Vanguard V5 Operator's Manual

V5
Operator’s Manual
Fire Alarm Panel
(AVF&LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 1 of 21
CONTENTS
1. GENERAL
1.1 Introduction 2
1.2 System Description 2
1.2.1 Zone Detection Module 3
1.2.2 System Control Module 3
1.2.3 LCD Event Logging Module 5
2. OPERATING INSTRUCTIONS
2.1. Normal Operating Conditions 5
2.2. Fire Alarm Condition 6
2.2.1. Silencing the Alarm Bells / Sounders 6
2.2.2. Resetting the System 7
2.3. Fault Condition 7
2.3.1. Silencing the Fault Buzzer 7
2.3.2. Resetting the System 7
2.4. Initiating Evacuate Alarm 8
2.4.1. Silencing Evacuate Alarm 8
2.5. Zone/Auxiliary Disable 8
2.6. Indicators Test 8
2.7 Alarm Verification Feature (AVF) 8
2.8 LCD Event Logging Module (LLM) 9
2.8.1 MENU Function 9
3. ROUTINE MAINTENANCE
3.1. Introduction 12
3.2. Maintenance Responsibilities 12
3.3. Operator Duties – Log Records 12
3.4. Regular Testing and Inspection 12
3.4.1 Daily Check 12
3.4.2 Weekly Test 13
3.4.3 Monthly Test 13
3.4.4 Annual Test 14
4. FAULT FINDING TIPS 16
5. TECHNICAL SPECIFICATION & INSTALLATION DIAGRAM 19
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 2 of 21
1. GENERAL
1.1 Introduction
This manual provided only the basis operator’s information on the control and operation of the Fire Alarm System. To ensure continuous reliability of the system, the owner or owner’s representative should establish an agreement to carry out regular maintenance of the installation with the manufacturer or manufacturer’s representative or a competent and qualified contractor trained to service and maintain this system.
The arrangements for maintenance should be such as well ensure that a qualified person is available on call at all time to provide service in the event of any fault that develops at the installation. For the requirements of the Regular Testing and Inspection, please refer to the section covered in this manual.
1.2 System Description
This Fire Alarm System utilises the V5 Fire Alarm Panel. The system may comprise one or more alarm panel networked together witch performs the task of processing the input signals and thereafter transmit the output signals or initiates other auxiliary functions. The alarm panel (s) are usually sited in the building fire command centre or any prominent location clearly visible from the main entrance.
Input devices are used to cause a change in panel status. These devices may be the combination of Manual Call Points (as in manual and automatic alarm system), Heat/Smoke Detectors (as in automatic alarm systems).
Output devices are used to provide an audio & visual warning. Output devices commonly used are alarm bells although sirens and strobe lights are sometimes used. These three components: Input Devices, Control Panel and Output Devices form the backbone of a Fire Alarm System.
Non-addressable Fire Alarm Systems operates on a “Zone” basis. These zones are groups of input devices grouped in accordance to the locality they are protecting. In the event of a Fire/Fault condition, the location where the signal had originated will be defined by the respective indication on the panel. It is therefore important to be familiar with the zoning of the protected area. A zoning diagram (or zone chart) is usually provided for this purpose.
The Alarm Panel is provided with a feature that continuously monitoring the continuity of the input/detection, output/sounder circuits to ensure integrity of the system. It is also equipped with a battery back-up supply (lasting at least 24 hours) in the event of an incoming supply failure.
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 3 of 21
1.2.1 Zone Detection Module
1
2
3
Zone Detection Module - ZDM
4
5
6
7
8
Indicators and Control
a) Fire (Red) : Zone in fire condition b) Fault (Amber) : Zone detection circuit open/short fault condition c) Disable (Amber) : Zone in disabled condition d) Disable Switch (Blue) : To disable zone fire & fault detection circuit
(Note: Zone disable function only prior to an alarm activation.)
1.2.2 System Control Module
5
V
Model No.
