VEGA BAR41 User Manual

Page 1
Operating Instructions
VEGABAR 41 (4 … 20 mA)
i ZERO SPAN
123 5678
-
+
­ VEGADIS 10
AM10
+
4...20mA
E12
Level and Pressure
123 5678
-
+
­ VEGADIS 10
+
4...20mA
E12
OK
AM10
p
Page 2
Safety information, Note Ex area

Safety information

Please read this manual carefully, and also take note of country-specific installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and acci­dent prevention rules. For safety and warranty reasons, any internal work on the instruments, apart from that in­volved in normal installation and electrical con­nection, must be carried out only by qualified VEGA personnel.
2 VEGABAR 41 (4 … 20 mA)

Note Ex area

Please note the attached safety instructions containing important information on installation and operation in Ex areas. These safety instructions are part of the operating instructions and come with the Ex approved instruments.
Page 3
Contents
Contents
Safety information ........................................................................ 2
Note Ex area ................................................................................ 2
1 Product description
1.1 Function and configuration .................................................. 4
1.2 Self-monitoring ..................................................................... 4
1.3 Technical data....................................................................... 5
1.4 Approvals and certificates ................................................ 10
1.5 Dimensions ......................................................................... 11
2 Mounting
2.1 Mounting instructions ......................................................... 14
2.2 Compensation of the atmospheric pressure ................... 14
3 Electrical connection
3.1 Connection instructions ..................................................... 14
3.2 Connection diagram .......................................................... 15
3.3 Connection examples ........................................................ 16
4Setup
4.1 Display module ................................................................... 17
4.2 Setup with module
"Adjustment of the basic functions“ .................................. 17
4.3 Setup with module
"Menu-driven adjustment with additional functions“ ........ 19
5 Diagnostics
5.1 Maintenance ....................................................................... 25
5.2 Failure rectification ............................................................. 25
6 Instrument modification
6.1 Exchange of adjustment modules .................................... 26
6.2 Exchange of electronics .................................................... 27
VEGABAR 41 (4 … 20 mA) 3
Page 4

1 Product description

Product description

1.1 Function and configuration

VEGABAR 41 is an efficient pressure trans­mitter with isolating system for process pres­sure measurement and hydrostatic level measurement. The hydrostatic pressure of the products acts on the separating dia­phragm of the isolating system and is trans­mitted via the isolating liquid to the metal­capacitive measuring cell. This capacitance change is detected by an ASIC (Application specific integrated circuit) and converted by the internal electronics with microcontroller into a pressure-proportional signal. The pre­cise, high-resolution digital processing of measurement data ensures perfect technical data.
Isolating systems are used to protect the measuring cell against corrosive products or high temperatures. With the right choice of isolating liquid and diaphragm material, these systems can provide a temperature resist­ance up to 400°C.
The electronics module is powered by a separate VEGA-signal conditioning instru­ment, a stabilised power supply unit or a PLC (active input). After adjustment, a standard current signal 4 … 20 mA is made available and can be displayed or (e.g. in PLC-sys­tems) further processed.

1.2 Self-monitoring

To improve reliability, the functionality of im­portant electronic components is continu­ously checked, and internal parameters such as sensor value, temperature and operating voltage are closely monitored.
VEGABAR 41 with the ceramic CERTEC measuring cell offers the advantage of con­tinuous self-monitoring. The measuring and reference capacitances of the measuring cell constitue a predefined ratio over the entire measuring range. Any deviation from these data is a reliable indicator of a malfunction of the measuring cell.
If errors or malfunctions are detected during these routines, a fault signal is triggered via the 4 … 20 mA-output (current jump to
3.6 mA or 22 mA).
®
-
For carrying out adjustment, the following alternatives are available:
- adjustment module directly on VEGABAR
- adjustment modules in external housing (VEGADIS 10)
4 VEGABAR 41 (4 … 20 mA)
Page 5
Product description

