed within the vent system using a
maximum of two 45-degree elbows.
(Ratio = 2/3, Hor./Vert.)
= Acceptable venting configuration
= Unacceptable venting configuration
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
1 2 4 6 8 10 12 14 16 18 20 22 24
A
B
NOTE: When venting staight vertical, without any
elbow, a minimum of 8 ft. vertical is required
off the top of the stove.
Outside Corner
Inside Corner
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
G =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
F =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
G
Balcony with no side wall
M =
Combustible &
Noncombustible
12" (305 mm)
M
Balcony with perpendicular side wall
M = 24" (610 mm)
P = 20” (508 mm)
M
F
Alcove Applications*
C
D
C
E
V
V
Combustible &
Noncombustible
V
V
V
E = Min. 6” (152 mm) for
non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls
O = 8’ (2.4 m) Min.
O
P
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions
specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All
mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All
gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.
Fig. 10 Termination clearances.
Dutchwest Direct Vent / Natural Vent Gas Heater
No.
of Caps D
1 3’ (.9 mm) 2 x D
2 6’ (1.8 m) 1 x D
3 9’ (2.7 m) 2/3 x D
4 12’ (3.7 m) 1/2 x D