Vaillant Control Center VR 65, VR 65 Installation Instructions Manual

For the qualified engineer
Installation instructions
Control Center VR 65
Control Center for storage connection (eBUS)
VR 65
GB
Contents
Notes on the documentation 1
Description of the appliance 2
Contents
1 Notes on the documentation . . . . . . . . . . . . . 3
2 Description of the appliance . . . . . . . . . . . . . . 3
2.1 Data badge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 CE label/conformity . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Safety instructions and regulations . . . . . . . 4
3.1 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.2 Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.1 Installation overview . . . . . . . . . . . . . . . . . . . . . . . . 5
4.2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.3 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4.4 Assembling Control Center VR 65 . . . . . . . . . . . . 6
5 Electrical installation . . . . . . . . . . . . . . . . . . . 6
5.1 Installing the VR 65 with one 3-port valve . . . . . 7
5.2 Installing the VR 65 with two 2-port valves . . . . 8
5.3 Installing the VR 65 with a NTC . . . . . . . . . . . . . . 9
6 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . 10
8 Factory customer service . . . . . . . . . . . . . . . . 11
The following information is intended to help you throughout the entire documentation. Further documents apply in combination with this instal­lation instructions.
We accept no liability for any damage caused by non­observance of these instructions.
Other applicable documents
When operating the equipment, please observe the oper­ating instructions for the different system components.
Attachment and storage of the documents
The wiring diagram can be found on the inside of the housing cover. Please pass on this installation manual to the owner of the system so that he can keep it available whenever it is required.
Symbols used
Please observe the safety instructions in this installation manual!
Danger!
Immediate risk of serious injury or death.
Danger due to high voltage!
Immediate danger to life and limb!
9 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . 11
Caution!
Potentially dangerous situation for the product and environment.
Note!
Useful information and instructions.
• Symbol for a necessary task
2 Description of the appliance
The Control Center VR 65 offers a solution to allow Vaillant low voltage ‘eBUS’ controls to be used with the traditional 230 V zone valves and DHW storage cylinder in the English market. Information about the heat required by the cylinder is forwarded by the Control Center VR 65 to the Vaillant ecoTEC heating appliance. The boiler then decides whether a hot water request has to be fulfilled and sends a signal to position the 230 V zone valves via the VR 65. In this way, the boiler can store different target tempera­tures for heating and warm water operation. Standard 230 V components can be integrated into the Vaillant eBUS system via the Control Center VR 65.
3Installation Instructions for Control Center VR 65
2 Description of the appliance 3 Safety instructions and regulations
The following components can be connected
- 230 V 3-port mid-position valve
- 230 V cylinder thermostat or alternatively
- 2 x 230 V 2-port zone valves
- 230 V cylinder thermostat
When Vaillant uniSTOR cylinder is installed, the NTC sen­sor VR 10 supplied with the VR 65 can be used instead of the 230 V cylinder thermostat. This will then allow the cylinder temperature to be set at the Vaillant ecoTEC boiler or at the Vaillant VRT 360 or VRC 400 control. The cylinder temperature can also be set remotely via vrnetDIALOG.
2.1 Data badge
The data badge is on the inside of the VR 65 Control Centre housing cover.
2.2 CE label/conformity
The CE label documents that the Control Center VR 65, in connection with Vaillant condensation boilers, fulfils the basic requirements of the following guidelines:
- Electromagnetic compatibility directive (Guideline 89/ 336/EEC of the council)
- Low voltage directive (73/23/EEC)
2.3 Intended use
The Control Center VR 65 is a state-of-the-art appliance which has been designed in accordance with recognised safety regulations. Nevertheless, dangers to the life and limb of the user or third parties can still occur or the appliance or other material assets may be impaired in the event of improper use or use for which the applianc­es are not intended. The Control Center VR 65 is an eBUS system compo­nent. It is responsible for the communication between the DHW cylinder, the boiler and external 230 V 2- or 3-port valves. Any other use or extended use is considered to be improper use. The manufacturer/supplier is not liable for any resulting damage. The user alone bears any risk. Intended use includes the observance of the installation manual.
3 Safety instructions and regulations
The Control Center must be installed by a suitably quali­fied heating engineer, who is responsible for observing all relevant standards and regulations. We accept no liability for damage caused by non-obser­vation of these instructions.
3.1 Safety instructions
Danger!