1.3 Technical data

Mechanical data
Materials, wetted parts
Process connection stainless steel 1.4571 Diaphragm stainless steel 1.4571, Hastelloy C276, Tantalum,
Extension stainless steel 1.4571
Materials, non-wetted parts
Housing high resistance plastic PBT (Polyester)
- optional Alu-die-casting, powder-coated Ground terminal stainless steel 1.4305 Window of the display module Lexan
Weight
VEGABAR approx. 0.8 … 8 kg (dependent on the isolating
Adjustment and indicating elements
Adjustment of the basic functions 2 keys, 1 rotary switch Menu-driven adjustment with additional functions
- adjustment elements 4 keys
- indicating elements DOT-Matrix display, 3 lines with 7 figures each Display module LC-display with
PTFE-foil on 1.4571
system)
- bar graph (20 segments)
- digital value (4 digits)
- tendency indicators for rising or falling values
VEGABAR 41 (4 … 20 mA) 5
Page 6
Product description
Nominal measuring range
Gau ge pressure resistance
Low pressure resistance
Gauge press ure
0…0,4 bar / 0…40 kPa 30 bar / 3 000 kPa -0,8 bar / -80 kP a 0…1,0 bar / 0…100 kPa 35 bar / 3 500 kPa -1,0 bar / -100 kP a 0…2,5 bar / 0…250 kPa 50 bar / 5 000 kPa -1,0 bar / -100 kP a 0…5,0 bar / 0…500 kPa 65 bar / 6 500 kPa -1,0 bar / -100 kP a 0…10,0 bar / 0…1 000 kPa 90 bar / 9 000 kPa -1,0 bar / -100 kP a 0…20,0 bar / 0…2 000 kPa 130 bar / 13 000 kPa -1,0 bar / -100 kP a 0…40,0 bar / 0…4 000 kPa 200 bar / 20 000 kPa -1,0 bar / -100 kP a 0…60,0 bar / 0…6 000 kPa 300 bar / 30 000 kPa -1,0 bar / -100 kP a
-0,05…+0,05 bar / -5…+5 kPa 15 bar / 1 500 kPa -0,2 bar / -20 kP a
-0,1…+0,1 bar / -10…+10 kPa 20 bar / 2 000 kPa -0,4 bar / -40 kP a
-0,2…+0,2 bar / -20…+20 kPa 30 bar / 3 000 kPa -0,8 bar / -80 kP a
-0,5…+0,5 bar / -50…+50 kPa 35 bar / 3 500 kPa -1,0 bar / -100 kP a
-1,0…0,0 bar / -100…0 kPa 35 bar / 3 500 kPa -1,0 bar / -100 kPa
-1,0…+1,5 bar / -100…+150 kPa 50 bar / 5 000 kPa -1,0 bar / -100 kP a
-1,0…+4,0 bar / -100…+400 kPa 65 bar / 6 500 kPa -1,0 bar / -100 kP a
-1,0…+10,0 bar / -100…+1 000 kPa 90 bar / 9 000 kPa -1,0 bar / -100 kP a
-1,0…+20,0 bar / -100…+2 000 kPa 130 bar / 13 000 kPa -1,0 bar / -100 kP a
-1,0 …+40,0 bar / -100…+4 000 kPa 200 bar / 20 000 kPa -1,0 bar / -100 kPa
-1,0…+60,0 bar / -100…+6 000 kPa 300 bar / 30 000 kPa -1,0 bar / -100 kP a
A bsolute pressure
0…1,0 bar / 0…100 kPa 35 bar / 3 500 kPa 0…2,5 bar / 0…250 kPa 50 bar / 5 000 kPa 0…5,0 bar / 0 …500 kPa 65 bar / 6 500 kPa 0…10,0 bar / 0…1 000 kPa 90 bar / 9 000 kPa 0…20,0 bar / 0…2 000 kPa 130 bar / 13 000 kPa 0…40,0 bar / 0…4 000 kPa 200 bar / 20 000 kPa 0…60,0 bar / 0…6 000 kPa 300 bar / 30 000 kPa
6 VEGABAR 41 (4 … 20 mA)
Page 7
Product description
Electrical data
Adjustment ranges
Zero adjustable from -20 … +95 % of nominal range Span adjustable from 3.3 … 120 % of nominal range
Supply and signal circuit
Supply voltage 12 … 36 V DC Exd-version Permissible residual ripple U Output signal
- range 3.8 … 20.5 mA
- resolution 6 µA Current limiting approx. 22 mA Fault signal 22 mA (3.6 mA) Integration time 0 … 10 s adjustable Rise time 85 ms (ti = 0 sec; 0 – 63 %) Connection line 2-wire Max. permissible load dependent on the supply voltage
Indicating and adjustment current circuit
For connection to VEGADIS 10 and/or display module Data transmission digital Connection cable 4-wire (standard cable) Max. line length 25 m
(pressure-tight encapsulation) 18 … 36 V DC
1 V
SS
(see load diagram)
1000
750 500 250
Load RLtotal in Ohm
0
12
18 24 30 36
Voltage of the external energy UH in Volts
Connection
Cable entry M20 x 1.5 (for cable-ø 5 … 10 mm) Screw terminals for conductor cross-sections of up to 2.5 mm
2
