VEGA BAR74 User Manual

Operating Instructions
VEGABAR 74 4 20 mA/HART
Process pressure/
Hydrostatic
p
1 About this document
1.1 Function . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
5
1.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . .
5
1.3 Symbolism used . . . . . . . . . . . . . . . . . . . . . . .
5
2 For your safety
2.1 Authorised personnel. . . . . . . . . . . . . . . . . . . .
6
2.2 Appropriate use. . . . . . . . . . . . . . . . . . . . . . . .
6
2.3 Warning about misuse . . . . . . . . . . . . . . . . . . .
6
2.4 General safety instructions . . . . . . . . . . . . . . . .
6
2.5 Safety approval markings and safety tips . . . . .
7
2.6 CE conformity . . . . . . . . . . . . . . . . . . . . . . . . .
7
2.7 Fullling NAMUR recommendations . . . . . . . . .
7
2.8 Safety instructions for Ex areas . . . . . . . . . . . .
8
2.9 Environmental instructions . . . . . . . . . . . . . . . .
8
3 Product description
3.1 Conguration. . . . . . . . . . . . . . . . . . . . . . . . . .
9
3.2 Principle of operation . . . . . . . . . . . . . . . . . . . .
10
3.3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
3.4 Packaging, transport and storage . . . . . . . . . . .
11
4 Mounting
4.1 General instructions. . . . . . . . . . . . . . . . . . . . .
12
4.2 Mounting steps . . . . . . . . . . . . . . . . . . . . . . . .
13
5 Connecting to power supply
5.1 Preparing the connection . . . . . . . . . . . . . . . . .
14
5.2 Connection procedure . . . . . . . . . . . . . . . . . . .
16
5.3 Wiring plan . . . . . . . . . . . . . . . . . . . . . . . . . . .
17
6 Set up
6.1 Setup steps without VEGADIS 12 . . . . . . . . . . .
19
6.2 Setup steps with VEGADIS 12 . . . . . . . . . . . . .
19
7 Setup with PACTware
7.1 Connect the PC with VEGACONNECT 3 . . . . .
22
7.2 Connect the PC with VEGACONNECT 4 . . . . .
23
7.3 Parameter adjustment with PACTware™. . . . . .
24
7.4 Parameter adjustment with AMSand PDM . .
24
7.5 Saving the parameter adjustment data . . . . . . .
24
2 VEGABAR 74 - 4 20 mA/HART
Contents
28432-EN-070718
8 Maintenance and fault rectication
8.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . .
25
8.2 Fault clearance . . . . . . . . . . . . . . . . . . . . . . . .
25
8.3 Instrument repair . . . . . . . . . . . . . . . . . . . . . . .
26
9 Dismounting
9.1 Dismounting steps. . . . . . . . . . . . . . . . . . . . . .
27
9.2 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
27
10 Supplement
10.1 Technical data. . . . . . . . . . . . . . . . . . . . . . . . .
28
10.2 Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . .
35
10.3 Industrial property rights. . . . . . . . . . . . . . . . . .
41
10.4 Trademark . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
Supplementary documentation
Information:
Depending on the ordered version, supplementary documen­tation belongs to the scope of delivery. You nd this documentation in chapter "Product description".
Instructions manuals for accessories and replacement parts
Tip:
To ensure reliable setup and operation of your VEGABAR 74, we oer accessories and replacement parts. The associated documents are:
l Supplementary instructions manual 3203
6 "Welded socket
and seals"
l Operating instructions manual 32798 "Breather housing
VEGABOX 02"
l Operatin
g instructions manual 20591 "External indicating
and adjustment unit VEGADIS 12"
VEGABAR 74 - 4 20 mA/HART 3
Contents
28432-EN-070718

1 About this document

1.1 Function

This operating instructions
manual provides all the information you need for mounting, connection and setup as well as important instructions for maintenance and fault rectication. Please read this information before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device.

