A. ITE Circuit Breaker Model 14.4K Timing Chart
B. CT-7500 Test Plan for ITE Circuit Breaker Model 14.4K.
C. CT-7500 Timing Chart for ITE Circuit Breaker Model 14.4K.
D. CT-7500 Tabulated Test Report for ITE Circuit Breaker Model 14.4K.
E. Timing Chart for Siemens TCP-149 Circuit Breaker
F. CT-7500 Test Plan for Siemens TCP-149 Circuit Breaker
Figure 5-1. CT-7500 Control Panel
Figure 8-1. Typical Circuit-Breaker Test Cable Hookup
Figure 8-2. Typical Series Contacts Test Cable hookup
Figure 8-3. Typical Dc Trip and Close Control Test Cable Hookup
Figure 8-4. Typical DC Trip and AC Close Control Test Cable Hookup
Figure 8-5. Typical Voltage-Monitoring Test Cable Hookup
Figure 8-6. Typical External Trigger Hookup
Figure 8-7. Transducer Cable Hookup
Figure 8-8. AC Current Sensor Hookup
Figure 9-0. CT-7500 Operating Steps
Figure 9-1. Steering Map of Menus and User Options
Figure 9-2. Typical Tabulated Printout of Open Operation on Thermal Printer
Figure 9-3. Typical Tabular Printout of Open Operation on Ink-Jet Printer
Figure 9-4. Typical Graphic result on Thermal Printer
Figure 9-5. Typical Graphic report on Ink-Jet Printer
Figure 9-6. Typical Graphic-Expansion result Printout on Thermal Printer
Figure 9-7. Open and Close Timing Graph Interpretation
Figure 9-8. Open-Close and Close-Open Graph Interpretation
Figure 9-9. Typical Timing Shot Directory Printout on Thermal Printer
Figure 9-10 Typical Test-Plan Printout on Thermal Printer
Figure 9-11 Typical Test Plan Directory Printout
Figure 9-12 Typical Slow-Close Test Report
Table 5-1 Model CT-7500 Controls and Display
Table 7-1 Voltage Selection Jumper Setting
Table 9-1. Open Operation with No Resistor
Table 9-2. Open Operation with Insertion Resistor
Table 9-3. Close-Open Operation with No Resistor
Table 9-4. Get Tabulated Results
Table 9-5. Plot Chart and Tabulated Report
Table 9-6. Save Timing Shot in EEPROM
Table 9-7. Print Timing Shot Directory
Table 9-8. Recall a Timing Shot
Table 9-9. Delete a Timing Shot
Table 9-10.Recall a Test Plan
Table 9-11.Print a Breaker Test Plan
Table 9-12.Print a Breaker Test Plan Directory
Table 9-13.Entering Shot Identification Header
Table 9-14.Select Channel Configuration
Table 9-15.Selecting or Aborting Computer Control
Table 9-16.Setting Up "OPEN" Analysis Points Using Distance
Table 9-17.Select Metric Units of Measure
Table 9-18.Setting the Clock and Calendar
Table 9-19.Programming a Slow-Close Test
Table 9-20.Performing a Transducer Self Test
Table 9-21.Checking the Cable Hookup
Table 9-22.Automatic Print Setting
The Model CT-7500 is a microprocessor-based digital time-versus-travel Circuit Breaker
Analyzer with a special on line test mode. This on line test mode (Quick-Shot mode) allows the
user to capture breaker contact close time and contact open (clear) time while the breaker is still in
service. In the off line test, the Model CT-7500 fully analyzes utility circuit-breaker performance:
contact time, stroke, velocity, over-travel, bounce-back, and contact wipe.
Contact-motion analysis includes: Open, Close, Open-Close, Close-Open, and Open-CloseOpen. A timing window is selectable between 1-second or 10-second periods. The 10-second
window allows timing of long events (e.g., circuit switcher contacts).
The CT-7500 is available in three models:
CT-7500-3; three contact channels.
CT-7500-6; six contact channels.
CT-7500-12; twelve contact channels.
All the CT-7500 models have the following input:
Three Digital Travel Transducer Input channels.
One Analog Voltage Monitor Input channel.
One Digital Voltage Monitor Input channel.