Protective measures
Protection
1)
IP 65 Protection class III Overvoltage category II
1)
Use of a suitable seal for the cable in the PG is necessary for maintaining the housing protection. If the seal used does not fit the cable, it should be replaced by a suitable one.
VEGABAR 41 (4 … 20 mA) 7
Page 8
Product description
Accuracy (similar to DIN 16 086, DIN V 19 259 - 1 and IEC 770)
Deviation
Reference conditions (acc. to IEC 770)
- temperature 15°C … 35°C
- rel. humidity 45 % … 75 %
- air pressure 860 mbar … 1060 mbar/86 kPa … 106 kPa Determination of characteristics limit point adjustment acc. to DIN 16 086 Characteristics linear Deviation in characteristics incl. hysteresis and repeatability
- Turn Down 1 : 1 < 0.25 % with accuracy class 0.25
- Turn Down up to 1 : 5 typ. < 0.3 % with accuracy class 0.25
- Turn Down up to 1 : 10 typ. < 0.4 % with accuracy class 0.25
Influence of the ambient temperature
Average temperature coefficient of the zero signal
2)
- Turn Down 1 : 1 < 0.15 %/10 K with accuracy class 0.25
- Turn Down up to 1 : 5 typ. < 0.225 %/10 K with accuracy class 0.25
- Turn Down up to 1 : 10 typ. < 0.3 %/10 K with accuracy class 0.25
Long-term stability
Long-term drift of the zero signal
1) 3)
< 0.1 % with accuracy class 0.1
typ. < 0.1 % with accuracy class 0.1
typ. < 0.2 % with accuracy class 0.1
< 0.05 %/10 K with accuracy class 0.1
typ. < 0.075 %/10 K with accuracy class 0.1
typ. < 0.1 %/10 K with accuracy class 0.1
< 0.1 % per 2 years
Other actuating variables
Calibration position upright, diaphragm points downwards Influence of mounting position < 0.2 mbar/20 Pa Vibration resistance mechanical vibrations with 4 g and
5 … 100 Hz, tested acc. to the regulations of German Lloyd GL-characteristics 2
1)
Relating to the nominal measuring range.
2)
In the compensated temperature range of 0°C … +80°C, reference temperature 20°C. Without isolating diaphragm, capillaries, cooling element (see: Influence of the ambient temperature).
3)
Acc. to IEC 770, point 6.1.2 relating to the nominal measuring range.
8 VEGABAR 41 (4 … 20 mA)
Page 9
Product description
Operating conditions
Ambient conditions
Ambient temperature -40°C … +85°C
- with display module -20°C … +70°C Storage and transport temperature -40°C … +85°C Product temperature, dependent on isolating liquid Temperature
- silicone oil -40°C … +150°C / -40°C … +130°C
- silicone oil and cooling element -40°C … +200°C / -40°C … +130°C
- silicone oil and capillaries 1 m -40°C … +200°C / -40°C … +130°C
- vegetable oil -10°C … +130°C / -10°C … +130°C
- vegetable oil and cooling element -10°C … +200°C / -10°C … +130°C
- high temperature oil and cooling elem. -10°C … +400°C / -10°C … +200°C
- high temperature oil and capillaries 1 m -10°C … +400°C / -10°C … +200°C
Additional temperature influence of isolating module
Process connection Temperature coefficient
FA Flange DN 25 PN 40 to DIN 2501,
seal surface to DIN 2526 Form D 1.8
FB Flange DN 40 PN 40 to DIN 2501,
seal surface to DIN 2526 Form D 1.0
FC Flange DN 50 PN 40 to DIN 2501,
seal surface to DIN 2526 Form D 2.0
FE Flange DIN 50 PN 40 with extens. 100 mm 1.9
FG Flange DN 50 PN 40 with extens. 200 mm 2.1
FH Flange DN 80 PN 40 to DIN 2501,
seal surface to DIN 2526 Form D 0.4
FK Flange DN 80 PN 40 with extens. 100 mm 0.5
FN Flange DN 1" 300 lbs to ANSI B 16.5,
seal surface RF 1.8
FO Flange DN 2" 600 lbs to ANSI B 16.5,
seal surface RF 2.0
p
> 1 bar / p
abs
[mbar/10 K]
4) < 1 bar
abs
- of cooling elements,
dependent on diaphragm-ø 0.1 … 1.5 mbar/10 K
- of 1 m capillary line
dependent on diaphragm-ø 0.1 … 15 mbar/10 K
VEGABAR 41 (4 … 20 mA) 9
Page 10
Product description