1.2 Target group

This operating instructions manual is directed to trained personnel. The contents of this manual should be made available to these personnel and put into practice by them.

1.3 Symbolism used

Information, tip, note
This symbol indicates helpful additional information.
Caution: If this warning is ignored, faults or malfunc- tions can result. Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result. Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.
Ex applications
This symbol indicates special instructions for Ex applications.
l List
The dot set in
front indicates a list with no implied sequence.
à Action
This arrow indicates a
single action.
1 Sequence
Numbers set in front indicate successive steps in a procedure.
4 VEGABAR 74 - 4 20 mA/HART
About this document
28432-EN-070718

2 For your safety

2.1 Authorised personnel

All operations descr
ibed in this operating instructions manual must be carried out only by trained specialist personnel authorised by the operator.
During work on and with the device the required personal protection equipment must always be worn.

2.2 Appropriate use

VEGABAR 74 is a pressure transmitter for measurement of gauge pressure, absolute pressure and vacuum.
You can nd detailed information on the application range in chapter "Product description".
Operational reliability is ensured only if the instrument is properly used according to the specications in the operating instructions manual as well as possible supplementary instructions.
Due to safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbitrary conversions or modications are explicitly forbidden.

2.3 Warning about misuse

Inappropriate or incorrect use of the instrument can give rise to application-specic hazards, e.g. vessel overll or damage to system components through incorrect mounting or adjustment.

2.4 General safety instructions

This is a high-tech instrument requiring the strict observance of standard regulations and guidelines. The user must take note of the safety instructions in this operating instructions manual, the country-specic installation standards as well as all prevailing safety regulations and accident prevention rules.
The instrument must only be operated in a technically awless and reliable condition. The operator is responsible for trouble­free operation of the instrument.
VEGABAR 74 - 4 20 mA/HART 5
For your safety
28432-EN-070718
During the entire duration of use, the user is obliged to
determine the compliance of the required occupational safety measures with the current valid rules and regulations and also take note of new regulations.

2.5 Safety approval markings and safety tips

The safety approval markings and safety tips on the device must be observed.

2.6 CE conformity

VEGABAR 74 is in CE conformity with EMC (89/336/EWG), fulls NAMUR recommendation NE 21 and is in CE conformity with LVD (73/23/EWG).
Conformity has been judged according to the following standards:
l EMC:
- Emission EN 61326: 2004 (class B)
- Susceptibil
ity EN 6132
6: 2004 including
supplement A
l LVD: EN 61010-1: 2001
VEGABAR 74 is not subject to the pressure device guideline.
1)
2.7 Fulfilling NAMUR recom
mendations
VEGABAR 74 fullls the following NAMUR recommendations:
l NE 21 (interference resistane and emitted interference) l NE 43 (signal level for failure
information)
l NE 53 (compatibility sensor and indicating/adjustment
components)
VEGA instruments are generally upward and downward compatible:
l Sensor
software to DTM VEGABAR 74 HART
l DTM
VEGABAR 74 for adjustment software PACTware
The parameter adjustment of the basic sensor functions is
independent of the software version. The range of available functions depends on the respective software version of the individual components.
The software version of VEGABAR 74 HART can be read out via PACTware™.
1)
Due to the ush diaphragm, no own pressure compartment is formed.
6 VEGABAR 74 - 4 20 mA/HART
For your safety
28432-EN-070718
You can view all software histories on our website www.vega.
com. Make use of this advantage and get registered for update information via e-mail.

2.8 Safety instructions for Ex areas

Please note the Ex-specic safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex­approved instruments.