Risk of death from electric shock through con­tact with live connections! Isolate the mains power supply before working on the unit, and ensure that the power cannot be accidentally restarted. Using the mains switch on the VR 65 or on the heating appliance is not sufficient to isolate all terminals of the system.
3.2 Regulations
All wiring must be in accordance with Building Regulations Part P, current IEE regulations, and must be carried out by a competent person.
Standard wires must be used for wiring. Minimum cross-section of wires:
- Power supply 230 V (connection cable to pumps or Control Center) 1.5 mm
- Extra-low voltage supply (sensor or bus wires) 0.75 mm
Do not exceed following maximum wire lengths:
- Sensor connection 50 m
- Bus wire 300 m
Where sensor and ‘eBUS’ cables run in parallel with 230 V cables over a length of 10 m, they must be sepa­rated by at least 25 mm.
2
230 V connection leads must be 1.5 mm using the cable clamps supplied.
Do not use free terminals on the devices as support ter­minals for other wiring.
The unit must be installed in a dry room.
and secured
2
2
Note!
The VR 65 is designed to control one 3-port valve or two 2-port valves. Systems requiring more zone valves or a combination of 3-port and 2-port valves are not possible.
Note!
The VR 65 requires a 230 V supply. The ecoTEC boiler also requires a 230 V supply. The eBUS wiring between the two will not provide 230 V from one device to the other!
4 Installation Instructions for Control Center VR 65
Installation 4
4 Installation
The Control Center can be wall-mounted near to the DHW cylinder. The hot water and heating programs as well as all required parameters are set at the VRT 360 or VRC 400. All heating circuit connections are made at the Control Center using a ProE plug.
4.1 Installation overview
Please check the following before installing the VR 65 Control Center:
- Read the installation instructions
- Check the scope of delivery
- Assemble the VR 65
- Carry out electrical installation
4.2 Scope of delivery
Using Table 4.1, check that all the components have been delivered with the VR 65.
Pos. Number Components
1 1 Control Center VR 65 2 1 Standard sensor VR 10
3 1 Cable clamps (7 pcs.) 4 1 Bag of screws
Table 4.1 Scope of delivery of the Control Centers VR 65
- VRC 400 Digital weather-dependent control with daily/weekly program for time and temperature control of heating and hot water. Designed to plug into the Vaillant ecoTEC boiler or for wall mounting.
Set the heating curve to adjust the flow temperature
to suit the heat requirement of the building. Optimises the flow temperature to the prevailing weather condi­tions. There are three individually programmable time win­dows per day for heating, hot water and a hot water circulation pump. Different target room temperatures can be set for each time window. The control can be set to run a weekly program or a daily program. By activating the calendar function, an automatic sum­mer/winter changeover is activated.
Caution!
Do not use a VRT 360 or VRC 400 in combina­tion with an additional room temperature ther­mostat e.g. VRT 30 due to the impact this may have on the operation of the VRT 360 or VRC
400.
4.3 Accessories
- timeSWITCH 140
Digital 2-channel timer with daily/weekly program for heating and hot water. The timeSWITCH 140 can be plugged into the Vaillant ecoTEC boiler. There are three individually programmable time win­dows per day for heating and hot water. The timer can be set to run a weekly or a daily program. By activating the calendar function, an automatic summer/winter changeover is activated.
- VRT 360
Digital room temperature thermostat with daily/weekly program for time and temperature control of heating and hot water. Designed for wall mounting. There are three individually programmable time win­dows per day for heating, hot water and a hot water circulation pump. Different target room temperatures can be set for each time window. The thermostat can be set to run a weekly or a daily program. By activating the calendar function, an automatic summer/winter changeover is activated.
5Installation Instructions for Control Center VR 65
4 Installation 5 Electrical installation
4.4 Assembling Control Center VR 65
The Control Centre connection terminals are provided with System ProE plugs. All onsite connections must be made using these plugs.
• Mark out the 2 fixing holes (2) and drill the holes.
• Select the wall plugs to suit the state of the wall and screw the housing
tight.
• Wire up the Control Center as shown in the wiring dia­grams (fig. 5.2 or 5.3).
• Fix all cables using the cable clamps (3).
• Finally, press the covering back onto the housing so that is clicks into place audibly.
5 Electrical installation
The electrical connection must be done by a suitably qualified heating engineer who is responsible for com­plying with the existing standards and guidelines.
Danger!
Risk of death from electric shock through con­tact with live connections! Isolate the mains power supply before working on the unit, and ensure that the power cannot be accidentally restarted. Using the mains switch on the VR 65 or on the heating appliance is not sufficient to isolate all terminals of the system.