1.4 Approvals and certificates

Approvals
- Ex Zone 2
- StEx Zone 10
- Ship approval
- CENELEC EEx ia IIC
- ATEX II 1G EEx ia IIC
- ATEX II 2G EExd ia IIC
If the use of approved instruments is required for certain applications, the relevant official documents (test reports, test certificates and conformity certificates) must be observed. These are supplied with the respective instrument.
CE conformity
VEGABAR 41 meets the requirements of EMC (89/336/EWG) and NSR (73/23/EWG). Con­formity has been judged acc. to the following standards. EMVG Emission EN 50 081 - 1: 1992
NSR EN 61 010 - 1: 1993
NAMUR regulations
Full compliance with the NAMUR-regulations NE 21 and NE 43.
Susceptibility EN 50 082 - 2: 1995
10 VEGABAR 41 (4 … 20 mA)
Page 11
Product description

1.5 Dimensions

Housing without indicating module with indicating module
85
~76
72
Pg 13,5
82
Ver sion plastic PBT
90
Ground connection
~76
Ver sion Alu-die casting
82
M20x1,5
Ground connection
156
90
~76
Version Alu-die casting in EExd
78
Ground connection
82
½" NPT
VEGABAR 41 (4 … 20 mA) 11
Page 12
Process fittings
Product description
Cooling element
Standard
100
d2
51
d4
k
D
FA, FB, FC FH FN, FO
D = outer flange diameter b = flange thickness k = diameter of hole circle d
= diameter of holes
2
d
= seal ledge diameter
4
= extension diameter
d
5
f = seal ledge strength R
= extension length
L
d
= diaphragm diameter
M
Standard
83
51
f
b
L
R
d5
FE, FG, FK
Flange connection to DIN 2501, seal ledge to DIN 2526 Form D
Order Flange Holes Seal ledge Extension code siz e D b k No. d2d
fRLd
4
d
5
M
FA DN 25 / PN 40 115 22 85 4 14 68 2 –– –– –– FB DN 40 / PN 40 150 18 110 4 18 88 3 –– –– –– FC DN 50 / PN 40 165 20 125 4 18 102 3 –– –– – – FE 100 48.3 47 FG 200 48.3 47 FH DN 80 / PN 40 200 24 160 8 18 138 3 –– –– –– FK 100 76 72
Flange connection to ANSI B 16.5, seal ledge RF
FN DN 1" / 300 lbs 125 22 89 4 20 51 2 FO DN 2" / 600 lbs 165 32 127 8 20 92 6.4
12 VEGABAR 41 (4 … 20 mA)
Page 13
Product description
Tube isolating module for mounting between flanges with connection to DIN 2501
Order DN PN D Mb code
RC 50 6 … 400 95 54.5
Tube isolating module with connection to DIN 11 851
Order DN PN G1 L2 D2 d6 g m code
RF 50 25 Rd78x1/6 156 70 68.5 11 18
Tube isolating module with Clamp­connection
Order DN PN L D d D1D2Mb code
RH 2" 40 1566456.3567548
60
D
Mb
g
d6
d
D
Mb
L2
D2
L
D2
D1
VEGABAR 41 (4 … 20 mA) 13
Page 14
Mounting, Electrical connection

2 Mounting

2.1 Mounting instructions

VEGABAR can be mounted in any position. Cable entries must point downwards to avoid moisture ingress. For this purpose the hous­ing can be rotated by 330° in relation to the mounting part.
A seal, appropriate for the connection, must be used for mounting. This seal is either supplied with VEGABAR or must be provided by the customer.
2.2 Compensation of the atmos­pheric pressure

3 Electrical connection

3.1 Connection instructions

The electronics in VEGABAR 41 requires a supply voltage of 12 … 36 V DC. It is pro­vided in two-wire technology, i.e. supply voltage and current signal are led to the terminals via the same two-wire connection cable.
This external energy is provided via a sepa­rate power supply unit:
- power supply unit, e.g. VEGASTAB 690
- processing unit with integrated DC current source (e.g. active PLC-input)
- VEGAMET or VEGADIS 371
Make sure that the external energy source is reliably separated from the mains circuits acc. to DIN VDE 0106, part 101. The above­mentioned VEGA instruments meet this re­quirement, and protection class III is there­fore ensured.
The external energy source must supply a terminal voltage of at least 12 V to the trans­mitter. The actual ter minal voltage on the transmitter depends on the following factors:
- output voltage of the external energy source under nominal load.
- electrical resistances of the connected instruments in the circuit (see Connected instruments, load resistor).
On instruments for gauge pressure meas­urement, the atmospheric pressure is com­pensated via a breather facility integrated in the housing.
14 VEGABAR 41 (4 … 20 mA)
Page 15
Electrical connection
Note the following instructions for electrical connection:
- Connection must be made according to the specific installation standards (e.g. in Ger­many acc. to the VDE-regulations).
- Terminal voltage must not exceed 36 V, to avoid damage to the electronics.
- Electrical connection must have a pre­ventative measure against inadvertent polarity reversal.
- The wiring between VEGABAR and the power supply can be carried out using standard two-wire cable.
- Screened cable is recommended if strong electromagnetic interference is to be ex­pected. The shielding must be grounded at the sensor end.
- If overvoltages are expected, we recom­mend the installation of VEGA-overvoltage arresters.
- In the cable connection, a seal must be used which fits the cable.
- For instrument version EExd (pressure­tight encapsulation) screened cable must be used for the instrument connection. Note the installation regulations.

