1520 S. Hellman Ave.
Ontario, California 91761, USA
TEL: (909) 923-9390
FAX: (909) 923-9391
August 2013
Revision 1
CT-7000 S3 USER’S MANUALREV 1
SAFETY SUMMARY
FOLLOW EXACT OPERATING PROCEDURES
Any deviation from the procedures described in this User’s Manual may create one or more
safety hazards, may damage the CT-7000 S3, or cause errors in the test results. Vanguard
Instruments Company, Inc. assumes no liability for unsafe or improper use of the CT-7000 S3.
All safety precautions provided in this manual must be observed during all phases of testing
including test preparation, test lead connection, actual testing, and test lead disconnection.
SAFETY WARNINGS AND CAUTIONS
Only trained operators shall use the CT-7000 S3. All devices under test shall be off-line and fully
isolated. Do not perform test procedures or service unless another person is also present who
is capable of rendering aid and resuscitation.
DO NOT MODIFY TEST EQUIPMENT
To avoid the risk of introducing additional or unknown hazards, do not install substitute parts or
perform any unauthorized modification to any CT-7000 S3 test unit. To ensure that all designed
safety features are maintained, it is highly recommended that repairs be performed only by
Vanguard Instruments Company factory personnel or by an authorized repair service provider.
Unauthorized modifications can cause safety hazards and will void the manufacturer’s
warranty.
WARNING
Do not remove test leads during a test. Failure to heed this warning can result in electrical
shock to personnel and damage to the equipment.
i
REV 1 CT-7000 S3 USER’S MANUAL
TABLE OF CONTENTS
CONVENTIONS USED IN THIS DOCUMENT ..................................................................................... 1
Figure 16. Sample Resistor Type Transducer Setup Directory ..................................................... 48
Figure 17. Sample Timing Report Using a Resistor Type Transducer ........................................... 49
Figure 18. Typical O-C-O Test Results Graph ................................................................................ 63
Figure 19. Typical Tabulated Test Results Printout for an O-C-O Operation ................................ 64
Figure 20. Typical On-Line Timing Test Graph Printout ................................................................ 65
Figure 21. Typical On-Line Timing Test Results Printout .............................................................. 66
Figure 22. Typical Tabulated Test Results Printout for a CLOSE Operation ................................. 69
Figure 23. Typical Test Results Graph (CB CLOSE Test) ................................................................ 71
Figure 24. Expansion Graph from 0ms to 200ms (CB CLOSE Test) ............................................... 72
Figure 25. Typical O-C-O Test Results Graph ................................................................................ 73
Figure 26. Typical Tabulated Test Results Printout for an O-C-O Operation ................................ 74
Figure 27. Graphical Interpretation of an OPEN Timing Shot ....................................................... 75
Figure 28. Graphical Interpretation of a CLOSE Timing Shot ........................................................ 75
Figure 29. Graphical Interpretations of an OPEN-CLOSE and CLOSE-OPEN Timing Shot ............. 76
Figure 30. Sample Test Record Directory Printout ....................................................................... 79
Figure 31. Typical Test Results Printout with Pass/Fail Indicators ............................................... 95
Figure 32. Typical Test Plan Directory Printout ............................................................................ 97
Figure 33. Typical Breaker Test Plan Printout ............................................................................. 106
Figure 34. Siemens SPS2 121 CLOSE Timing Illustration ............................................................. 107
Figure 35. Siemens SPS2 121 OPEN Timing Illustration .............................................................. 108
Figure 36. Typical Slow-Close Test Results Printout ................................................................... 110
Figure 37. Partial Data Points Printout ....................................................................................... 116
iv
CONVENTIONS USED IN THIS DOCUMENT
This document uses the following conventions:
•
A key or switch on the CT-7000 S3 is indicated as
CT-7000 S3 USER’S MANUALREV 1
[KEY]
and
[SWITCH]
.
Menu options are referenced as (MENU OPTION).
•
Screen and menu names are referenced as “SCREEN/MENU NAME”.
•
The terms “test record” and “test shot” are used interchangeably.
