Vanguard V5 Operator's Manual

V5
Operator’s Manual
Fire Alarm Panel
(AVF&LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 1 of 21
CONTENTS
1. GENERAL
1.1 Introduction 2
1.2 System Description 2
1.2.1 Zone Detection Module 3
1.2.2 System Control Module 3
1.2.3 LCD Event Logging Module 5
2. OPERATING INSTRUCTIONS
2.1. Normal Operating Conditions 5
2.2. Fire Alarm Condition 6
2.2.1. Silencing the Alarm Bells / Sounders 6
2.2.2. Resetting the System 7
2.3. Fault Condition 7
2.3.1. Silencing the Fault Buzzer 7
2.3.2. Resetting the System 7
2.4. Initiating Evacuate Alarm 8
2.4.1. Silencing Evacuate Alarm 8
2.5. Zone/Auxiliary Disable 8
2.6. Indicators Test 8
2.7 Alarm Verification Feature (AVF) 8
2.8 LCD Event Logging Module (LLM) 9
2.8.1 MENU Function 9
3. ROUTINE MAINTENANCE
3.1. Introduction 12
3.2. Maintenance Responsibilities 12
3.3. Operator Duties – Log Records 12
3.4. Regular Testing and Inspection 12
3.4.1 Daily Check 12
3.4.2 Weekly Test 13
3.4.3 Monthly Test 13
3.4.4 Annual Test 14
4. FAULT FINDING TIPS 16
5. TECHNICAL SPECIFICATION & INSTALLATION DIAGRAM 19
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 2 of 21
1. GENERAL
1.1 Introduction
This manual provided only the basis operator’s information on the control and operation of the Fire Alarm System. To ensure continuous reliability of the system, the owner or owner’s representative should establish an agreement to carry out regular maintenance of the installation with the manufacturer or manufacturer’s representative or a competent and qualified contractor trained to service and maintain this system.
The arrangements for maintenance should be such as well ensure that a qualified person is available on call at all time to provide service in the event of any fault that develops at the installation. For the requirements of the Regular Testing and Inspection, please refer to the section covered in this manual.
1.2 System Description
This Fire Alarm System utilises the V5 Fire Alarm Panel. The system may comprise one or more alarm panel networked together witch performs the task of processing the input signals and thereafter transmit the output signals or initiates other auxiliary functions. The alarm panel (s) are usually sited in the building fire command centre or any prominent location clearly visible from the main entrance.
Input devices are used to cause a change in panel status. These devices may be the combination of Manual Call Points (as in manual and automatic alarm system), Heat/Smoke Detectors (as in automatic alarm systems).
Output devices are used to provide an audio & visual warning. Output devices commonly used are alarm bells although sirens and strobe lights are sometimes used. These three components: Input Devices, Control Panel and Output Devices form the backbone of a Fire Alarm System.
Non-addressable Fire Alarm Systems operates on a “Zone” basis. These zones are groups of input devices grouped in accordance to the locality they are protecting. In the event of a Fire/Fault condition, the location where the signal had originated will be defined by the respective indication on the panel. It is therefore important to be familiar with the zoning of the protected area. A zoning diagram (or zone chart) is usually provided for this purpose.
The Alarm Panel is provided with a feature that continuously monitoring the continuity of the input/detection, output/sounder circuits to ensure integrity of the system. It is also equipped with a battery back-up supply (lasting at least 24 hours) in the event of an incoming supply failure.
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 3 of 21
1.2.1 Zone Detection Module
1
2
3
Zone Detection Module - ZDM
4
5
6
7
8
Indicators and Control
a) Fire (Red) : Zone in fire condition b) Fault (Amber) : Zone detection circuit open/short fault condition c) Disable (Amber) : Zone in disabled condition d) Disable Switch (Blue) : To disable zone fire & fault detection circuit
(Note: Zone disable function only prior to an alarm activation.)
1.2.2 System Control Module
5
V
Model No.
