ntary documents appropriate to the ordered version come
with the delivery. You can find them listed in chapter "Product
description".
Instructions manuals for accessories and replacement parts
Tip:
re reliable setup and operation of your VEGABAR 14, we offer
To ensu
accessories and replacement parts. The corresponding documentations are:
l 32036 - Welded socket and seals
Editing status: 2011-09-23
22441-EN-111006
VEGABAR 143
1 About this document
1 About this document
1.1 Function
is operating instructions manual provides all the information you
Th
need for mounting, connection and setup as well as important
instructions for maintenance and fault rectification. Please read this
information before putting the instrument into operation and keep this
manual accessible in the immediate vicinity of the device.
1.2 Target group
This operating instructions manual is directed to trained qualified
personnel. The contents of this manual should be made available to
these personnel and put into practice by them.
1.3 Symbolism used
Information, tip, note
This
symbol indicates helpful additional information.
Caution: If this
result.
Warning: If this warning is ignored, injury to persons and/or serious
damage to the instrument can result.
Danger: If this warning is ignored, serious injury to persons and/or
destruction of the instrument can result.
applications
Ex
Th
symbol indicates special instructions for Ex applications.
is
lList
The dot set in front indicates a list with no implied sequence.
warning is ignored, faults or malfunctions can
àAction
This a
rrow indicates a single action.
1Sequence
Numbers set in front indicate successive steps in a procedure.
22441-EN-111006
4VEGABAR 14
2 For your safety
2 For your safety
2.1 Auth
All operations described in this operating instructions manual must be
carried out only by trained specialist personnel authorised by the plant
operator.
During work on and with the device the required personal protective
equipment must always be worn.
orised personnel
2.2 Appropriate use
VEGABAR 14 is a pressure transmitter for measurement of gauge
pressure, absolute pressure and vacuum.
You can find detailed information on the application range in chapter
"Product description".
Operational reliability is ensured only if the instrument is properly used
according to the specifications in the operating instructions manual as
well as possible supplementary instructions.
For safety and warranty reasons, any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer. Arbitrary
conversions or modifications are explicitly forbidden.
2.3 Warning about misuse
Inappropriate or incorrect use of the instrument can give rise to
application-specific hazards, e.g. vessel overfill or damage to system
components through incorrect mounting or adjustment.
2.4 General safety instructions
This is a high-tech instrument requiring the strict observance of
standard regulations and guidelines. The user must take note of the
safety instructions in this operating instructions manual, the countryspecific installation standards as well as all prevailing safety
regulations and accident prevention rules.
The instrument must only be operated in a technically flawless and
reliable condition. The operator is responsible for trouble-free
operation of the instrument.
During the entire duration of use, the user is obliged to determine the
compliance of the necessary occupational safety measures with the
current valid rules and regulations and also take note of new
regulations.
22441-EN-111006
VEGABAR 145
2 For your safety
2.5 Safety label
The safety approval markings and safety tips on the device must be
observed.
on the instrument
2.6 CE conformity
This device fulfills the legal requirements of the applicable EC
guidelines. By attaching the CE mark, VEGA provides a confirmation
of successful testing. You can find the CE conformity declaration in the
download area of
2.7 Measuring range - permi
www.vega.com.
ssible process pres-
sure
Due to the application, a measuring cell with a measuring range higher
than the permissible pressure range of the process fitting may have
been integrated. The permissible process pressure is stated with
"Process pressure" on the type label, see chapter 3.1 "Configuration".
For safety reasons, this range must not be exceeded.
2.8 Fulfillment of NAMUR recommendations
With respect to interference resistance and emitted interference, the
NAMUR recommendation NE 21 is fulfilled.
2.9 Safety instructions for Ex areas
Please note the Ex-specific safety information for installation and
operation in Ex areas. These safety instructions are part of the
operating instructions manual and come with the Ex-approved
instruments.
2.10 Environmental instructions
Protection of the environment is one of our most important duties. That
is why we have introduced an environment management system with
the goal of continuously improving company environmental protection.
The environment management system is certified according to DIN
EN ISO 14001.