One Trip/Close current monitor channel.
There are two modes of operation for the CT-7500: Stand Alone Mode and Computer Control
Mode. This manual will focus on the CT-7500 Stand Alone Mode. The Computer Control Mode is
covered under the CT-7500 PC software manual.
2.0 CT-7500 Description
2.1 On-line Timing (Quick-Shot) mode
A clamp-on AC current probe connected to the breaker bushing CT lets the CT-7500
measure breaker switching time (while the breaker’s still in service). The CT-7500 can time an
OPEN operation by sensing the time when the OPEN coil is energized until the bushing CT
current returns to zero. CLOSE time is detected when the close coil is energized until the bushing
CT current is detected.
This “Quick-Shot” mode provides a quick way to diagnose breaker performance and savings in
maintenance cost.
The CT-7500 applies a 35Vdc voltage to each of the contact channels. This test voltage is
sensed by an analog to digital converter (A/D) to determine the state of the contact (close, or
open, or insertion resistor). The CT-7500 records the A/D reading at a 10 KHz rate, and stores
these readings in memory. The contact/resistor time is then derived from data stored in memory.
The CT-7500 uses three up-down counters to sense the breaker’s transducer reading. The
CT-7500 travel transducer employs an optical encoder to send quadrature signals to the CT7500’s counters. With the use of the digital transducer and counters, the user never has to set up
1
Rev 2 Jan 2001
MODEL CT-7500OPERATING INSTRUCTIONS
or calibrate the transducer.
The CT-7500 has a built-in initiate circuit to operate circuit breakers. Since this solid-state
circuit is controlled by the micro-processor, the CT-7500 can perform multiple operations (O-C, CO, O-C-O) with ease. Each Trip and Close initiate circuit is fuse protected. The user is also
required to hold the “ARM” switch during a test to complete the initiate circuit.
The CT-7500 can also store up to 200 breaker-timing test records and 45 breaker test-plans in
FLASH EEPROM. Stored timing test records can be recalled and printed or transferred to the PC.
Using the breaker test plan during a test, the users do not have to set the velocity calculating
points. The CT-7500 will also print “PASS” and “FAIL” results on test report.
2.2.1 Contact Timing Channels
A breaker's interruption of contacts is timed with the dry-contact input channels. Each channel
can detect the main contacts and insertion resistor contacts times (in millisecond and cycles).
Note
The CT-7500 can detect insertion resistors in a 10-7000 ohm range. Resistances over 7000
ohms are detected as an open contact.
2.2.2 Analog Voltage Monitoring Channel
An analog voltage input is dedicated to monitoring a breaker's dc power supply or coil voltages
(0-255 V dc or peak ac).
Note
Input voltage range is 0-300Vdc or peak AC. Reading range is 0-255Vdc.
2.2.3 Digital Voltage Monitoring Channel
One digital voltage input channel monitors voltage on/off status. Voltage threshold from 30-255
Vdc is considered as “ON” status. Voltage threshold less than 30 Vdc is considered as “OFF”
status.
2.2.4 Trip/Close Current Monitoring
A built-in Hall-effect sensor records Trip and Close coil current levels and duration. The
breaker's operate coil current waveform is graphically plotted on a printout. Current reading is also
printed in the tabulated report.
2.2.5 Travel Transducer Input Channels
Each CT-7500 has 3 digital transducer input channels. These transducer channels require
neither setup nor calibration.
2.2.6 Breaker Initiate Capability
A built-in solid-state initiate device lets users operate a breaker from the CT-7500. Operational
modes include: Open, Close, Open-Close, Close-Open, Open-Close-Open. Multiple operations
2
Rev 2 Jan 2001
MODEL CT-7500OPERATING INSTRUCTIONS
(e.g., Open-Close, Close-Open, Open-Close-Open) can be initiated with a programmable delay
time or by sensing the breaker's contact state.
Because solid-state switching is used in the initiate circuitry, the CT-7500 can switch a
breaker's ac or dc control circuit. Each trip and close circuit is protected by a 3-ampere fuse. The
initiate circuit is also protected by an interlock "ARM" switch.
2.2.7 Built-in Thermal Printer
A 4.5-inch wide thermal printer prints the breaker's contact analysis results in both tabular and
graphic formats.
