Please read this manual carefully, and also take
note of country-specific installation standards
(e.g. the VDE regulations in Germany) as well
as all prevailing safety regulations and accident prevention rules.
For safety and warranty reasons, any internal
work on the instruments, apart from that involved in normal installation and electrical connection, must be carried out only by qualified
VEGA personnel.
2VEGABAR 40 (Profibus PA)
Note Ex area
Please note the attached safety instructions
containing important information on installation
and operation in Ex areas.
These safety instructions are part of the
operating instructions and come with the Ex
approved instruments.
6.1 Exchange of adjustment modules .................................... 30
6.2 Exchange of electronics .................................................... 31
6.3 Exchange of the process fitting ........................................ 32
VEGABAR 40 (Profibus PA)3
1 Product description
Product description
1.1 Function and configuration
VEGABAR 40 process pressure transmitters
are efficient instruments for process pressure measurement. As pressure sensor
element, the dry ceramic-capacitive measuring cell CERTEC
sure effects via the diaphragm a capacitance
change within the measuring cell. This capacitance change is detected by an ASIC
(application specific integrated circuit) and
converted into a pressure-proportional signal
by the integrated oscillator with
microcontroller. In addition, the process temperature is detected via a sensor element
and converted into a temperature-dependent
signal. Precise, high-resolution digital
processing of measurement data ensures
excellent technical data.
The electronics module is powered by a
Profibus DP - PA segment coupler. The
measured pressure is transmitted via the
bus cable as a digital signal to the processing system and can be displayed on the
indicating module or the external indicating
instrument VEGADIS 10.
The following adjustment variants are available:
- adjustment module directly on VEGABAR
- adjustment modules in external housing
(VEGADIS 10)
- via PC with adjustment software VEGA
Visual Operating (VVO)
®
is used. The process pres-
1.2 Self-monitoring
To improve reliability, the functionality of important electronic components is continuously checked, and internal parameters such
as sensor value, temperature and operating
voltage are closely monitored.
VEGABAR 40 with the ceramic CERTEC
measuring cell offers the advantage of continuous self-monitoring. The measuring and
reference capacitances of the measuring cell
constitute a predefined ratio over the entire
measuring range. Any deviation from these
data is a reliable indicator of a malfunction of
the measuring cell.
If errors or malfunctions are detected during
these routines, fault signals are triggered
according to the Profibus PA specification.
®
The instrument profile of VEGABAR follows
the profile specification version 3.0. The instrument master file (GSD) is available as
download on the homepage of VEGA
(www.vega-g.de).
4VEGABAR 40 (Profibus PA)
Product description
1.3 Technical data
Mechanical data
Materials, wetted parts
Process connectionbrass 2.041, stainless steel 1.4571
Diaphragmsaphire-ceramic
