Advanced Technology Transmitter for transmission of level and
temperature data from the tankside to inventory management
systems.
Installation and
Operations Manual
IOM003GVAE1007
www.varec.com
5834 Peachtree Corners East, Norcross (Atlanta), GA 30092 USA
Tel: +1 (770) 447-9202 Fax: +1 (770) 662-8939
Varec, Inc.
4000
Copyright
All rights reserved. Printed in the United States of America. Except as permitted under
the United States Copyright Act of 1976, no part of this publication may be reproduced,
stored in a retrieval system or transmitted in any form or by any means- electronic,
mechanical, photocopying, recording or otherwise- without the prior written permission
of the Publisher:
Varec, Inc.
5834 Peachtree Corners East
Norcross (Atlanta) GA 30096
USA
Trademarks acknowledged
Varec, Inc. recognizes all other trademarks. Trademarks of other products mentioned in
this document are held by the companies producing them.
Varec® is a registered trademark of Varec, Inc. Copyright 2003
FuelsManager® is a registered trademark of Varec, Inc. Copyright 2004
MODBUS® is a registered trademark of Modicon, Inc.
TIWAY® is a registered trademark of Texas Instruments Corporation.
HART® interface is a registered trademark of HART communications foundation.
Rosemount® and Smart Family® are registered trademarks, and HART is a
trademark of Rosemount Inc.
i
Tank Gauge Transmitter
Disclaimer of Warranties
The contract between the Seller and the Buyer states the entire obligation of the Seller.
The contents of this document shall not become part of or modify any prior or existing
agreement, commitment or relationship between the Seller and Buyer. There are no
express or implied warranties set out in this document. The only warranties that apply
are those in the existing contract between the Seller and Buyer.
Varec, Inc. products have not been tested by Varec, Inc. under all possible operational
conditions, and Varec, Inc. may not have all the data relative to your application. The
information in this document is not all inclusive and does not and cannot take into
account all unique situations. Consequently, the user should review this product
literature in view of his/her application. If you have any further questions, please contact
Varec, Inc. for assistance.
Limitations of Seller's Liability
In the event that a court holds that this document created some new warranties, Seller's
liability shall be limited to repair or replacement under the standard warranty clause. In
no case shall the Seller's liability exceed that stated as Limitations of Remedy in the
contract between the Seller and Buyer.
Terms of Use
The information provided in this document is provided “as is” without warranty of any
kind. Varec, Inc. disclaim all warranties, either express or implied, including the
warranties of merchantability and fitness for a particular purpose. In no event shall
Varec, Inc. or its suppliers be liable for any damages whatsoever including direct,
indirect, incidental, consequential, loss of business profits or special damages, even if
Varec, Inc. or its suppliers have been advised of the possibility of such damages.
Use of parts that are not manufactured or supplied by Varec, Inc. voids any Varec, Inc.
warranty and relieves Varec, Inc. of any obligation to service the product under warranty.
Varec, Inc. recommends the use of only Varec, Inc. manufactured or supplied parts to
maintain or service Varec, Inc. products.
ii Installation and Operations Manual
4000
Safety Precaution Definitions
Caution!Damage to equipment may result if this precaution is disregarded.
Warning!Direct injury to personnel or damage to equipment which can cause injury to
personnel may result if this precaution is not followed.
Safety Precautions
READ AND UNDERSTAND THIS INSTRUCTION MANUAL BEFORE INSTALLING, OPERATING
OR PERFORMING MAINTENANCE ON VAREC 4000 SERIES TANK GAUGE TRANSMITTER.
FOLLOW ALL PRECAUTIONS AND WARNINGS NOTED HEREIN WHEN INSTALLING,
OPERATING OR PERFORMING MAINTENANCE ON THIS EQUIPMENT.
This manual is designed to assist the user with the installation, configuration, operation, maintenance, and
troubleshooting of the Varec Model 4000 Advanced Technology Transmitter (ATT).
1.2Getting Acquainted with the Advanced Technology Transmitter (ATT)
The Varec Model 4000 Advanced Technology Transmitter (ATT), in conjunction with a host, represents a data
acquisition and communications system for use in liquid level measurement and/or other measurement applications.
Liquid level measurement is provided by the Advanced Technology Transmitter coupled to a Varec Model 2500 or other
level gauge, as shown in Figure 1-1.
