
DE, EN, ES, HR, IT, NL, TR, PL

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Proper Use of the Unit
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
3 Identification of the Unit
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Qualification of the Installation Personnel
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
Methods for the Correct Discharge of the
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
Making Holes for the Pipes
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation of the Cassette Indoor Unit
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
4 Installation of the Condensed Water Pipe
Installation of the Coolant Pipes
Handling the Coolant Pipes
. . . . . . . . . . . . . . . . . .
Laying of the Coolant Pipes
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11 Installation of the Duct Indoor Unit
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
11.3 Installation of the indoor unit
. . . . . . . . . . . . . . . . .
11.4 Installation of the drainage pipe
. . . . . . . . . . . . . . .
11.5 Hanging the indoor unit
. . . . . . . . . . . . . . . . . . . . . .
Installation of the Outdoor Unit
12.1 Selecting the Assembly Location
. . . . . . . . . . . . .
12.2 Planning the Coolant Return
. . . . . . . . . . . . . . . . .
12.3 Connection of the Coolant Pipes
. . . . . . . . . . . . .
12.4 Connection of the Pipe for the Drainage of the
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
13.3 Electric Connection of the Indoor Unit
13.4 Electric Characteristics
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
14.1 Address setting for Cassette and V6 Wall Indoors
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14.4 Address setting for Wall Indoors V 10 by using the
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2 Proper Use of the Unit
the unit's installation manual.
Note!
The relevant personnel performing any service of
maintenance operations involving the handling of
the refrigerant fluid must have the necessary
certification to comply with all local and
international regulations.
2 Extreme Operating Conditions
these ranges are not exceeded.
3 Identification of the Unit
to know the specific model of your unit please refer to
Your Safety 1
Extreme operating conditions 2
Identification of the Unit 3
Note!
This equipment contains R-410A refrigerant. Do
not vent R-410A into atmosphere: R-410A, is a
fluorinated greenhouse gas, covered by Kyoto
Protocol, with a Global Warming Potential (GWP)
= 1975.
Note!
The refrigerant fluid contained in this
equipment must be properly recovered for
recycling, reclamation or destruction before
the final disposal of the equipment.

3 Remote controller and holder
4 Connections and channels
Table 5.1 Dimensions and weights of the indoor unit.
4 Declaration of Conformity
5 Description of the Unit

Table 5.2 Dimensions and Weights of the Indoor Unit (plant).
Table 5.3 Dimensions of the Indoor Unit (lateral).
Table 5.4 Dimensions and Weights of the Indoor Unit.
Description of the Unit 5

Table 5.5 Dimensions and weights of the outdoor unit.
5 Description of the Unit

Table 5.6 Accessories supplied with the unit.
Table 5.7 Accessories supplied with the unit.
Table 5.8 Accessories supplied with the unit.
Description of the Unit 5

Table 5.9 Technical specifications
Table 5.10 Technical specifications
these specifications without prior notice.
5 Description of the Unit

Danger of injury and physical damage!
fall and injure anyone within the immediate
Danger of injury and physical damage!
Danger of injury and physical damage!
Danger of injury and physical damage!
the Regulations and Standards for refrigerator,
electrical and mechanical installation prevailing
the gas pipe, water pipe, lightning conductor or
Transport 6
Unpacking 7
Installation 8

3 Pipe for draining the condensed water
3 Pipe for draining the condensed water

3 Pipe for draining the condensed water
Table 8.1 Indoor unit minimum assembly distances.
Table 8.2 Indoor unit minimum assembly distances.

Place the assembly plate in the assembly location,
take the requirements described in this section
Using an external pump for condensed water, carrying
the condensed water to the outside or to the house
tilt, the condensed water pipe must also have a
tilt from the indoor unit.
9 Installation of the Wall Mounted Indoor Unit

wear in the coolant pipes.
take the following points into consideration:
which are thermally insulated as a Vaillant
Do not bend the pipes where possible. When bending
them, keep the radius as wide as possible to minimise
Carefully squeeze the flaring connector, centring the
thread and cause a reduction in the water tightness in
wear of materials due to dripping water.
Installation of the Wall Mounted Indoor Unit 9

the distance of its free end from the floor is at least 5
3 Securing with adhesive tape
9 Installation of the Wall Mounted Indoor Unit

wear in the coolant pipes.
the mounting plate and the unit (see Figure 9.9).
1 Heat-resistant material
Securely hang the indoor unit body onto the upper
Installation of the Wall Mounted Indoor Unit 9

Danger of physical damage!
will provide you with more space.
10.2 Selecting the Assembly Location
Danger of personal injury and material damage
10 Installation of the Cassette Indoor Unit

10.3 Recommended Installation Process
10.4 Installation of the Condensed Water Pipe
10.4.1 Handling the Condensed Water Pipe
wear of materials due to dripping water.
- Ensure that air circulates through the
that the water can be freely released.
through the indoor unit body.
- Mount the pipe without bending it in order to
- If the water pipe is channelled outdoors,
- If the condensed water pipe is installed in a
- Avoid installing the condensed water pipe with
- Avoid installing the condensed water pipe with
- Avoid installing the condensed water pipe with
- Install the condensed water pipe in such a way
that the distance of its free end from the floor
- Install the condensed water pipe in such a way
that its free end is kept away from unpleasant
odours to ensure that they do not penetrate
the room.
10.4.2 Laying of the Condensed Water Pipe
1 Pump flange (jacketing)
Installation of the Cassette Indoor Unit 10

