Velleman VMB1TCW User Manual

V
V
V
Temperature control module for the
M
M
M
B
B
B
Velbus system
1
1
1
T
T
T
C
C
C
W
W
W
CONTENTS
CONTENTS ......................................................................................................................................... 2
DESCRIPTION ..................................................................................................................................... 4
CHARACTERISTICS ........................................................................................................................... 4
VELBUS CHARACTERISTICS ........................................................................................................... 6
EMBEDDING THE TEMPERATURE CONTROLLER ......................................................................... 8
EMBEDDING A TEMPERATURE SENSOR ....................................................................................... 9
EMBEDDING A TEMPERATURE CONTROLLER TOGETHER WITH A SENSOR ......................... 10
OVERVIEW HEATING INSTALLATION ............................................................................................ 11
CONNECTION ................................................................................................................................... 12
Connecting the temperature controller VMB1TC ............................................................................................................. 12
Connecting the temperature sensor VMB1TS .................................................................................................................. 12
Relay cabinet wiring ......................................................................................................................................................... 13
Terminator ........................................................................................................................................................................ 14
Addressing ........................................................................................................................................................................ 14
Allocate the relay channels ............................................................................................................................................... 14
SCREEN INDICATIONS .................................................................................................................... 15
LED INDICATION .............................................................................................................................. 15
BUTTON FUNCTIONS ...................................................................................................................... 16
MENU STRUCTURE .......................................................................................................................... 17
Direct access menu .......................................................................................................................................................... 17
Extended menu................................................................................................................................................................. 18
CONFIGURATION OF THE TEMPERATURE CONTROLLER ......................................................... 20
Choice of language ........................................................................................................................................................... 20
Temperature read-out (°Celsius or °Fahrenheit) .............................................................................................................. 21
Master clock ...................................................................................................................................................................... 22
Global alarm ..................................................................................................................................................................... 23
Battery backup .................................................................................................................................................................. 24
Addressing ........................................................................................................................................................................ 25
Assign an action to the wake-up time ............................................................................................................................... 25
Assign an action to the go-to-bed time ............................................................................................................................. 25
Searching for temperature sensors .................................................................................................................................. 26
Setting the clock ............................................................................................................................................................... 27
Setting the alarm clock ..................................................................................................................................................... 28
Disabling the alarm clock function .................................................................................................................................... 30
Setting the display contrast .............................................................................................................................................. 31
Setting the backlight of the display ................................................................................................................................... 32
CONFIGURATION OF THE TEMPERATURE SENSORS ................................................................ 33
Assign sensor names ....................................................................................................................................................... 34
Defining zones .................................................................................................................................................................. 35
Change the default zone names....................................................................................................................................... 37
Heating or cooling mode ................................................................................................................................................... 39
Lock or unlock local mode setting .................................................................................................................................... 41
Default duration of temporary mode (default sleep time) ................................................................................................. 42
Low temperature alarm ..................................................................................................................................................... 43
High temperature alarm .................................................................................................................................................... 44
Anti-freeze temperature .................................................................................................................................................... 45
Heating limit ...................................................................................................................................................................... 46
Minimum cooling temperature .......................................................................................................................................... 47
Maximum cooling temperature ......................................................................................................................................... 48
Hysteresis temperature .................................................................................................................................................... 49
Temperature difference .................................................................................................................................................... 50