Alarm CounterAlarm Counter
1 2 3 4 5 61 2 3 4 5 6
System Control Module - SCM
Indicators
a) Power On (Green) : System energised by Mains and/or Standby Battery b) Fire (Red) : General Fire Indicator, system in fire condition c) Fault (Amber) : General Fault Indicator, system in fault condition
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 4 of 21
d) Disabled (Amber) : General Disabled Indicator, system in disabled condition e) System Fault (Amber) : Indicate Programmable Micro Controller failure f) Fire Sent (Red) : Fire Signal to Alarm Remote Monitoring Station activated (Optional) g) Fire Line Trouble (Amber) : Fire Signal Line open/short (Optional)
(Note: It shall not be suppressed during the Fire Alarm condition) h) Fault line Trouble (Amber) : Fault Signal Line open/short (Optional) i) Sounder Fault (Amber) : Alarm sounder line open/short (Note : It shall not be suppressed during Fire Alarm condition) j) Earth Fault (Amber) : Field input/output wires shorted to ground k) Auxiliary Fault (Amber) : Auxiliary supply / auxiliary supervised line open/short l) Mains Failure (Amber) : 230V AC Mains supply failure m) Charger fault (Amber) : Charger Fuse blown / charger voltage (low / high) n) Battery Fault (Amber) : Battery supply disconnected / battery fuse blown /
battery voltage (low / high)
o) Alarm Counter (3x7Seg.) : Indicate that number of alarm (false) been activated
(for FALSE Alarm Management) p) AVF Off (Amber) : Indicate that AVF function been set off q) Retard State (Amber) : Indicate that system in Retard State r) Confirmation State (Amber) : Indicate that system in Confirmation State
Control Switches
a) Buzzer Silence (Black) (1) : To silence fault buzzer (Audio & Visual) b) Sounder Silence (Amber) (2) : To silence alarm sounder (Audio & Visual) c) System Reset (Brown) (3) : To normalise the system
(Note: Silence alarm sounder before RESET) d) Indicators Test (White) (4) : To test the working condition of all LED indicators and buzzer e) Auxiliary Disable (Blue) (5) : To disable auxiliary output control function
(Audio & Visual)
f) Sound Alarm (Red) (6) : To raise alarm sounder manually for
emergency evacuation (Audio & Visual)
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 5 of 21
1.2.3 LCD Event Logging Module
FIRE ALARM SYSTEM
07/04/06 M000 20:06
LCD Event Logging Module - LLMLCD Event Logging Module - LLM
Indicators
a) Power On (Green) : System energised by Mains and/or Standby Battery b) Processor Fault (Amber): Indicates that Micro Processor Unit failure in processing c) LCD Display : To display the Panel Status and the Alarm / Fire event c/w date and time (20 Characters x 4 Lines)
Control Switches
a) Escape (Yellow) : To exit from current function / screen b) Menu (1) (Green) : To access other level of function or password key as “1” c) Up (2) (White) : To move cursor up / page up or password key as “2” d) Down (3) (Blue) : To move cursor down / page down or password key as “3” e) Enter (Red) : To select / accept the function / setting
2. OPERATING INSTRUCTIONS
2.1 Normal Operating Conditions
Under normal operating conditions a) The “POWER ON” LED (Green) lighted b) No other indicator shall be lighted c) The panel and all alarms should be completely silent d) LCD display shown as
(07/04/06: 7th April 2006, M000: “Main” panel address “000”, 20:06: 8:06PM)
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
FIRE ALARM SYSTEM
07/04/06 M000 20:06
O&M-V5-FAP-AVF-LCD R0
Pg 6 of 21
2.2 Fire Alarm Condition
The panel / system shall enter into an alarm condition when an input device (such as smoke/heat detector, call point; or pressure/flow switch) is activated.
Under Fire Alarm conditions:
a) Twin “FIRE” LEDs (Red) of the alarm zone lighted b) General, “FIRE “ LED (Red) lighted c) A “Fire sent” LED (Red) lighted (If Alarm Monitoring Station is connected) d) Panel Alarm Buzzer sound e) External alarm bells/sounders activated f) Signal sent to alarm monitoring station (If Alarm Monitoring Station is connected) g) Auxiliary functions activated (eg: Lift homing, AHU shutdowns) h) LCD display shown as (Individual Fire event – latched and recorded)
(01: 1st event of 001EC, M00Z002: “Main” panel address “000” Zone “002” Fire, at 14:49: 2:49PM)
i) For multiple fire events, it shall be displayed by manual action (Up / Down key)
2.2.1 Silencing the Alarm Bells / Sounders
It is a requirement under the Singapore standard Code of Practice CP 10: 2005 that the first alarm can only be silenced after 3 minutes of continuous operation and any subsequent alarms may be silenced immediately. Any attempts to silence the first alarm during the initial 3 minutes of operation will have no effect on the system.
