Vaillant ecoMAX 635 Instructions For Installation And Servicing

For the installer
ecoMAX 635
GB
Instructions for installation and servicing
ecoMAX
Wall hung room sealed fan assisted condensing boilers
2
Table of contents
Instructions for installation and servicing ecoMAX2
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 EC designation . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Boiler specification . . . . . . . . . . . . . . . . . . . 5
2.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3 Boiler connections . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 Functional diagram . . . . . . . . . . . . . . . . . . . . . . 6
2.5 Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.6 Identification plate . . . . . . . . . . . . . . . . . . . . . . . 7
3 General requirements . . . . . . . . . . . . . . . . . 8
3.1 Preliminary remarks . . . . . . . . . . . . . . . . . . . . . 8
3.2 Related documents . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Contents included with boiler . . . . . . . . . . . . . . 8
3.4 Boiler location . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.5 Gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.6 Flue system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.7 Flue termination . . . . . . . . . . . . . . . . . . . . . . . . 9
3.8 Air supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.8.1 Cupboard or compartment ventilation . . . . . . 10
3.9 Electrical supply . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.10 Guide to system requirements . . . . . . . . . . . . . 10
3.10.1 Water circulation system . . . . . . . . . . . . . . . . . . 10
3.10.2 Filling and make up . . . . . . . . . . . . . . . . . . . . . . 11
3.10.3 Pressure relief valve . . . . . . . . . . . . . . . . . . . . . 11
3.10.4 Pressure gauge . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.10.5 Expansion vessel . . . . . . . . . . . . . . . . . . . . . . . . 11
3.11 Pump specifications . . . . . . . . . . . . . . . . . . . . . 11
3.11.1 Circulating pump . . . . . . . . . . . . . . . . . . . . . . . . 11
3.11.2 System by–pass . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.11.3 Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.12 Condensate trap . . . . . . . . . . . . . . . . . . . . . . . . . 11
4 Boiler installation sequence . . . . . . . . . . . . 12
4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1.1 Select position of boiler . . . . . . . . . . . . . . . . . . 12
4.1.2 Unpack the boiler . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1.3 Using boiler template . . . . . . . . . . . . . . . . . . . . 12
4.2 Rear flue exit . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.3 Other flue options . . . . . . . . . . . . . . . . . . . . . . . 12
4.4 Fitting the boiler hanging bracket . . . . . . . . . . 13
4.5 Install the flue system . . . . . . . . . . . . . . . . . . . . 13
4.6 Fitting the boiler . . . . . . . . . . . . . . . . . . . . . . . . 13
4.7 Removing the front case . . . . . . . . . . . . . . . . . . 13
4.8 Gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.9 Central heating flow and return pipework . . . 14
4.10 Pressure Relief Valve . . . . . . . . . . . . . . . . . . . . . 14
4.11 Condensate drain . . . . . . . . . . . . . . . . . . . . . . . . 15
4.12 Connection to a uniSTOR cylinder . . . . . . . . . 16
4.13 Connect the flue system to the boiler . . . . . . . 16
4.14 Electrical installation . . . . . . . . . . . . . . . . . . . . . 16
4.14.1 General requirements . . . . . . . . . . . . . . . . . . . . 16
4.14.2 Connection to the main supply . . . . . . . . . . . . 16
4.14.3 Electronic board layout . . . . . . . . . . . . . . . . . . . 17
4.14.4 Connection details for programmable
thermostats . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.15 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.15.1 External electrical controls . . . . . . . . . . . . . . . . 19
4.15.2 Connection of external electrical controls . . . 19
4.15.3 Connection details using an external
wiring centre . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.16 Thermostatic radiator valves . . . . . . . . . . . . . . 20
4.17 Frost protection . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.18 Circulating pump . . . . . . . . . . . . . . . . . . . . . . . . 20
4.19 Anti–cycling ‘economiser’ control . . . . . . . . . . 20