Please help us fulfil this obligation by observing the environmental
instructions in this manual:
l Chapter "Packaging, transport and storage"
l Chapter "Disposal"
6VEGABAR 14
22441-EN-111006
3 Product description
3
1
2
3.1 Structure
3 Product description
pe of delivery
Sco
Structure
Type label
e scope of delivery encompasses:
Th
l VEGABAR 14 process pressure transmitter
l depending on the version, with plug connector, direct cable outlet
or plug connector with connection cable
l Documentation
- this operating instructions manual
- Ex-specific "Safety instructions" (with Ex versions)
- if necessary, further certificates
Fig. 1: VEGABAR 14 with
1Process fitting
2Housing
3Cable outlet
with electronics
cable
outlet
The type label contains the most important data for identification and
use of the instrument:
l Article number
l Serial number
l Technical data
l Article numbers, documentation
With the serial number, you can access the delivery data of the
instrument via
www.vega.com, "VEGA T
ools" and "serial number
search". In addition to the type label outside, you can also find the
serial number on the inside of the instrument.
3.2 Principle of operation
Application area
22441-EN-111006
VEGABAR 147
VEGABAR 14 is a pressure transmitter for measurement of gauge
pressure, absolute pressure or vacuum. Measured products are
gases, vapours and liquids.
3 Product description
Func
tional principle
Voltage supply
Packaging
Transport
Transport inspection
®
The sensor element is the CERTEC
measuring cell with rugged
ceramic diaphragm. The process pressure causes a capacitance
change in the measuring cell via the ceramic diaphragm. This change
is converted into an appropriate output signal and outputted as
measured value.
Two-wire electronics 4 … 20 mA for power supply and measured
value transmission over the same cable.
3.3 Operation
The instrument offers no adjustment options.
3.4 Packaging, transport and storage
The device was protected by packaging during transport. Its capacity
to handle normal loads during transport is assured by a test according
to DIN EN 24180.
The packaging of standard instruments consists of environmentfriendly, recyclable cardboard. For special versions, PE foam or PE foil
is also used. Dispose of the packaging material via specialised
recycling companies.
Transport must be carried out under consideration of the notes on the
transport packaging. Nonobservance of these instructions can cause
damage to the device.
The delivery must be checked for completeness and possible transit
damage immediately at receipt. Ascertained transit damage or
concealed defects must be appropriately dealt with.
Storage
Up to the time of installation, the packages must be left closed and
stored according to the orientation and storage markings on the
outside.
Unless otherwise indicated, the packages must be stored only under
the following conditions:
l Not in the open
l Dry and dust free
l Not exposed to corrosive media
l Protected against solar radiation
l Avoiding mechanical shock and vibration
Storage and transport
temp
erature
l Storage and transport temperature see chapter "Supplement -
Technical data - Ambient conditions"
l Relative humidity 20 … 85 %
8VEGABAR 14
22441-EN-111006
4 Mounting
4 Mounting
bility for the pro-
Suita
cess condition
Mounting position
Welding the socket
Sealing/Screw
s
ing
4.1 General ins
Make sure that all parts of the instrument exposed to the process, in
particular the sensor element, process seal and process fitting, are
suitable for the existing process conditions. These include above all
the process pressure, process temperature as well as the chemical
properties of the medium.
You can find the specifications in chapter "Technical data" or on the
type label.
tructions
4.2 Instructions for installation
VEGABAR 14 functions in any installation position. It is mounted
according to the same directives as a manometer (DIN EN 839-2).
Information:
We recommen
siphons from our line of accessories.
d using lock fittings, measuring instrument holders and
4.3 Mounting steps
For mounting VEGABAR 14, a welded socket is required. You can find
these components in the supplementary instructions manual "Welded
socket and seals".
in
Use the attached seal:
l Process fitting GV, GB and GP
- or -
Seal the thread with teflon, hemp or a similar resistant seal material:
l Process fitting GN
à Screw VEGABAR 14 into the welded socket. Tighten the hexagon
screw on the process fitting. Wrench size, see chapter "Dimen-sions", torque see chapter "Technical data".
22441-EN-111006
VEGABAR 149