•
• CT-7000 S3 LCD screen output is shown as:
1. OPTION 1
2. OPTION 2
3. OPTION 3
4. OPTION 4
5. OPTION 5
• When instructions are provided, the menu item that should be selected is shown in bold as
shown below (option 3 should be selected):
1. OPTION 1
2. OPTION 2
3. OPTION 3
4. OPTION 4
5. OPTION 5
• Warning messages are indicated as:
Warning message
WARNING
• Important notes are indicated as:
Note details
NOTE
1
REV 1 CT-7000 S3 USER’S MANUAL
1.0 INTRODUCTION
1.1 General Description and Features
The CT-7000 S3 is Vanguard's fourth generation EHV circuit breaker analyzer. The CT-7000 S3 is
available with 3 (part number 9021-UC) or 6 contact timing channels (part number 9100UC).The CT-7000 S3 can fully analyze a circuit breaker's performance by measuring the main
contact and resistor contact time, stroke, velocity, over-travel, bounce back and contact wipes.
Both contact and motion analysis can be performed on all circuit breaker operations (OPEN,
CLOSE, OPEN-CLOSE, CLOSE-OPEN, and OPEN-CLOSE-OPEN). The CT-7000 S3's timing window is
selectable between 1 second, 10 seconds, and 20 seconds.
Contact Timing Input Channels
The CT-7000 S3's dry contact timing channels (up to 6 channels) are used to time the circuit
breaker main contacts. Each main contact timing channel is capable of detecting the main
contact and insertion resistor contact time. Timing results are displayed in milliseconds and
cycles.
Breaker Stroke and Velocity
Three dedicated digital travel transducer channels are available on the CT-7000 S3 for
measuring circuit-breaker contact stroke, velocity, over-travel, and bounce back. With the use
of the Vanguard digital travel transducers, neither calibration nor setting is required. Circuit
breaker contact velocity is calculated based on contact’s travel distance over a period of time.
Special formulas to calculate velocity is also accommodated by the CT-7000 S3. Special feature
is also available to “Slow-Close” test the circuit breaker and obtain a test result report.
Resistor Type Transducer Inputs
The CT-7000 S3 offers 3 resistor type transducer input channels. These input channels are used
to interface with any resistor-type transducer to monitor the circuit breaker motion. Transducer
resistance ranges from 200 Ohms to 10K Ohms.
Voltage Monitoring Channels
The CT-7000 S3 features three voltage monitoring input channels (V1, V2, and V3). The V1
voltage channel is dedicated to monitoring the substation DC supply or coil voltage (0-255 V, DC
or peak AC). The nominal and minimum DC supply voltage levels are recorded and printed on
the tabulated report. An analog waveform showing the DC power supply is plotted on the
graphical report. The two digital voltage input channels, V2 and V3, are dedicated to monitoring
voltage on/off status presence or absence of the circuit breaker auxiliary switches. Digital
waveforms showing V2 and V3 activity are plotted on the graphical report. Three timing events
of the V2 and V3 activities are recorded and printed on the tabulated report.
2
CT-7000 S3 USER’S MANUALREV 1
Breaker Initiate Features
A built-in solid-state initiate device is used to operate a breaker from the CT-7000 S3.
Operational modes include OPEN, CLOSE, OPEN-CLOSE, CLOSE-OPEN, and OPEN-CLOSE-OPEN.
Multiple operation like OPEN-CLOSE, CLOSE-OPEN, and OPEN-CLOSE-OPEN can be initiated by
using a programmable delay time (in milliseconds) or by sensing a specific breaker contact
condition.
OPEN/CLOSE Coil Current Monitoring
One built-in, hall-effect sensor records the OPEN/CLOSE coil current amplitude and waveform.
The circuit breaker’s coil current waveform, effectively, a coil performance “fingerprint” or
“current profile”, can be used as a diagnostic tool for analyzing the circuit breaker’s
performance.
Computer Interface
The CT-7000 S3 can be computer-controlled via the USB or optional Bluetooth interface.