2.2.8 Printer Port
A parallel printer port can drive a H-P color ink-jet printer, from which a color graphic of timing
charts and tabulated results can be printed on 8½-11-inch paper.
An Ink-Jet printer is supplied with each CT-7500.
2.2.9 Computer Interface Capabilities
A built-in RS-232C port lets timing shots stored in CT-7500 EEPROMs to be down-loaded to an
IBM-compatible PC. Windows-based (Windows 95, Windows 98, Windows Me, Windows 2000,
and Windows NT) Breaker Analysis Software is supplied with the CT-7500. This software allows
the user to:
Time Circuit breakers from a PC.
Retrieve timing shots stored in CT-7500.
Recall timing shots from a hard drive for re-analysis (at an office PC).
Create breaker test plans on a PC and load into the CT-7500.
2.2.10 Timing Shots Storage Capabilities
The CT-7500 uses Electrical Erasable PROMs (EEPROM) to store timing-shot data. Unlike
other media, EEPROMs are immune to temperature, shock, and humidity. Stored shots can be
recalled to reanalyze test data, to re-print test reports, or transfer data to an IBM compatible PC
for record keeping. Up to 200 timing shots can be stored in the EEPROMs. The number of shots
stored in EEPROMs can vary, depending on the size of the shot records.
2.2.11 Breaker Test Plan Storage Abilities
Up to 45 breaker’s test plans can be stored in the CT-7500. Test plans comprise breaker
specifications (i.e., stroke, velocity, contact time). By recalling and using a test plan, operators
can immediately test breakers and view a pass/fail report (made by comparing test performance
with specifications in the test plan). Breaker specifications need not be referenced to compare
test results to determine if a breaker passed.
A breaker test plan can be created by using the Breaker Analysis Software (supplied with each
CT-7500). The test plan is then loaded into the CT-7500 via an RS-232C serial port.
2.2.12 Diagnostic Capabilities
The CT-7500 can run diagnostics on its own electronics. Self-testing of contact cable hook-ups
and transducers lets users checkout CT-7500 accessories whenever verification is required.
3
Rev 2 Jan 2001
MODEL CT-7500OPERATING INSTRUCTIONS
2.2.13 CT-7500 Display and Control Switches
An alpha-numeric keypad lets the user enter breaker’s name plate data (Substation name,
Breaker Model, etc) and control function. A 4-line by 20-character LCD readout displays user
messages. The LCD is back lighted so messages can be viewed in low light levels.
3.0 Test Result Tabulation
3.1 Electrical Measurement Results
Each CT-7500 contact channel provides the following test results:
Contact Close time, (Quick-Shot) Mode.
Contact Open (Clear) time, (Quick-Shot) Mode.
The CT-7500 can detect insertion resistors in a 10-7000 ohm range. Resistances over 7000
ohms are detected as an open contact.
Main contact and insertion resistor contact times (Time-Travel Test).
Contact bounce time (Time-Travel Test).
Contact spread time (Time-Travel Test).
NOTE
3.2 Mechanical Measurement Results
Each digital transducer channel provides the following test results:
Breaker stroke (Time-Travel Test).
Over travel (Time-Travel Test).
Bounce back (Time-Travel Test).
Contact wipe (Time-Travel Test).
Velocity (Time-Travel Test).
Breaker contact speed calculation is based on a contact's travel distance over a period of time,
which is defined by the manufacturer's specifications.
A CT-7500 not only calculates simple distance-over-time speeds, but can also support other
formulas. An example is Siemen TCP breaker calculation formula:
V=12.2 x a/b
The formula and analysis points can be stored in a test plan for use later in the field.
NOTE
If operators use a breaker test plan (see paragraph 9.8) during testing, the test report will also
indicate a Pass/Fail condition for each test parameter (i.e. contact time, stroke, velocity, etc.).
3.3 Analog Voltage Input Results
The analog voltage input channel (V1) measures the breaker's dc control voltage during
operation. Printed voltage readings include nominal voltage (supply voltage at no load) and
minimum voltage (supply voltage under load or when a coil is energized).
