VEGA BAR53 User Manual

0 (0)

Operating Instructions

Pressure transmitter with metallic measuring cell

VEGABAR 53

4 … 20 mA

Document ID: 36721

Contents

Contents

1 About this document

4

1.1

Function............................................................................................................................

1.2

Target group......................................................................................................................

4

1.3

Symbolism used...............................................................................................................

4

2 For your safety

5

2.1

Authorised personnel........................................................................................................

2.2

Appropriate use................................................................................................................

5

2.3

Warning about incorrect use.............................................................................................

5

2.4

General safety instructions................................................................................................

5

2.5

Safety label on the instrument...........................................................................................

5

2.6

CE conformity...................................................................................................................

6

2.7

Measuring range - permissible process pressure.............................................................

6

2.8

Fulfillment of NAMUR recommendations..........................................................................

6

2.9

Safety instructions for Ex areas.........................................................................................

6

2.10

Safety instructions for oxygen applications.......................................................................

6

2.11

Environmental instructions................................................................................................

6

3 Product description

7

3.1

Configuration....................................................................................................................

3.2

Principle of operation........................................................................................................

8

3.3

Operation..........................................................................................................................

9

3.4

Packaging, transport and storage.....................................................................................

9

3.5

Accessories and replacement parts................................................................................

10

4 Mounting

11

4.1

General instructions........................................................................................................

4.2

Instructions for installation...............................................................................................

13

4.3

Mounting steps...............................................................................................................

13

4.4

Mounting steps, external housing...................................................................................

13

5 Connecting to power supply

15

5.1

Preparing the connection................................................................................................

5.2

Connection procedure....................................................................................................

16

5.3

Wiring plan, single chamber housing..............................................................................

17

5.4

Wiring plan - version IP 66/IP 68, 1 bar...........................................................................

18

5.5

Wiring plan, external housing with version IP 68.............................................................

19

5.6

Switch-on phase.............................................................................................................

20

6 Set up with the display and adjustment module PLICSCOM

22

6.1

Short description.............................................................................................................

6.2

Insert display and adjustment module.............................................................................

22

6.3

Adjustment system..........................................................................................................

23

6.4

Setup steps.....................................................................................................................

24

6.5

Menu schematic.............................................................................................................

32

6.10

Saving the parameter adjustment data...........................................................................

34

7Maintenance and fault rectification

7.1

Maintain..........................................................................................................................

35

7.2

Rectify faults...................................................................................................................

35

7.3

Exchanging the electronics module................................................................................

36

7.4

Software update..............................................................................................................

37

 

 

 

 

2

 

VEGABAR 53 • 4 … 20 mA

130321-EN-36721

36721-EN-130321

 

 

 

 

Contents

 

 

7.5

Instrument repair.............................................................................................................

37

8

Dismounting

39

 

8.1

Dismounting steps..........................................................................................................

 

8.2

Disposal..........................................................................................................................

39

9

Supplement

40

 

9.1

Technical data.................................................................................................................

 

9.2

Dimensions.....................................................................................................................

48

Supplementary documentation

Information:

Supplementary documents appropriate to the ordered version come with the delivery.You can find them listed in chapter "Product description".

Editing status: 2013-03-11

VEGABAR 53 • 4 … 20 mA

3

1 About this document

1 About this document

1.1Function

This operating instructions manual provides all the information you need for mounting, connection and setup as well as important instructions for maintenance and fault rectification.Please read this information before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device.

1.2Target group

This operating instructions manual is directed to trained specialist personnel. The contents of this manual should be made available to these personnel and put into practice by them.

1.3Symbolism used

Information, tip, note

This symbol indicates helpful additional information.

Caution: If this warning is ignored, faults or malfunctions can result.

Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result.

Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.

Ex applications

This symbol indicates special instructions for Ex applications.

List

The dot set in front indicates a list with no implied sequence.

Action

This arrow indicates a single action.

1Sequence

Numbers set in front indicate successive steps in a procedure.

Battery disposal

This symbol indicates special information about the disposal of batteries and accumulators.

130321-EN-36721

4

VEGABAR 53 • 4 … 20 mA

36721-EN-130321

2 For your safety

2 For your safety

2.1Authorised personnel

All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator.

During work on and with the device the required personal protective equipment must always be worn.

2.2Appropriate use

VEGABAR 53 is a pressure transmitter for measurement of gauge pressure, absolute pressure and vacuum.

You can find detailed information on the application range in chapter "Product description".

Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions.

For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbitrary conversions or modifications are explicitly forbidden.