Windows-based Circuit Breaker Analysis Software is provided with each unit. Using this
software, circuit breakers can be timed from the PC. Test records can be retrieved from the CT7000 S3 and then stored on the PC for future analysis and report generation. Circuit breaker
test plans can also be created on the PC and transferred to the CT-7000 S3. Additionally, test
records can be automatically exported in Excel, PDF, and XML formats.
Internal Test Record and Test Plan Storage
The CT-7000 S3 uses Flash memory to store up to 200 test records internally. Test records can
be recalled and printed on the unit's built-in 4.5" wide thermal printer. Test records can also be
transferred to a USB Flash drive or exported to a PC via the USB port or Bluetooth (optional)
with the included Windows-based software. Up to 100 circuit breaker test plans can be stored
in the CT-7000 S3's Flash memory. A test plan is comprised of all circuit breaker performance
specifications (contact time, stroke, velocity, etc.). When a test plan is used with a timing test, a
Pass/Fail report is generated by comparing the actual performance with the specifications in
the stored test plan. Test plans can be transferred to the CT-7000 S3 from a USB Flash drive, or
from a PC via the USB port or Bluetooth (optional).
External Test Record and Test Plan Storage
A USB Flash drive can be used to store and transfer test plans and up to 999 test records.
Built-in Thermal Printer
The CT-7000 S3's built-in 4.5" wide thermal printer can print the breaker contact analysis
results in both tabular and graphic formats.
User Interface
The CT-7000 S3 features a back-lit graphic LCD screen (240 x 128 pixels) that is viewable in
direct sunlight and low-light levels. A rugged 44-key "QWERTY"-style membrane keypad is used
to control the unit and input information.
3
REV 1 CT-7000 S3 USER’S MANUAL
Diagnostic Capabilities
The CT-7000 S3 can perform diagnostics on its internal electronics. Diagnostics can be
performed to verify contact cable connections and to test the travel transducer’s electronics.
1.2 Optional Features
“On-line” Timing Mode
In addition to the conventional off-line timing mode, the CT-7000 S3 also offers an optional
three-phase “on-line” timing mode. In this mode, the CT-7000 S3 captures the breaker’s trip or
close time, the trip/close coil current “fingerprint”, and the battery supply voltage while the
breaker is still in service. The trip/close time is derived from the time of trip, or close coil
initiation, to the breaker’s bushing current breaker-make as detected by a AC clamp-on current
sensing probes. Trip/Close current waveforms are also captured by an external clamp-on DC
current probe.
The “on-line” timing mode can detect a breaker’s operating conditions with little or no down
time. In this mode, the first trip operation time of the breaker is captured. If a breaker has been
in service for a long period of time and sitting in close position, the first trip time of the breaker
may be slow possibly due to a sticky mechanism. The “on-line” mode is very useful in such
cases because traditional breaker timing may not detect this condition since several operations
may have occurred before the first timing test is conducted.
Dual Ground Testing Mode
With the optional dual ground testing mode, the CT-7000 S3 can measure a CB contact time
with ground being applied to both sides of the bushings. The clamp-on probe is connected to
one side of the CB safety ground straps, and an AC signal is coupled to this strap. A sensor on
the probe will detect a change in the induced AC signal when the CB contact is opened or
closed.
Bluetooth Interface
The optional Bluetooth interface can be used to wirelessly connect the CT-7000 S3 with a PC.
4
1.3 Technical Specifications
Table 1. CT-7000 S3 Technical Specifications
TYPE
Portable circuit-breaker analyzer
PHYSICAL SPECIFICATIONS
INPUT POWER
DRY-CONTACT INPUTS
TIMING WINDOWS
TIMING RESOLUTIONS
TIMING ACCURACY
DRY-CONTACT CHANNEL PROTECTION
DRY-CONTACT DETECTION RANGE
INSERTION RESISTOR DETECTION
RANGE
TRIGGER INPUT VOLTAGE
VOLTAGE SENSING INPUT RANGE
BREAKER OPERATIONS
BREAKER INITIATE CAPACITY
INITIATE CURRENT READING RANGE
DIGITAL TRAVEL TRANSDUCER
INPUTS
RESISTOR TYPE TRANSDUCER INPUTS
CONTACT TRAVEL POINT DIFFERENCE
DISPLAY
PRINTER
INTERNAL TEST RECORD STORAGE
EXTERNAL TEST RECORD STORAGE
COMPUTER INTERFACES
PC SOFTWARE
CABLES
OPTIONS
SAFETY
ENVIRONMENT
HUMIDITY
ALTITUDE
WARRANTY
14”W x 21 K” L x 8” D (35 cm x 53 cm x 20 cm); 15 lbs (6.8 Kg)
100-240Vac, 3A, 50/60Hz
3 channels (9021-UC) or 6 channels (9100-UC). Channel can detect the main contact
and resistor contact time.