Tank Gauge
and
Transmitter
Power
Loop
Communcations
3-wire
RTD
8130 RTU
FuelsManager
Software
or
8300 TGI
CPU
+24V
+5V
COMM
I/O
+15V
ERROR
-15V
Communications
between DCS/PLCs
for control capabilities
Field
Junction Box
Star Communcations e.
Figure 1-1: Tank Installation with Model 4000 ATT
Loop Communcations
. Mark/Space
1
IntroductionTank Gauge Transmitter
1.3Operation
The ATT uses an incremental counting technique for determining liquid level. An initial level is identified as part of the
calibration procedure. Changes to that level are determined through incremental increases or decreases detected by
the ATT.
The host computer collects measurement information by polling the Advanced Technology Transmitter over a variety
of communication interfaces such as EIA485 and Mark/Space. Several communication protocols are supported. Among
them are Modbus and Mark/Space.
1.4Configuration
The Varec Model 1200 Handheld Terminal is used to configure the ATT. It connects to the same ATTI bus used to
interconnect other input/output devices to the ATT. There is a special connection located inside the junction box for
the Handheld Terminal.
1.5Construction
The Advanced Technology Transmitter is housed within an aluminum enclosure. The enclosure and assembly meet
explosion proof requirements and are environmentally sealed to prevent internal exposure to contamination.
7.5 "
(190 mm)
12 "
(308 mm)
4 "
(101 mm)
3.7 "
(94 mm)
Figure 1-2: Model 4000 Advanced Technology Transmitter Assembly
3.4 "
(86 mm)
8 "
(203 mm)
6.8 "
(172 mm)
2 Installation and Operations Manual
4000Installation
2Installation
2.1Overview
This section contains instructions for unpacking, mounting, grounding, and wiring the Varec Model 4000 Advanced
Technology Transmitter (ATT) assembly. An installation checklist is also included.
Warning!To avoid electric shock and possible injury, do not perform any service procedures other than those specified in this
manual. These installation instructions are for use by qualified service technicians.
Figure 2-1: Model 4000 ATT mounted on Model 2500 ATG
2.1.1Unpacking
Remove the ATT from the shipping container and inspect it for evidence of shipping or handling damage. Report any
shipping damage to the carrier. Verify that the contents of the shipping container agrees with the packing list.
2.1.2Storage Prior to Installation
If the ATT is to be stored prior to installation, it should be repackaged in its shipping container and stored in a
temperature and humidity controlled environment.
2.1.3Becoming Familiar with the ATT
The ATT is housed within an explosion proof enclosure. A cover is provided to permit access to both the electronics
and backup batteries.
3/4- and 2 1/2-inch NPT plugs are provided for wiring access. Wiring to the ATT consists of connecting power, host
communication, RTD input and an optional ground connection.
2.1.4Hardware Configuration
All configuration is performed using the Model 1200 Handheld Terminal or a download from a host computer.
However, certain parameters such as communication address and speed must be configured via the Model 1200
Handheld Terminal.
3
InstallationTank Gauge Transmitter
e
E
2.2Mounting the Equipment
The ATT is bolted to the Model 2500 Automatic Tank Gauge head as illustrated in Figure 2-2. It may also be mounted
to Endress+Hauser, Sakura, Tokyo-Keiso, Shand & Jurs, and Gauging Systems, Inc. float and tape gauges with the
Endress+Hauser adapter shown in the following table.
13-05956-202Whessoe 2006, 2026, 2036 and L&J (Shand & Jurs) 92006
Mounting the ATT to the Level Gauge is accomplished in the following manner:
1.Remove the back cover of the Level Gauge.
2.Remove the access cap from the back cover of the Level Gauge.
3.Mount the ATT in place of the access cap, making certain that the word "TOP" cast into the housing lines up with
the top of the Level Gauge back cover.
4.Install the Level Gauge back cover with the transmitter in the Level Gauge. Make certain that the slot in the ATT
drive coupling engages with the pin on the tape sheave of the Level Gauge.
5.Proceed with field wiring.
Back
cover
Junction
box cover
Integral junction
box
Drive coupling
5/16-18 X 1 mounting bolts (4 places)
5/16 split lock washers (4 places)
Transmitter
Pin drive
Sprocket Sheave
2500
Automatic
Tank Gaug
Back Cover
xternal enclosure ground
connection by installer
External Ground Lug
Gauge cover mounting
bolts (15 places)
Figure 2-2: ATT Mounting Diagram
4 Installation and Operations Manual
4000Installation
2.3Grounding the Equipment
Warning!The ATT must be grounded before communication and power connections are made.