Seal measuring cellViton, EPDM, Hifluour, Kalrez
- display elementsDOT-matrix display, 3 lines with 7 figures each
Version without adjustment module
- adjustment element8-pole mini coding switch for adjustment of the
bus address
Display moduleLC-display with
- bar graph (20 segments)
- digital value (4 digits)
- tendency indicators for rising or falling
values
®
(99.9 % Oxideceramic)
VEGABAR 40 (Profibus PA)5
Product description
Nominal measuring range
Gau ge pressure
resistance
Low pressure
resistance
Gauge pressure
0…0,1 bar / 0…10 kPa15 bar / 1 500 kPa-0,2 bar / -20 kPa
0…0,2 bar / 0…20 kPa20 bar / 2 000 kPa-0,4 bar / -40 kPa
0…0,4 bar / 0…40 kPa30 bar / 3 000 kPa-0,8 bar / -80 kPa
0…1,0 bar / 0…100 kPa35 bar / 3 500 kPa-1,0 bar / -100 kPa
0…2,5 bar / 0…250 kPa50 bar / 5 000 kPa-1,0 bar / -100 kPa
0…5,0 bar / 0…500 kPa65 bar / 6 500 kPa-1,0 bar / -100 kPa
0…10,0 bar / 0…1 000 kPa90 bar / 9 000 kPa-1,0 bar / -100 kPa
0…20,0 bar / 0…2 000 kPa130 bar / 13 000 kPa-1,0 bar / -100 kPa
0…40,0 bar / 0…4 000 kPa200 bar / 20 000 kPa-1,0 bar / -100 kPa
0…60,0 bar / 0…6 000 kPa200 bar / 20 000 kPa-1,0 bar / -100 kPa
-0,05…+0,05 bar / -5… +5 kPa15 bar / 1 500 kPa-0,2 bar / -20 kPa
-0,1…+0,1 bar / -10… +10 kPa20 bar / 2 000 kPa-0,4 bar / -40 kPa
-0,2…+0,2 bar / -20… +20 kPa30 bar / 3 000 kPa-0,8 bar / -80 kPa
-0,5…+0,5 bar / -50… +50 kPa35 bar / 3 500 kPa-1,0 bar / -100 kPa
-1,0…0,0 bar / -100…0 kPa35 bar / 3 500 kPa-1,0 bar / -100 kPa
-1,0…+1,5 bar / -100… +150 kPa50 bar /5 000 kPa-1,0 bar / -100 kPa
-1,0…+4,0 bar / -100… +400 kPa65 bar / 6 500 kPa-1,0 bar / -100 kPa
-1,0…+10,0 bar / -100… +1 000 kPa90 b ar / 9 000 kPa-1,0 bar / -100 kPa
-1,0…+20,0 bar / -100… +2 000 kPa130 b ar / 13 000 kPa-1,0 bar / -100 kPa
-1,0 …+40,0 bar / -100…+4 000 kPa200 bar / 20 000 kPa-1,0 bar / -100 kPa
-1,0…+60,0 bar / -100… +6 000 kPa200 b ar / 20 000 kPa-1,0 bar / -100 kPa
A bsolute pressure
0…1,0 bar / 0…100 kPa35 bar / 3 500 kPa
0…2,5 bar / 0…250 kPa50 bar / 5 000 kPa
0…5,0 bar / 0 …500 kPa65 bar / 6 500 kPa
0…10,0 bar / 0…1 000 kPa90 bar / 9 000 kPa
0…20,0 bar / 0…2 000 kPa130 bar / 13 000 kPa
0…40,0 bar / 0…4 000 kPa200 bar / 20 000 kPa
0…60,0 bar / 0…6 000 kPa200 bar / 20 000 kPa
6VEGABAR 40 (Profibus PA)
Product description
Electrical data
Adjustment ranges
Zeroadjustable from -20 … +95 % of nominal range
Spanadjustable from 3.3 … 120 % of nominal range
Supply and signal circuit
Supply voltage9 … 32 V DC
Current consumption10 mA ± 1 mA
Integration time0 … 50 s
Rise time85 ms (ti = 0 sec; 0 – 63 %)
Display and adjustment circuit
For connection toVEGADIS 10 and/or display module
Data transmissiondigital
Connection line4-wire (standard line)
Max. line length25 m
Connection
Cable entryM20 x 1.5 (for cable-ø 5 … 10 mm)
Screw terminalsfor conductor cross-sections of up to 2.5 mm
Recommended bus cable types- SINEC 6XV 830-5AH10 (Siemens AG)
Protective measures
Protection
1)
Protection classIII
Overvoltage categoryIII
(delivered by the segment coupler)
- SINEC L2 6XV1 830-35H10 (Siemens AG)
- 3079 A (Belden)
IP 65
2
1)
Use of a suitable seal for the cable in the PG is necessary for maintaining the housing protection. If the seal
used does not fit the cable, it should be replaced by a suitable one.