Difference sensor ............................................................................................................................................................. 51
Protecting the circulation pump ........................................................................................................................................ 52
Protecting the valves ........................................................................................................................................................ 53
Calibrating the sensor ....................................................................................................................................................... 54
VERIFY SOFTWARE VERSION ........................................................................................................ 55
PIN CODE PROTECT THE EXTENDED MENU ................................................................................ 56
OPERATING THE TEMPERATURE SENSOR VMB1TS .................................................................. 58
Anti-freeze, night, day or comfort mode indication ........................................................................................................... 58
Cooling or heating mode indication .................................................................................................................................. 58
Air-conditioner or heater active indication ........................................................................................................................ 58
Operation .......................................................................................................................................................................... 59
OPERATING THE TEMPERATURE CONTROLLER VMB1TC ........................................................ 60
Select room or zone ......................................................................................................................................................... 60
Recall and change the desired temperature .................................................................................................................... 61
Temporarily switching between comfort, day, night or anti-freeze mode ......................................................................... 61
Setting the sleep time (temporary mode) ......................................................................................................................... 63
Holiday setting .................................................................................................................................................................. 64
Summer setting................................................................................................................................................................. 65
Setting the comfort, day and night temperature ............................................................................................................... 66
STATISTICS ...................................................................................................................................... 68
Requesting statistics ......................................................................................................................................................... 68
Reset statistics.................................................................................................................................................................. 70
PROGRAM INSTRUCTIONS LOCATION ......................................................................................... 71
PROGRAMMING ............................................................................................................................... 73
Overview program instruction ........................................................................................................................................... 75
Entering a new program instruction .................................................................................................................................. 76
Changing a program instruction ....................................................................................................................................... 78
Removing a program instruction....................................................................................................................................... 80
DIFFERENTIAL THERMOSTAT ....................................................................................................... 81
The passage automatically 3° cooler than the office ........................................................................................................ 82
Passive cooling of a bedroom .......................................................................................................................................... 85
DESCRIPTION
The temperature controller (VMB1TC) forms in combination with one or more temperature se nsors (VMB1TS) and relay modules (VMB1RY or VMB4RY) a programmable thermostat to control a heating or cooling installation. The different sensors can be adjusted, operated and programmed from one lo cation by using this temperature controller. Multiple controllers at multiple locations are possible. It is also possible to define zones to group the sensors.
CHARACTERISTICS
Forms a programmable thermostat together with a Velbus temperature sensor and relay modules Ideal to control the heating or air-conditioning of your residence Can control a maximum of 32 temperature sensors (VMB1TS) Up to 7 zones can be defined Each sensor/zone can be placed in automatic mode (to follow the program), temporary mode (the program is suspended for a certain time) or manual mode (the program is disabled for an undefined time perio d) Configurable both locally or via PC (using the serial or USB interface in combination with the Velbus link software) All settings are retained in case of a power cut Relay control through the Velbus e.g. for alarms Possibility to set up a differential thermostat using two sensors
LED indication
When the heater or cooler is active When in temporary mode (sleep timer), a LED is flashing During high or low temperature alarm, a LED will flash When power supply is detected When receiving or transmitting data over the Velbus
LCD:
2 lines of 16 characters to indicate the name of the selected sensor/zone, the selected mode (comfort, day or night,
anti-freeze), the temperature and the time
On screen indication of manual mode, temporary mode, duration of temporary mode (sleep time), key guard and
cooling function
Adjustable white backlight Possibility to adjust backlight automatically every day (2 times) Adjustable contrast
Clock
Built-in clock with day indication Adjusting one clock synchronizes all other clocks on the Velbus system. Possibility to use one clock as reference for all other clocks in the system Wake-up function: 2 moments (wake-up time and sleep time) can be set
Local control
Scroll through the different sensors with one button. Direct access to change the mode (comfort, day, night or anti-freeze) and the desired temperature. A short press on the menu button will open the short configuration menu:
set the comfort, day or night temperature switch the alarm clock on or off, configure the wake-up and sleep times) adjust the clock configure the duration of the sleep mode (sleep time)
Press and hold the menu button (4s) to enter the extended configuration menu:
enter or change program instructions configure the sensors (cooling/heating, lock/unlock control, sleep time, low and high temperature alarm, anti-freeze
temperature, upper heat temperature, lower and upper cool temperature, hysteresis, temperature difference, unblock pump/valve, zone number, difference sensor, sensor calibration and sensor name)
select language, read out (°C or °F), reference clock (on/off), alarm time (global/local), emergen cy power supply
(on/off) or change PIN
set the address (254 possible), link the alarm output or search for all sensors p r esent on the Velbus change the contrast and the backlight of the display recall statistics (minimum, maximum temperature and duration of heating/cooling)
The extended configuration menu can be secured by a PIN. The menu is closed automatically after ±1 minute of inactivity.