Alarm CounterAlarm Counter
1 2 3 4 5 61 2 3 4 5 6
System Control Module - SCM
Indicators
a) Power On (Green) : System energised by Mains and/or Standby Battery b) Fire (Red) : General Fire Indicator, system in fire condition c) Fault (Amber) : General Fault Indicator, system in fault condition
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 4 of 21
d) Disabled (Amber) : General Disabled Indicator, system in disabled condition e) System Fault (Amber) : Indicate Programmable Micro Controller failure f) Fire Sent (Red) : Fire Signal to Alarm Remote Monitoring Station activated (Optional) g) Fire Line Trouble (Amber) : Fire Signal Line open/short (Optional)
(Note: It shall not be suppressed during the Fire Alarm condition) h) Fault line Trouble (Amber) : Fault Signal Line open/short (Optional) i) Sounder Fault (Amber) : Alarm sounder line open/short (Note : It shall not be suppressed during Fire Alarm condition) j) Earth Fault (Amber) : Field input/output wires shorted to ground k) Auxiliary Fault (Amber) : Auxiliary supply / auxiliary supervised line open/short l) Mains Failure (Amber) : 230V AC Mains supply failure m) Charger fault (Amber) : Charger Fuse blown / charger voltage (low / high) n) Battery Fault (Amber) : Battery supply disconnected / battery fuse blown /
battery voltage (low / high)
o) Alarm Counter (3x7Seg.) : Indicate that number of alarm (false) been activated
(for FALSE Alarm Management) p) AVF Off (Amber) : Indicate that AVF function been set off q) Retard State (Amber) : Indicate that system in Retard State r) Confirmation State (Amber) : Indicate that system in Confirmation State
Control Switches
a) Buzzer Silence (Black) (1) : To silence fault buzzer (Audio & Visual) b) Sounder Silence (Amber) (2) : To silence alarm sounder (Audio & Visual) c) System Reset (Brown) (3) : To normalise the system
(Note: Silence alarm sounder before RESET) d) Indicators Test (White) (4) : To test the working condition of all LED indicators and buzzer e) Auxiliary Disable (Blue) (5) : To disable auxiliary output control function
(Audio & Visual)
f) Sound Alarm (Red) (6) : To raise alarm sounder manually for
emergency evacuation (Audio & Visual)
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 5 of 21
1.2.3 LCD Event Logging Module
FIRE ALARM SYSTEM
07/04/06 M000 20:06
LCD Event Logging Module - LLMLCD Event Logging Module - LLM
Indicators
a) Power On (Green) : System energised by Mains and/or Standby Battery b) Processor Fault (Amber): Indicates that Micro Processor Unit failure in processing c) LCD Display : To display the Panel Status and the Alarm / Fire event c/w date and time (20 Characters x 4 Lines)
Control Switches
a) Escape (Yellow) : To exit from current function / screen b) Menu (1) (Green) : To access other level of function or password key as “1” c) Up (2) (White) : To move cursor up / page up or password key as “2” d) Down (3) (Blue) : To move cursor down / page down or password key as “3” e) Enter (Red) : To select / accept the function / setting
2. OPERATING INSTRUCTIONS
2.1 Normal Operating Conditions
Under normal operating conditions a) The “POWER ON” LED (Green) lighted b) No other indicator shall be lighted c) The panel and all alarms should be completely silent d) LCD display shown as
(07/04/06: 7th April 2006, M000: “Main” panel address “000”, 20:06: 8:06PM)
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
FIRE ALARM SYSTEM
07/04/06 M000 20:06
O&M-V5-FAP-AVF-LCD R0
Pg 6 of 21
2.2 Fire Alarm Condition
The panel / system shall enter into an alarm condition when an input device (such as smoke/heat detector, call point; or pressure/flow switch) is activated.
Under Fire Alarm conditions:
a) Twin “FIRE” LEDs (Red) of the alarm zone lighted b) General, “FIRE “ LED (Red) lighted c) A “Fire sent” LED (Red) lighted (If Alarm Monitoring Station is connected) d) Panel Alarm Buzzer sound e) External alarm bells/sounders activated f) Signal sent to alarm monitoring station (If Alarm Monitoring Station is connected) g) Auxiliary functions activated (eg: Lift homing, AHU shutdowns) h) LCD display shown as (Individual Fire event – latched and recorded)
(01: 1st event of 001EC, M00Z002: “Main” panel address “000” Zone “002” Fire, at 14:49: 2:49PM)
i) For multiple fire events, it shall be displayed by manual action (Up / Down key)
2.2.1 Silencing the Alarm Bells / Sounders
It is a requirement under the Singapore standard Code of Practice CP 10: 2005 that the first alarm can only be silenced after 3 minutes of continuous operation and any subsequent alarms may be silenced immediately. Any attempts to silence the first alarm during the initial 3 minutes of operation will have no effect on the system.
The Sounder Silence LED will flash when the 3 minutes is lapsed; to indicate alarm silencing is permit-able. To silence the alarm upon expiry of the initial 3 minutes and any subsequent alarm, carry out the following procedure:
a) Press “SOUNDER SILENCE” Switch (Amber) (2) b) Sounder Silence LED becomes steady c) External alarm bells/sounders silence d) To silence Alarm Buzzer, press “BUZZER SILENCE” Switch (Black) (1) e) Panel remains in fire state until reset
001EC FIRE
01 M00Z002 14:49
(001EC: Current Event Counter “001”, Fire)
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
Loading...
+ 15 hidden pages