Potentially dangerous situation for the product
and the environment.
Note!
Useful information and indications.
1.2 Correct Use of the Unit
This unit has been designed and manufactured for the
sole purpose of comfort cooling and heating occupied
residential and commercial premises. The use thereof
for other domestic or industrial purposes shall be the
exclusive responsibility of the persons specifying,
installing or using them in that way.
Prior to handling, installing, start up, using or
performing maintenance on the unit, the persons
assigned to perform these tasks should be familiar with
all the instructions and recommendations set forth in
the unit's installation manual.
Note!
Keep the manuals throughout the service life of
the unit.
Note!
The relevant personnel performing any service of
maintenance operations involving the handling of
the refrigerant fluid must have the necessary
certification to comply with all local and
international regulations.
2 Extreme Operating Conditions
This unit has been designed to operate within the range
of temperatures indicated on Figure 2.1. Ensure that
these ranges are not exceeded.
COOLING
Outdoor
Indoor
Fig. 2.1 Operating ranges of the unit.
Legend
D.B. Temperature measured by dry bulb
45ºC D.B.
0ºC D.B.
30ºC D.B.
17ºC D.B.
Note!
The working capacity of the unit changes
depending on the working temperature range of
the outdoor unit.
HEATING
24ºC D.B.
-15ºC D.B.
30ºC D.B.
17ºC D.B.
Note!
3 Identification of the Unit
The information relating to this unit is divided between
two manuals: installation manual and user manual.
This manual is valid for the Split system series. In order
to know the specific model of your unit please refer to
Note!
This equipment contains R-410A refrigerant. Do
not vent R-410A into atmosphere: R-410A, is a
the unit nameplates.
The nameplates are located on the outdoor and indoor
units.
fluorinated greenhouse gas, covered by Kyoto
Protocol, with a Global Warming Potential (GWP)
= 1975.
Note!
The refrigerant fluid contained in this
equipment must be properly recovered for
recycling, reclamation or destruction before
the final disposal of the equipment.
Split Type Installation Manual3EN
Split Type Installation Manual4
4 Declaration of Conformity
5 Description of the Unit
4 Declaration of Conformity
The manufacturer declares that this unit has been
designed and constructed in compliance with the
standard in force with regard to obtaining the CE
Marking.
5 Description of the Unit
This unit is comprised of the following elements:
- Indoor unit.
- Outdoor unit.
- Remote controller.
- Connections and accessories.
Figure 5.1 shows the unit components.
5.1 Indoor Unit
The indoor unit heats and cools air to be supplied to the
room to be conditioned.
The dimensions and weights of the indoor unit are
shown on Figure 5.2 and Table 5.1, depending on the
model (please consult the model nameplate).
The dimensions are given in mm.
Fig. 5.2 Dimensions of the indoor unit.
Legend
H Height
L Length
D Depth
Fig. 5.1 Unit components.
Legend
1 Indoor Unit
2 Outdoor Unit
3 Remote controller
4 Interconnecting pipework (not supplied)
5 Condensed water drainage pipe
MODELHLDkg
VAI 2-025 WNI
AI 2-035 WNI
V
able 5.1 Dimensions and weights of the indoor unit.
T
2657902008,5
2657902008,5
5.2 Outdoor Unit
The outdoor unit ensures that the absorbed heat is
released to the outside from the room during operation
in cooling mode and that the heat introduced into the
room during operation in heat pump mode is taken from
the outside.
The dimensions and weights of the outdoor unit are
shown on Figure 5.3 and Table 5.2, depending on the
model (please consult the model nameplate).
The dimensions are given in mm.
Description of the Unit 5
Fig. 5.3 Dimensions of the outdoor unit.
Legend
H Height
L Length
D Depth
A Length of valves
B Distance between valves
C Distance from the second valve to the floor
F Distance from the third valve to the floor
I Distance between fixing holes
J Distance between fixing supports