Programming
A program instruction can switch a sensor between comfort, day, night or anti-freeze mode at a certain time. Possibility to enter program instructions that are applicable for all zones or for all sensors in a defined zone. Up to 31 program instructions can be saved per sensor or zone. Program types:
day programs: every Monday, Tuesday, Wednesday, Thursday, Friday, Saturday or Sunday working day programs: from Monday up to and including Friday or Saturday weekend programs: every Saturday and Sunday week programs: every day
Wake-up time and sleep time can be used inside program instructions.
Power supply
Required power supply: 12 to 18VDC Consumption backlight off: 25mA Maximum consumption (LEDs activated, backlight max.): 50mA Battery emergency power supply: 3V Lithium battery (CR2032 included) Consumption emergency power supply not active: 0.5µA Consumption emergency power supply activated: 200µA Display warning when battery needs replacement
Dimensions
Module (L x B x H): 66 x 44 x 40mm Dimensions including cover plate (L x B x H): 118 x 80 x 40mm Cover plate not included
VELBUS CHARACTERISTICS
2-wire communication for Velbus data and 2 wires for power supply data transmission: 16.6 Kbit/s Serial data protocol: CAN (Controller Area Network) Short circuit proof (towards negative or positive pole of the power supply) LED indication when receiving or transmitting data over the Velbus bus error indication: 2 short flashes of the LEDs auto recovering after 25 seconds when a bus error occurs
The temperature controller module can be given a designation with a maximum of 16 characters.
The temperature controller module can transmit following messages:
the current time the output status of the alarm clock the controller status the controller type (including software version) the controller name the communication error counter a program instruction the memory content
The temperature controller module can transmit following instructions:
Request the:
o module type (to search for sensors) o current time o memory content o sensor name o sensor set-up o sensor status o sensor temperature o sensor time statistics o program instruction
Set the:
o program storage location o program availability o program instruction o sensor zone o desired temperature for a sensor o sensor comfort temperature for heating o sensor day temperature for heating o sensor night temperature for heating o sensor anti-freeze temperature for heating o upper heat temperature o temperature difference for fast heating/cooling or differential thermostat o hysteresis temperature for a sensor o sensor comfort temperature for cooling o sensor day temperature for cooling o sensor night temperature for cooling o lower limit of the cooling preset range o upper limit of the cooling preset range o sensor calibration factor o low temperature alarm of a sensor o high temperature alarm of a sensor
put the sensor in:
o heating mode o cooling mode o comfort mode o in day mode o night mode o anti-freeze mode
synchronize the alarm clock time lock the local sensor controls unlock the local sensor controls standard duration for temporary mode (sleep time) for a sensor
reset the minimum and/or maximum temperature reset the time statistics of a sensor set or reset the de-blocking of the valve and/or circulation pump
write to sensor memoryThe address of the linked sensor to set up a differential thermostat
The temperature controller module can receive following messages:
the sensor type the sensor name the sensor temperature the sensor status the sensor settings the sensor time statistics the sensor program instruction
The temperature controller module can receive following instructions:
request the current time set the current time synchronize the alarm clock set the alarm clock times request the module type request the communication error counter request the controller status request the controller name request the memory content change the memory content set the sensor program storage location set the sensor zone request a program instruction change a program instruction
EMBEDDING THE TEMPERATURE CONTROLLER
It is also possible to use a 3-module wide frame with cover plate from the BTicino Living series. The module must be pushed into the build-in frame from the front.
It is also possible to use a 3-module wide frame with cover plate from the BTicino Light or Light Tech series. The module must be pushed into the build-in frame from the front.
To build the controller in into a hollow wall, use a hollow wall pattress.
EMBEDDING A TEMPERATURE SENSOR
The temperature sensor VMB1TS / VMB1TSW can be embedded in combination with a blank frame VMBFBI and a cover plate from the BTicino Living series. The module must be pushed into the build-in frame from the front.