The Sounder Silence LED will flash when the 3 minutes is lapsed; to indicate alarm silencing is permit-able. To silence the alarm upon expiry of the initial 3 minutes and any subsequent alarm, carry out the following procedure:
a) Press “SOUNDER SILENCE” Switch (Amber) (2) b) Sounder Silence LED becomes steady c) External alarm bells/sounders silence d) To silence Alarm Buzzer, press “BUZZER SILENCE” Switch (Black) (1) e) Panel remains in fire state until reset
001EC FIRE
01 M00Z002 14:49
(001EC: Current Event Counter “001”, Fire)
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
2.2.2 Resetting the System
Pg 7 of 21
Before the system is reset, the cause of the alarm must be investigated and duly rectified. In the case of a false alarm, make sure that there is no incident of fire before resetting the system.
Note : It is not possible to reset the system before the alarm is silenced.
a) Re-instate the affected devices to normal b) Press “System Reset” Switch (Green) (3) c) Upon resetting, the system should resume to normal operating condition, if there are
no other events to cause another alarm and the original cause of the alarm being rectified.
2.3 Fault Conditions
A self diagnostic circuit are provided to check itself and indicates a wide range of possible faults.
Under Fault Conditions: a) The respective zone fault Amber LED lighted and/or b) The respective system fault Amber LED lighted c) General, amber “FAULT” LED lighted d) Panel fault buzzer sound e) LCD display shown as (Common Fault – non-latching)
FAULT
07/04/06 M000 10:06
(07/04/06: 7th April 2006, M000: “Main” panel address “000”, 10:06: 10:06AM)
2.3.1 Silencing the Fault Buzzer
If the fault cannot be rectified, it may be silenced by: a) Press “BUZZER SILENCE” Switch (Black) (1) b) Buzzer Silence Amber LED lighted c) Panel remains in fault state until fault rectified
2.3.2 Resetting the System
The cause of the fault should be investigated and rectified. If it is due to a mains supply failure, the system will normalise when the mains supply resumes. Some faults are internal to the system and are not covered in this manual. Once the fault(s) are rectified, the panel shall be normalised.
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 8 of 21
2.4 Initiating Evacuate Alarm
The system is provided with a “Sound Alarm” switch in the event of emergency.
To sound alarms for emergency evacuate: a) Press “Sound Alarm” switch (Red) (6) b) Sound Alarm amber LED lighted c) External alarm bells/sounders activated
2.4.1 Silencing Evacuate Alarm
To silence the evacuate alarm: a) Re-press the “Sound Alarm” Switch (Red) (6)
b) External alarm bells/sounders silenced
2.5 Zone/Auxiliary Disable
This function is executed when disable of the respective zone(s) and/or auxiliary functions is intended. Zone disable switches will render the respective zone(s) in­operative and will not be affected by the change in condition of the related input device(s). Note : It is not possible to perform a zone disable when an fire alarm condition has already occurred in the respective zones.
To carry out zone/auxiliary disablement: a) Press “Disable” for zone respectively or “Auxiliary Disable” Switch (Blue) (5) b) Disabled amber LED lighted c) General, “Disabled” amber LED lighted d) Zone(s)/auxiliary function remains in Disable Condition until normalised
2.6 Indicators Test
An “Indicators Test” switch is provided to test the working condition of the visible (LEDs) and audible (Buzzer) indicators. a) Press the momentary “Indicators Test” Switch (White) (4)
b) All the LED indicators lighted and Buzzer sounds c) Release the switch to normalise
2.7 Alarm Verification Feature (AVF)
Alarm Verification Feature (AVF) is provided to reduce the alarm caused by the transient environmental conditions. AVF feature is only subjected to the auto detection zones (e.g. Smoke, Heat). Alarm Counter (max 999) is incorporated to record the number of alarm activation been filtered by AVF.