2.9 Environmental instructions

Protection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental protection. The environment man­agement system is certied according to DIN EN ISO 14001.
Please help us full this obligation by observing the environ­mental instructions in this manual:
l Chapter "Packaging, transport
and
storage"
l Chapter "D isposal"
VEGABAR 74 - 4 20 mA/HART 7
For your safety
28432-EN-070718

3 Product description

3.1 Conguration
The scope
of delivery encompasses:
l VEGABAR 74 pressure transmitter l Documentation
- this
operating instructions manual
- Test certicate for pressure transmitters
- Ex-specic "Safety instructions" (with Ex-versions)
- if necessary, further certicates
VEGABAR 74 consists of the following components:
l Process tting
with measuring cell
l Housing
with electronics
l Connection cable (direct cable outlet)
The
components are available in dierent versions.
1
2
3
Fig. 1: Example of a VEGABAR 74 with process tting G1½ A 1 Connection cable 2 Housing with electronics 3 Process tting with measuring cell
Scope of delivery
Components
8 VEGABAR 74 - 4 20 mA/HART
Product description
28432-EN-070718

3.2 Principle of operation

VEGABAR 74 is a pressure transmitter for use in the paper, food processing and pharmaceutical industry. Thanks to the high protection class IP 68/IP 69K it is particularly suitable for use in humid environment. Depending on the version, it is used for level, gauge pressure, absolute pressure or vacuum measurements. Measured products are gases, vapours and liquids, also with abrasive contents.
The sensor element is the CERTEC
®
measuring cell with ush, abrasion resistant ceramic diaphragm. The hydrostatic pressure of the medium or the process pressure causes a capacitance change in the measuring cell via the diaphragm. This change is converted into an appropriate output signal and outputted as measured value.
The CERTEC
®
measuring cell is also equipped with a temperature sensor. The temperature value can be processed via the signal output.
Two-wire electronics 4 … 20 mA/HART for power supply and measured value transmission over the same cable.
The supply voltage range can dier depending on the instrument version.
The data for power supply are stated in chapter "Technical data" in the "Supplement".

3.3 Operation

VEGABAR 74 4 20 mA/HART can be adjusted with dierent adjustment media:
l with external adjustment/indication VEGADIS 12 l an adjustment software according to FDT/DTM stan
dard,
e.g. PACTwareand PC
l with
a HART handheld
The kind
of adjustment and the adjustment options depend on the selected adjustment component. The entered parameters are generally saved in the respecitive sensor, when adjusting with PACTwareand PC optionally also in the PC.
Area of application
Functional principle
Supply
VEGABAR 74 - 4 20 mA/HART 9
Product description
28432-EN-070718

3.4 Packaging, transport and storage

Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test according to DIN EN 24180.
The packaging of standard instruments consists of environ-
ment-friendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.
Transport must be carried out under consideration of the notes on the transport packaging. Nonobservance of these instruc­tions can cause damage to the device.
The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or concealed defects must be appropriately dealt with.
Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside.
Unless otherwise indicated, the packages must be stored only under the following conditions:
l Not
in the open
l Dry and dust free l Not exposed to corrosive media l Protected against solar
radiation
l Avoiding mechanical shock and vibration
l Storage and transport temperature see "Supplement -
Technical data - Ambient condi
tions"
l Relative humidity 20 85 %
Packaging
Transp
ort
Transport inspection
Storage
Storage and transport tem-
perature
10 VEGABAR 74 - 4 20 mA/HART
Product description
28432-EN-070718

4 Mounting

4.1 General instructions

Make sure that
the wetted parts of VEGABAR 74, especially the seal and process tting, are suitable for the existing process conditions such as pressure, temperature etc. as well as the chemical properties of the medium.
You can nd the specications in chapter "Technical data" in the "Supplement".
Higher process temperatures often mean also higher ambient temperatures. Make sure that the upper temperature limits stated in chapter "Technical data" for the environment of the electronics housing and connection cable are not exceeded.
1
2
Fig. 2: Temperature ranges 1 Process temperature 2 Ambient temperature
l The connection cable has a capillary for atmospheric
pressure compensation
à Lead the cable end into a dry space or into a suitable
terminal housing.
Information:
VEGA recommends the breather housing VEGABOX 02 or the indication/adjustment VEGADIS 12. Both contain terminals and a ventilation lter for pressure compensation. For mounting outdoors, a suitable protective cover is available.
Materials, wetted parts
Temperature limits
Connection
VEGABAR 74 - 4 20 mA/HART 11
Mounting
28432-EN-070718