Caution!
In order to avoid damage to the heating appli­ance or the VR 65 Control Centre, any existing 230 V wiring box installation must be removed completely.
Fig. 4.1 Opening the Control Centers
• Press the catch on the upper edge of the box down­wards using a screw driver.
• Pull the housing cover forwards.
4
230V~
CYL. CH DHW
NL
Fig. 4.2 Assembling the Control Centers
Key
1 Operating LED 2 Fixing holes 3 Cable clamps 4 On/Off switch
Non onoff
DHW
onN
DO NOT
BUS
NTC
USE
+-
21
optional
VRC 693 for
optional
(VRT 360 or
VR 65
1
230 V
2
3
VRC 400)
VRC 400
eBUS connection
Fig. 5.1 Connection of eBUS and mains cable in the system
Vaillant ecoTEC
230 V~
6 Installation Instructions for Control Center VR 65
5.1 Installing the VR 65 with one 3-port valve
• Wire up the Control Center as shown in fig. 5.2.
• Connect the eBUS terminals of the VR 65 to the eBUS terminals of the heating appliance using a two-core cable. The polarity of the eBUS cable can be mixed. The eBUS can be branched at any part of the system.
The Control Center VR 65 requires its own 230 V mains supply via a switched fused spur. The boiler also requires a 230 V supply.
Note!
The VR 65 has a mains switch (see fig. 4.2) to isolate the internal electronics as well as all connected zone valves for the purposes of tests and maintenance. When the housing cover has been removed, a green LED indicates if the VR 65 is still connected to the mains voltage.
Connection of Control Center
Electrical installation 5
NL
M
CYL.
CH DHW
Non onoff
WHITE
BLUE
BROWN or
EARTH
230 V~
230 V~
3-Port
Fig. 5.2 Connection with 3-port valve
GREY
ORANGE
DHW
BUS
NTC
onN
+-
21
* Cylinder thermostat
* Note: With Vaillant uniSTOR - use either the cylinder thermostat or the NTC
DO NOT
USE
VR 65
* NTC (for use with Vaillant uniSTOR only)
Vaillant ecoTEC
230 V wires eBUS (24 V) optional (24 V)
optional
(VRT 360 or
VRC 400)
230 V~
7Installation Instructions for Control Center VR 65
5 Electrical installation
5.2 Installing the VR 65 with two 2-port valves
• Wire up the Control Center as shown in fig. 5.3.
• Connect the eBUS terminals of the VR 65 to the eBUS terminals of the heating appliance using a two-core cable. The polarity of the eBUS cable can be mixed. The eBUS can be branched at any part of the system.
The Control Center VR 65 requires its own 230 V mains supply via a switched fused spur. The boiler also requires a 230 V supply.
Note!
The VR 65 has a mains switch (see fig. 4.2) to isolate the internal electronics as well as all connected zone valves for the purposes of tests and maintenance. When the housing cover has been removed, a green LED indicates if the VR 65 is still connected to the mains voltage.
Connection of Control Center
CYL.
NL
230 V~
CH
M
2-Port
Fig. 5.3 Connection with two 2-port valves
DHW
M
CH DHW
Non onoff
BLUE
EARTH
BROWN
DHW
EARTH
BUS
NTC
onN
BLUE
+- 21
* Cylinder thermostat
BROWN
* Note: With Vaillant uniSTOR - use either the cylinder thermostat or the NTC
DO NOT230 V~
USE
VR 65
* NTC (for use with Vaillant uniSTOR only)
Vaillant ecoTEC
230 V wires eBUS (24 V) optional (24 V)
optional
(VRT 360 or
VRC 400)
230 V~
8 Installation Instructions for Control Center VR 65
5.3 Installing the VR 65 with a NTC
Electrical installation 5
Note!
To comply with the approvals, the boiler must be Vaillant ecoTEC if the cylinder NTC solution is used.
Before installing the NTC, first remove the cylinder con­trol with two capillary tubes for the cylinder thermostat and thermal cut out. The cylinder control is be fitted in one of two ways (A or B).
• Disconnect the wires (1) from the terminal block of the cylinder control (a).
Version A, fig. 5.4: Unclip the cylinder control (a) and remove it from the terminal box (see 2, fig. 5.4).