It is also possible to use a 2- or 3-module wide frame with cover plate from the BTicino Light or Light Tech series. The module must be pushed into the build-in frame from the front.
To build the sensor in into a hollow wall, use a hollow wall pattress.
EMBEDDING A TEMPERATURE CONTROLLER TOGETHER WITH A SENSOR
The controller (VMB1TC) can be embedded together with a sensor (VMB1TS) in a 4-module wide frame with cover plate from the BTicino Living series. The module must be pushed into the build-in frame from the front.
The controller (VMB1TC) can be build-in together with a sensor (VMB1TS) in a 4-module wid e frame with cover plate from the BTicino Light of Light Tech series. The module must be pushed into the build-in frame from the front.
To build the controller and sensor in into a hollow wall, use a hollow wall pattress.
OVERVIEW HEATING INSTALLATION
A heating installation usually consists of radiators or convectors, a boiler, circulation pump and a collector with valves for every radiator group. Every room is equipped with a temperature sensor VMB1TS which is controlled by one or multiple temperature controllers VMB1TC. The sensors in turn steer the relay modules VMB4RY (or VMB1RY) that control the valves. As soon as one of the valves is opened, a relay channel can activate the circulation pump and when one of the sensors is in day or comfort mode, a relay channel can put the boiler in day mode. When convectors with built-in fan are used, a relay channel can steer this fan in case the room temperature deviates too much from the desired temperature, e.g. to speed up heating in the morning.
CONNECTION
To interconnect the Velbus modules the use of twisted-pair cable (EIB 2x2x0.8mm2, UTP 8x0.51mm - CAT5 or equivalent) is recommended. Connect the bus to the module (beware of the polarity). Connect the 12V to 18V direct current to the module (beware of the polarity).
Connecting the temperature controller VMB1TC
Connecting the temperature sensor VMB1TS
Relay cabinet wiring
Terminator
Normally only 2 ‘TERM’ terminators must be used in a complete Velbus installation. Usually this will be on the end of 2 bus wires (for example in the attic and in the basement.
On all other modules, the terminator must be removed.
Remark: In case the wiring contains a lot of branches, still a terminator will be set on the end of 2 bus wires (= 2 terminators). When communication errors occur, an additional terminator can be set as close as possible to one of the two existing terminators. However, the number of terminators should be limited as more terminators place a heavy load on the bus (max 3).
Addressing
The address of the temperature controller is set via Velbuslink
©
Allocate the relay channels
Every temperature sensor module VMB1TS can steer a relay channel to:
open the valve that provides hot water to the radiator switch on the fan of a convector to speed up heating (when the difference between desired temperature and room
temperature is too high)
set the boiler in day mode switch on the air-conditioning switch on the circulation pump (when on of the valves is open) generate an alarm at low room temperature (heating system down) generate an alarm at high room temperature (valve fails to close)
Every relay channel that is steered by a temperature sensor must be placed in instant control. The easiest way to allocate those relay channels is by using the Velbus link software via a PC connected to a Velbus interface (VMB1USB, VMB1RS or VMBRSUSB).
g
SCREEN INDICATIONS
Room or zone
- Anti-freeze mode
Night mode Day mode Comfort mode
Temporary mode Mode locked
p Room program active z Zone program active
A All rooms program active
Heating or aircoditioning on
Location
Living room
Mo 14:23 23
Mode
Alarm off
Alarm On
Clock with day indication
LED INDICATION
Menu
Heating
* Coolin
or
remaining ‘sleep time’
Current temperature
Location
Living room
Mo 14:23 23
Mode
Flashing when sleep timer is on
Remark: When a menu is active, de LED indication is replaced with flashing LEDs on the ↑ and buttons that indicate the scrolling direction.
Menu
Flashing when low or high temperature alarm
BUTTON FUNCTIONS
Location
Living room
Mo 14:23 23
Mode
Menu
Location
Living room
Mo 14:23 23
Mode
Menu
Location
Mode
Location
Change room or zone. Push and hold to switch between rooms and zones.
