The described module must only be installed
and operated as described in these operating
instructions. Please note that other action can
cause damage for which VEGA does not take
responsibility.
2VEGABAR 24
Note Ex-area
Please note the approval documents attached
(yellow binder), and especially the safety data
sheet included .
Contents
Contents
Safety information ........................................................................ 2
6.2 Exchange of the hygienic form seal on VEGABAR 24 .... 24
VEGABAR 243
1 Product description
Product description
1.1 Function and configuration
The VEGABAR 24 process pressure transmitters are efficient instruments for process
pressure measurement. The dry CERTEC
ceramic-capacitive measuring cell is used as
a pressure sensor element. The process
pressure causes a capacitance change
within the measuring cell via the diaphragm.
This capacitance change is detected by an
ASIC (application specific integrated circuit)
and converted into a pressure proportional
signal by an integral oscillator with microcomputer. Precise digital processing of measured data with highest resolution ensures
excellent technical data.
The oscillator is powered by a separate
VEGA-signal conditioning instrument, a stabilised power supply unit or a PLC (active
input). After adjustment, a standardised
current signal of 4 … 20 mA is available
which can be displayed (e.g. in PLC-systems) or further processed.
For versions are available for adjustment:
- adjustment module directly on VEGABAR
- adjustment module in external housing
(VEGADIS 10)
- via PC with adjustment software (see
manual “VEGA Visual Operating (VVO)“)
- in the control room on the signal conditioning instrument
®
1.2 Self-monitoring
Important electronic components are
checked for their function, while internal parameters, such as sensor value, temperature
and operating voltage, are monitored to increase reliability.
VEGABAR 20 with the ceramic CERTEC®measuring cell offers the advantage of continuous self-monitoring. The measuring and
reference capacitances of the measuring cell
are in a defined ratio over the complete
measuring range. Any deviation from these
data is a reliable indicator for a malfunction of
the measuring cell.
If failures or malfunctions are detected during
these routines, a fault signal is triggered via
the 4 … 20 mA-output (current jump to
3,6 mA or 22 mA).
4VEGABAR 24
Product description
1.3 Technical data
Mechanical data
Materials, wetted parts
Process connectionstainless steel 1.4571, PVDF
1)
Diaphragmceramic (99,5 % Oxydeceramic)
Seal measuring cellViton, Kalrez, EPDM
Adjustment of the basic functions2 keys, 1 rotating switch
Menu-guided adjustment with
additional function
- adjustment elements4 key
- indicating elementsDOT-matrix display, 3 lines with 7 figures each
Indicating moduleLC-display with
- bar graph (20 segments)
- digital value (4-digit)
- tendency indicators for raising or lowering
values
Electrical data
Connection
Cable entryPG 13,5 (for cable-ø 5 … 10 mm)
Screw terminalsfor conductor cross-sections of up to
2,5 mm
2
Protective measures
Protection
1)
IP 65
Protection classIII
Overvoltage categoryIII
CE-conformity
VEGABAR 24 meets the requirements of EMC (89/336/EWG) and NSR (73/23/EWG). The
conformity has been judged acc. to the following standards
EMCEmissionEN 50 081 - 1: 1992
SusceptibilityEN 50 082 - 2: 1995
NSREN 61 010 - 1: 1993
1)
Use of a suitable seal for the cable in the PG is necessary for maintaining the housing protection. If the seal
used does not fit the cable, it should be replaced by a suitable one.
VEGABAR 245
NAMUR-regulations
The NAMUR-regulations NE 21, May 1993 are met.