This connection allows the user to monitor the DC power supply voltage fluctuation during
breaker’s operation. This feature is handy to detect breaker’s power supply problem; which
4
Rev 2 Jan 2001
MODEL CT-7500OPERATING INSTRUCTIONS
normally can not be seen using a volt meter.
NOTE
Voltage reading range is 1.0-255 V dc.
3.4 Digital Voltage Input Results
The Digital Voltage Input channel (V2) monitors voltage on/off conditions and graphs the result.
A voltage level above 30Vdc is considered as “ON” condition. This input channel is dedicated to
monitor breaker’s auxiliary switch action during breaker’s operation.
NOTE
Input voltage range is 1.0-300 V ac/dc.
3.5 Initiate Current Results
The CT-7500 not only plots Trip or Close current waveforms, but also prints steady-state
current readings of trip and close coils during operation.
NOTE
1. If the CT-7500 initiates the OPEN test or CLOSE test under the Quick-Shot test, the test report
will show OPEN or CLOSE coil current reading and current wave form.
2. If the user operates the breaker for the Quick-Shot test (external trigger), no coil current reading
or waveform will be recorded.
3.6 Slow-Close Test
A slow-close test finds the contact touch distance and penetration by using the travel
transducer and dry contact channels.
4.0 Test-Results Graphics
4.1 Thermal Printer Graphic Printout
A 4.5” wide built-in thermal printer prints graphic waveforms of contact channels, travel curves,
and actuator-coil currents. With a zoom graphics mode, the user can select an enlargement by
specifying the timing zone.
4.2 Ink-Jet Printer Output
A color graphic report can be printed on the HP Ink-jet printer (supplied with each CT-7500).
The CT-7500 will print color graphics of contact channels, travel channels, current waveforms on
8½- by 11-inch paper.
5.0 Controls and Display
(See Figure 5-1 and Table 5-1.)
Before using the CT-7500 Analyzer, users should become familiar with all of its controls and
display indications. The keypad and display are used to operate the CT-7500 Analyzer. Figure 51 shows the control panel and numbered lines pointing to each control and indicator. The line
numbers refer to Table 5-1, which describes the function of each control and indication.
5
Rev 2 Jan 2001
MODEL CT-7500OPERATING INSTRUCTIONS
Figure 5-1. CT-7500 Control Panel
6
Rev 2 Jan 2001
MODEL CT-7500OPERATING INSTRUCTIONS
Table 5-1. Model CT-7500 Controls and Displays
Fig. 5-1
Index no.PANEL MARKING
FUNCTIONAL DESCRIPTION
1
2
3
4
5
6
7
8
9
CONTACT INPUT (1-12)Connector, 3-pin: each input is a continuity (dry)
sensor for detecting a contact closing or opening (a
timing input to the processor).
(30V-300V) VOLTAGE
V1 & V2/ VOLTAGE INPUT
TRIGGER/VOLTAGE INPUTConnector, 3-pin: input (30-300 Vac, dc, or peak)
CTAC current sensor input channel.
AC 100-240V; 5A MAXPower plug (3-wire), ac fuse, ON/OFF switch: Switch
GROUNDStud, 5/16-18 threads, with wing nut; safety ground
TRANSDUCER INPUT
(T1, T2, T3)
(Printer; No panel marking)Thermal printer; prints on specially treated 4½-inch
PRINTERPrinter port connector, 25-pin.
Connector, 3-pin: each input is a voltage detector for
timing voltage (30-300 V dc/peak) of trip or close coil
switching (active period).
triggers timing functions.
is 2-pole rocker, input power on & off.
terminal.
Connector, 16-pin: each input (T1-T3) is a Travel
Encoder output (contact motion data).
wide paper; processor controlled.
10
11
12
13
14
15
1-9, 0, ENTER, START, STOP,
CLEAR, ↑ PAPER LCD,
PAPER LCD
↓
REMOTE ARM SWITCHRemote Arm Switch connector. The remote Arm
"PUSH" TO ARMPushbutton switch, spring-loaded: press & hold to
(Display; no panel marking)Liquid-Crystal Display (LCD), back lighted: 4-line by
CLOSE/ 3 AClose circuit fuse (3 amperes).
OPEN/ 3 AOpen circuit fuse (3 amperes).