Under Auto Detection Zone (been set to AVF mode) goes into alarm a) Twin “FIRE” LEDs (Red) of the alarm zone lighted and panel will reset itself
automatically
b) Alarm Counter increase One count c) “RETARD STATE” LED (Amber) lighted (20sec)
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
PRINTER
d) No outputs are activated (FIRE output, external Alarm Bells/ Aux output) e) When Retard State (20 sec) lapses, Retard State LED go off f) “CONFIRMATION STATE” LED (Amber) lighted (120sec)
During Confirmation State (120sec) a) If no alarm activated, panel back to normal condition itself when Confirmation State (120 sec) expire b) If any zone goes into alarm, panel goes into FIRE condition
Pg 9 of 21
2.8 LCD Event Logging Module (LLM)
LCD Event Logging Module (LLM) is provided as add on feature to display and record the activated alarm zone information complete with date and time.
LLM is integrated with non-volatile memory (EEPROM) to store and record the activated alarm zone event up to 999, it will not be lost even the system total power failure. The recorded zone alarm event are essential for the FALSE ALARM MANAGEMENT.
LLM is also incorporated with backup battery for real time clock, it will be continuous running during the system total power failure.
LLM is operated by Micro Controller Processor Unit, it is fully supervised and monitored for the software processing. In the events of Processor fault, and audio & visual signal will be given. The failure of the Porcessor will not impair the Primary Function of
the Fire Alarm System.
2.8.1 MENU Function It is provided easy and user friendly operation.
MENU
VIEW FIRE ARCHIVE
PRINT FIRE ARCHIVE
SETUP
PNL ADR
TIME
DATE
DELETE
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 10 of 21
2.8.1.a VIEW FIRE ARCHIVE To view the recorded alarm zone event;
a) Press “Menu”
b) Select “VIEW FIRE ARCHIVE” by “Up” / “Down” key and press “Enter”
017TC FIRE
017 M00-Z005 02/04/06 15:32:12
(017TC: Total Event Counter “017”, Fire)
(017: 17th event of 017TC, M00-Z005: “Main” panel address “000” Zone “005” Fire) at
(02/04/06: 2nd April 2006, 15:32:12: 3:32:12PM)
c) The rest recorded event are able to view by manual action (Down/Up key)
2.8.1.b PRINT FIRE ARCHIVE To print the recorded alarm zone event; a) Connect the Printer b) Press “Menu” c) Select “PRINT FIRE ARCHIVE” by “Up” / “Down” key and press “Enter”
PRINT FROM
017/TC017
Print start from (017/TC017: 17th event of Total Event Counter “017”)
d) Select the starting event by “Up” / “Down” key and e) Press “Enter”, Printer will start print the backward event until the last event “000” and stop f) During the printing: to stop the print, press “Escape”
2.8.1.c SETUP To setup the panel; a) Press “Menu” b) Select “SETUP” by “Up” / “Down” key and Press “Enter”
PNL ADR TIME DATE DELETE
PRINTER
c) Select the required setup function by “Up” / “Down” key and Press “Enter”
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 11 of 21
(1) PNL ADR: To set the Panel Address, select by “Up” / “Down” key and press “Enter” to save
(e.g. M000: Main Panel Address 000, S001: Sub Panel Address 001)
PANEL ADDRESS M000
PRESS ENTER TO SAVE
(2) TIME: To set the Time, select the time by “Up” / “Down” key and press “Enter” to save (Hour:Minute:Second – 24Hr System)
HH:MM:SS
19:46:22
(3) DATE: To set the Date, select the Date by “Up” / “Down” key and press “Enter” to save (Day:Month:Year)
DD/MM/YY
10/04/06
(4) DELETE: To delete the recorded event, key in the password and press
press “Enter” (Delete all recorded event)
(Password and Access Level control is provided to prevent unauthorized system control and alteration of alarm event recorded.)
?????
PASSWORD
(5) PRINTER: To Enable / Disable the printer for on-line printing,
select Enable / Disable by “Up” / “Down” key and
press “Enter” to save
[ENABLE] DISABLE
PRINTER
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 12 of 21
3. ROUTINE MAINTENANCE
3.1 Introduction
To ensure continuous reliability of the fire alarm system, regular testing and servicing shall be carried out. Only trained and competent personal are allowed to performance the routine testing and maintenance.