2.3Warning about incorrect use

Inappropriate or incorrect use of the instrument can give rise to application-specific hazards, e.g.vessel overfill or damage to system components through incorrect mounting or adjustment.

2.4General safety instructions

This is a high-tech instrument requiring the strict observance of standard regulations and guidelines. The user must take note of the safety instructions in this operating instructions manual, the country-specific installation standards as well as all prevailing safety regulations and accident prevention rules.

The instrument must only be operated in a technically flawless and reliable condition. The operator is responsible for trouble-free operation of the instrument.

During the entire duration of use, the user is obliged to determine the compliance of the necessary occupational safety measures with the current valid rules and regulations and also take note of new regulations.

2.5Safety label on the instrument

The safety approval markings and safety tips on the device must be observed.

VEGABAR 53 • 4 … 20 mA

5

2 For your safety

2.6CE conformity

This device fulfills the legal requirements of the applicable EC guidelines.By attaching the CE mark,VEGA provides a confirmation of successful testing.You can find the CE conformity declaration in the download area of "www.vega.com".

2.7Measuring range - permissible process pressure

Due to the application, a measuring cell with a measuring range higher than the permissible pressure range of the process fitting may have been integrated. The permissible process pressure is stated with

"Process pressure" on the type label, see chapter 3.1 "Configuration".

For safety reasons, this range must not be exceeded.

2.8Fulfillment of NAMUR recommendations

The device fulfills the requirements of the applicable NAMUR recommendations.

2.9Safety instructions for Ex areas

Please note the Ex-specific safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex-approved instruments.

2.10 Safety instructions for oxygen applications

For instruments in oxygen applications the special instructions in chapters "Storage and transport", "Mounting" as well as "Technical data" under "Process conditions"must be noted.Furthermore the valid national regulations, implementation instructions and memorandums of the professional assocations must be noted.

2.11 Environmental instructions

Protection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental protection.The environment management system is certified according to DIN EN ISO 14001.

Please help us fulfill this obligation by observing the environmental instructions in this manual:

Chapter "Packaging, transport and storage"

Chapter "Disposal"

130321-EN-36721

6

VEGABAR 53 • 4 … 20 mA

3 Product description

3 Product description

3.1Configuration

Scope of delivery

The scope of delivery encompasses:

 

VEGABAR 53 process pressure transmitter

 

Documentation

 

––

this operating instructions manual

 

 

––

Test certificate for pressure transmitters

 

 

––

Safety Manual 31637 "VEGABAR series 50 and 60 -

 

 

––

4 … 20 mA/HART" (optional)

 

 

Operating instructions manual 27835 "Display and adjustment

 

 

––

module PLICSCOM" (optional)

 

 

Supplementary instructions manual 31708 "Heating for display

 

 

––

and adjustment module" (optional)

 

 

Supplementary instructions manual "Plug connector for con-

 

 

––

tinuously measuring sensors" (optional)

 

 

Ex-specific "Safety instructions" (with Ex versions)

 

 

––

Certificate "Oil and grease-free for oxygen applications" (with

 

 

––

respective versions)

 

 

if necessary, further certificates

Supplementary label "Oil and grease-free for oxygen applications"

Constituent parts

Instruments in the version "Oil and grease-free for oxygen applications" are equipped with a supplementary label.The supplementary label contains instructions on oil and grease-free parts of the instrument.

The VEGABAR 53 consists of the components:

Process fitting with measuring cell

Housing with electronics, optionally available with plug connector

Housingmodule cover, optionally available with display and adjustment

The components are available in different versions.

1

2

3

36721-EN-130321

Fig.1:Example of aVEGABAR 53 with manometer connection G½ A according to EN 837 and plastic housing

1 Housing cover with integrated display and adjustment module (optional)

2Housing with electronics

3Process fitting with measuring cell

VEGABAR 53 • 4 … 20 mA

7

3 Product description

Type plate

Scope of this operating instructions manual

Application area

Functional principle

The nameplate contains the most important data for identification and use of the instrument:

1

2

14

13

3

 

4

5

 

6

12

7

11

8

 

9

10

Fig.2:Layout of the type label (example)

1 Instrument type

2 Product code

3Approvals

4 Measuring range

5 Process pressure

6Process temperature

7 Electronics, voltage supply

8 Protection rating

9 Order number

10Serial number

11Data-Matrix-Code for Smartphone-App

12Material process seal

13ID numbers, instrument documentation

14Notified authority for CE marking

With the serial number, you can access the delivery data of the instrument via www.vega.com, "VEGATools" and "serial number search". In addition to the type label outside, you can also find the serial number on the inside of the instrument.

