Vanguard Accu-Trans User Manual

OPERATING INSTRUCTIONS
for the
ACCU-TRANS™
TRANSFORMER-WINDING
RESISTANCE METER
Series II
Part Number VIC-8000-S2
1710 Grevillea Court Ontario, California 91761
TEL: (909) 923-9390 July 2001 FAX: (909) 923-9391 Rev 0
Accu-Trans Operating Procedures
SAFETY SUMMARY
The following safety precautions must be observed during all phases of test set-up, test hookups, testing, and test-lead disconnects.
Do Not Service or Test Alone
Do not perform test procedures or service unless another person is also present who is capable of rendering aid and resuscitation.
Avoid Contact with High Voltage
Because electric utility station environments contain high voltages and currents, there’s always the possibility of personal contact with an unexpected lethal voltages generated by magnetically induced and/or electrostatic leakage from nearby live circuitry. When test units are connected to de-energized ("dead") lines, regardless of how short these lines may be, always discharge the lines before attaching test lead. Because of the possibly deadly consequences of physical contact with such lines, engineers and technicians must always treat electrical equipment and hookups as though a lethal condition will eventually occur. Therefore, no matter how unlikely it may be, never assume anything about the safety of any test setup. Ensure the safety of personal by checking
first-hand to eliminate every possible hazard!
Avoid Contact With High-Voltage “Kicks”
Any transformer with many windings turns and an iron core supports induced magnetic fields, such that even low-level test currents produce a magnetic field that, if interrupted,
can produce a high-voltage spike capable of causing severe injury or death. Accordingly, its important for personnel safety that test leads be securely attached to the transformer terminals to prevent their being accidentally disconnected during testing. All personnel are warned to stand clear of the transformer during all testing. Test technicians should always ensure that all non-technical personnel (who may not understand the hazards) be required to stand clear of all transformers and equipment during all phases of transformer testing.
Do Not Modify Test Equipment
Because of the added risk of introducing additional or unknown hazards, do not install substitute parts or perform any unauthorized modification to the Accu-Trans. To ensure all designed safety features are maintained, it is recommended that all Accu-Trans repairs be performed at Vanguard Instruments Co. or by an authorized repair-service. Unauthorized equipment modifications can create safety hazards and will void the Accu-Trans warranty.
Follow Exact Operating Procedures
Any deviation from the operating procedures described in this manual may create one or more safety hazards, damage the unit or cause test result errors; Vanguard Instruments Co. assumes no liability for unsafe or improper use of the Accu-Trans.
i
Accu-Trans Operating Procedures
1
Table of Contents
SAFETY SUMMARY................................................................................................................. I
1.0 INTRODUCTION...................................................................................................................3
1.1 APPLICABILITY................................................................................................................3
1.2 SUPERSEDURE NOTICE..................................................................................................3
1.3 GENERAL DESCRIPTION................................................................................................3
1.4 FUNCTIONAL DES CRIPTION.........................................................................................3
1.5 FURNISHED ACCESSORIES ...........................................................................................3
2.0 ACCU-TRANS SPECIFICATIONS.......................................................................................4
3.0 CONTROLS and INDICATORS ............................................................................................5
4.0 PRETEST SETUP ...................................................................................................................7
4.1 OPERATING VOLTAGES.................................................................................................7
4.2 ACCU-TRANS LCD CONTRAST CONTROL.................................................................8
4.3 ACCU-TRANS PRINTER PAPER CONTROL.................................................................8
5.0 ACCU-TRANS PRINTER PAPER.........................................................................................8
6.0 OPERATING PROCEDURES................................................................................................8
6.1 GENERAL PROCEDURES................................................................................................8
6.2 STEP-BY-STEP PROCEDURES AT START-UP MENU..............................................10
6.2.1 START-UP MENU:.......................................................................................................10
6.2.2 TEST TRANSFORM ER PROCEDURE.......................................................................10
6.3 SETUP MENU:..................................................................................................................11
6.3.1 TRANSFORMER ID ENTRIES:..................................................................................12
6.3.2 REVIEW TEST RECORDS PROCEDURE .................................................................13
6.3.3 RESTORE RECORDING PROCEDURES ..................................................................14
6.3.4 PRINTING TEST-RECORD DIRECTORY.................................................................15
6.3.5. ERASE RECORDING PROCEDURE..........................................................................17
6.3.6 ENABLING COMPUTER INTERFACE.....................................................................18
6.3.7 SETTING DATE AND TIME.......................................................................................18
6.3.8 ENABLE PASSIVE TEST MODE ...............................................................................19
6.3.9 VOLTAGE REGULATOR TEST.................................................................................19
Accu-Trans Operating Procedures
2
Table of Figure
Figure 1.0 Accu-Trans Controls and Indicators............................................................................5
Figure 2.0 90 to 130Vac Jumper Setting.......................................................................................7
Figure 3.0 210 to 240Vac Jumper Setting.....................................................................................7
Figure 4.0 Summary of Step-by-Step Accu-Trans Operat ion.......................................................9
Figure 5.0 Typical Test Report Printout......................................................................................12
Figure 6.0 Typical Record Directory Printout .............................................................................17
Accu-Trans Operating Procedures
3
1.0 INTRODUCTION
1.1 Applicability
This manual applies to a second-generation Accu-Trans™ (Series II, henceforth, called the Accu-Trans), part number VIC-80000­S2 manufactured by the Vanguard Instruments Co. A prior manual supports a first generation Accu-Trans (i.e., a Series I configuration).