3.2 Maintenance Responsibilities
The owner shall appoint a competent person to supervise and coordinate all matters in relation to the fire alarm systems. This include arranging for the system to be checked, tested and serviced in accordance with the requirements as described in the Singapore Standard CP 10 : 2005 – Code of Practice for the installation and Servicing of Electrical Fire Alarm Systems.
3.3 Operator Duties – Log Records
The operators / owner appointed competent person shall also be responsible for keeping all the log records for all alarms activation (genuine, practice, test or false), faults, service tests and routine preventive maintenance, repair and alteration works carried out on the fire alarm system.
3.4 Regular Testing and Inspection
The following regular testing and inspection procedures are recommended:
3.4.1 Daily Check
3.4.2 Weekly Test
3.4.3 Monthly Test
3.4.4 Annual Test
3.4.1 Daily Check
A check should be made everyday to ascertain if the system is operating normally. Fault(s) detected should be recorded and steps taken immediately to ensure that the fault(s) is rectified.
a) Check that only the green “POWER ON” LED is lighted. All other indicators should
be off and the panel completely silent. If a fault has occurred and the panel buzzer sounding, the appropriate indicator will light up.
b) Record the fault (s) detected.
c) Determine the area affected by the fault and decide whether special actions (such as
fire patrols) are required in that area.
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 13 of 21
d) If possible, determine the cause of the fault or note the activities immediately prior to
the area affected.
e) Silence the fault buzzer.
f) Inform the maintenance contractor responsible for servicing and arrange for repair.
3.4.2 Weekly Test
The following tests and checks should be made by the operator or by the maintenance’s contractor responsible for servicing and performance of the system.
a) Carry out a simulated and transmission of fire alarm and faults signals to the
monitoring station and confirm it is functioning correctly.
Note : It will be necessary to contact the alarm monitoring company prior to transmitting of the simulated fire alarm and faults signals being tested and also to check with the monitoring company after completion of test to ensure that the fire alarm and faults signal was received and advise them the system reset.
b) Check the battery condition and the voltage reading by the use of a multi-meter.
c) On completion of the above tests, ensure that all switches are in the correct
operating position.
d) Rectify all faults (if any) immediately.
e) Enter the test result(s) and follow-up actions in the log record.
3.4.3 Monthly Test
In addition to the weekly test, the following checking and testing procedures are to be carried out each month.
a) Simulate fire and fault condition in all zones one by one. The procedure of the
simulation should follow section 2 (operating instruction) of this manual. Confirm with the monitoring station that the fire alarm and fault signals have been received.
b) Remove the bell line fuse. The buzzer should sound together with “SOUNDER
FAULT” and both amber “O” indications lighted. The panel should be silenced when “BUZZER SILENCE” is activated. Replace the bell line fuse. System should normalise.
c) Disable a zone in accordance to the procedures as described in section 2.5. Active a
device in that respective zone. It should have no alarm signal activated on the panel. Normalise the disable zone.
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 14 of 21
d) Check charger voltage and battery terminals condition. Ensure that no faults signal
are indicated on the panel.
e) Disconnect the battery supply. The “POWER ON” and “BATTERY FAULT”
indicators should be lighted and the buzzer sounding. Connect back the battery and system should normalise itself.
f) Switch off incoming mains supply. The “POWER ON”, “MAINS FAULT” and
“CHARGER FAULT” indicators should be lighted and the buzzer sounding. The standby battery should take over the supply to the system. Resume the mains supply and system should normalise itself.
g) Check earth leakage function by applying a short between the positive leg of the
detector line and earth (chassis). The buzzer should sound together with “EARTH FAULT” and red “+” indication lighted. Repeat, using the negative leg of the detector line. The buzzer should sound together with “EARTH FAULT” and amber “-“ indication lighted.
h) Check that the panel is in a clean and operative condition.
i) Visually inspect the condition of the components, terminations and cables.
j) Ensure that all faulty parts are satisfactorily replaced and recorded. Enter in the log
record any fault(s) that require repair.
k) Check that all switches are return to their operating positions after test.
l) Enter the test results and follow-up actions, if any, in the log record.
