VEGA BAR40 User Manual

Operating Instructions
PROF I
VEGABAR 40 (Profibus PA)
Address 12345678
on off
Zum Anschluss an
For connection to
123 5678
PA+PA
VEGADIS 10
­E21PA
PROCESS FIELD BUS
BUS
S H
AM10
Level and Pressure
123 5678
PA+PA
VEGADIS 10
­E21PA
OK
AM10
p
Contents
Safety information ........................................................................ 2
Note Ex area ................................................................................ 2
1 Product description
1.1 Function and configuration .................................................. 4
1.2 Self-monitoring ..................................................................... 4
1.3 Technical data ....................................................................... 5
1.4 Approvals and certificates .................................................. 9
1.5 Dimensions ......................................................................... 10
2 Electrical connection
2.1 Connection instructions ..................................................... 11
2.2 Connection diagram .......................................................... 11
Contents

Safety information

Please read this manual carefully, and also take note of country-specific installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and acci­dent prevention rules. For safety and warranty reasons, any internal work on the instruments, apart from that in­volved in normal installation and electrical con­nection, must be carried out only by qualified VEGA personnel.
2 VEGABAR 40 (Profibus PA)

Note Ex area

Please note the attached safety instructions containing important information on installation and operation in Ex areas. These safety instructions are part of the operating instructions and come with the Ex approved instruments.
Contents
3 Mounting
3.1 Mounting instructions ......................................................... 12
3.2 Compensation of the atmospheric pressure ................... 12
4Setup
4.1 Adjustment of the Profibus PA address ........................... 13
4.2 Display module ................................................................... 14
4.3 Setup with module
"Menu-driven adjustment with additional functions“ ........ 15
4.4 Setup with adjustment software
VEGA Visual Operating (VVO) ......................................... 21
5 Diagnostics
5.1 Maintenance ....................................................................... 29
5.2 Failure rectification ............................................................. 29
6 Instrument modification
6.1 Exchange of adjustment modules .................................... 30
6.2 Exchange of electronics .................................................... 31
6.3 Exchange of the process fitting ........................................ 32
VEGABAR 40 (Profibus PA) 3

1 Product description

Product description

1.1 Function and configuration

VEGABAR 40 process pressure transmitters are efficient instruments for process pres­sure measurement. As pressure sensor element, the dry ceramic-capacitive measur­ing cell CERTEC sure effects via the diaphragm a capacitance change within the measuring cell. This ca­pacitance change is detected by an ASIC (application specific integrated circuit) and converted into a pressure-proportional signal by the integrated oscillator with microcontroller. In addition, the process tem­perature is detected via a sensor element and converted into a temperature-dependent signal. Precise, high-resolution digital processing of measurement data ensures excellent technical data.
The electronics module is powered by a Profibus DP - PA segment coupler. The measured pressure is transmitted via the bus cable as a digital signal to the process­ing system and can be displayed on the indicating module or the external indicating instrument VEGADIS 10.
The following adjustment variants are avail­able:
- adjustment module directly on VEGABAR
- adjustment modules in external housing (VEGADIS 10)
- via PC with adjustment software VEGA Visual Operating (VVO)
®
is used. The process pres-

1.2 Self-monitoring

To improve reliability, the functionality of im­portant electronic components is continu­ously checked, and internal parameters such as sensor value, temperature and operating voltage are closely monitored.
VEGABAR 40 with the ceramic CERTEC measuring cell offers the advantage of con­tinuous self-monitoring. The measuring and reference capacitances of the measuring cell constitute a predefined ratio over the entire measuring range. Any deviation from these data is a reliable indicator of a malfunction of the measuring cell.
If errors or malfunctions are detected during these routines, fault signals are triggered according to the Profibus PA specification.
®
The instrument profile of VEGABAR follows the profile specification version 3.0. The in­strument master file (GSD) is available as download on the homepage of VEGA (www.vega-g.de).
4 VEGABAR 40 (Profibus PA)
Product description