4.20 Automatic pump spin control (APS) . . . . . . . . 20
5 Commissioning part I . . . . . . . . . . . . . . . . . 23
5.1 Preliminary electrical checks . . . . . . . . . . . . . . 23
5.2 Gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.3 Initial system flush (”Cold”) . . . . . . . . . . . . . . . 23
5.4 Filling the heating system . . . . . . . . . . . . . . . . . 23
5.5 Initial system flush (”Cold”) . . . . . . . . . . . . . . . 23
5.6 Filling condensate trap . . . . . . . . . . . . . . . . . . . 23
5.7 Adjusting pump speed . . . . . . . . . . . . . . . . . . . . 23
5.8 Checking the gas supply settings . . . . . . . . . . . 24
5.8.1 Factory–adjusted gas settings . . . . . . . . . . . . . 24
5.8.2 Gas inlet working pressure . . . . . . . . . . . . . . . . 24
5.8.3 Check gas rate . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.9 Refitting the case . . . . . . . . . . . . . . . . . . . . . . . . 25
5.10 Adjusting the central heating output
(range rating) . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6 Functional checks (commissioning part II) . 26
6.1 Functional checks . . . . . . . . . . . . . . . . . . . . . . . 26
6.1.1 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.1.2 Heating system . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.1.3 Final system flush (”Hot”) . . . . . . . . . . . . . . . . . 27
6.1.4 Handing over to the user . . . . . . . . . . . . . . . . . 27
7 Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.1 Inspection and maintenance . . . . . . . . . . . . . . . 28
7.2 Initial inspection . . . . . . . . . . . . . . . . . . . . . . . . 28
7.2.1 Removing the compact thermal module . . . . . 28
7.2.2 Inspect main heat exchanger . . . . . . . . . . . . . . 29
7.2.3 Inspect burner . . . . . . . . . . . . . . . . . . . . . . . . . . 29
7.2.4 Refitting the compact thermal module . . . . . . 30
7.2.5 Cleaning the condensate trap . . . . . . . . . . . . . 30
7.2.6 Check expansion vessel . . . . . . . . . . . . . . . . . . . 30
7.3 Recommissioning the boiler . . . . . . . . . . . . . . . 30
7.4 Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
8 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . 32
8.1 Logical fault finding procedure . . . . . . . . . . . . 32
8.1.1 Status mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
8.1.2 Diagnosis mode . . . . . . . . . . . . . . . . . . . . . . . . . 32
8.1.3 Fault codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.1.4 Fault memory . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8.2 Test programs . . . . . . . . . . . . . . . . . . . . . . . . . . 34
9 Parts replacement . . . . . . . . . . . . . . . . . . . 36
9.1 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . 36
9.1.1 Initial preparation . . . . . . . . . . . . . . . . . . . . . . . 36
9.1.2 Removal of burner assembly . . . . . . . . . . . . . . 36
9.2 Replacement of burner . . . . . . . . . . . . . . . . . . . 36
3
Table of contents
Instructions for installation and servicing ecoMAX 3
9.3 Replacement of fan . . . . . . . . . . . . . . . . . . . . . . 36
9.4 Replacement of gas valve . . . . . . . . . . . . . . . . . 36
9.5 Replacement of central heating
expansion vessel . . . . . . . . . . . . . . . . . . . . . . . . 37
9.6 Replacement of main heat exchanger . . . . . . . 38
9.7 Replacement of the electronic control board . 38
9.8 Check CO
2
content and adjust if necessary
(air–ratio adjustment) . . . . . . . . . . . . . . . . . . . . 38
10 Recycling and eventual scrapping . . . . . . . . 40
10.1 The appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
10.2 Packing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Benchmark gas boiler commissioning checklist . . 41
4
1 Introduction
Instructions for installation and servicing ecoMAX4
1 Introduction
1.1 Introduction
Note! This boiler must be installed and serviced by a competent person in accordance with the Gas Safety (Installation and Use) Regulations 1998. In the UK ‘CORGI’ registered installers underta­ke the work to a safe and satisfactory standard.
ecoMAX 635
The ecoMAX 635 is a fully automatic, wall mounted, room sealed condensing (high efficiency) system boiler for central heating and domestic hot water (where a separate indirect hot water storage cylinder is also incorporated in the system). The ecoMAX 635 boiler is available in Natural Gas.