3.4.4 Annual Test
The annual checks should include all the inspections and testing procedures specified in sections 3.4.1, 3.4.2, 3.4.3. and the following:
a) The maintenance/servicing personnel should arrange to check the operation of at
least 20 percent of the detectors in an installation each year. The selection of detectors to be tested should be spread over as many zones as possible and should be made in such a way that all detectors in an installation should have been checked at least once in 5 years.
The checking of the detectors should take the form of in situ testing to ensure it is operational.
b) Circuits connecting ancillary equipment which require automatic voltage regulated
supplies should be checked to ensure correct operation and voltage output.
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 15 of 21
c) Where the heat-sensitive element of thermal detectors or the enclosure of other
detectors are found to be coated with paint or any material likely to affect the operation of the detectors, such material should be cleaned off or if necessary have the detector replaced. Note: In certain environments it may be necessary to clean and test the smoke detectors at more frequent intervals.
d) Enter the test results and follow-up actions, if any, in the log record.
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
4. FAULT FINDING TIPS
CHECK LIST
FAULT
Zone Fire
(False Alarm)
Indication
Specific
- Manual Call-point - Vandalise
- Heat / Smoke
Detector
- Flow Switch - Leakage
- Sub Alarm Panel - Activated
- EOL Resistor - Shall be 6.8K Ohm
Possible Causes
- Glass Broken
- Environment
- Faulty
- Misused
Pg 16 of 21
ACTION SHOULD
BE TAKEN
- Inspect the alarm
activated zone
IF FALSE ALARM
1. Check the possible
causes and rectified the
problem
2. Press “Sounder
Silence” (Yellow-2)
(After 3 min alarm)
3. Press “Reset”
(Green-3)
If unable to Reset
1. Press “Buzzer
Silence” (Black-1)
2. Press “Sounder
Silence” (Yellow-2)
(After 3 min alarm)
3. Call for service
Zone Fault
All Zone Fault - Detector Fuse - Blown
Sounder Fault
“LS” (Red) - Line Short
(@ back of ZDM)
If not,
May be Line Open
Alm-1 / Alm-2
“O” (Amber) - Open
(@ FBM)
Alm-1 / Alm-2
“S” (Red) - Short
(@ FBM)
- Zone line - Line short circuit
- Zone line - Line open circuit
- Zone Detector - Missing / Removed
- Zone Termination - Loose
- Sub Alarm Panel - Fault at Sub Panel
- EOL Resistor - Shall be 6.8K Ohm
- Alarm Fuse - Blown
- Termination - Loose
- EOL Resistor - Shall be 6.8K Ohm
- Alarm line - Open circuit
- Alarm line - Connection reversed
- Short circuit
- Bell / Sounder - Polarized Bells /
Sounders shall be used
- Connection reversed
- Faulty
1. Press “Buzzer
Silence” (Black-1)
2. Check the possible
causes and rectified
3. When fault is
rectified, back to normal
If unable to normalise
1. Call for service
Tip: To segregate, the
fault caused by either
Line or Panel problem:
1. Dismantle the line
2. Terminate with EOL
Resistor
Fault clear,
- LINE problem
Fault remains,
- PANEL problem
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 17 of 21
FAULT
Earth Fault
Auxiliary Fault
Mains Failure
Charger Fault
Charger Fault
Battery Fault
Specific
Indication
Earth “+VE” (Red)
(@ FBM)
Earth “-VE” (Amber)
(@ FBM)
(@ FBM)
Alm-2 “O” / “S”
(@ FBM)
- “Mains Failure”
(Amber)
- “Charger Low /
Fuse” (Amber)
(@ PSM)
“Charger Low /
Fuse” (Amber)
(@ PSM)
“CH/BAT High” (Red)
(@ PSM)
“Battery Low / Dis.”