1.3 Technical data

Mechanical data
Materials, wetted parts
Process connection brass 2.041, stainless steel 1.4571 Diaphragm saphire-ceramic Seal measuring cell Viton, EPDM, Hifluour, Kalrez
Materials, non-wetted parts
Housing high resistance plastic PBT (Polyester)
- optional Alu die casting, powder-coated Ground terminal stainless steel 1.4305 Display module window Lexan
Weight
VEGABAR approx. 0.8 kg
Adjustment and display elements
Menu-driven adjustment with additional function
- adjustment elements 4 keys
- display elements DOT-matrix display, 3 lines with 7 figures each Version without adjustment module
- adjustment element 8-pole mini coding switch for adjustment of the bus address
Display module LC-display with
- bar graph (20 segments)
- digital value (4 digits)
- tendency indicators for rising or falling
values
®
(99.9 % Oxideceramic)
VEGABAR 40 (Profibus PA) 5
Product description
Nominal measuring range
Gau ge pressure resistance
Low pressure resistance
Gauge pressure
0…0,1 bar / 0…10 kPa 15 bar / 1 500 kPa -0,2 bar / -20 kPa 0…0,2 bar / 0…20 kPa 20 bar / 2 000 kPa -0,4 bar / -40 kPa 0…0,4 bar / 0…40 kPa 30 bar / 3 000 kPa -0,8 bar / -80 kPa 0…1,0 bar / 0…100 kPa 35 bar / 3 500 kPa -1,0 bar / -100 kPa 0…2,5 bar / 0…250 kPa 50 bar / 5 000 kPa -1,0 bar / -100 kPa 0…5,0 bar / 0…500 kPa 65 bar / 6 500 kPa -1,0 bar / -100 kPa 0…10,0 bar / 0…1 000 kPa 90 bar / 9 000 kPa -1,0 bar / -100 kPa 0…20,0 bar / 0…2 000 kPa 130 bar / 13 000 kPa -1,0 bar / -100 kPa 0…40,0 bar / 0…4 000 kPa 200 bar / 20 000 kPa -1,0 bar / -100 kPa 0…60,0 bar / 0…6 000 kPa 200 bar / 20 000 kPa -1,0 bar / -100 kPa
-0,05…+0,05 bar / -5… +5 kPa 15 bar / 1 500 kPa -0,2 bar / -20 kPa
-0,1…+0,1 bar / -10… +10 kPa 20 bar / 2 000 kPa -0,4 bar / -40 kPa
-0,2…+0,2 bar / -20… +20 kPa 30 bar / 3 000 kPa -0,8 bar / -80 kPa
-0,5…+0,5 bar / -50… +50 kPa 35 bar / 3 500 kPa -1,0 bar / -100 kPa
-1,0…0,0 bar / -100…0 kPa 35 bar / 3 500 kPa -1,0 bar / -100 kPa
-1,0…+1,5 bar / -100… +150 kPa 50 bar /5 000 kPa -1,0 bar / -100 kPa
-1,0…+4,0 bar / -100… +400 kPa 65 bar / 6 500 kPa -1,0 bar / -100 kPa
-1,0…+10,0 bar / -100… +1 000 kPa 90 b ar / 9 000 kPa -1,0 bar / -100 kPa
-1,0…+20,0 bar / -100… +2 000 kPa 130 b ar / 13 000 kPa -1,0 bar / -100 kPa
-1,0 …+40,0 bar / -100…+4 000 kPa 200 bar / 20 000 kPa -1,0 bar / -100 kPa
-1,0…+60,0 bar / -100… +6 000 kPa 200 b ar / 20 000 kPa -1,0 bar / -100 kPa
A bsolute pressure
0…1,0 bar / 0…100 kPa 35 bar / 3 500 kPa 0…2,5 bar / 0…250 kPa 50 bar / 5 000 kPa 0…5,0 bar / 0 …500 kPa 65 bar / 6 500 kPa 0…10,0 bar / 0…1 000 kPa 90 bar / 9 000 kPa 0…20,0 bar / 0…2 000 kPa 130 bar / 13 000 kPa 0…40,0 bar / 0…4 000 kPa 200 bar / 20 000 kPa 0…60,0 bar / 0…6 000 kPa 200 bar / 20 000 kPa
6 VEGABAR 40 (Profibus PA)
Product description
Electrical data
Adjustment ranges
Zero adjustable from -20 … +95 % of nominal range Span adjustable from 3.3 … 120 % of nominal range
Supply and signal circuit
Supply voltage 9 … 32 V DC
Current consumption 10 mA ± 1 mA Integration time 0 … 50 s Rise time 85 ms (ti = 0 sec; 0 – 63 %)
Display and adjustment circuit
For connection to VEGADIS 10 and/or display module Data transmission digital Connection line 4-wire (standard line) Max. line length 25 m
Connection
Cable entry M20 x 1.5 (for cable-ø 5 … 10 mm) Screw terminals for conductor cross-sections of up to 2.5 mm Recommended bus cable types - SINEC 6XV 830-5AH10 (Siemens AG)
Protective measures
Protection
1)
Protection class III Overvoltage category III
(delivered by the segment coupler)
- SINEC L2 6XV1 830-35H10 (Siemens AG)
- 3079 A (Belden)
IP 65
2
1)
Use of a suitable seal for the cable in the PG is necessary for maintaining the housing protection. If the seal used does not fit the cable, it should be replaced by a suitable one.
VEGABAR 40 (Profibus PA) 7
Product description
Accuracy (similar to DIN 16 086, DIN V 19 259 - 1 and IEC 770)
Deviation
Reference conditions (acc. to IEC 770)
- temperature 15°C … 35°C
- rel. humidity 45 % … 75 %
- air pressure 860 mbar … 1060 mbar/86 kPa … 106 kPa Determination of characteristics limit point adjustment acc. to DIN 16 086 Characteristics linear Deviation in characteristics incl. hysteresis and repeatability
- Turn Down 1 : 1 < 0.25 % with accuracy class 0.25
- Turn Down up to 1 : 5 typ. < 0.3 % with accuracy class 0.25
- Turn Down up to 1 : 10 typ. < 0.4 % with accuracy class 0.25
Influence of the ambient temperature
Average temperature coefficient of the zero signal
2)
- Turn Down 1 : 1 < 0.15 %/10 K with accuracy class 0.25
- Turn Down up to 1 : 5 typ. < 0.225 %/10 K with accuracy class 0.25
- Turn Down up to 1 : 10 typ. < 0.3 %/10 K with accuracy class 0.25
Long-term stability
Long-term drift of the zero signal
1) 3)
< 0.1 % with accuracy class 0.1
typ. < 0.1 % with accuracy class 0.1
typ. < 0.2 % with accuracy class 0.1
< 0.05 %/10 K with accuracy class 0.1
typ. < 0.075 %/10 K with accuracy class 0.1
typ. < 0.1 %/10 K with accuracy class 0.1
< 0.1 % per 2 years
Other actuating variables
Calibration position upright, diaphragm points downward Influence of mounting position < 0.2 mbar/20 Pa Vibration resistance mechanical vibrations with 4 g and
5 … 100 Hz, tested acc. to the regulations of German Lloyd GL-characteristics 2
1)
Relating to the nominal range.
2)
In compensated temperature range of 0°C … +80°C, reference temperature 20°C.
3)
Acc. to IEC 770, point 6.1.2 relating to the nominal range.
8 VEGABAR 40 (Profibus PA)
Product description
Operating conditions
Ambient conditions
Ambient temperature -40°C … +85°C
- with display module -20°C … +70°C
Storage and transport temperature -40°C … +85°C Product temperature, dependent on seal material of the measuring cell
- Viton -20°C … +100°C
- EPDM -40°C … +100°C
- Hifluour -10°C … +100°C
- Kalrez 0°C … +100°C

