
Split Type Installation Manual
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Correct Use of the Unit
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
3 Identification of the Unit
. . . . . . . . . . . . . . . . . .
4 Declaration of Conformity
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Qualification of the Installation Personnel
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
9 Installation of the Indoor Unit
. . . . . . . . . . . . .
9.1 Selecting the Indoor Unit Location
. . . . . . . . . . . . .
9.2 Fixing the Assembly Plate
. . . . . . . . . . . . . . . . . . . .
9.3 Installation of the Pipe Work
. . . . . . . . . . . . . . . . .
Correct Removal of the Condensate Water
9.3.2 Handling the Refrigerant Pipes
. . . . . . . . . . . . . . .
Making Holes for the Pipes
. . . . . . . . . . . . . . . . . . .
9.3.5 Correct installation of the refrigerant pipe work
9.3.6 Installation of the Indoor Unit Body
10 Installation of the Outdoor Unit
10.1 Selecting the Assembly Location
. . . . . . . . . . . . . .
10.2 Planning the Refrigerant Return
. . . . . . . . . . . . . .
10.3 Connection of the Refrigerant Pipe Work
10.4 Connection of the Pipe for the Removal of
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
11.3 Electric Connection to the Indoor Unit
11.4 Electric Connection to the Outdoor Unit
11.5 Electrical Characteristics
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
12.2 Evacuating the Installation
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .

Split Type Installation Manual
1.2 Correct Use of the Unit
sole purpose of comfort cooling and heating occupied
the unit's installation manual.
The information relating to this unit is divided between
two manuals: installation manual and user manual.
Your Safety 1
Extreme operating conditions 2
Identification of the Unit 3
Note!
The relevant personnel performing any service of
maintenance operations involving the handling of
the refrigerant fluid must have the necessary
certification to comply with all local and
international regulations.
2 Extreme Operating Conditions
these ranges are not exceeded.
3 Identification of the Unit
to know the specific model of your unit please refer to
Note!
This equipment contains R-410A refrigerant. Do
not vent R-410A into atmosphere: R-410A, is a
fluorinated greenhouse gas, covered by Kyoto
Protocol, with a Global Warming Potential (GWP)
= 1975.
Note!
The refrigerant fluid contained in this
equipment must be properly recovered for
recycling, reclamation or destruction before
the final disposal of the equipment.

Split Type Installation Manual
standard in force with regard to obtaining the CE
4 Interconnecting pipework (not supplied)
shown on Figure 5.2 and Table 5.1, depending on the
Table 5.1 Dimensions and weights of the indoor unit.
4 Declaration of Conformity
5 Description of the Unit

Split Type Installation Manual
transferred and released to the outside from the room
shown on Figure 5.3 and Table 5.2, depending on the
J Distance between fixing supports
Table 5.2 Dimensions and weights of the outdoor unit.
Description of the Unit 5

Split Type Installation Manual
there is a line of sight to the indoor unit.
Table 5.3 Accessories supplied with the unit.
5 Description of the Unit

Split Type Installation Manual
Additional charge per metre
Table 5.4 Technical specifications.
these specifications without prior notice.
Description of the Unit 5

Split Type Installation Manual
Danger of injury and physical damage!
fall and injure anyone within the immediate
correctly (consult the respective user
fixings in the mounting points provided.
equipment (helmet, gloves, safety boots and
Danger of injury and physical damage!
correctly (consult the respective user
equipment (helmet, gloves, safety boots and
standards in force. Do not dispose of packaging
Danger of injury and physical damage!
capacity for the unit weight.
equipment (helmet, gloves, safety boots and
Danger of injury and physical damage!
The unit should be installed in accordance with
the Regulations and Standards for refrigeration,
electrical and mechanical installation pertaining
to the country in which the installation is being
6 Transport
7 Unpacking
8 Installation

Split Type Installation Manual
3 Condensate connection for outdoor unit
A Clearance to the front of the internal unit (minimum 10 cm)
9.1 Selecting the Indoor Unit Location
9.2 Fixing the Mounting Plate
Installation 8
Installation of the indoor unit 9

Split Type Installation Manual
9.3 Installation of the Pipe Work
9.3.1 Correct Removal of Condensate Water
take the recommendations described in this
to cover the flexible pipework.
the condensed water, carrying the condensed water to
9.3.2 Handling the Refrigerant Pipes
specific class ‘O’ closed cell insulation.
subsequent refrigerant leaks.
there is no strain on the pipe joints.
thread and may allow water ingress into the
9 Installation of the indoor unit

Split Type Installation Manual
9.3.3 Correct Installation of the Condensate Pipe
water leaks and blockages from unit and
Minimum distance from the floor.
Installation of the indoor unit 9

Split Type Installation Manual
9.3.4 Making Holes for the Pipes
since the indoor unit body has knock outs which can
the most convenient one for the desired outlet
3 Securing with adhesive tape
9.3.5 Correct Installation of Indoor Unit Refrigerant
to go through the wall width. If this is not the case
the condensed water hose to the installation drain.
separately. To do so, cover any possible cuts with
the corresponding insulation material suitable for air
9 Installation of the indoor unit