Exit the menu. Changes made in a data entry screen (flashing item) are discarded.
Mode
Switch between anti-freeze, night, day and comfort mode and start the sleep timer. Push and hold to stop the sleep timer.
Move one level back in the menu. Changes made in a data entry screen (flashing item) are discarded.
Location
Living room
Mo 14:23 23
Mode
Menu
Menu
Menu
Open the menu. Push and hold to open the extended menu.
Move to the next level in het menu. Changes made in a data entry screen (flashing item) are retained.
Location
↑ ↓
Alter the data entry (flashing item) or scroll through the menu.
Living room
Mo 14:23 23
Mode
Menu
Direct access menu
Location
Living room
Mo 14:23 23
MENU STRUCTURE
Mode
Menu
Open the menu by pressing the ‘Menu’ button. Scroll through the menu with the or button.
Sleep timer1 Temp. Settings
Comfort Day temp Night temp To main menu
Alarm clock set Clock set Exit
1. This menu is only available when temporary mode (sleep timer) is activated.
Select a menu item with the button. Scroll through sub menus with the or button and select with the button. Alter the data entry field (flashing item) with the or button. Confirm or move to the next data entry field with the button. To cancel or return to the previous item, use the button. Quit the menu using the button.
When a data entry field (flashing item) is still active, changes are discarded when using the button.
Extended menu
To change the program, settings or statistics of the different sensors or to change the configuration of the temperature controller, use the extended menu. This extended menu can be secured by setting a PIN.
1. Open the extended menu by pushing and holding the
‘Menu’ button for about 4 seconds.
Location
4. Select the third number of the PIN using the or button and confirm with the button.
Location
Living room
Mo 14:23 23
Mode
Menu
If the menu is not protected by a PIN, steps 2 to 5 are skipped.
2. Select the first number of the PIN using the or button and confirm with the button.
Location
Living room PIN code _000
Mode
Menu
3. Select the second number of the PIN using the or button and confirm with the button.
Living room PIN code 12_0
Mode
Menu
5. Select the last number of the PIN using the or button and confirm with the button.
Location
Living room PIN code 123_
Mode
Menu
6. The first item of the extended menu is shown on the display.
Location
Location
Living room PIN code 1_00
Living room Program
Mode
Menu
Mode
Menu
Scroll through the menu using the and buttons.
Program Settings
Operating mode Button lock Sleep timer Low temp. alarm High temp. alarm Anti-freeze temp Upper heat temp Lower cool temp Upper cool temp Hysteresis Temp difference Unjam pump Unjam valve Local program Zone number1 Diff. Sensor1 Sensor cal.1 Change name2 To main menu
Configuration
Language Temp. read-out Master clock Global alarm Battery backup Change PIN code Firmware version Address1 Link wake-up1 Link go-to-bed1 Scan sensors1 To main menu
Display
Contrast Backlight To main menu
Statistics1
Min temp 16.0° Max temp 23.0°
- 0m/5m 0m/5m 8m/1h10m 10m/1h15m 18m/2h35m To main menu
Exit
1. This menu is not available when a zone or ‘all
rooms’ is selected.
2. This menu is not available when ‘all rooms’ is
selected.
Note: The naming of the menus and sub-menus might differ depending on the controllers’ firmware version. Always make sure to use the latest firmware version.
Select the menu item with the button. When applicable, scroll through the sub menus with
the or button and select with the button.
Change the data entry field (flashing item) using the
or button.
Confirm or move to the next entry field with the
button.
Cancel or return to the previous item by using the
button.
Exit the menu with the  button.
When a data entry field (flashing item) is still active, changes are discarded when using the button.
English
CONFIGURATION OF THE TEMPERATURE CONTROLLER
Choice of language
The menu text can be displayed in different languages. Factory default is English, but the language can be set to French, Dutch, Spanish or German.