3.2 Connection diagram

Note:
An ammeter for local control of the output current can be connected to terminals 1 and 3. This measurement can be made during operation without interrupting current on the supply line.
VEGABAR with display module
Ammeter for local control
Function ground
1)
321
Plug connec­tion
8765
Display module
VEGADIS 10 with display module
0 - 20 bar
+
Supply voltage 12 … 36 V DC 4 … 20 mA
1)
If screened cable is used, the screening should be grounded in the terminal compartment and the ground terminal outside on the housing must be grounded according to regulations. The terminals are connected to each other in the housing.
VEGABAR 41 (4 … 20 mA) 15
0 - 20 bar
Page 16

3.3 Connection examples

Supply via power supply unit
Processing is carried out using an indicating instrument
Ammeter for local control
+ – –
1 2 3
VEGABAR terminals
Supply via a PLC with active input circuit
Processing is carried out by a PLC with active input circuit.
Ammeter for local control
analogue / digital indicat­ing instrument
Power supply unit
~
+
Electrical connection
+ – –
1 2 3
VEGABAR terminals
PLC
PLC
+
16 VEGABAR 41 (4 … 20 mA)
Page 17
Setup

4 Setup

Electrical connection and setup can be sim­plified by temporarily mounting the cover or the display module on VEGABAR laterally or downwardly displaced.
VEGABAR
+ ­4 ¼ 20 mA
12 ¼ 36 V DC E12
OK
87654321
-
DISPLAY
+
VEGADIS 10
Tighten screws lightly
Display module