This operating instructions manual applies to the following instrument versions:

Software from 3.82

3.2Principle of operation

VEGABAR 53 is a pressure transmitter for measurement of overpressure, absolute pressure or vacuum. Measured products are gases, vapours and liquids in measuring ranges up to 4000 bar (400 MPa); with front-flush version also viscous liquids in measuring ranges up to 600 bar (60 MPa).

The process pressure acts on the sensor element via the stainless steel diaphragm and an internal transmission liquid. This causes a resistance change which is converted into a corresponding output signal and outputted as a measured value. With measuring ranges up to 16 bar a pieoresistive sensor element is used, with measuring ranges from 25 bar a strain gauge (DMS) sensor element.

8

VEGABAR 53 • 4 … 20 mA

130321-EN-36721

36721-EN-130321

 

 

 

3 Product description

 

Voltage supply

4 … 20 mA two-wire electronics for voltage supply and measured

 

 

value transmission on the same cable.

 

 

The supply voltage range can differ depending on the instrument ver-

 

 

sion.The exact range is stated in chapter "Technical data".

 

 

The backlight of the display and adjustment module is powered by

 

 

the sensor. The prerequisite for this is a supply voltage at a certain

 

 

level.The exact voltage specifications are stated in chapter "Technical

 

 

data".

 

 

The optional heating requires its own operating voltage.You can find

 

 

details in the supplementary instructions manual "Heating for display

 

 

and adjustment module".

 

 

This function is generally not available for approved instruments.

 

 

3.3 Operation

 

 

The instrument can be adjusted with the following adjustment media:

 

 

With the display and adjustment module

 

 

with the suitable VEGA DTM in conjunction with an adjustment

 

 

software according to the FDT/DTM standard, e.g. PACTware and

 

 

 

PC

 

 

3.4 Packaging, transport and storage

Packaging

Your instrument was protected by packaging during transport. Its

 

 

capacity to handle normal loads during transport is assured by a test

 

 

based on ISO 4180.

 

 

The packaging of standard instruments consists of environment-

 

 

friendly, recyclable cardboard. For special versions, PE foam or PE

 

 

foil is also used. Dispose of the packaging material via specialised

 

 

recycling companies.

 

 

Caution:

 

 

Instruments for oxygen applications are sealed in PE foil and provided

 

 

with a label "Oxygen! Use no Oil".Remove this foil just before mount-

 

 

ing the instrument! See instruction under "Mounting".

Transport

Transport must be carried out under consideration of the notes on the

 

 

transport packaging. Nonobservance of these instructions can cause

 

 

damage to the device.

Transport inspection

The delivery must be checked for completeness and possible transit

 

 

damage immediately at receipt. Ascertained transit damage or con-

 

 

cealed defects must be appropriately dealt with.

Storage

Up to the time of installation, the packages must be left closed and

 

 

stored according to the orientation and storage markings on the

 

 

outside.

 

 

Unless otherwise indicated, the packages must be stored only under

 

 

the following conditions:

 

 

Not in the open

 

 

Dry and dust free

 

 

 

VEGABAR 53 • 4 … 20 mA

 

9

3 Product description

Storage and transport temperature

Not exposed to corrosive media

Protected against solar radiation

Avoiding mechanical shock and vibration

Storage and transport temperature see chapter "Supplement - Technical data - Ambient conditions"

Relative humidity 20 … 85 %

3.5Accessories and replacement parts

Display and adjustment

The display and adjustment module PLICSCOM is used for measured

module

value indication, adjustment and diagnosis. It can be inserted into the

 

sensor and removed at any time.

 

You can find further information in the operating instructions "Display

 

and adjustment module PLICSCOM" (Document-ID 27835).

Flanges

Flanges are available in different versions according to the following

 

standards: DIN 2501, EN 1092-1, ANSI B 16.5, JIS B 2210-1984,

 

GOST 12821-80.

 

You can find additional information in the supplementary instructions

 

manual "Flanges according to DIN-EN-ASME-JIS" (Document-ID

 

31088).

Measuring instrument

The measuring instrument holder is used for wall/tube mounting of

holder

VEGABAR series 50 pressure transmitters and VEGAWELL 52 sus-

 

pension pressure transmitters. Supplied reducers enable the adapta-

 

tion to different instrument diameters.The material used is 316L.

Protective cover

The protective cover protects the sensor housing against soiling and

 

intense heat from solar radiation.