1.4 Approvals and certificates

Approvals
- Ex Zone 2
- StEx Zone 10 (applied for)
- CENELEC EEx ia IIC
- ATEX II 1G EEx ia IIC
If the use of approved instruments is required for certain applications, the appropriate official documents (test reports, test certificates and conformity certificates) must be ob­served. These are supplied with the respective instrument.
CE conformity
VEGABAR 40 meets the requirements of EMC (89/336/EWG) and NSR (73/23/EWG). Conformity has been judged acc. to the following standards: EMC Emission EN 50 081 - 1: 1992
NSR EN 61 010 - 1: 1993
Susceptibility EN 50 082 - 2: 1995
NAMUR-regulations
Full compliance with the NAMUR-regulations NE 21, May 1993.
VEGABAR 40 (Profibus PA) 9

1.5 Dimensions

Housing without indicating module with indicating module
85
~76
Product description
Version plastic PBT
72
82
Process connections
92
SW 27
25
90
¼" NPT
½" NPT
GN
M20x1,5
Ground connection
Ground connection
92
SW 27
25
20
15
82
ø11,4
½" NPT
GA
~76
Version Alu die casting
M20x1,5
92
SW 27
25
5
20
ø3
ø6
M20x1,5
GB
92
SW 27
25
5
ø3
ø6
G ½ A
GM/GV
87
SW 27
20
3
G ¼
ø17,5
G ½ A
GP
87
SW 27
20
3
ø11,4
ø17,5
G ½ A
GR
92
SW 27
25
5
ø3
ø6
G ½ A
GI
10 VEGABAR 40 (Profibus PA)
Electrical connection

2 Electrical connection

2.1 Connection instructions

The electronics in VEGABAR 40 requires a supply voltage of 9 … 32 V DC. The supply voltage and the digital output signal are lead via the same two-wire connection cable to the terminals. The external energy is provided via a segment coupler.

2.2 Connection diagram

VEGABAR with display module
Function ground
Plug connec-
321
+
tion
8765
Display module
Note the following instructions for electrical connection:
- Connection must be made according to the specific installation standards (e.g. in Ger­many acc. to the VDE-regulations).
- Electrical connection must have a protec­tive measure against polarity reversal.
- The connection of field instruments is gen­erally made via T-adapters on stubs.
- Screened cable is recommended for con­nection (cable types see chapter "1.3 Tech­nical data“). The shielding must be grounded on both ends (on the T-adapter and on VEGABAR).
- For use in Ex areas, the installation regula­tions must be observed.
VEGADIS 10 with display module
0 - 20 bar
Stub
+
Bus cable
T-adapter
VEGABAR 40 (Profibus PA) 11
0 - 20 bar