An external grounding lug is provided on the ATT. A connection from the ground lug to earth ground must be made
before any other wiring connections are made.
Note!For adequate/proper operation of the ATT lightning arrestor, a ground strap must be attached to the ATT. Grounding
through mounting kits or pipe coupling is not adequate.
Note!Properly seal all ports to prevent moisture or other contamination from entering the wiring compartment.
2.4Wiring
Connections should be made in a conventional manner according to local or plant electric codes.
Warning!Explosion-proof seals must be installed in all wiring entries. Any unused entries must be plugged with pipe plugs and
secured with Loctite®, or equivalent.
2.4.1ATT Wiring
Wiring the ATT is described in the following paragraphs. The wiring diagram provided in Figure 2-3 on page 6 should
be used in conjunction with these wiring instructions.
2.4.2Wiring Preparation
Remove the two thread protectors from the 1/2-inch NPT conduit entries at the top and bottom of the ATT. Remove
the rear cover from the ATT housing.
2.4.3Connecting Input Power
Warning!When connecting DC power leads to the ATT, make certain that power is OFF.
The ATT operates on a 24-48 volts DC power source. The input power connection to the ATT is accomplished in the
following manner.
Connect the positive side of the power supply to terminal 10, B+, and the negative side to terminal 9, B-, of the
terminal block assembly. See Figure 2-3 on page 6.
5
InstallationTank Gauge Transmitter
Figure 2-3: ATT Field Terminal Block Wiring
Terminal Block One TB1Terminal Block Two TB2
1 L+ = ATTI expansion Bus +
power
2 HPORT = ATTI bus HART Signal 11M = Mark or EIA485 -
3 L- = ATTI expansion Bus -
power
4 C = RTD C lead9 B - = ATT - power
5B = RTD B lead8 -- = Reserved
6A = RTD A lead 7 -- = Reserved
12S = Space or EIA485 +
10B + = ATT + power
2.4.4Connecting Host Communication
The procedure used to wire the ATT to the host computer depends on the type of host interface option ordered with
the ATT.
6 Installation and Operations Manual
4000Installation
2.4.5ATT EIA485 Wiring
The ATT uses a 2-wire EIA485 hardware interface to communicate with the Modbus master. EIA485 is a high speed
differential communications network which allows up to 32 devices to operate on one network. The ATT and Modbus
master share a twisted pair of wires to communicate. Figure 2-4 illustrates the typical EIA485 wiring.
The communication distance that EIA485 can reliably travel is dependent on baud rate (communication speed), wire
quality, environmental noise, wiring configuration, and the number of multi-dropped ATTs. The recommended wire
for EIA485 systems is 18-gauge or larger, shielded, twisted pairs. The shield should be earth grounded at the Modbus
master (control system or computer end). The shield at the ATT should be open. The ATT B- power line acts as a
common reference tie to the Modbus master. Figure 2-5 on page 8 illustrates the EIA485 Modbus system.
TB2
TB2
Power Supply
6
5
4
+48
VDCCommon
Figure 2-4: Typical EIA485 Wiring
RTU 8130 with 8230 expansion module
7
InstallationTank Gauge Transmitter
Field Junction Box
Model 4000 ATT
Transmitters*
Model 4000 ATT
* Up to 31 units with
5000 ft. max. wiring distance
using good quality wire.
Two 18 AWG
twisted pair
cables
Field Junction Box
EIA85 comm.
with MODBUS to FIC
Two 18 AWG
twisted pair cables
Transmitters*
Area 0
Area 1
RTU 8130
Model 8130 with optional
48 VDC power supply.
110/220 VAC 50/60 Hz.
RS232 To FuelsManager
or other MODBUS master
RS232 serial port
50 feet max to FIC
Office Printer
Host Computer Interface
certified by Honeywell
FuelsManager
MODBUS interface is
Figure 2-5: Typical EIA485 System Wiring
8 Installation and Operations Manual
4000Installation
2.4.6ATT Mark/Space Wiring
For an ATT using the Mark/Space field communications option, the following additional wiring connections must be
made. (Refer to Input Power Wiring in Section 6 to determine the minimum wire size required.). See Figure 2-6.
• Run two twisted pairs of 18 AWG wire (Mark/Space wires) into the ATT through the conduit entry along with the
48 VDC power wiring.
• Connect the Mark line to terminal 11, M/485-, and the Space line to terminal 12,
S/485+, on the terminal block assembly.