1 second, 10 seconds, or 20 seconds
±50 micro-seconds @ 1 sec. duration
±500 micro-seconds @ 10 sec. duration
±1.0 milli-seconds @ 20 sec. duration
0.05% of reading ±0.05 ms @ 1 second duration
All contact inputs are grounded until test. Input channels are also protected against
static discharge.
Closed: Less than 20 Ohm.
Opened: greater than 5000 ohm
50 – 5,000 ohms
Open/Close trigger voltage: 24 V – 300V DC or peak AC
V1: analog input; 0 – 250 V DC or peak AC; sensitivity ±1 V; record and print voltage
level
V2 and V3: voltage presence/absence detector input; 24 – 255 V DC or peak AC;
record and print 3 timing events
Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open
30A, 250 Vac/dc max
one, non-contact, Hall-effect sensor, 0 – 20 amp range, dc to 5 Khz AC
3 digital travel transducer channels; linear range: 0.0 – 60.0 in (±0.01 in)
rotary range: 0 – 360 degrees (±0.36 degrees)
3 channels, 200 ohms – 10K ohms
measures “slow-close” contact-point distances; results can be printed
back-lit LCD screen (128 x 240 pixels); viewable in bright sunlight and low light
built-in 4.5” wide thermal printer that can print both graphic contact travel waveforms
and tabulated test results
Store up to 200 test records and 100 test plans
USB Flash drive interface for external storage of test records (999 max) and test plans
One USB port, optional Bluetooth wireless interface
Windows® based Breaker Analysis software included with purchase price
furnished with full set of test leads
transportation cases (available for the CT-7000 S3 and travel transducers), on-line
timing mode, dual ground testing mode, bluetooth interface
designed to meet UL 6101A-1 and CAN/CSA C22.2 No 1010.1-92 standards
Operating: -10°C to +50°C (+15°F to +122°F)
Storage: -30°C to +70°C (-22°F to +158°F)
90% RH @ 40°C (104°F) non-condensing
2,000 m (6,562 ft) to full safety specifications
one year on parts and labor
CT-7000 S3 USER’S MANUALREV 1
The above specifications are valid at nominal operating voltage and at a
temperature of 25°C (77°F). Specifications may change without prior notice.
NOTE
5
REV 1 CT-7000 S3 USER’S MANUAL
1.4 CT-7000 S3 Controls and Indicators
The CT-7000 S3’s controls and indicators are shown in Figure 1 below. A leader line with an
index number points to each control and indicator, which is cross-referenced to a functional
description in Table 2. The table describes the function of each item on the control panel. The
purpose of the controls and indicators may seem obvious, but users should become familiar
with them before using the CT-7000 S3. Accidental misuse of the controls will usually cause no
serious harm. Users should also be familiar with the safety summary found on the front page of
this User’s Manual.
6
Figure 1. CT-7000 S3 Controls and Indicators
CT-7000 S3 USER’S MANUALREV 1
Table 2. Functional Descriptions of CT-7000 S3 Controls and Indicators
Item
Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Panel Markings Functional Description
CONTACT INPUT
(C1-C6)
T1, T2, T3 Digital travel transducer channels (16-p in conne ctor s).
R1, R2, R3 Resistor type transducer inputs (5-pin).
V1 V1 voltage input channel dedicated to monitoring circuit breaker DC power
V2, V3 V2 and V3 voltage input channels dedicated to detecting voltage ab sence or
EXT. TRIGGER Triggers voltage input for external trigger application. Voltage level ranges from
DC CURRENT External DC current probe connector.