1.2 General Notes
The boiler has been designed for use with a sealed cen­tral heating system, and comes fully tested and assemb­led with a built in circulating pump and expansion vessel. The boiler is easily sited on any internal wall and can be installed with either a horizontal or vertical RSF (room sealed fan assisted) flue. The boiler uses a standard flue system (125 mm outside diameter) which allows flue lengths up to 21 m. Flue extensions and additional bends and elbows are availa­ble for the flue system to increase the siting flexibility. If desired, an inhibitor may be used in the system. Guidance on the use of inhibitors is contained in these instructions. All boilers have a built in diagnostic system which indica­tes the operational status of the boiler. This feature pro­vides key information to aid commissioning and fault fin­ding. The data badge is fitted to the underside of the boiler. See text of General Requirements for installation requirements or notes.
1.3 EC designation
ecoMAX boilers carry the ‘CE’ Mark. This demonstrates that the boilers fulfil the essential requirements of the Gas Appliance Directive (90/396/EEC) and the Gas Appliance (Safety) Regulations 1992. The ‘CE’ Mark also demonstrates that the boilers comply with the requirements of the Electromagnetic Compatibility Directive (89/336/EEC), the Low Voltage Directive (72/23/EEC), the Boiler Efficiency Directive (92/42/EEC) and the Boiler (Efficiency) Regulations 1993.
Note! Vaillant Ltd. support the Benchmark initiative. In the installation manual you will find the Benchmark gas boiler commissioning checklist. It is very important that this is completed correctly at the time of installation and com­missioning.
5
Boiler Specification 2
Instructions for installation and servicing ecoMAX 5
2 Boiler specification
2.1 Technical data
ecoMAX 635 Units
Maximum CH heat input (G 20) (net) 34.9 kW
Maximum CH heat input (G 31) (net) 34.9 kW
CH heat output range
80 °C flow/60 °C return 10.5 - 34.9 kW
50 °C flow/30 °C return 11.0 - 36.7 kW
SEDBUK A Band
SAP Seasonal Efficiency 91.2 %
Inlet gas working pressure required
(natural gas) 20 mbar
Inlet gas working pressure required
(Propane) 37 mbar
Gas supply (G20) Gross CV (s.t.) 37.8 MJ/m
3
Gas supply (G31) Gross CV (s.t.) 95.65 MJ/m
3
Gas rate (natural gas) max. 3.7 m3/h
Gas rate (Propane) max. 2.7 kg/h
CH temperature flow range 30 - 85 °C
Minimum CH water flow (for 20 °C rise) 1480 l/h
Pump pressure available 0.25 bar
10l expansion vessel pre–charge pressure 0.75 bar
Maximum CH system pressure 2.5 bar
Connections heating flow/return 22 mm
Gas inlet 15 mm
Pressure relief discharge pipework (min.) 15 mm
Condensate drain (min. internal drain) 19 mm
Weight 41 kg
Primary water content 2,2 l
Volume of condensate (max.) 3,3 l/h
Maximum flue gas temperature 70 °C
Electrical supply voltage 230/50 V ~/Hz
Internal fuse (slow) main voltage 4 A
Internal fuse (slow) low voltage 4 A
Power input 115 W
6
2 Boiler Specification
Instructions for installation and servicing ecoMAX6
2.2 Dimensions
Fig. 2.1
2 Hanging bracket 3 Heating–system return 5 Gas connection 7 Heating–system flow
2.3 Boiler connections
2.2 Boiler connections
2.4 Functional diagram
Fig. 2.3 Functional diagram ecoMAX 635
1 Air duct 2 Main heat exchanger 3 Burner 4 Condensate trap 5 Temperature sensor (NTC 1) 6 Temperature sensor (NTC 2) 7 Automatic air vent 8 Circulating pump 10 Automatic bypass valve 12 CH flow service valve 14 Gas service valve 16 CH return service valve 17 Pressure relief valve 20 Pressure gauge 21 Main ON/OFF control 22 Boiler display 23 Electronic box 24 Gas valve 25 Fan 26 Expansion vessel 27 Expansion vessel charging valve 28 Flue gas duct
28 27
26
2
4
5 6
7
8
10
12
3
1
25
24
22
23
21
20
17
16 14
Ø22
Ø22
25
33.5
100100
Ø 15
750
703
150
79
Ø15
113
190
480
800
2
100
450
7
Ø 20
100 100
Ø 20
5
3
7
Ø 20
20
R 1
/2
180
7
Boiler Specification 2
Instructions for installation and servicing ecoMAX 7
2.5 Design
Fig. 2.4 Functioning elements, ecoMAX 635 configuration
1 Expansion vessel 2 Air suction pipe 3 Burner assembly 4 Ignition electrode 8 Electronic box 9 Circulating pump 10 Gas valve assembly 11 Auto air vent 12 Main Heat exchanger 13 Air/flue gas duct
2.6 Identification plate
The identification plate of the Vaillant ecoMAX is sup­plied ready–attached to the bottom of the unit.