Supply and signal circuit
Supply voltage12 … 36 V DC
Permissible residual rippleUSS - 1 V
Output signal
- range3,8 … 20,5 mA
- resolution6 µA
Current limitationapprox. 22 mA
Fault signal22 mA (3,6 mA)
Integration time0 … 10 s adjustable
Average delay time150 ms
Connection cable2-wire
Max. permissible loaddependent on the supply voltage
(see load diagram)
1000
750
in Ohm
500
total
250
Load RL
0
12
18 24 30 36
Voltage of the external energy UH in Volts
Product description
Indicating and adjustment circuit
For connection toVEGADIS 10 and/or the indicating module
Data transmissiondigital
Connection cable4-wire (standard cable)
Cable lengthmax. 25 m
Transmission reaction
Measuring ranges
Min. pressure10 mbar
Zero-20 % … +95 % adjustable of nominal range
Span3,3 % … 120 % adjustable of nominal range
Turn upup to +95 %
Turn downup to 1 : 30
Recommended turn down:
Accuracy class 0,25up to 1 : 5
accuracy class 0,1up to 1 : 10
6VEGABAR 24
abs
Product description
Measuring ranges
Nominal rangeGauge pressure Low pressure
resistance
1)
resistance
Gauge pressure
0 … 0,1 bar10 bar-0,1 bar
0 … 0,2 bar15 bar-0,2 bar
0 … 0,4 bar20 bar-0,4 bar
0 … 1,0 bar25 bar-1,0 bar
0 … 2,5 bar35 bar-1,0 bar
0 … 5,0 bar45 bar-1,0 bar
0 … 10,0 bar60 bar-1,0 bar
0 … 20,0 bar90 bar-1,0 bar
-0,05 … 0,05 bar10 bar-0,1 bar
-0,1 … +0,1 bar15 bar-0,2 bar
-0,2 … +0,2 bar20 bar-0,4 bar
-0,5 … +0,5 bar25 bar-1,0 bar
-1,0 … +0,0 bar25 bar-1,0 bar
-1,0 … +1,5 bar35 bar-1,0 bar
-1,0 … +4,0 bar45 bar-1,0 bar
-1,0 … +10,0 bar60 bar-1,0 bar
-1,0 … +20,0 bar90 bar-1,0 bar
Absolute pressure
0 … 1,0 bar25 bar
0 … 2,5 bar35 bar
0 … 5,0 bar45 bar
0 … 10,0 bar60 bar
0 … 20,0 bar90 bar
0 … 40,0 bar140 bar
0 … 60,0 bar200 bar
1)
Note nominal pressure stage of the process connection!
VEGABAR 247
Product description
Accuracy (similar to DIN 16 086, DIN V 19 259 - 1 and IEC 770)
Deviation
Reference conditions (acc. to IEC 770)
- temperature18°C … 30°C rel. humidity
- air pressure860 kPa … 1060 kPa
Determination of characteristicslimit point adjustment acc. to DIN 16 086
Characteristicslinear
Deviation in characteristics
- accuracy class 0,25< 0,25 %
- accuracy class 0,1< 0,1 %
Hysteresis
Repeatability
1)
1)
Influence of the ambient temperature
Average temperature coefficient
of the zero signal
1) 2)
- accuracy class 0,25< 0,15 %/10 K
- accuracy class 0,1< 0,05 %/10 K
1)
< 0,02 %
< 0,02 %
Long-term stability
Long-term drift of the zero signal
1) 3)
< 0,1 %
Other actuating variables
Calibration positionstanding, diaphragm points downwards
Influence of the installation position< 0,2 mbar
Vibration resistancemechanical vibrations with 4 g and
5 … 100 Hz, tested acc. to the regulations of
German Lloyd GL-characteristics 2
Operating conditions
Product
Aggregate conditionsgas, steam, liquid up to high viscosity
Ambient conditions
Ambient temperature-40°C … +85°C
- indicating module-20°C … +70°C
Storage and transport temperature-40°C … +85°C
Product temperature-40°C … +100°C
also abrasive and aggressive with suitable
material selection of wetted parts
acc. to order code
1)
Relating to the nominal measuring range.
2)
In the compensated temperature range of 0°C … +80°C, reference temperature 20°C.
3)
Acc. to IEC 770, point 6.1.2 relating to the nominal measuring range.
8VEGABAR 24
Product description
1.4 Approvals
Ex Zone 2
StEx Zone 10
Ship approval
CENELEC EEx ia IIC
ATEX II 1G EEx ia IIC and WHG
ATEX II 1G EEX ia IIC and ship approval
DVGW (applied)
If the use of approved instruments is required for certain applications, the appropriate legal
documents (test reports, test certificates and conformity certificates) must be observed.
These are supplied with the appropriate instrument.
1.5 Dimensions
Housing
without indicating modulewith indicating module
85
~76
72
Pg 13,5
Earth connection
82
Breather facility
VEGABAR 249