INITIATE 4-pin connector used for the switching circuit for operating the circuit breaker
GROUND Safety ground terminal.
120-240Vac, 3A
50-60Hz
OPEN
250V/5A
CLOSE
250V/5A
"PUSH TO ARM" Spring-loaded pushbutton switch. Press and hold to co mpl ete the Trip or Close
Built-in 4.5" wide thermal printer.
BLUETOOTH Bluetooth status indicator (optional).
Rugged "QWERTY" style membrane keypad.
Back-lit LCD screen (128 x 240 pixels); viewable in bright sunlight and low light.
USB PC USB computer interface port.
USB MEM USB Flash drive interface port.
Female connectors for the contact channels. The CT-7000-6 S3 is pictured
with 6 channels.
supply or coil voltages. Voltage sensing range is from 0-250 V DC or peak AC.
presence. Voltage input ranges from 24-255 V DC or peak AC. Each voltage
channel records 3 timing events (voltage on /off) and the re sults are printed on
the tabulated report.
24 - 300 V DC or peak AC.
under test.
Power plug, power switch, line filter, and fuse holder
Open circuit fuse: 5 Ampere, 250V, Fast-Blow.
Close circuit fuse: 5 Ampere, 250V, Fast-Blow.
circuits for breaker tests.
7
REV 1 CT-7000 S3 USER’S MANUAL
2.0 PRE-TEST SETUP
2.1 LCD Screen Contrast Control
To increase the LCD screen contrast, press and hold the [] key for two seconds. Release the
button when the desired contrast level has been reached.
To decrease the LCD screen contrast, press and hold the [] key for two seconds. Release the
button when the desired contrast level has been reached.
2.2 Printer Paper Control
To advance the thermal printer paper, press and release the [] key.
To retract the thermal printer paper, press and release the [] key.
2.3 Printer Paper
The CT-7000 S3’s built-in thermal printer uses 4.5-inch wide thermal paper for printing test
results. To maintain the highest print quality and to avoid paper jams, the use of thermal paper
supplied by Vanguard Instruments Company is highly recommended. Additional paper can be
ordered from the following sources:
Vanguard Instruments Co, Inc.
1520 S. Hellman Avenue
Ontario, CA 91761
Tel: 909-923-9390
Fax: 909-923-9391
Part Number: VIC TP-4 paper
BG Instrument Co.
13607 E. Trent Avenue
Spokane, WA 99216
Tel: 509-893-9881
Fax: 509-893-9803
Part Number: VIC TP-4 paper
8
CT-7000 S3 USER’S MANUALREV 1
2.4 Replacing the Thermal Printer Paper
The roll of thermal paper is housed inside a dispenser underneath the printer cover. To replace
the paper, follow the steps below:
• Unscrew the two large printer cover screws and remove the printer cover.
• Remove the leftover thermal paper roll from the paper holder.
• Unroll the new thermal paper roll.
• Feed the thermal paper into the slot between the paper pocket and the rubber roller.
The printer will automatically pull the paper under the thermal head.
• Place the paper roll into the paper holder.
• Lift the thermal head and align the thermal paper if necessary.
• Re-install the printer cover.
Thermal paper has a chemical coating on one side of the paper. This side should be
facing the thermal print head. Incorrect paper loading may result in blank output on
NOTE
the thermal paper.
The thermal paper will show a red stripe to indicate that the roll is about to run out
of paper.
9
REV 1 CT-7000 S3 USER’S MANUAL
3.0 OPERATING PROCEDURES
3.1 Cable Connections
3.1.1. Contact Cable Connections
A typical contact cable connection to a circuit breaker is shown in Figure 2. Red and black clips
are connected across the circuit contact phases A, B, and C. A typical circuit breaker with series
contacts is shown in Figure 3.