Keypad, 16-key; keys are momentary-contact
pushbutton switches: makes menu selections, enters
alpha-numeric data, adjusts LCD contrast, and
moves paper.
switch with a 15ft cable is provided with each CT-
7500.
complete trip & close circuits for breaker tests.
20 characters per line: displays menus, options,
prompts, and test-result data.
7
Rev 2 Jan 2001
MODEL CT-7500OPERATING INSTRUCTIONS
Table 5-1. Model CT-7500 Controls and Displays (cont’)
Fig. 5-1
Index no.PANEL MARKING
FUNCTIONAL DESCRIPTION
16
17
INITIATEConnector, 4-pin; switching circuit for operating the
Measures"Slow-Close" contact point distance (Hard Copy)
Analysis software runs on IBM-compatible. Software package for graphic
numerical reports, and database utility for shop or office
RS-232C Port
Back-lighted LCD screen: 4 lines by 20 characters, sunlight viewable
Contact travel waveforms & tabulated results print on 4.5-inch thermal paper
Built-in parallel printer port. CT-7500 produces both graphic and tabulated test
results in color on 8.5 by 11 (inches) paper via external ink-jet printer
o)
CARRYING CASE (optional)
Hard shipping case for both CT-7500 and Travel Transducer
9
Rev 2 Jan 2001
MODEL CT-7500OPERATING INSTRUCTIONS
WARRANTY
One year warranty on parts and labor; post-warranty service contracts available
10
Rev 2 Jan 2001
MODEL CT-7500OPERATING INSTRUCTIONS
7.0 CT-7500 Special Features
7.1 CT-7500 Operating Voltages
The CT-7500 operating voltage is selectable between 110/120 V, 50/60 Hz or 220/240 V,
50/60 Hz. Voltage selection is set by one jumper/connector on the Initiate PCB (JP3) and one
jumper/connector on the Power Supply PCB (JP1). Jumper setting for both connectors is shown
in table 7-1.
Table 7-1. Voltage Selection Jumper Setting
VOLTAGE SELECTIONCONNECTOR PIN
110/120 VacPin 1& 2, 3 & 4
220/240 VacPin 2 & 3
Note:
Operating voltage is set from the factory.
7.2 CT-7500 Main Power Fuse
The CT-7500 uses an AC input module containing the AC receptacle, Power switch, and
Protective fuse. Replacement fuse should be: 20mm, 2A-250Vac slow blow.
7.3 CT-7500 Printer and Printer Paper
The CT-7500 built-in thermal printer uses 4.5-inch wide thermal paper for printing test
results. To maintain the highest quality test-result printing and to avoid paper jamming, the use
of paper supplied by our factory is highly recommended. Additional paper can be ordered from
either of the two sources listed below:
Vanguard Instruments Co, Inc.
1710 Grevillea Court
Ontario, CA 91761
Tel: 909-923-9390
Fax: 909-923-9391
Part Number: TP-4 Paper
OR
BG Instrument Co.
13607 E. Trent Avenue
Spokane, WA 99216
Tel: 509-893-9881
Fax: 509-893-9803
Part Number: TP4 paper
7.4 CT-7500 Printer Paper Control
To advance paper from the printer, press and release the “↑ PAPER LCD” switch; to
retract the paper from the printer, press and release “↓ PAPER LCD” switch.
11
Rev 2 Jan 2001
MODEL CT-7500OPERATING INSTRUCTIONS
7.5 Replacing CT-7500 Thermal Paper
The thermal paper roll is residing in the pocket under the printer cover. To replace the
thermal paper roll, follow these steps:
Remove printer cover.
Remove leftover thermal paper roll from paper holder.
Unroll new thermal paper roll.
Feed thermal paper into the slot between the paper pocket and roller.
The printer will pull paper under the thermal head.
Roll thermal paper roll and place this paper roll in paper holder.
Lift thermal head and align thermal paper if necessary.
Reinstall printer cover.
Note
Thermal paper will show a red stripe to indicate “Close to End of Paper”.
7.6 CT-7500 LCD Contrast Control
To Darken the LCD display, press and hold the “↑ PAPER LCD” switch for two seconds; to
lighten the LCD display, press and hold the “↓ PAPER LCD” switch for two seconds.