4.1 Display module

Digital value
- 4 digital and decimal point
- basic function module: indicates a perma­nent bar measurement range
- menu-driven module: allows individual scaling of bar measurement range
Connection is made via a plug connector according to the "Electrical connection“ sec­tion.
4.2 Setup with module "Adjustment of the basic functions“
Adjustment elements
Rotary switch: Select requested function
Key +: Modify
OPERATE t
i
ZERO SPAN
Adjustment system
• Select the required function with the rotary
switch.
• Change the value with the "+“ and "–“ keys.
• Reset rotary switch to OPERATE, the ad-
justed values are transferred to the EEP­ROM-memory. They remain there even in case of voltage drop.
Adjustment
For adjustment of zero and span, an amme­ter must be connected to terminals 1 and 3. The measured value is identical to the output current.
value (increase
Key –: Modify value (de­crease)
Tendency indication
Bar graph
(e.g. process pressure zero or vessel empty)
• Set rotary switch to zero
• By pushing the "+“ and "–“ keys (simulta-
neously) the current jumps directly to 4 mA
1 Adjustment of zero
Digital value
or set it to 4 mA by pushing the "+“ and "–“ keys.
Adjustment range of zero:
-20 % … +95 % of the nominal range (corre-
sponds to turn of up to +95 %)
VEGABAR 41 (4 … 20 mA) 17
Page 18
Setup
2 Adjustment of span
(e.g. process pressure or vessel level at maximum)
• Set rotary switch to span
• By pushing the "+“ and "–“ keys (simulta­neously) the current jumps directly to 20 mA or set it to 20 mA by pushing the "+“ and "–“ keys.
Adjustment range of span:
3.3 % … 120 % of the nominal range (corre-
sponds to turn down 1 : 30)
Note:
- A modification of zero does not influence the span.
- It is also possible to adjust currents for partial fillings or partial pressures, e.g. 8 mA for 25 % and 16 mA for 75 %. VEGA­BAR automatically calculates the current values for 0 % or 100 % (only possible at 3.3 %).
Integration time
An integration time ti of 0 … 10 s can be ad­justed for damping of pressure shocks.
Procedure
• Set rotary switch to t
• By pushing the "-“ key 10 times make sure that the integration time is set to 0 s
• For every 1 s requested integration time, push the "+“ key once
The integration time is the time required by the current output signal to reach 90 % of the actual level after a sudden change of the process pressure.
i
18 VEGABAR 41 (4 … 20 mA)
Page 19
Setup
4.3 Setup with module "Menu-driven adjustment with additional functions“
Adjustment elements
Indication of:
- measured value
- functions in menu
Jump to the menu below
with the OK key
Reset to the menu above
with the OK key
Depending on parameter: change value (increase) or choose out of a list
+
OPERATE
3.00
mbar
Depending on parameter: change value (decrease) or choose out of a list
–>
OK
The adjustment with the multifunctional mod­ule is menu-orientated and is made via the four keys in conjunction with the text display. The move from the measured value indication to the main menu is made with the "OK“ key. Use the "“ key to change within a menu from one menu item to another.
Branching points
A branching point is shown by the symbol and enables a jump to the menu below with the "OK“ key. In this menu you can find pa­rameters which are linked (possibly in other submenus).
Choose menu item or interrupt adjustment
Depending on the menu item, save the adjusted value or change the menu level
Reset
A reset is shown by the symbol and ena­bles a jump back to the menu above with the "OK“ key.
Automatic jump back to measured value indication is triggered 60 minutes after the last key push.
Parameters have no or symbol. The value of the parameters can be modified with the "+“ and "–“ keys or chosen from the list. When these keys are pushed once, the value flashes first. When pushed again, the value is modified. The modified value can be saved with the "OK“ key. Push the "“ key to inter­rupt input (without saving the modification).
Certain parameters can be displayed but not modified.
VEGABAR 41 (4 … 20 mA) 19
Page 20
Menu schematic
Setup
Operate
0.2
mbar
Ad-
just-
ment
Adjust
with
press.
Measured value indication
Calcu-
lation
ti
1
s
Adjust
without
press.
Unit
0.0
mbar
psi kPa
Output Simula-
Unit
0.0
mbar
psi kPa % Scal. mA
Current
output
4-20mA
20-4mA
Scaling
indica-
tion
0%=
0
Fault
signal
22mA
Escape
3.6mA
Escape
The scaling can be carried out only if in the menu item "unit“ the option "scal“ had been previously chosen.
100%=
1000
Decimal
point
888.8
Escape
On sensors with a measuring range < 1 bar the unit
mbar
can be chosen instead of
Offset
correc-
tion
Offset
corr. OK?
Zero
0.0
mbar
bar
Span
100.0
mbar
.
Escape
Escape
tion
Sim.
xx.x
mbar
Sensor
unpres-
surized?
Zero
4.000
mA
Span
4.000
mA
Escape
20 VEGABAR 41 (4 … 20 mA)
Page 21
Setup
Addi­tional funct.
Sensor
data
Escape
Lan-
guage
Lan-
guage
English
Reset
Reset OK ?
Escape
Franc. Ital. Español Deutsch
Fabr.-
Date
49.98
1)
The values indicated here (min. and max. values) can be set to the present value by pushing the "+“ and "–“ keys simulta­neously.
P min
-0.3
mbar
1)
Use the arrow key to move to the right in the menu plan.
Reset
Now!
OK ?
P max
150
mbar
1) 1) 1)
Temp.
30.7
°C
T min
23.5
°C
T max
36.2
°C
Diagno-
stic no.
- - -
Escape
Adjust
with
press.
Escape
Scaling indica-
tion
In the menu items with these symbols, you can move to the top or bottom with the "OK“ key.
Light grey menu points are only dis­played if necessary (dependent on the instrument version).
Span
100.0
mbar
Lan-
guage
English
Franc. Ital. Español
White letters indicate the parameters which can be modified with the "+“ or "–“ key and saved with the "OK“ key.
Sensor or measured value information which cannot be modified in these positions are in italics.
List These options can be selected with the "+“ or "–“ key and saved with the "OK“ key.