4.2 Mounting steps

Seal the thread with teon, hemp or a similar resistant seal material on the process tting thread 1½ NPT.
à Screw VEGABAR 74 into the welded socket. Tighten the
hexagon on the process tting with a suitable wrench.
Wrench size, see chapter "Dimensions".
Seal the ange connections according to DIN/ANSI with a
suitable, resistant seal and mount VEGABAR 74 with suitable screws.
Use the seal suitable for the respective process fitting. You cannd the components in the line of VEGA accessories in the
supplementary instructions manual "Welded socket and seals".
Sealing/Screwing in threaded versions
Sealing/Screwing in ange versions
Sealing/Screwing in hygienic ttings
12 VEGABAR 74 - 4 20 mA/HART
Mounting
28432-EN-070718

5 Connecting to power supply

5.1 Preparing the
connection
Always keep in mind the following safety instructions:
l Connect only in the complete absence of line voltage l If overvoltage surges are expected, versions with inte-
grated
overvoltage arresters should be used or external
overvoltage arresters should be installed
Tip:
We recommend the version of VEGABAR 74 with integrated overvoltage arrester or VEGA type ÜSB62-36G.X as external overvoltage arreaster.
In hazardous areas you should take note of the appropriate regulations, conformity and type approval certicates of the sensors and power supply units.
Power supply and current signal are carried on the same two­wire cable. The voltage supply range can dier depending on the instrument version.
The data for power supply are stated in chapter "Technical data" in the "Supplement".
Provide a reliable separation of the supply circuit from the mains circuits according to DIN VDE 0106 part 101.
VEGA power supply units VEGATRENN 149AEx, VEGASTAB 690, VEGADIS 371 as well as all VEGAMETs meet this
requirement. When using one of these instruments, protection class III is ensured for VEGABAR 74.
Bear in mind the following factors regarding supply voltage:
l Outpu
t voltage of the power supply unit can be lower under
nominal
load (with a sensor current of 20.5 mA or 22 mA in
case of fault message)
l Inuence
of additional instruments in the circuit (see load
values in chapter "Technical data")
VEGABAR 74 is connected with standard two-wire cable without screen. An outer cable diameter of 5 … 9 mm ensures the seal eect of the cable gland when connecting via VEGABOX 02 or VEGADIS 12. If electromagnetic interference is expected which is above the test values of EN 61326 for
Note safety instructions
Take note of safety
instructions for Ex applications
Select power supply
Selecting connection cable
VEGABAR 74 - 4 20 mA/HART 13
Connecting to power supply
28432-EN-070718
industrial areas, screened cable should be used. For HART multidrop operation we recommend as standard practice the use of screened cable.
1
2
Fig. 3: Connection of VEGABAR 74 1 Direct connection 2 Connection via VEGABOX 02 or VEGADIS 12
If screened cable is necessary, connect the cable screen on both ends to ground potential. In the VEGABOX 02 or VEGADIS 12, the screen must be connected directly to the internal ground terminal. The ground terminal on the outside of the housing must be connected to the potential equalisation (low impedance).
If potential equalisation currents are expected, the connection on the processing side must be made via a ceramic capacitor (e.g. 1 nF, 1500 V). The low frequency potential equalisation currents are thus suppressed, but the protective eect against high frequency interference signals remains.
Take note of the corresponding installation regulations for Ex applications. In particular, make sure that no potential equal­isation currents ow over the cable screen. In case of grounding on both sides this can be achieved by the use of a capacitor or a separate potential equalisation.
Cable screening and ground­ing
Select connection cable for Ex applica­tions
14 VEGABAR 74 - 4 20 mA/HART
Connecting to power supply
28432-EN-070718