1. When applying power to the controller for the first time, only the time is shown on the display.
Location
Mo 0:00
Mode
Menu
2. Press and hold the ‘Menu’ button for ±4 seconds to open the extended menu.
Location
5. Select the language menu with the button.
Location
_________
Mode
Menu
6. Choose the desired language with the or button.
Location
Configuration
Mode
Menu
3. If necessary scroll through the extended menu using the or button until the ‘Configuration’ item appears
Location
Configuration
Mode
Menu
4. Select the configuration menu with the button.
Location
Language
Mode
Menu
English
Mode
Menu
7. Confirm the language selection with the button.
Location
Mode
Menu
8. Exit the menu with the button.
Location
Mo 0:01
Mode
Menu
Temperature read-out (°Celsius or °Fahrenheit)
Default setting for the temperature read-out is degrees Celsius. Change the setting to see the read-out in degre es Fahrenheit.
1. Press and hold the ‘Menu’ button for ±4 seconds to open the extended menu.
Location
5. Select the temperature Readout menu with the button.
Location
Configuration
Mode
Menu
2. If necessary scroll through the extended menu using the or button until the ‘Configuration’ item appears
Location
Configuration
Mode
Menu
3. Select the configuration menu with the button.
Location
__________
Mode
Menu
6. Set the read-out to °Celsius or °Fahrenheit using the or button.
Location
Fahrenheit
Mode
Menu
7. Confirm the read-out setting with the button.
Location
Language
Mode
Menu
4. Scroll through the configuration menu using the or button until the ‘Temp. Read-out’ item appears.
Location
Temp. read-out
Mode
Menu
Temp. read-out
Mode
8. Exit the menu with the button.
Location
Menu
Menu
Mo 0:02
Mode
Master clock
When your Velbus installation contains multiple modules with built-in clock (temperatu re controllers VMB1TC and control panel VMB4PD) it is important that all clocks have the same time setting. This can be achieved by setting the clock of one module as reference (master). This module will then synchronize the other module clocks every day. This function is default disabled.
1. Press and hold the ‘Menu’ button for ±4 seconds to open the extended menu.
Location
5. Select the temperature Master clock menu with the button.
Location
Configuration
Mode
Menu
2. If necessary scroll through the extended menu using the or button until the ‘Configuration’ item appears
Location
Configuration
Mode
Menu
3. Select the configuration menu with the button.
Location
Language
Mode
Menu
Master clock ___
Mode
Menu
6. Switch the master clock on or off using the or button.
Location
Master clock On
Mode
Menu
7. Confirm the master clock setting with the button.
Location
Master clock
Mode
Menu
4. Scroll through the configuration menu using the or button until the ‘Master clock’ item appears.
Location
Master clock
Mode
Menu
8. Exit the menu with the button.
Location
Menu
Mo 0:03
Mode
Global alarm
This setting only applies when multiple temperature controllers are connected to your Velbus installation. Default the global alarm function is disabled. Changing the alarm time on a module that has the global alarm function enabled will result in changing the alarm time on all temperature controllers that have the global alarm function enabled. For modules that have the global alarm time disabled, changes in alarm time will only apply to that module.
1. Press and hold the ‘Menu’ button for ±4 seconds to open the extended menu.
Location
Configuration
Mode
Menu
5. Select the global alarm menu with the button.
Location
Global alarm ___
Mode
Menu
2. If necessary scroll through the extended menu using the or button until the ‘Configuration’ item appears
Location
Configuration
Mode
Menu
3. Select the configuration menu with the button.
Location
Language
Mode
Menu
6. Switch the global alarm function on or off using the or button.
Location
Global alarm On
Mode
Menu
7. Confirm the global alarm setting with the button.
Location
Global alarm clk
Mode
Menu
4. Scroll through the configuration menu using the or button until the ‘Global alarm clk’ item appears.
Location
Global alarm clk
Mode
Menu
8. Exit the menu with the button.
Location
Mo 0:04
Mode
Menu
Battery backup
To avoid losing the clock when a power failure occurs, a backup battery (3V Lithium CR2032) can be installed in the battery holder at the back of the module. To avoid premature depletion of the battery, only install it when permanent power is supplied to the Velbus system.