(Amber)
(@ PSM)
CHECK LIST
Possible Causes
- One or more Field
“+VE” line and/or
- Alarm “–VE” line
(in normal condition)
- One or more Field
“-VE” line and/or
- Alarm “+VE” line
(in normal condition)
- Aux Fuse - Blown “Aux Fuse” (Amber)
- Auxiliary Output - Over loaded
- Alarm-2 output is used for Auxiliary
(Option as provided)
- Refer to “Sounder Fault” for fault finding
- AC 230V Mains - Failure
- AC Fuse - Blown
- AC Switch - OFF position
- Termination - Loose
- Charger Fuse - Blown
- System total load - Over loaded
- System Voltage - Low < 21V
- System Voltage - High > 30V
- Battery Fuse - Blown
- Termination - Loose
- Battery - Low > 21V
- Shorted to Chassis /
Trucking / Conduit
- Line shorted
- Cable shorted
- Connection Reversed
- Faulty
ACTION SHOULD
BE TAKEN
1. Press “Buzzer
Silence” (Black-1)
2. Dismantle all the
Line accordingly with
proper marking
3. Terminate back the
lines one by one to
trace the faulty lines
4. Rectify the fault.
5. When fault is clear,
back to normal
If unable to normalise
1. Call for service
1. Press “Buzzer
Silence” (Black-1)
2. Check the possible
causes and rectified
3. When fault is
rectified, back to normal
If unable to normalise
1. Call for servicing
Remark:
1. Fuse shall be
replaced with Rated
Fuse as accordingly.
2. System normal
operating voltage shall
be DC 27.5V.
(Adjustable by VR1 @
PSM)
“CH/BAT High” (Red)
(@ PSM)
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
- System Voltage - High > 30V
O&M-V5-FAP-AVF-LCD R0
Pg 18 of 21
FAULT
Fire Line Trouble
(Alarm Monitoring
Station)
Fault Line Trouble
(Alarm Monitoring
Station)
Legend:
ZDM
FBM
SCM
PSM
DIM
Specific
Indication
(@ DIM)
“1” (Red) - Short
(@ DIM)
(@ DIM)
“2” (Red) – Short
(@ DIM)
: Zone Detection Module
: Fire Base Module
: System Control Module
: Power Supply Module
: DECAM Interfacing Module
CHECK LIST
Possible Causes
- Fire signal Line - Disconnected “1” (Amber) - Open
- Termination - Loose
- Fire signal Line - Shorted
- Alarm Monitoring
Transmitter Panel
- Fault signal Line - Disconnected “2” (Amber) - Open
- Termination - Loose
- Fault signal Line - Shorted
- Alarm Monitoring
Transmitter Panel
- Faulty
- Faulty
LS
: Line Short
O
: Open circuit
S
: Short circuit
EOL
: End Of Line Resistor
ACTION SHOULD
BE TAKEN
1. Press “Buzzer
Silence” (Black-1)
2. Check the possible
causes and rectified
3. When fault is
rectified, back to normal
If unable to normalise
1. Call for service
Remark:
Fire and Fault signals
are connected to Alarm
Monitoring Transmitter
Panel only at Main
Alarm Panel when
required.
(This function is
provided as an option
when required)
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
Pg 19 of 21
V5
Technical Specification
and
Installation Diagram
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
O&M-V5-FAP-AVF-LCD R0
TECHNICAL SPECIFICATION
Fire Alarm Panel
S/N I/P – O/P Description Capacity / Rating
End Of
Line
Resistor
(EOLR)
Pg 20 of 21
Feature
1 ZONE - Min 4 Zones
(Multiple of 4 Zones)
- Max 136 Zones
- 40 Heat or 20 Smoke Detectors per Zone
- Max 2.4 mA per Zone
- Wire: 1.5mm2
2 ALM - 1 Output - DC 24V
- Fuse: Max 2Amp
- Wire: 2.5mm2
3 ALM – 2 Output - DC 24V
- Fuse: Max 2Amp
- Wire: 2.5mm2