It is advisable to ground one side of the contacts for most testing purposes. If a
breaker is floating or un-grounded, ensure that the contact channel inputs are
Figure 3. Typical Connections for Series Contact Circuit Breaker
11
REV 1 CT-7000 S3 USER’S MANUAL
3.1.2. Initiate Cable Connections
The CT-7000 S3 can trip or close breakers through a solid-state device operating on any AC or
DC control voltage ranging from 10 to 300 Volts. Both the trip and close circuits are protected
by 5 Ampere fuses. A typical DC trip and DC close control circuit connection is shown in Figure
4. A typical DC trip and AC close control circuit connection is shown in Figure 5.
Figure 4. Typical DC Trip and DC Close Control Circuit Connection
Auxiliary switches, in series with the OPEN and CLOSE coil control circuit, are used to
interrupt the coil current.
NOTE
12
CT-7000 S3 USER’S MANUALREV 1
Figure 5. Typical DC Trip and AC Close Control Circuit Connection
13
REV 1 CT-7000 S3 USER’S MANUAL
3.1.3. Online Timing Connections (w it h optional Online Timing feature)
In addition to the conventional off-line timing mode, the CT-7000 S3 also offers an optional
three-phase “on-line” timing mode. In this mode, the CT-7000 S3 captures the breaker’s trip or
close time, the trip/close coil current “fingerprint”, the battery supply voltage, and auxiliary
switch times while the breaker is still in service. The trip/close time is derived from the time of
trip, or close coil initiation, to the breaker’s bushing current breaker make/break as detected by
a AC clamp-on current sensing probes. Trip/Close current waveforms are also captured by an
external clamp-on DC current probe.
The “on-line” timing mode can detect a breaker’s operating conditions with little or no down
time. In this mode, the first trip operation time of the breaker is captured. If a breaker has been
in service for a long period of time and sitting in close position, the first trip time of the breaker
may be slow possibly due to a sticky mechanism. The “on-line” mode is very useful in such
cases because traditional breaker timing may not detect this condition since several operations
may have occurred before the first timing test is conducted.
The CT-7000 S3 On-Line timing mode requires the use of 3 AC current sensors (provided with
the Online Timing Option, Part no. 9021-OT) to monitor the contact time phases A, B, and C.
The Open and Close coil current is monitored by using the provided DC current sensor
(provided with the Online Timing Option, Part no. 9021-OT). The On-Line timing mode requires
the External trigger to be connected. Please see Figure 7 for the On-Line timing test
connections.
14
Figure 6. On-line Timing Probe Set (Part No. 9021-OT)
CT-7000 S3 USER’S MANUALREV 1
Figure 7. Typical Connections for Optional On-line Timing Mode
15
REV 1 CT-7000 S3 USER’S MANUAL
3.1.4. Dual Ground Connections (w ith optional Dual Ground feature)
With the optional dual ground testing mode, the CT-7000 S3 can measure a CB contact time
with ground being applied to both sides of the bushings. The clamp-on probe is connected to
one side of the CB safety ground straps, and an AC signal is coupled to this strap. A sensor on
the probe will detect a change in the induced AC signal when the CB contact is opened or
closed.
The CT-7000 S3 Dual Ground test mode requires the use of the Vanguard Dual Ground Current
Probes (provided with the Dual Ground option, part no. 9021-DG). Up to 3 timing channels are
available with the Dual Ground option. Only timing channels 1, 2, and 3 are used for this mode
(see Figure 8).
Figure 8. Typical Connections for Optional Dual Ground Testing Mode
Transducer channels, voltage monitoring channels, and the initiate circuit are
connected the same as the regular time travel test mode.
NOTE
16
CT-7000 S3 USER’S MANUALREV 1
3.1.5. Analog and Digital Vo ltage Monitoring Connections
The analog voltage input “V1” can monitor a breaker’s DC control voltage during an operation.
The analog voltage input records the nominal DC voltage at no load and the minimum DC
voltage while the Trip or Close coil is energized. The nominal and minimal voltage readings are
printed on a tabulated report, and the analog waveforms are plotted in graphical format. This
allows the user to see the breaker’s DC control voltage “dip” under load conditions and helps
detect problems such as a poor connection or an excessive voltage drop during operation.