12
Rev 2 Jan 2001
MODEL CT-7500OPERATING INSTRUCTIONS
8.0 TEST HOOKUP CONNECTIONS
8.1 Contact Cable Hookup
A typical contact cable connection to a circuit breaker is shown in Figure 8-1.
NOTE
It is advisable to ground one side of the contacts for most testing. If a breaker is floating
(i.e., ungrounded), ensure contact-channel inputs are protected against static discharge.
A typical series contact connection is shown in Figure 8-2.
8.2 Initiate Cable Hookup
A CT-7500 will trip or close breakers with a solid-state device, which will operate on any ac or
dc control voltage from 10 to 300 volts. Both the trip and close circuits are protected by 3-ampere
fuses.
A typical dc trip and dc close control circuit test hookup is shown in Figure 8-3.
A typical dc trip and ac close control circuit is shown in Figure 8-4.
8.3 Analog Voltage Monitor Hookup
The analog voltage input (V1) lets users monitor a breaker's dc-control voltage during
operation. The analog voltage input (V1) will record the norminal dc voltage (at no load) and the
minimum dc voltage (while the Trip or Close coil is energized).
Nominal and minimum voltage readings will print on a tabulated report. Analog waveform will
also plot in a graphic report. This lets the user see the breaker's dc control voltage "dip" under
load. Problems, such as a poor connection or an excessive voltage drop, during operation can
thus be easily detected.
A typical voltage monitoring hook up is shown on Figure 8.5.
NOTE
Maximum voltage recorded is 255 Vdc.
8.4 Digital Voltage Monitor Hookup
The Digital V2 voltage input channel lets users monitor the voltage ON/OFF state. The voltage
ON/OFF state will be plotted on the graphic report. A typical hook up is shown on Figure 8.5.
8.5 External Trigger Input
External trigger mode lets a user start a recording when the CT-7500 senses a voltage. A
typical application for this external trigger mode is to time a circuit breaker in a close operation and
to start timing only when the close coil is energized (bypassing the 52X relay delay time).
Since the 52X relay carries the close coil current, the user wants to connect the CT-7500’s initiate
cable to the close terminal (figure 8-4). The CT-7500 will energize the 52X relay to start the close
operation. The CT-7500 then will start the timing when it senses the voltage across the closing
coil. See Figure 8.6 for a typical test hookup.
Another application (for external trigger) is to start timing the breaker when the user trips or closes
the breaker remotely.
13
Rev 2 Jan 2001
MODEL CT-7500OPERATING INSTRUCTIONS
NOTE
Minimum trigger voltage is set for 30 V ac/dc. Maximum continous voltage is 300Vac/dc.
Different trigger voltages can be set at the factory, based on specific requests from users.
The CT-7500 will start looking for the external trigger input voltage after the CT-7500 Initiate
Sequence is completed (CT-7500 stops beeping after the user presses “START” key) and
message “LOOKING FOR TRIGGER VOLTAGE” is shown on LCD.
This external trigger voltage needs to be sensed by the CT-7500 within 5 second after the
Initiate sequence. The CT-7500 will return to main menu if no voltage is sensed.
8.6 AC Current Sensor Hookup
A clamp-on AC current sensor connecting to the breaker bushing CT allows the CT-7500 to
sense breaker bushing current. The AC current sensor requires a 100mA current to operate.
Maximum current is 25 amperes. Typical hookup is shown on figure 8-8.
14
Rev 2 Jan 2001
MODEL CT-7500OPERATING INSTRUCTIONS
Figure 8-1. Typical Single Break Contact Cable Hookup
Figure 8-2. Typical Series Contacts Test Cable Hookup
15
Rev 2 Jan 2001
MODEL CT-7500OPERATING INSTRUCTIONS
Firgure 8-3. Typical DC Trip and Close Control Test Cable Hookup
Figure 8-4. Typical DC Trip and AC Close Control Test Cable Hookup
16
Rev 2 Jan 2001
MODEL CT-7500OPERATING INSTRUCTIONS
Figure 8-5. Typical Voltage-Monitoring Test Cable Hookup
Figure 8-6. Typical External Trigger Hookup
17
Rev 2 Jan 2001
Loading...
+ 53 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.