VEGA Housing type 505 User Manual

Operating Instructions
Housing type 505
Level and Pressure
ESC
%
+
-
OK
CONNECT
2
1
on
VEGAMET
514V
out
in
Contents
Safety information ........................................................................ 2
Note Ex-area ................................................................................ 2
1 Product description
1.1 Function and configuration .................................................. 3
1.2 Types and versions ............................................................. 4
1.3 Technical data ....................................................................... 4
1.4 Dimensions ........................................................................... 5
2 Mounting
2.1 General ................................................................................. 6
2.2 Coding with Ex-instruments ................................................ 6
2.3 Transparent cover ............................................................... 6
2.4 Retrofitting of the housing with a power supply unit ......... 6
3 Electrical connection
3.1 Terminal coordination on VEGAMET ................................... 9
3.2 Terminal coordination on VEGATOR ................................. 10
3.3 Terminal coordination on VEGASEL .................................. 11
3.4 Terminal coordination on VEGACOM 557 ........................ 12
Contents

Safety information

The described module must only be installed and operated as described in these operating instructions. Please note that other action can cause damage for which VEGA does not take re­sponsibility.

Note Ex-area

Please note the approval documents attached (yellow binder), and especially the included safety data sheet.
2 Housing type 505
Product description

1 Product description

1.1 Function and configuration

The housing type 505 is used for single mount­ing of a series 500 signal conditioning instrument.
The housing can be either screwed directly on to the mounting plate or mounted on to a carrier rail (35 x 15 acc. to EN 50 022).
The housing generally consists of three com­ponents:
- Socket with terminals The connection terminals for the sensors are located at the bottom and the ones for the outputs and the power supply on top of the socket. The necessary separation between intrinsically safe and not-intrinsi­cally safe circuits in Ex-applications is thereby ensured. An appropriate adapter is integrated in the socket for carrier rail mounting.
- Upper part of the housing with guide rails and ventilation slots. A sufficient ventilation is also ensured when connecting several housings in series. No external ventilation is necessar y.
- The bag attached includes blue Ex-labels and coded pins.
The module instruments of the new series 500
- VEGATOR…
- VEGAMET…
- VEGASEL… and
- VEGACOM 557
are generally provided for a power supply of 20 … 53 V AC or 20 … 72 V DC.
(width 5 TE = 25,4 mm)
If you only have other supply voltages avail­able, use a housing with integrated power supply unit.
The power supply unit is suitable for a volt­age range of 90 … 250 V AC and DC and can power the module units.
A later retrofitting of the housing with a power supply unit is possible.
Note:
The housing type 505 is only designed for series 500 instruments:
- VEGAMET 513(V) … 515(V)
- VEGASEL 543 … 547
- VEGATOR 521 … 527, 532, 535 … 537
- VEGACOM 557
The power supply unit of the housing pro­vides no galvanic isolation from the supply voltage. Series 500 instruments realise the galvanic isolation in the signal conditioning instrument.
If you already have a power supply of 20 … 53 V AC or 20 … 72 V DC available, you can use the housing without power sup­ply unit.
Housing type 505 3
Product description

1.2 T ypes and versions

Housing with power supply unit
90 … 250 V AC
Power supply unit
Signal condi­tioning instru­ment
Housing without power supply unit
20 … 53 V AC 20 … 72 V DC
Adapter plug
Signal condi­tioning instru­ment

1.3 T echnical data

Power supply
Supply voltage 20 … 72 V DC
Supply voltage with integral power supply unit 90 … 250 V AC galvanically not isolated
20 … 53 V AC
(18 W; 50 VA)
Material
Terminal socket PPE (Noryl) black, self-extinguishing Upper part of housing PPE (Noryl) grey (RAL 7036),
self-extinguishing
Multipoint connectors
Number 1 Version acc. to DIN 41 612, series F , 48-pole, 3 r ows,
d, b, z (partly equipped)
Strip terminal
Cross-section area of conductor max. 2,5 mm
2
Protection classes
Protection IP 20 Protection class II Overvoltage categories II
4 Housing type 505