 

You will find additional information in the supplementary instructions

 

manual "Protective cover" (Document-ID 34296).

Electronics module

The electronics module is a replacement part for pressure transmitter

 

VEGABAR. One version is available for each type of signal output.

 

You find further information in the operating instructions "Electronics

 

moduleVEGABAR series 50 and 60 " (Document-ID 30175).

130321-EN-36721

10

VEGABAR 53 • 4 … 20 mA

4 Mounting

4 Mounting

4.1General instructions

Suitability for the process Make sure that all parts of the instrument coming in direct contact conditions with the process, especially the sensor element, process seal and

process fitting, are suitable for the existing process conditions, such as process pressure, process temperature as well as the chemical properties of the medium.

You can find the specifications in chapter "Technical data" and on the nameplate.

Diaphragm protection

To protect the diaphragm, the process fitting is covered by a protec-

 

tive cap.

 

Remove the protective cap just before installation so that the dia-

 

phragm will not get damaged. It is recommended to keep the cap and

 

use it again later for storage or transport.

Installation position

Select an installation position you can easily reach for mounting and

 

connecting as well as later retrofitting of a display and adjustment

 

module. The housing can be rotated by 330° without the use of any

 

tools.You can also install the display and adjustment module in four

 

different positions (each displaced by 90°).

Moisture

Use the recommended cables (see chapter "Connecting to power

 

supply") and tighten the cable gland.

 

You can give your instrument additional protection against moisture

 

penetration by leading the connection cable downward in front of the

 

cable entry.Rain and condensation water can thus drain off.This ap-

 

plies mainly to outdoor mounting as well as installation in areas where

 

high humidity is expected (e.g.through cleaning processes) or on

 

cooled or heated vessels.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36721-EN-130321

Fig.3:Measures against moisture penetration

Ventilation and pressure The ventilation of the electronics housing as well as the atmospheric compensation pressure compensation for the measuring cell are realised via a filter element in the area of the cable gland.

VEGABAR 53 • 4 … 20 mA

11

4 Mounting

1

1

1

2

2

2

 

 

2

 

1

 

Fig.4:Position of the filter element 1 Filter element

2Blind plug

Caution:

Due to the filter effect, the pressure compensation is time delayed.

When opening/closing the housing cover quickly, the measured value can change for a period of approx. 5 s by up to 15 mbar.

Information:

Make sure that the filter element is always free of buildup during operation. A high-pressure cleaner may not be used for cleaning.

With instrument versions in protection IP 66/IP 68, 1 bar, the ventilation is realised via the capillaries in the permanently connected cable.

The filter element is replaced by a blind plug.

Temperature limits

Higher process temperatures often mean also higher ambient

 

temperatures. Make sure that the upper temperature limits stated in

 

chapter "Technical data" for the environment of the electronics hous-

 

ing and connection cable are not exceeded.

1

Fig.5:Temperature ranges

1 Process temperature

2 Ambient temperature

12

2

130321-EN-36721

VEGABAR 53 • 4 … 20 mA

36721-EN-130321

 

 

 

 

 

 

 

4 Mounting

 

Oxygen applications

Instruments in the version "Oil and grease free for oxygen" should

 

 

 

 

 

 

be unpacked just before mounting. After the protective cover of the

 

 

 

 

 

 

process fitting has been removed, the label "O2" on the process fitting

 

 

 

 

 

 

is visible.

 

 

 

 

 

 

Danger:

 

 

 

 

 

 

Avoid oil, grease or contamination.Explosion danger!

 

 

 

 

 

 

4.2

Instructions for installation

Checking the diaphragm

Please check the diaphragm visually for damage and leaking fluid

 

 

 

 

 

 

before mounting and setting up the instrument. Make sure that the

 

 

 

 

 

 

diaphragm doesn't get damaged during installation.

 

 

 

 

 

 

Caution:

 

 

 

 

 

 

The instrument may only be used if it is in a technically flawless condi-

 

 

 

 

 

 

tion and has an undamaged diaphragm.

Installation position

VEGABAR 53 functions in any installation position. It is mounted ac-

 

 

 

 

 

 

cording to the same directives as a manometer (DIN EN 839-2).

 

 

 

 

 

 

Information:

 

 

 

 

 

 

We recommend using lock fittings, measuring instrument holders and

 

 

 

 

 

 

siphons from our line of accessories.