4 AUX – 1 Output - C, NC, NO Contact
(Max DC 24V, 5Amp)
- Wire: 2.5mm2
5 AUX – 2 Output - C, NC, NO Contact
(Max DC 24V, 5Amp)
- Wire: 2.5mm2
6 To MAP Output - Wire: 1.5mm2 - - For SAP : Common Fire & Fault
7 FIRE Output - C, NC, NO Contact
(Max DC 24V, 1Amp)
- Wire: 1.5mm2
8 FAULT Output - C, NC, NO Contact
(Max DC 24V, 1Amp)
- Wire: 1.5mm2
9 AUX 24V DC Output - DC 24V
- Fuse: Max 2Amp
- Wire: 2.5mm2
10 G-ALM OP-IP Terminal - Wire: 1.5mm2 -
11 G-SIL OP-IP Terminal - Wire: 1.5mm2 -
12 G-RST OP-IP Terminal - Wire: 1.5mm2 -
13 G-AUX OP-IP Terminal - Wire: 1.5mm2 -
6.8K Ohm - Line Open / Short supervised
6.8K Ohm - Line Open / Short supervised c/w Fuse Protection
- Expendable by additional module
6.8K Ohm - Line Open / Short supervised c/w Fuse Protection
- Option for “Supervised Auxiliary” function provided
- Expendable by additional module
- - Option for “Voltage Contact” selection provided
- - Option for “Voltage Contact” selection provided
signal to Main Alarm Panel (MAP) Zone
- - Common Fire Volt-Free Contact Output
- - Common Fault Volt-Free Contact Output
- - Constant 24V DC Output c/w Fuse Protection
- General Alarm, Silence, Reset and Auxiliary control function (MAP to SAPs common connection)
Alarm Remote Monitoring Station (Optional)
14 FIRE Output - Max DC 24V, 120mA
15 FAULT Output - Max DC 24V, 120mA
Remark:
Terminal Wire Range : 24-12AWG 2.5 mm
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
- Wire: 1.5mm2
- Wire: 1.5mm2
2
Signal to Alarm
Monitoring
Transmitter
Panel
- Line Open / Short supervised
- Line Open / Short supervised
- Normally energized output (for Panel Total Failure signal)
O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/w AVF & LCD)
Pg 21 of 21
1
Z1
+ -2-+
Z2
3 4
-+
Z3
5 6
-+
Z4
7 8
-+
Z5
9 10
-+
Z6
11 12
-+
Z7
13 14
-+
Z8
15 16
-+
ALM-1
17 18
-+
ALM-2
19 20
C+ NC-
AUX-1
21 22 23
NO- C+
AUX-1
24
NO-NC-
25 26
3
C
FIRE
+ -
TO MAP
1 2
NC NOCNONC
FAULT
864 5 7 109
++
1211
--
1413
G-ALM
IPOP
1615
G-SIL
IPOP
1817
G-RST
IPOP
2019
G-AUX
IPOP
AUX - DC 24V
VC
FC
AUX-1
1
2
3
FC
VC
1
3 2
AUX-2
ALM-1 ALM-2 AUX
FUSES
MAP SAP
G-RST
JS1
ZONE FUSE
BELL
AUX
ALM-2
+ - CO
JS2
EARTH
+VE -VE OS
ALM-1OSALM-2
+ - CO
CO - +
AC AC
OFF
ON
SW1
24V DC
+ -
BATTERY
BATTERY FUSE
CHARGER FUSE
VR1
Vanguard
V5-PSM-1
Vanguard
V5-FBM-1
N E L
AC 230V
MAIINS
Fuse
EOLR
6K8 OHM
DETECTORS / CALLPOINTS
POLARISED SOUNDERS / BELLS
6K8 OHM
As (Z1) Connection
As ALM-1 Connection
Auxiliary Output-1
Auxiliary Output-2
}
As per Jumper Setting (1,2) FC = Free Contact Output
Signal to Main Alarm Panel (MAP) Zone
Common FIRE Output (Free Contact)
Common FAULT Output (Free Contact)
DC 24V Constant Supply Output
For General Alarm Signal
For General Sounder Silence Signal
For General Reset Signal
For General Auxiliary Signal
Transformer
24V DC Standby Battery
AC 230V Mains Supply
LEGEND:
EOLR
EOLR = End Of Line Resistor
(Shall be placed at last device)
Jumper Setting for ALM-2 output to operate as BELL or AUXILIARY function
LEGEND:
S = Line Short O = Line Open
Filename:
(2,3) VC = Voltage Contact Output
FC
VC
1
3 2
FC
VC
1
3 2
BELL
BELL
AUX
ALM-2
AUXILIARY
BELL
AUX
ALM-2
V5-FBM-1-TIL
Title:
Typical terminal installation layout of Fire Base Module (V5-FBM-1)
TB3
TB2
Loading...