Please note that the maximum voltage that can be recorded is 250 Vdc.
The digital voltage input channels “V2” and “V3” can monitor the voltage status as “ON” or
“OFF” states. The voltage “ON” or “OFF” states are plotted on the graphical report. Three
voltage on/off events are also printed on the tabulated timing report. Typical analog (“V1”) and
digital (“V2”) voltage monitoring connections are shown in Figure 9.
Figure 9. Typical Analog and Digital Voltage Monitoring Connections
17
REV 1 CT-7000 S3 USER’S MANUAL
3.1.6. External Trigger Input Connections
The External Trigger Mode can be used to start recording data when the CT-7000 S3 senses a
voltage. A typical application for the External Trigger Mode is to time a circuit breaker in a Close
operation and to start timing only when the Close coil is energized, thus bypassing the 52X relay
delay time.
Since the 52X relay carries the Close coil current, the CT-7000 S3’s initiate cable must be
connected to the Close terminal as shown in Figure 4. The CT-7000 S3 will energize the 52X
relay to start the Close operation, which will then start the timing when the CT-7000 S3 senses
the voltage across the closing coil. Typical external trigger input connections are shown in
Figure 10.
Another application for the External Trigger is to start timing the breaker when the user trips or
closes the breaker remotely.
• The minimum trigger voltage is 30 Vac/dc. Maximum, continuous voltage is limited
to 300 Vac/dc. Different trigger voltages can be set at the factory by request.
NOTES
• The CT-7000 S3 will start looking for the external trigger voltage when the message
“AWAITING TRIGGER…” is displayed on the LCD screen. The external trigger
voltage must be sensed by the CT-7000 S3 within 15 seconds after the initiate
sequence has begun. The CT-7000 S3 will return to the “START-UP” menu if no
voltage is sensed.
A typical digital transducer connection is shown in Figure 11.
Figure 11. Typical Digital Transducer Connection
19
REV 1 CT-7000 S3 USER’S MANUAL
3.1.8. Resistor Type Transducer Con nection
The CT-7000 S3 provides three channels for resistor type transducers. The transducer resistance
input can range from 200 Ohms to 10K Ohms. The CT-7000 S3 supplies a 5 Vdc reference
voltage to power the resistor type transducer. The sense voltage is translated into a travel
distance based on the transducer calibration parameters. The user is required to setup the
resistor transducer before performing a test. Up to nine transducer setups can be stored in the
CT-7000 S3’s internal memory. Once a transducer setup is stored, it can be recalled quickly
before running a test. A typical resistor type transducer connection is shown in Figure 12.
• When a resistor type transducer is selected, all three resistor transducer channels
(R1, R2, and R3) are active and will be shown on the test results (see Figure 17).
NOTES
• A 15-foot transducer cable with 3 quick disconnect clips is provided with each CT-
7000 S3. The 3 clips are labeled “+5V”, “Signal”, and “GND”.
• See section 3.2.11 for resistor type transducer calibration information.
20
Figure 12. Typical Resistor Type Transducer Connection
CT-7000 S3 USER’S MANUALREV 1
3.2 Changing Setup Parameters
3.2.1. Entering Test Record Header Information
You can enter the test record header information before performing tests. The record header
includes identifying information such as the company, station, circuit, model number, etc. Once
the header information has been entered, it will apply to all subsequent test records. To enter
the header information:
a. When the unit is turned on and the firmware is loaded, you will be presented with the
“START-UP” menu as shown below:
1. TIME BREAKER 09/12/13
2. GET RESULTS 10:10:10
3. SAVE/RESTORE
4. SETUP
5. DIAGNOSTICS
Press the [4] key (SETUP).
b. The following screen will be displayed:
1. ANALYSIS POINTS
2. MEASUREMENT UNITS
3. SHOT DESCRIPTION
4. NUMBER OF CHANNELS
5. NEXT PAGE
Press the [3] key (SHOT DESCRIPTION).
c. The following screen will be displayed:
COMPANY:
_
↑↓to position
"ENTER" TO ACCEPT
Type the company name using the keypad. To erase a character at the cursor position,
press the [CLEAR] key. Press the [] key to move to the next character. Press the []
key to move to the previous character. Press the [ENTER] key when you are done
typing the company name.