Fig. 2.5 Identification plate (example)
1
2
3
4
8
9
10
11
12
13
8
3 General requirements
Instructions for installation and servicing ecoMAX8
3 General requirements
3.1 Preliminary remarks for roomsealed appliances
This appliance should only be installed in conjunction with either a Vaillant flue system or an alternative ap­proved system (details of flue approval categories can be found in the technical section of the installation manual). Install the flue system as detailed in the separate flue in­stallation instructions supplied with this boiler.
3.2 Related documents
The installation of the boiler must be in accordance with the relevant requirements of Gas Safety (Installation and Use) Regulations 1998, Health and Safety Document No. 635 (The Electricity at Work Regulations 1989), BS7671 (IEE Wiring Regulations) and the Water Supply (Water Fitting) Regulations 1999, or The Water Bylaws 2000 (Scotland). It should also be in accordance with the rele­vant requirements of the Local Authority, Build-ing Regulations, The Building Regulations (Scotland). The Building Regulations (Northern Ireland) and the relevant recommendations of the following British Standards: BS 6700: Services supplying water for domestic use within buildings and their curtilages. BS 6798: Specification for installation of gas fired boil­ers not exceeding 60 kW input. BS 6891: Specification for installation of low pressure gas pipework up to 28 mm (R1) in domestic premises (2nd family gas). BS 7593: Treatment of water in domestic hot water central heating systems. Institute of Gas Engineers Publication IGE/UP/7/1998: ”Guide for gas installations in timber framed housing” BS. 5482: Pt. 1 Domestic butane and propane gas bur­ning installations. IGE/UP1: Soundness testing and purging of industrial and commercial gas installation. IGE/UP2: Gas installation pipework, boosters and com­pressors on industrial and commercial premises. IGE/UP10: Installation of gas appliances in industrial and commercial premises. BS. 6644: Installation of gas fired hot water boilers of rated inputs between 60 kW and 2 MW (2nd and 3rd family gases). BS. 5449: Forced circulation hot water central heating systems for domestic premises. Note: only up to 45 kW. BS. 6880: Low temperature hot water heating systems of output greater than 45 kW.Part 1 Fundamental and design considerations. Part 2 Selection of equipment. Part 3 Installation, commissioning and maintenance. BS. 4814: Specification for: Expansion vessels using an internal diaphragm, for sealed hot water heating systems. BS. 5440: Installation and maintenance of flues and ventilation for gas appliances of rated input not excee­ding 70 kW net (1st, 2nd and 3rd family gases). Part 1 Specification for installation of flues.Part 2 Specification for installation and main-tenance of ventilation for gas appliances.
Attention!
The appliance must be installed and serviced by
a Competent Person as stated in the Gas Safety (Installation and Use) Regulations 1998. In IE, the installation must be in accordance with the current edition of I.S.813 ‘Domestic Gas Instal–lations’, the current Building Regulations and reference should be made to the current ETCI rules for electrical installation.
Attention!
When tightening or loosening screwed connec-
tions always use suitable open–ended spanners (not pipe wrench, or extensions, etc.). Incorrect use and/or unsuitable tools can lead to damage being caused (e.g. gas or water leakage)!
3.3 Contents included with boiler
Ensure that all contents are included before commen­cing installation.
Fig. 3.1 Items supplied with unit
Do not remove the boiler from the polystyrene base at this stage.
Item Quantity Description
1 1 Boiler 2 1 Hanging bracket 3 3 Installation and Servicing, Users and
Flue Installation Instructions 4 1 Installation and connection accessories 5 1 Guarantee Card 6 1 Template 7 4 Copper tails for gas and water pipework 8 3 Flow and return service valve, gas service
valve 9 1 Pressure relief valve
Table 3.1 Items supplied with unit
4
5
2
6
7
3 1
8
9
9
General requirements 3
Instructions for installation and servicing ecoMAX 9
3.4 Boiler location
The location chosen for the boiler must permit the provi­sion of a satisfactory flue termination. The location must also provide adequate space for servicing and air circu­lation around the boiler. The boiler may be installed in any room, although particular attention is drawn to the requirements of BS7671 (IEE Regulations), the electrical provisions of the Building Standards (Scotland) Regula–tions, and in IE the current edition of IS813 and the current ETCI rules, in respect of the installation of a boiler in a room containing a bath or shower.