The temperature controller can display a message when the battery needs repl acement.
Location
Replace battery
Mo 14:23 23
Mode
Menu
The battery voltage watchdog must be enabled through the configuration menu.
1. Press and hold the ‘Menu’ button for ±4 seconds to open the extended menu.
Location
Configuration
Mode
Menu
3. Select the configuration menu with the button.
Location
Language
Mode
Menu
2. If necessary scroll through the extended menu using the or button until the ‘Configuration’ item appears
Location
Configuration
Mode
Menu
4. Scroll through the configuration menu using the or button until the ‘Battery backup’ item appears.
Location
Battery backup
Mode
Menu
5. Select the battery backup menu with the button.
7. Confirm the battery backup setting with the button.
Location
Batt. backup __
Mode
Menu
6. Enable the battery backup watchdog when a battery is inserted or disable it when no battery is present using the or button.
Location
8. Exit the menu with the button.
Location
Battery backup
Mode
Menu
Location
Mo 0:05
Batt. backup On
Mode
Menu
Mode
Menu
Addressing
Every module on the Velbus system must have its own unique address. These address are set via the Velbuslink
Assign an action to the wake-up time
The wake-up time can be used with the thermostat program but also to perform a certain action e.g. switching off staircase lighting, opening the roll-down window shutters, switching certain mains outlets on or off… This can be set via Velbuslink
©
©
.
Assign an action to the go-to-bed time
The go-to-bed time can be used with the thermostat program but also to perform a certain action e.g. switching on staircase lighting, closing the roll-down window shutters, switching certain mains outlets off… This can be set via Velbuslink
©
Searching for temperature sensors
Before the controller can work together with the temperature sensors VMB1TS it must first scan the network for all connected temperature sensors. When temperature sensors are installed or removed afterwards, the search process must be repeated to update the list of sensors to the new situation.
1. Press and hold the ‘Menu’ button for ±4 seconds to open the extended menu.
Location
4. Scroll through the configuration menu using the or button until the ‘Scan sensors’ item appears.
Location
Configuration
Mode
Menu
2. If necessary scroll through the extended menu using the or button until the ‘Configuration’ item appears.
Location
Configuration
Mode
Menu
3. Select the configuration menu with the button.
Location
Language
Mode
Menu
Scan sensors
Mode
Menu
5. Select the scan sensors menu with the button. The search for sensors on the network is now in progress.
Location
Scanning 00
Mode
Menu
6. Once the search process is completed, the first of the connected temperature sensors is shown on the display.
Location
Temp sensor 01
Mo 0:09 20
Mode
Menu
Setting the clock
This module works together with one or more temperature sensoresVMB1TS to form a programmable thermostat. It is important to set the right time for the internal clock. Setting the time on this module will set the clocks of all clock containing modules that are connected to the Velbus simultaneously.
1. Open the menu by pressing the ‘Menu’ button.
Location
Temp sensor 01 Temp. settings
Mode
Menu
5. Confirm with the button. The hour-indication flashes.
Location
Temp sensor 01 Clk set Mo __:10
Mode
Menu
2. Scroll through the menu using the button until the ‘Clock set’ item appears.
Location
Temp sensor 01 Clock set
Mode
Menu
3. Select the set clock menu with the button. The day-indication flashes.
Location
Temp sensor 01 Clk set __ 0:10
Mode
Menu
6. Set the hour with the or button.
Location
Temp sensor 01 Clk set Mo 14:10
Mode
Menu
7. Confirm with the button. The minutes-indication flashes.
Location
Temp sensor 01 Clk set Mo 14:__
Mode
Menu
4. Set the day with the or button.
Location
Temp sensor 01 Clk set Mo 0:10
Mode
Menu
8. Set the minutes with the or button.
Location
Temp sensor 01 Clk set Mo 14:24
Mode
Menu
Loading...
+ 63 hidden pages