Split Type Installation Manual
1 Heat-resistant material
3 Insulated refrigeration pipes
the connections at the rear of the unit first before
9.3.6 Installation of the Indoor Unit Body
supports properly, repeat this process.
10.1 Selecting the Assembly Location
for subsequent maintenance and repair
Danger of personal injury and material damage
or liquids or easily combustible substances and
free from thick dust formation.
Danger of personal injury and material damage
and can withstand the weight of the outdoor
Installation of the indoor unit 9
Installation of the outdoor unit 10

Split Type Installation Manual
10.2 Planning the Refrigerant Return
the outdoor unit compressor. To assist the return of the
10.3 Connection of the Refrigerant Pipes
separately. To do so, cover any joints in the insulation
10.4 Connection of the Condensate Drain Pipe to
90º to fix it (see Figure 10.1).
3 Drainage hose (not supplied)
10 Installation of the outdoor unit

Split Type Installation Manual
All electrical works should be completed by an
electrician or a similarly qualified person.
two or three pole isolating switch
the model, (single phase or three-phase) with a
distance of at least 3 mm between contacts
electrical sockets only use with a suitable
adaptor or replace the plug with a UK style one
or remove and connect directly into a suitable
Installation of the outdoor unit 10
Electric Wiring 11

Split Type Installation Manual
11.2 Remark with regard to Directive 2004/108/CE
the start up of the compressor (technical process), the
supply connected directly to the distribution board.
Ensure the completed electrical installation has low
11.3 Electric Connection to the Indoor Unit

Split Type Installation Manual
V 7-025 NW, V 7-035 NW and
1 Terminal connections for the indoor unit
2 Terminal connections for the outdoor unit
11.4 Electric Connection to the Outdoor Unit
terminal leaving no exposed conductor before
tightening the screws to clamp the cable.
the unused cable wires using electrical tape and

Split Type Installation Manual
11.5 Electrical Characteristics
Thermal-magnetic circuit breaker, type D (A)
Table 11.1 Electrical Characteristics.

Split Type Installation Manual
3 Service manifold (suitable for R410a refrigerant)
testing should only be undertaken by competent
the gas line stop valve of the outdoor unit.
the service valve on the outdoor unit as this will release
the pre-charged refrigerant from the outdoor unit.
valves on the service manifold and remove the
test has been successfully completed.
tests are performed and the results correctly logged into
the maintenance record of the machine. The leakage
test must be done with the following frequency:
12.2 Evacuating the Installation
12.2 Evacuating the installation
3 Service manifold (suitable for R410a refrigerant)
the gas line of the outdoor unit.
15 minutes (depending on the size of the installation)

Split Type Installation Manual
should indicate -0.1 MPa (-76 cmHg - >3 Torr). If the
service manifold gauge is not capable of measuring to
these pressures a separate Torr vacuum gauge should
open and vacuum pump operational.
15 minutes have elapsed: the pressure should not rise.
them (Check all joints and connections to the service
satisfactory evacuation of the installation has
closed and the vacuum pump switched off: checking
2 Allen key to open valves
the allen key anticlockwise as far as it will go.
2 Three-way service valve
3 Allen key (not supplied) to open valves

Split Type Installation Manual
2 Two and three-way valve covers

Split Type Installation Manual
1) Room-temperature sensor may be faulty
2) Indoor PCB may be faulty
1) Heat-exchange sensor may be faulty
2) Indoor PCB may be faulty
1) Defrosting temperature sensor may be faulty
2) Outdoor PCB may be faulty
1) Exhaust temperature sensor may be faulty
2) Outdoor PCB may be faulty
1) Ambient temperature sensor may be faulty
2) Outdoor PCB may be faulty
1) Suction temperature sensor may be faulty
2) Outdoor PCB may be faulty
1) The outdoor mainboard may be damp and needs drying
2) The indoor mainboard may be damp and needs drying
3) The linking cable between the indoor and outdoor units
4) The indoor PCB may be faulty
The wiring of compressor is incorrect or the connection is
2) The SPDU may be faulty
3) Compressor may be damaged.
1) The refrigerant may have been leaked during installation,
2) Exhaust temperature sensor may be faulty
3) The outdoor mainboard is damaged and needs be

Split Type Installation Manual
1) The SPDU may be faulty
2) The power supply is incorrect
3) The system may have been over or under charged with
1) IPM Module may be overheating
2) IPM Module may be damaged
3) Compressor may be damaged
1) Check whether the indoor unit has poor airflow due to
2) The system is over charged with refrigerant.
3) Indoor pipe sensor may be faulty.
1) The indoor PCB might be damaged
2) The outdoor PCB might be damaged
1) Check whether Terminal CN2 on the indoor mainboard is
2) The indoor mainboard may be faulty
3) The motor of the indoor unit may be faulty
1) Check whether terminal CN2 on the outdoor mainboard
2) The mainboard of the indoor unit may be faulty
3) The motor of the Outdoor unit may be faulty
1) The connection between IPM and the outdoor PCB may
2)The mainboard of the outdoor unit may be damaged
3)The IPM module may be damaged
1) The IPM module may be damaged
2) Check power supply is correct
3) The transformer of outdoor mainboard is damage
4) The rectifying bridge or IPM module may be faulty