 

 

 

 

 

 

 

 

 

 

 

 

4.3

Mounting steps

Welding the socket

For mountingVEGABAR 53, a welded socket is required.You can find

 

 

 

 

 

 

these components in the supplementary instructions manual "Welded

 

 

 

 

 

 

socket and seals".

Sealing/Screwing in

Use the seal corresponding to the instrument:

 

 

 

 

 

 

Process fitting GV, GF, GC:seal in front of the thread

 

 

 

 

 

 

- or -

 

 

 

 

 

 

 

 

Seal the thread with resistant seal material:

 

 

 

 

 

 

Process fitting GN

 

 

 

 

 

 

Screw VEGABAR 53 into the welded socket. Tighten the hexagon

 

 

 

 

 

 

on the process fitting with a suitable wrench.Wrench size, see

 

 

 

 

 

 

chapter "Dimensions".

 

 

 

 

 

 

Warning:

 

 

 

 

 

 

The housing must not be used to screw the instrument in! Applying

 

 

 

 

 

 

tightening force can damage internal parts of the housing.

Sealing/Screwing in

Use the seal suitable for the respective process fitting.You can find

hygienic fittings

the components in the supplementary instructions manual "Welded

 

 

 

 

 

 

socket and seals".

 

 

 

 

 

 

4.4 Mounting steps, external housing

Wall mounting

1. Mark the holes according to the following drilling template

 

 

 

 

 

 

2. Depending on the mounting surface, fasten the wall mounting

 

 

 

 

 

 

plate with 4 screws

 

 

 

 

 

 

 

VEGABAR 53 • 4 … 20 mA

 

13

4 Mounting

 

90 mm (3.54")

 

 

 

70 mm (2.76")

 

8 mm

 

 

3mm

(0.32")

 

 

 

 

 

(0.12")

 

 

 

mm

 

 

3,5

 

 

R

.14")

 

 

 

(0

 

110 mm (4.33")

93 mm (3.66")

 

 

Fig.6:Drilling template - wall mounting plate

Tip:

Mount the wall mounting plate so that the cable entry of the socket housing points downward. The socket housing can be displaced by 180° to the wall mounting plate.

Warning:

The four screws of the socket housing must only be hand screwed. A torque > 5 Nm (3.688 lbf ft) can damage the wall mounting plate.

130321-EN-36721

14

VEGABAR 53 • 4 … 20 mA

36721-EN-130321

 

 

 

 

 

 

 

5 Connecting to power supply

 

 

 

 

 

 

 

5 Connecting to power supply

 

 

 

 

 

 

5.1 Preparing the connection

Safety instructions

Always keep in mind the following safety instructions:

 

 

 

 

 

 

Connect only in the complete absence of line voltage

 

 

 

 

 

 

If overvoltage surges are expected, overvoltage arresters should

 

 

 

 

 

 

 

be installed

 

 

 

 

 

 

Tip:

 

 

 

 

 

 

We recommend using VEGA overvoltage arresters B63-48 and

 

 

 

 

 

 

ÜSB 62-36G.X.

 

 

 

 

 

 

In hazardous areas you must take note of the respective regulations,

 

 

 

 

 

 

conformity and type approval certificates of the sensors and power

 

 

 

 

 

 

supply units.

Voltage supply

Power supply and current signal are carried on the same two-wire

 

 

 

 

 

 

cable.The voltage supply range can differ depending on the instru-

 

 

 

 

 

 

ment version.

 

 

 

 

 

 

The data for power supply are specified in chapter "Technical data".

 

 

 

 

 

 

Provide a reliable separation between the supply circuit and the

 

 

 

 

 

 

mains circuits according to DIN EN 61140 VDE 0140-1. The VEGA

 

 

 

 

 

 

power supply units VEGATRENN 149A Ex, VEGASTAB 690 as well

 

 

 

 

 

 

as all VEGAMETs and VEGASCANs meet this requirement.

 

 

 

 

 

 

Keep in mind the following additional factors that influence the operat-

 

 

 

 

 

 

ing voltage:

 

 

 

 

 

 

Output voltage of the power supply unit can be lower under nomi-

 

 

 

 

 

 

nal load (with a sensor current of 20.5 mA or 22 mA in case of fault

 

 

 

 

 

 

message)

 

 

 

 

 

 

Influence of additional instruments in the circuit (see load values in

 

 

 

 

 

 

 

chapter "Technical data")

Connection cable

The instrument is connected with standard two-wire cable without

 

 

 

 

 

 

screen. If electromagnetic interference is expected which is above the

 

 

 

 

 

 

test values of EN 61326 for industrial areas, screened cable should

 

 

 

 

 

 

be used.