8203 With 8210
expansion module
Field Junction Box
4 Conductor
Cable
18 AWG
Shielded
To Other
4-Wire
Transmitters
in Area 0
Ground shield at RTU8130 ONLY!
Do NOT ground shield at transmitter.
Details of RTU8130 with 8210 expansion
module and ATT termination board wiring
External
Power Supply
Varec
Model 4000
ATT
Figure 2-6: Typical Mark/Space Field Wiring
9
InstallationTank Gauge Transmitter
2.5Connecting the RTD
The following list shows how the ATT is wired to an RTD device. The ATT’s temperature circuit is designed to work
with a platinum or copper 3-wire RTD.
2.5.1Connecting the Handheld Terminal
Figure 2-3 on page 6 shows how the 1200 Hand Held Terminal is connected to the ATTI bus on the ATT. The Model
268 can also be used to configure the ATT.
Warning!The 1200 Hand Held Terminal on the ATT is not Intrinsically Safe. Care must be taken to only use in a non-hazardous
environment
Wire as follows:
• Connect the RTD's A terminal to the ATT's terminal 6, A.
• Connect the RTD's B terminal to the ATT's terminal 5, C.
• Connect the RTD's C terminal to the ATT's terminal 4, C.
2.5.2Wiring Completion
Caution!Do not overtighten metal plugs used to seal wiring compartment ports. Overtightening may damage the housing.
Properly seal the 1/2-inch NPT conduit entry. Install cover and tighten to ensure that the O-ring seal is adequately
compressed. Proper sealing of all ports is necessary to prevent moisture or other contamination from entering the
wiring compartment.
2.5.3Installation Checkout
After a thorough check that all connections are correctly made and that all covers and plugs are installed, turn on
power to the ATT. Proceed to Chapter 3, Configuration.
2.5.4Installation Checklist
The steps required in the installation process are summarized in the following checklist. Since each step is detailed
specifically with accompanying notes, cautions, and warnings, be sure to refer to the sub-sections indicated for further
information.
StepSub-Section(s) Reference
Unpack the ATT and check the packing list.Unpacking
Verify that the required input power is available.Mounting the ATT, Wiring
Mount the ATT.Mounting the Equipment
Ground the ATT.Grounding the Equipment
Route the conduit between the ATT and other
devices and seal all ports.
Wire the host communications.Connecting Host Communication
Wire the RTDConnecting the RTD
Wire the input power connections.Connecting Input Power
Apply power to the ATT.Installation Checkout
Wire the Model 1200 Handheld TerminalConnecting Handheld Terminal
Proceed to ATT configuration procedure.ATT Configuration (Section 3)
Wiring Completion
10 Installation and Operations Manual
4000Configuration
3Configuration
The Varec Model 4000 Advanced Technology Transmitter (ATT) must be configured for the specific tank, attached
sensors, and host interface. This section provides detailed information on ATT configuration.
The ATT can be configured with a 1200 Hand Held Terminal or from a host program such as Varec TankView.
3.1Configuration Parameters
Configuration parameters associated with ATT operation are entered and modified using the Model 1200 and can be
divided into the following areas:
• General Configuration - includes units of measure, level calibration, temperature type selection, and alarm
setpoints.
• Host Configuration - includes the type of host interface used, baud rate selection, and emulation modes for other
level transmitters.
3.21200 Hand Held Terminal
The ATT can be used with a 1200 Hand Held Terminal, see Figure 3-3 on page 13. The Model 1200 provides a local
terminal interface to configure the ATT and encoder at tankside. It is connected to the ATTI bus. It can be physically
attached via two banana plugs located inside the terminal block housing.
The ATT uses the Model 1200 in a different mode of operation. Normally, the Model 1200 polls the ATTI BUS device,
recognizes it, and goes into an internal menu system that is specifically tailored to that ATTI Bus device. The ATT
however, uses the Model 1200 in what is called ASCII Terminal mode. In this mode, the Model 1200 sends keyboard
activity to the ATT and displays screen information from the ATT. The ATT can not be configured with the Rosemount
Model 275 Terminal.
Because of the way the ASCII Terminal mode works on the Model 1200, the ATT is unable to poll any ATTI BUS device
while communicating to it. The ATT goes from an operational mode to an off-line mode. The operational mode is
automatically switched to when the Model 1200 is removed from the ATTI BUS bus.