Deutsch
VEGABAR 41 (4 … 20 mA) 21
Page 22
Setup
Adjustment taking the current pres­sure into account (live adjustment)
Live adjustment comprises two steps: 1 Adjustment of zero 2 Adjustment of span
The appropriate output current is indicated via the DOT-matrix.
1 Adjustment of zero
(e.g. process pressure zero or vessel empty)
Set the current value to 4.000 mA
Zero
4,000
with the "+“ or "–“ key. Then push the
mA
"OK“ key.
2 Adjustment of span
(e.g. process pressure or vessel level max.)
Set the current value to 20.000 mA
Span
20,000
with the "+“ or "–“ key. Then push the
mA
"OK“ key.
Note:
- A modification of zero does not influence the adjusted span.
- Push “+” and “-” simultaneously for stand­ard adjustment of zero/span. The value jumps directly to 4 mA/20 mA.
- In the case of a high turn down, the "+“ and "–“ should generally be pushed simultane­ously for adjustment (due to resolution).
- When pushing the "+“ or "–“ keys individu­ally, the output current remains at the last value, it takes on the adjusted value only after saving with the "OK“ key.
- It is also possible to adjust currents for partial fillings or partial pressures, e.g. 8 mA for 25 % and 16 mA for 75 %. VEGA­BAR then automatically calculates the cur­rent values for 0 % or 100 % (only possible with a delta >3.3 %).
Adjustment without taking the current pressure into account (dry adjustment)
Adjustment without pressure comprises four steps: 1 Selection of the unit in which the adjustment
is to be carried out 2 Offset correction 3 Adjustment of zero 4 Adjustment of span
The offset correction (only in mode gauge pressure) defines the reference position for the measurement. It can be carried out:
- before or after adjustment of zero and
span
- before or after installation of VEGABAR.
VEGABAR must be unpressurised for the offset correction!
Adjustment without pressure can be carried out with the sensor installed or not installed (e.g. workroom). Any currently existing pres­sure has no effect on the adjustment.
1 Selection of the unit
Adjust
without
Choose the unit with the "+“ or "–“ key. Save the selected unit with the
press.
"OK“ key.
Unit
0.0
mbar
psi kPa
22 VEGABAR 41 (4 … 20 mA)
Page 23
Setup
3 Adjustment of zero
Zero
Adjust zero with the "+“ or "–“ key
0,0
and save with the "OK“ key.
mbar
4 Adjustment of span
Span
Adjust span with the "+“ or "–“ key
100,0
and save with the "OK“ key.
mbar
Note:
- A modification of zero does not influence the span, i.e. the final value of the measur­ing range will simply be shifted.
- By pushing the "+“ and "–“ keys, the output current remains on the last value, after saving with the "OK“ key, the output current takes on the adjusted value.
Evaluation
Adjustment of the integration time
An integration time ti of 0 s ... 10 s
ti
1
can be adjusted with the “+” or “-”
s
shocks. The adjusted value can be saved with the "OK“ key.
key for damping of pressure
Indication scaling
In operating condition, the actual measured pressure is displayed on the display module:
- as a bar graph with 20 segments
- as a 4-digit digital value.
Scaling
indica-
tion
0%=
100%=
0 Escape
1000
Decimal
point
888.8
Bar graph and digital value relate to the ad­justed measuring range and change in pro­portion to the current output. Digital values < –10 % or > 110 % are shown as flashing figures.
As a result of scaling, the 4 mA or 20 mA user-specific current output values are sent to the display module as 4-digit digital val­ues.
Outputs
Current output/Selection of the character­istics
Selection of the indicated unit
The actually measured pressure is
Unit
0.0
indicated on the DOT-matrix in the
mbar
measured value indication. The
psi
appropriate unit can be chosen
kPa
with the "+“ or "–“ key and the "OK“
%
key from a list. When choosing the
Scal.
unit "Scal.“, the following menu
mA
items are available.
The current output provides the actual meas­ured pressure as an analogue current signal 4 … 20 mA depending on the adjustment.
The characteristics can be also
Current
output
4-20mA
inverted, i.e. switched to 20 ... 4 mA with the "+“ or "–“ keys and the
20-4mA
"OK“ key
Fault signal
The fault signal is triggered via the current output if, during continuous self-monitoring, failures, damage or interference of the meas­uring cell or the electronics are detected.
You can choose whether the failure
Fault
signal
current should be 22 mA or 3.6 mA
22mA
3.6mA
VEGABAR 41 (4 … 20 mA) 23
with the "+“ or "–“ keys and the "OK“ key.
Page 24
Setup
Simulation
Simula-
You can set with the "+“ or "–“ keys
tion
an individual pressure or %-value to check the outputs of VEGABAR and
Sim.
the connected components. The set
xx,x
value flashes during activated simu-
mbar
lation. The simulation can be
stopped with the "OK“ key.
Additional functions
Sensor data
Important sensor data can be displayed via the DOT-matrix for information and diagnostic purposes:
- manufacturing date
- pointer function (p
- pointer function (p
- actual temperature value (Temp)
- pointer function (T
- pointer function (T
- diagnostic number
Addi-
tional
funct.
min
max
min
max
)
)
)
)
Language
Lan-
guage
Lan-
guage
English
Franc. Ital. Español Deutsch
Reset
Reset
Reset OK ?
Reset
Now!
OK ?
VEGABAR comes adjusted to the language in which it is ordered. The languages German, English, French, Italian or Spanish can be chosen with the "+“ or "–“ key and the "OK“ key.
The reset function deletes the ad­justed values and resets the param­eters to the default values. The adjustment data again correspond to the nominal measuring range.
Sensor
data
Fabr.
P min
P max
Tem p.
date
49.98
1)
The min. and max. values can be set to the actual value by pushing the "+“ and "–“ keys simultane­ously.
24 VEGABAR 41 (4 … 20 mA)
150
-0.3
mbar
mbar
1)
1) 1) 1)
30.7
°C
T min
23.5
°C
T max
36.2
°C
Diagno-
stic no.
- - -
Page 25
Diagnostics