 

 

 

 

 

 

Use cable with round cross-section.A cable outer diameter of

 

 

 

 

 

 

5 … 9 mm (0.2 … 0.35 in) ensures the seal effect of the cable gland.

 

 

 

 

 

 

If you are using cable with a different diameter or cross-section,

 

 

 

 

 

 

exchange the seal or use a suitable cable gland.

 

 

 

 

 

 

We generally recommend the use of screened cable for HART multi-

 

 

 

 

 

 

drop mode.

Cable gland ½ NPT

On the instrument with cable entry ½ NPT and plastic housing there is

 

 

 

 

 

 

a metallic ½" threaded insert moulded into the plastic housing.

 

 

 

 

 

 

Caution:

 

 

 

 

 

 

No grease should be used when screwing the NPT cable gland or

 

 

 

 

 

 

steel tube into the threaded insert. Standard grease can contain

 

 

 

 

 

 

additives that corrode the connection between threaded insert and

 

 

 

 

 

 

 

VEGABAR 53 • 4 … 20 mA

 

15

5 Connecting to power supply

Cable screening and grounding

housing.This would influence the stability of the connection and the tightness of the housing.

If screened cable is necessary, connect the cable screen on both ends to ground potential. In the sensor, the screen must be connected directly to the internal ground terminal. The ground terminal on the outside of the housing must be connected to the potential equalisation (low impedance).

If potential equalisation currents are expected, the connection on the processing side must be made via a ceramic capacitor (e.g.1 nF, 1500V).The low-frequency potential equalisation currents are thus suppressed, but the protective effect against high frequency interference signals remains.

Warning:

Considerable potential differences exist inside galvanic plants as well as vessels with cathodic corrosion protection. Very large equalisation currents can flow through the cable screen when the screen

is grounded on both ends. To avoid this, the cable screen must be connected to ground potential only on one end (inside the switching cabinet) in such applications.The cable screen must not be connected to the internal ground terminal in the sensor and the outer ground terminal on the housing not to potential equalisation!

Information:

The metallic parts of the instrument (transmitter, process fitting, etc.) are conductively connected with the inner and outer ground terminal on the housing. This connection exists either as a direct metallic contact or via the shielding of the special connection cable on instruments with external electronics.You can find specifications on the potential connections within the instrument in chapter "Technical data".

Take note of the corresponding installation regulations for Ex applications. In particular, make sure that no potential equalisation currents flow over the cable screen.In case of grounding on both sides this can be achieved by the use of a capacitor or a separate potential equalisation.

Single/Double chamber housing

5.2Connection procedure

Proceed as follows:

1.Unscrew the housing cover

2.If a display and adjustment module is installed, remove it by turning it to the left.

3.Loosen compression nut of the cable entry

4.Remove approx. 10 cm of the cable mantle, strip approx. 1 cm insulation from the individual wires

5.Insert the cable into the sensor through the cable entry

6.Lift the opening levers of the terminals with a screwdriver (see following illustration)

7.Insert the wire ends into the open terminals according to the wiring plan

16

VEGABAR 53 • 4 … 20 mA

130321-EN-36721

5 Connecting to power supply

8.Press down the opening levers of the terminals, you will hear the terminal spring closing

9.Check the hold of the wires in the terminals by lightly pulling on them

10.Connect the screen to the internal ground terminal, connect the outer ground terminal to potential equalisation

11.Tighten the compression nut of the cable entry. The seal ring must completely encircle the cable

12.Screw the housing cover back on

The electrical connection is hence finished.

Fig.7:Connection steps 6 and 7

5.3Wiring plan, single chamber housing

The following illustrations apply to the non-Ex as well as to the Ex-ia version.

36721-EN-130321

VEGABAR 53 • 4 … 20 mA

17

VEGA BAR53 User Manual

5 Connecting to power supply

Electronics and connection compartment

4...20mA

Display

 

1

1

2

2

Fig.8:Electronics and connection compartment, single chamber housing

1Spring-loaded terminals for voltage supply

2Ground terminal for connection of the cable screen

Wiring plan

4...20mA

Display

 

1 2

1

Fig.9:Wiring plan, single chamber housing

1Voltage supply/Signal output

5.4Wiring plan - version IP 66/IP 68, 1 bar

Wire assignment, connection cable

1

2

Fig.10:Wire assignment, connection cable

1 brown (+) and blue (-) to power supply or to the processing system

2Shielding

130321-EN-36721

18

VEGABAR 53 • 4 … 20 mA