(Version B, fig. 5.5:
To remove the cylinder control (a) release the clips with two screw drivers as shown in fig. 5.5)
• Remove the capillary tubes (3) of the thermostat and the thermal cutout from the dry pocket of the uniSTOR. Ensure that the capillary tube of the immersion sensor is not removed.
• Now the NTC can be pushed into the free dry pocket of the cylinder as shown in fig. 5.6.
• The NTC is wired into the VR 65 as shown in fig. 5.2 or fig. 5.3.
b
1
a
3
Fig. 5.5 Removing the cylinder control (Version B)
Legende:
a Cylinder control b Immersion Heater Control
b
1
a
2 3
Fig. 5.4 Removing the cylinder control (Version A)
Legende:
a Cylinder control b Immersion Heater Control
Fig. 5.6 Installing the NTC
9Installation Instructions for Control Center VR 65
6 Start-up 7 Troubleshooting
6 Start-up
The initial start-up of the VR 65 is carried out together with the initial start-up of the heating appliance.
Note!
In the factory settings, the heating appliance operation is set to warm water priority.
Note!
To comply with the approvals, the boiler must be Vaillant ecoTEC if the cylinder NTC solution is used.
If a parallel operation for central heating and charging of the DHW cylinder is required, change this setting on the boiler in the following way.
• Press the “i” and “+” keys simultaneously. The display shows “d.00”.
• Use the “+” or “-” keys to scroll to the diagnostic number d.97 to enter the second diagnostic level.
• Press the “i” key. The display shows the relevant diagnostic information.
• Use the “+” or “-” keys to change the value (display flashes) to 17 (password).
• Save the new value by pressing and holding down the “i” key for approx. 5 seconds until the display no long­er flashes.
• Use the ‚+‘ and ‚-‘ keys to scroll to the diagnostic point d.70
• Press the “i” key. Change the setting using the ‚+‘ and ‚-‘ keys.
• Save the new value by holding down the “i” key for approx. 5 seconds until the display no longer flashes.
You can end the diagnostic mode as follows:
• Press the “i” and “+” keys simultaneously.
The following settings are possible:
Display Meaning
0 Warm water priority
- The 3-port valve is in the heating or hot water position depending on the operating mode.
- With 2-port valves, either the DHW valve or the CH valve is open, both valves are closed on standby.
1 Enable mid position
- The 3-port valve is in the mid position for simultaneous heating and hot water request, or in the heating or hot water position, depending on the operating mode.
- With 2-port valves, both valves are open during simultaneous heating and hot water request. Otherwise, only one valve is always open and both valves are closed on standby.
2 Only heating mode (only for test
operation!)
- Only the CH valve is activated.
Table 6.1 Heating appliance settings
Factory setting
x
7 Troubleshooting
The Control Center VR 65 has a green Operating LED, which can be monitored when the housing cover is removed (see fig. 4.2).
Problem Cause Remedy
LED permanently off
LED permanently onNo error - Normal operation
No 230 V supply available or fuse in appliance defective
- Check whether the mains voltage cable is connected correctly.
- Check the mains fuse for the 230 V supply and reconnect the mains supply.
- Replace the mains fuse in the VR 65 (4 A slow).
10 Installation Instructions for Control Center VR 65
LED flashes quickly Short circuit of the
connected tempera­ture sensor (NTC) in the DHW cylinder
LED flashes slowly Communication error
in eBUS protocol to the boiler
Table 7.1 Troubleshooting
- Check the cable of the temperature sensor (NTC) for damage.
- Replace the temper­ature sensor (NTC) in the DHW cylinder.
- Inform the Vaillant customer service.
8 Factory customer service
To ensure regular servicing, it is strongly recommended that arrangements are made for a Maintenance Agreement. Please contact Vaillant Service Solutions (0870 6060 777) for further details.
9 Technical data
Feature Unit VR 65
Operating voltage V 230 Power consumption VA 2 Contact load of output relays (max.) cos ϕ > 0.6
Contact voltage for DHW cylinder thermostat V 230 Operating voltage of temperature sensor (NTC) V 5 Minimum cross-section of the temperature sen-
sor cables, eBUS cables Minimum cross-section of the power supply
cable (rigid cable, NYM) Maximum ambient temperature °C 70
Housing dimensions
Height mm 174 Width mm 272
Depth mm 52 Level of protection IP 20 Protection class II
Table 9.1 Technical data
A2
2
mm
mm
0.75
2
1.5
Factory customer service 8
Technical data 9
11Installation Instructions for Control Center VR 65
00 2000 7476_02 GB 11 2005