1.2 Supersedure Notice
This Operator’s manual is the basic issue for the Accu-Trans and does not supersede any previously published manual.
1.3 General Description
Vanguard Instruments Company produces the Accu-Trans, a microprocessor-controlled winding resistance meter that measures low resistances of a transformer’s inductive windings, in a range from 1 micro-ohm to 200 ohms with very high accuracy. This instrument can also measure any low milliohm resistance (e.g., the contact resistance of a circuit breaker). This Accu-Trans is simple-to-use; it features keypad controls and an alpha/numeric display of the measured resistance, test current, and operator-entered test parameters and identifying data. The Accu-Trans uses a 48-volt dc power supply and a special current-regulator to quickly measure transformer-winding resistances. A typical single- phase 400MVA
transformer winding resistance can be measured in less than 3 minutes. To ensure
operator safety, the Accu-Trans automatically discharges the energy stored in the transformer at the end of each test. A built-in thermal printer prints test results on 2.5-inch-wide thermal paper. Resistance and test current display on a 4-line by 20­character, back lighted LCD. Up to 63 records (96 readings each) can be stored in the Accu-Trans FLASH EEPROM. The user can recall stored reports for printing. A RS-232C serial interface port is provided for
diagnostic testing and down loading test records. The Accu-Trans is field-portable, rugged; it features simple, easy operation by first-time users with little training.
1.4 Functional Description
The Accu-Trans’s operation is based on the electrical relationships described by Ohm’s law: R=V/I, where I is a known current and V is the dc voltage measured across the unknown resistance (typically, a circuit­breaker’s contacts). The value of the unknown resistance under test is the direct function of the measured voltage divided by the current and being calculated by the microprocessor. Resistance reading is then displayed on a back-lighted 4 line by 20 character LCD. The Accu-Trans’ 48V dc power supply applies up to 2 amperes test current to the device under test. Accu-Trans voltmeter test leads are run separately from the current­bearing test leads to the resistive load; thus, voltages are measured at the terminals of the resistance being measured, eliminating error from the I•R voltage drop in the test current cables. The Accu-Trans makes precise micro-ohm measurements possible without calculating compensation for test-current­lead resistance errors. A built-in discharge circuit automatically discharges the energy stored in the transformer at the end of each test.
1.5 Furnished Accessories
The Accu-Trans is shipped with two 45-foot test cables with “quick disconnect” type test plugs on the unit end and battery-type clamps at the test load end. One power cord, one ground cable, and a cable-carrying bag.
Accu-Trans Operating Procedures
4
2.0 ACCU-TRANS SPECIFICATIONS
Table 1. ACCU-TRANS SPECIFICATIONS
TYPE Special-purpose test equipment, portable, micro-ohmmeter SIZE (inches) 16.8 wide by 12.6 high by 10.6 deep WEIGHT Less than 21 pounds RESISTANCE 1 micro-ohm to 200 ohms TEST CURRENT 2 amperes max DISPLAY LCD, back-lighted, 4-line by 20-character PRINTER 2.5-inch wide thermal printer ACCURACY ± 1 % reading, ± 1 count POWER 2 amps, 90-120 / 200-240 V ac (selectable), 50/60 Hz SERIAL INTERFACE RS-232C connector port ENVIRONMENT Operating: 0°C to 55°C; Storage: -40°C to 65°C WARRANTY One-year parts & labor (post warranty service is available)
NOTE: THE ABOVE SPECIFICATIONS ARE VALID AT NOMINAL OPERATING VOLTAGE AND AT A TEMPERATURE OF 25 °C (77°F)
?ACCU-TRANS SPECIFICATIONS MAY BE UPGRADED AND CHANGED WITHOUT PRIOR NOTICE.
Accu-Trans Operating Procedures
5
3.0 CONTROLS AND INDICATORS
(See Figure 1 and refer to Table 1.) Accu-Trans controls and indicators are shown in Figure 1.0. A leader line with an index number points to each control and indicator, which is cross-referenced to a functional description in Table 2. This table describes the function of each item on the
control-panel. The purpose of the controls and indicators may seem obvious, but users should become familiar with them before using the Accu-Trans. Accidental misuse of the controls will usually cause no serious harm. Users should also be familiar with the Safety Summary found on the front page of this operator’s manual.
Figure 1.0 Accu-Trans Controls and Indicators
Loading...
+ 19 hidden pages