5 Diagnostics

5.1 Maintenance

VEGABAR process pressure transmitters are maintenance-free.

5.2 Failure rectification

Fault signals
VEGABAR provides maximum reliability with its self-test and continuous self-monitoring. If however malfunctions occur, VEGABAR diag­nosis distinguishes between atypical proc­ess conditions and faults in the VEGABAR.
Atypical process conditions
Exceeding or falling short of measuring range limits (fault signal extinguishes when the measured value is again in the measuring range).
Failure in VEGABAR
Failure in the electronics, interference or damage in the measuring cell.
The following table assists in analysis of fault signals.
Reason Fault signal via
Clea rly "OPERATE Bar graph 0 % outside ???? or 100 % Cu rrent measuring bar“ digital value value range flashes 3.6 mA
Overload Bar graph 0 % range or 100 %, of the digital value meas. cell four segments
Failure in all segments VEGABAR flash
DOT-matrix Bar graph Current
Digital indication output
or >21.6 mA
flash
On instruments with menu-driven adjustment with additional functions, the possible rea­sons are displayed under the menu item "Diagnosis-no.“ in case of failure.
Diagnosis-no. Meaning
1 No frequency from C/f-converter
2 Frequency signal of the capacitor not
within the limit values
3 Frequency signal of the reference
capacitor not within the limit values
4 Frequency signal temperature not
within the limit values
7 Communication error to EEPROM
9 Error in EEPROM CRC-checksum
11 Process fitting or electronics unit has
been exchanged (appears for approx. 20 s after first switching on after exchange)
Troubleshooting
If the displayed value does not correspond to the level in the vessel or to the process pressure, the following measures must be taken:
- check the pressure compensation (only with gauge pressure measuring ranges)
- check the electrical connection.
VEGABAR 41 (4 … 20 mA) 25
Page 26
Diagnostics, Instrument modification

6 Instrument modification

Checking pressure compensation
Open the housing of VEGABAR. The meas­ured value must not change. However, if the displayed value changes, compensation of the atmospheric pressure is not ensured, which will lead to distortion of the measured value. Check the breather on the VEGABAR­housing.
Checking the electrical components
–+
1 2 3
mA
Ammeter for local control
V
mA
External energy source
~
+
Voltage Current
Voltage
- the terminal voltage on VEGABAR must be at least 12 V DC
Current
Current value Condition
3.8 … 20.5 mA standard range for the output
0 mA signal line interrupted
< 3.6 mA sensor electronics or pressure
22 mA shortcircuit in the signal line,
current
sensor element defective
sensor electronics or pressure sensor element defective

6.1 Exchange of adjustment modules

Display module
Module for basic functions
Module for menu-driven adjustment
VEGABAR
The modular construction of VEGABAR allows retrofitting, interchange or removal of the display module. Data previously saved (e.g. adjustment values) are not stored in the ad­justment module but in an EEPROM of the sensor electronics and therefore readjust­ment is not necessary. The connection of the modules is made via a 4-pole plug connec­tion.
Module without adjustment
26 VEGABAR 41 (4 … 20 mA)
Page 27
Instrument modification
Exchange of the adjustment module
Removal of the adjustment module
• Separate VEGABAR from the power supply
• Loosen the screws on the upper side of the housing and remove the cover or the display module
• Loosen connection cables from the termi­nals, if necessary pull out the plug con­nection of the display module
• Remove the two screws of the adjustment module
• Remove adjustment module and pull out plug connection
Insertion of an adjustment module
• Plug the plug connection of the new ad­justment module into the plug-in socket of the sensor electronics
• Fasten the new adjustment module
• Reconnect the connection cables, if nec­essary, also the cable from the display module
• Close cover or display module of VEGA­BAR
• Reconnect VEGABAR to power supply

6.2 Exchange of electronics

You first have to remove the adjustment mod­ule, as described in chapter "6.1 Exchange of adjustment modules“, in order to exchange the complete electronic module of VEGABAR.
Ground screw
Fixing screw
Fixing screw
Plug connection
• Remove the ground screw and the two smaller fixing screws connecting the elec­tronic unit with the housing
• Pull the electronic unit to the top and pull out the plug connection
• Proceed in reverse sequence when install­ing the new electronics module
Note:
No new adjustment is necessary after ex­changing the electronics module. When switching on the first time (connection of the supply voltage) after exchange of the elec­tronics units, it takes approx. 20 s until the current measured value is displayed.
VEGABAR 41 (4 … 20 mA) 27
Page 28
VEGA Grieshaber KG Am Hohenstein 113 D-77761 Schiltach Germany Phone +49 (0) 7836 50-0 Fax +49 (0) 7836 50-201 E-Mail info@de.vega.com
www.vega.com
ISO 9001
The statements on types, application, use and operating conditions of the sensors and processing systems correspond to the latest infor­mation at the time of printing.
Technical data subject to alterations
2.23 561 / Octobre 2001