21
REV 1 CT-7000 S3 USER’S MANUAL
d. The following screen will be displayed:
STATION:
_
↑↓to position
"ENTER" TO ACCEPT
Type the station name using the keypad and then press the
e. The following screen will be displayed:
CIRCUIT:
_
↑↓to position
"ENTER" TO ACCEPT
Type the circuit information using the keypad and then press the
f. The following screen will be displayed:
MANUFACTURER:
_
↑↓to position
"ENTER" TO ACCEPT
[ENTER] key.
[ENTER] key.
Type the circuit breaker manufacturer name using the keypad and then press the
[ENTER] key.
g. The following screen will be displayed:
MODEL:
_
↑↓to position
"ENTER" TO ACCEPT
Type the circuit breaker model information using the keypad and then press the
[ENTER] key.
22
h. The following screen will be displayed:
SERIAL NUMBER:
_
↑↓to position
"ENTER" TO ACCEPT
CT-7000 S3 USER’S MANUALREV 1
Type the circuit breaker serial number using the keypad and then press the
[ENTER]
key.
i. The following screen will be displayed:
OPERATOR:
_
↑↓to position
"ENTER" TO ACCEPT
Type the operator’s name using the keypad and then press the
[ENTER] key. All
header information will be saved, and you will be returned to the “START-UP” menu.
23
REV 1 CT-7000 S3 USER’S MANUAL
3.2.2. Setting the Clock
Follow the steps below to set the CT-7000 S3’s internal clock:
a. Start from the “START-UP” menu:
1. TIME BREAKER 09/12/13
2. GET RESULTS 10:10:10
3. SAVE/RESTORE
4. SETUP
5. DIAGNOSTICS
Press the [4] key (SETUP).
b. The following screen will be displayed:
1. ANALYSIS POINTS
2. MEASUREMENT UNITS
3. SHOT DESCRIPTION
4. NUMBER OF CHANNELS
5. NEXT PAGE
Press the [5] key (NEXT PAGE).
c. The following screen will be displayed:
1. SET DATE & TIME
2. SET PRINT MODE
3. SET 50/60 HZ
4. SET LANGUAGE
5. BLUETOOTH DEV RESET
6. PREVIOUS PAGE
Press the
[1] key (SET DATE & TIME).
d. The following screen will be displayed:
ENTER
mm-dd-yy hh:mm:ss
_
Enter the month, date, time, hours, minutes, and seconds (in 24-hour format) using the
alpha-numeric keypad. When the last digit is entered, the clock will be set and you will
be returned to the “START-UP” menu.
24
CT-7000 S3 USER’S MANUALREV 1
3.2.3. Configuring Automatic or Manual Printing of Test Results
The CT-7000 S3 can be configured to print graphs and tabulated results automatically or
manually after each test. To configure the printing method:
a. Start from the “START-UP” menu:
1. TIME BREAKER 09/12/13
2. GET RESULTS 10:10:10
3. SAVE/RESTORE
4. SETUP
5. DIAGNOSTICS
Press the [4] key (SETUP).
b. The following screen will be displayed:
1. ANALYSIS POINTS
2. MEASUREMENT UNITS
3. SHOT DESCRIPTION
4. NUMBER OF CHANNELS
5. NEXT PAGE
Press the [5] key (NEXT PAGE).
c. The following screen will be displayed:
1. SET DATE & TIME
2. SET PRINT MODE
3. SET 50/60 HZ
4. SET LANGUAGE
5. BLUETOOTH DEV RESET
6. PREVIOUS PAGE
Press the
[2] key (SET PRINT MODE).
d. The following screen will be displayed:
SET PRINT MODE:
1. AUTOMATIC PRINT
2. BY REQUEST ONLY
Press the
Press the
[1] key (AUTOMATIC PRINT) to automatically print test results after each test.
[2] key (BY REQUEST ONLY) to manually print test results after each test.
Please see section 3.3.5 for instructions on how to manually print test results.
25