Warning!The 1200 Hand Held Terminal on the ATT is not Intrinsically Safe. Care must be taken to only use in a non-hazardous
environment.
Function keys F1 through F4, defined in Figure 3-1 on page 11, are used for basic scrolling of the ATT menus and
selection of configuration parameters.
Function KeyDescription
HELPHelp Message
F1Scroll Up
F2Scroll Down
F3Alter/Backspace
F4Enter
Previous Function [Ü]Return to previous menu or abort data entry
Table 3-1:Model 1200 Function Keys
Alpha and numeric information is entered from the keypad directly. Numeric data is entered using a single keystroke,
while alpha information is entered with a two-key combination. The two-key combination for alpha data consists of a
shift key followed by a numeric key to select the desired alpha character.
11
ConfigurationTank Gauge Transmitter
For example, to enter the alpha character "N"; first press the shift key, then press the number 4. To enter the alpha
character "R"; first press the shift key, then press the number 1.
Terminal Mode Configuration
When the Model 1200 is connected to the ATTI Bus and turned on, a blank screen will appear on the Model 1200 after
a self test sequence. Pressing any key will cause the following screen to appear on the Model 1200 display:
The version indicated is the software version of the ATT.
Enter a "D" (to select Display Mode entries) or an "A" (to select Alter Mode entries) and press F4 (Enter).
If the Display Mode is selected with a "D", current status and configuration data may be examined but cannot be
modified. This mode is useful for verifying ATT configuration. This mode cannot be used to actively monitor ATT
operation, as normal ATT operation is suspended when the Model 1200 is connected.
Figure 3-1: ATT Alter Mode Menu Tree
If the Alter Mode is selected with an "A", all applicable configuration parameters can be modified. Figure 3-2 on
page 12 illustrates the display mode menu tree and Figure 3-1 on page 12 illustrates the Alter Mode menu tree. The
menu tree groups related items under separate menus and sub-menus. The menu grouping is provided to permit the
field operator to configure and display items in a related and logical order. Once a menu is selected, the operator can
scroll through related items.
Figure 3-2: ATT Display Mode Menu Tree
12 Installation and Operations Manual
4000Configuration
ON / OFF
Previous Function
Shift
Figure 3-3: 1200 Hand Held Terminal
3.3Terminal Mode Operation
The 1200 Hand Held Terminal is used to scroll through the various ATT menus. Basic scroll and selection operations
are performed using the four function keys (F1 through F4) immediately below the display.
Line 1 of the display contains the menu title. Lines 2 and 3 are item display lines. Line 4 is an error message/status line.
If the item displayed on line 2 is preceded with an "M>", the item being displayed is a menu. You can select the menu
by pressing F4 (Enter). If the item is preceded by a "C>" the item being displayed is a command that can be executed
by pressing F4 (Enter).
Where:
F1 = Up
F2 = Down
F3 = Alter
F4 = Enter
13
ConfigurationTank Gauge Transmitter
3.4Menu Operation
For example, when the Main Menu is displayed on the top line, pressing F1 (Up) will scroll up through the possible
main menu selections while pressing F2 (Down) will scroll down through the possible main menu selections.
Pressing F4 (Enter) will cause the selection of the sub-menu displayed on lines two and three (such as Config Menu).
Scrolling through a sub-menu is performed in the same manner as scrolling through the Main Menu using the F1 and
F2 keys.
To return to the Main Menu, press the PREVIOUS FUNCTION key [Ü], as shown in Figure 3-3 on page 13.
When a parameter is encountered which is to be changed, pressing the F3 key (Alter) will cause the display of the
current parameter in a form which permits its modification.
When a specific set of parameters is available, the F1 and F2 keys can be used to scroll through the valid selections.
When the desired selection is displayed, pressing the F4 key (Enter) will cause selection of the new parameter. When
the parameter consists of numeric or free format characters, the Model 1200 keyboard can be used to enter the
parameter. Note that parameter alteration is not final until the session is completed with the EXIT AND SAVE command
from the Main Menu.
To complete parameter alteration, scroll through the Main Menu until the following display is presented, then press
F4 (Enter) to exit and save the altered parameters.
If parameter alteration is to be aborted (new parameters not saved), scroll through the Main Menu until the following
display is presented and press F4 (Enter) to quit without saving alterations. The QUIT or EXIT AND SAVE commands
must be initiated before turning off or disconnecting the 1200 Hand Held Terminal.
14 Installation and Operations Manual
Loading...
+ 54 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.