VEGABAR 40 (Profibus PA)7
Product description
Accuracy (similar to DIN 16 086, DIN V 19 259 - 1 and IEC 770)
Deviation
Reference conditions (acc. to IEC 770)
- temperature15°C … 35°C
- rel. humidity45 % … 75 %
- air pressure860 mbar … 1060 mbar/86 kPa … 106 kPa
Determination of characteristicslimit point adjustment acc. to DIN 16 086
Characteristicslinear
Deviation in characteristicsincl. hysteresis and repeatability
- Turn Down 1 : 1< 0.25 % with accuracy class 0.25
- Turn Down up to 1 : 5typ. < 0.3 % with accuracy class 0.25
- Turn Down up to 1 : 10typ. < 0.4 % with accuracy class 0.25
Influence of the ambient temperature
Average temperature coefficient
of the zero signal
2)
- Turn Down 1 : 1< 0.15 %/10 K with accuracy class 0.25
- Turn Down up to 1 : 5typ. < 0.225 %/10 K with accuracy class 0.25
- Turn Down up to 1 : 10typ. < 0.3 %/10 K with accuracy class 0.25
Long-term stability
Long-term drift of the zero signal
1) 3)
< 0.1 % with accuracy class 0.1
typ. < 0.1 % with accuracy class 0.1
typ. < 0.2 % with accuracy class 0.1
< 0.05 %/10 K with accuracy class 0.1
typ. < 0.075 %/10 K with accuracy class 0.1
typ. < 0.1 %/10 K with accuracy class 0.1
< 0.1 % per 2 years
Other actuating variables
Calibration positionupright, diaphragm points downward
Influence of mounting position< 0.2 mbar/20 Pa
Vibration resistancemechanical vibrations with 4 g and
5 … 100 Hz, tested acc. to the regulations of
German Lloyd GL-characteristics 2
1)
Relating to the nominal range.
2)
In compensated temperature range of 0°C … +80°C, reference temperature 20°C.
3)
Acc. to IEC 770, point 6.1.2 relating to the nominal range.
8VEGABAR 40 (Profibus PA)
Product description
Operating conditions
Ambient conditions
Ambient temperature-40°C … +85°C
- with display module-20°C … +70°C
Storage and transport temperature-40°C … +85°C
Product temperature, dependent on
seal material of the measuring cell
- Viton-20°C … +100°C
- EPDM-40°C … +100°C
- Hifluour-10°C … +100°C
- Kalrez0°C … +100°C
1.4 Approvals and certificates
Approvals
- Ex Zone 2
- StEx Zone 10 (applied for)
- CENELEC EEx ia IIC
- ATEX II 1G EEx ia IIC
If the use of approved instruments is required for certain applications, the appropriate
official documents (test reports, test certificates and conformity certificates) must be observed. These are supplied with the respective instrument.
CE conformity
VEGABAR 40 meets the requirements of EMC (89/336/EWG) and NSR
(73/23/EWG). Conformity has been judged acc. to the following standards:
EMCEmissionEN 50 081 - 1: 1992
NSREN 61 010 - 1: 1993
SusceptibilityEN 50 082 - 2: 1995
NAMUR-regulations
Full compliance with the NAMUR-regulations NE 21, May 1993.
The electronics in VEGABAR 40 requires a
supply voltage of 9 … 32 V DC. The supply
voltage and the digital output signal are lead
via the same two-wire connection cable to the
terminals. The external energy is provided
via a segment coupler.
2.2 Connection diagram
VEGABAR with display module
Function
ground
Plug connec-
321
–
+
tion
8765
Display module
Note the following instructions for electrical
connection:
- Connection must be made according to the
specific installation standards (e.g. in Germany acc. to the VDE-regulations).
- Electrical connection must have a protective measure against polarity reversal.
- The connection of field instruments is generally made via T-adapters on stubs.
- Screened cable is recommended for connection (cable types see chapter "1.3 Technical data“). The shielding must be
grounded on both ends (on the T-adapter
and on VEGABAR).
- For use in Ex areas, the installation regulations must be observed.
VEGADIS 10 with display module
0 - 20 bar
Stub
+
Bus cable
T-adapter
VEGABAR 40 (Profibus PA)11
–
0 - 20 bar