10.5 Installation of the Coolant pipes
10.5.1 Handling the Coolant Pipes
wear in the coolant pipes.
take the following points into consideration:
they cannot become displaced. Ensure that
they will not cause traction in the joins.
which are thermally insulated as a Vaillant
10.5.2 Laying of the Coolant Pipes
Cut the pipes, leaving enough extra piping hanging
the corresponding insulation material used for cooling.
10 Installation of the Cassette Indoor Unit

10.6 Installation of the Fresh Air
Table 10.1 Models with lines available for renewing fresh air.
1 Flange on the fresh air line
10.7 Indoor Unit Assembly in the Ceiling
the indicated measurements.
Installation of the Cassette Indoor Unit 10

10.9 Installation of the decorative panel
that it is flush with the lower part of the false ceiling
10 Installation of the Cassette Indoor Unit

the air which may flow towards the indoor unit. The
the electromagnetic waves will have a direct
to the pipes and cables and to maintenance.
Attachment of the indoor unit
transmission of vibration and noise, installing, if
Installation of the drainage pipe
Installation of the Duct type Indoor Unit 11

Selecting the Assembly Location
Danger of personal injury and material damage
or easily combustible substances and free from
Danger of personal injury and material damage
weight of the outdoor unit and allow it to fit in a
3 Pipe for draining the condensed water
Top separation in relation to the ceiling (minimum 5 cm)
Side separation connections side (minimum 15 cm)
12 Installation of the Outdoor Unit

12.2 Planning the Coolant Return
to the compressor the following is recommended:
to further assist the oil return.
12.3 Connection of the Coolant Pipes
wear in the coolant pipes.
12.4 Connection of the Pipe for the Drainage of the
the water into a collection tray located at the bottom
Installation of the Outdoor Unit 12

distance of at least 3 mm between contacts
the electric power supply wiring.
13.2 Remark with regard to Directive 89/336/EEC
the start up of the compressor (technical process), the
the distribution with low impedance. Normally the
to power details of the air conditioner consult

Shield from the shield wire

13.4 Electric Characteristics
Table 13.1 Electric Characteristics.
Thermal-magnetic circuit breaker, type
Thermal-magnetic circuit breaker, type

Before setting up the communication between
units, the installation process must have fully
completed, both the refrigerant and electrical
parts, and the valve keys must be open.
Otherwise the installation process will report an
error and will not function.
1 Emergency operation/operation test switch
1 Emergency operation/operation test switch
14 Communication between the Indoor and Outdoor Units
Address setting for Cassette and V6 Wall
you press it, the setup will vary:
If you wish to know the direction configured in
the Indoor unit, press the emergency button for
20 seconds and you will hear 5 beeps.
Following, the LED TIMER will flicker as many
times as the direction configures in the unit.
Each unit must have the following setup:
With the indoor unit connected to valve A (see
installation layout), the direction should be "1"
With the indoor unit connected to valve B (see
installation layout), the direction should be "2"
With the indoor unit connected to valve C (see
installation layout), the direction should be "3"
With the indoor unit connected to valve D (see
installation layout), the direction should be "4"

3 Remote controller and holder
4 Connections and channels
14.2 Address setting for Cassette and Duct Indoor
Duct type of indoor units can only set the
address by using the dip switch.
Make sure before doing the address setting in
the PCB switches that the system is powered off.
1) Please note that the address must be set as the follo-
2) Address setting process when using the dip switches
2.1 The dip switches SW01 and SW03 are on the Indo-
2.2 Before conducting the address setting process the
2.3 Access the indoor unit PCB
2.4 Change the position of DIP 7 of SW01 from OFF to
address setting will not work.
In order to set the corresponding address from 1 to
4, please change the DIP 6 to 8 from SW03, following
Address setting for Wall units when using the
the PCB switches that the system is powered off.
1) Please note that the address must be set as the follo-
2) Address setting process when using the dip
2.1 The dip switches SW01 and SW02 are on the Indoor unit
2.2 Before conducting the address setting process the
Communication between the Indoor and Outdoor Units 14

2.3 Access the indoor unit PCB
2.4 Change the position of DIP 7 of SW01 from OFF to
2.5 In order to set the corresponding address from 1 to
4, please change the DIP 6 to 8 from SW02, following
14.4 Address setting for Wall Indoors V 10 by using
the remote and the LCD display board
you press it, the setup will vary:
14 Communication between the Indoor and Outdoor Units

EN
Preparation for Use 15
valve in the suction hose.
15.2 Purging the Installation
15.2 Purging the installation.
valve in the suction hose.
the low valve on the combined meter and the gas faucet.
15 minutes (depending on the size of the installation)

the vacuum pump and close the vacuum valve.
15 minutes have elapsed: the pressure should not rise.
them (check the joints, joins, the indoor and outdoor
closed: checking for leaks.
2 Two and three-way valve covers

troller be disconnected, faulty PCB
1. Please contact the installer or distributors
when trouble happens to repair it

troller be disconnected, faulty PCB

temperature too high, or IPM input voltage
too low,or faulty SPDU(or ISPM).

when trouble happens to repair it
when trouble happens to repair it

ture too high, or IPM input voltage too low, or faul-