Note! Where a room sealed boiler is installed in a room containing a bath or shower, any electrical switch or boiler control utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower.
Where the installation of the boiler will be in an unusual location, special procedures may be necessary and BS 5546 and BS 6798 give detailed guidance on this aspect. The boiler must be mounted on a flat, vertical wall, which must be sufficiently robust to take the weight of the boi­ler. The boiler may be installed on a combustible wall, subject to the requirements of the Local Authorities and Building Regulations. A compartment used to enclose the boiler must be desi­gned and constructed specifically for this purpose. (An existing cupboard or compartment may be used provi­ded that it is modified for the purpose). Details of essen­tial features of cupboard/compartment design including airing cupboard installations are given in BS 6798. If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with Institute of Gas Engineers Publication IGE/UP/7/1998 ”Guide for Gas Installation in Timber Framed Housing”.
3.5 Gas supply
The gas supplier should ensure the availability of an ade­quate supply of gas. A gas meter may only be connected to the service pipe by the supplier of gas or their contrac­tor. An existing meter should be checked to ensure that it is capable of passing the rate of gas supply required. Installation pipes should be fitted in accordance with BS 6891. In IE the current edition of IS 813. Pipework from the meter to the boiler must be of an adequate size. Do not use pipes of a smaller size than the boiler gas connection (15 mm). The complete installation must be tested for soundness and purged as described in BS 6891.
3.6 Flue system
3.6.1 Optional 125 mm flue system
A concentric flue system of 125 mm outside diameter is available and can be used to achieve flue lengths up to 21 m. A vertical flue system is also available. Refer to flue system installation instructions for full details.
Fig. 3.2 Art.–No. 303 209
Fig. 3.3 Art.–No. 303 200
3.7 Flue termination
The following details refer to both flue systems. a.The terminal must be positioned such that the produc-
ts of combustion can disperse freely at all times.
b.A plume of water vapour will sometimes be visible
from the flue terminal. Positions where this could be a nuisance should be avoided.
c. If the terminal is fitted less than 2 m above a balcony,
above ground or above a flat roof to which people have access then a suitable terminal guard must be provided and fitted (contact Tower Flue Components, Tonbridge, TN9 1TB).
Fig. 3.4 Flue termination
Note! Vertical flues must not terminate within 600 mm of an openable window, air vent or any other ventilation opening.
A
BCD
A G
H, I
F
J
B
F
M
L
L
K
K
G
G
F
F
E
A
A
1530
880
70
70
1103
70
15
10
3 General requirements
Instructions for installation and servicing ecoMAX10
The flue assembly shall be so placed or sheilded as to prevent ignition or damage to any pary of the building.
Terminal position mm
A Directly below an opening, above an opening or
horizontal to an opening, air brick, opening window, etc. 300 B Below gutters, soil pipes or drain pipes 75 C Below eaves 200 D Below balconies 200 E From vertical drain pipes and soil pipes 25 F From internal or external corners 300 G Above ground, roof or balcony 300 H From a surface facing a terminal 600 I From a terminal facing a terminal 1200 K Vertically from a terminal on the same wall 1500 L Horizontally from a terminal on the same wall 300 M Distance from adjacent for vertical Flue 500
Table 3.2 Terminal position for a fan assisted concentric flue
Note! In addition, the terminal should not be nearer than 150 mm to an opening in the building fabric formed for the purpose of accommodating a built–in element such as a window.
BS 5440–1 It is recommended that the fanned flue termi­nal should be positioned as follows: a) at least 2m from an opening in the building directly
opposite, and
b) so that the products of combustion are not directly
directed to discharge across a boundary.
1) Dimensions B, C and D: These clearances may be reduced to 25 mm without affecting the performance of the boiler. In order to ensure that the condensate plume does not affect adjacent surfaces the terminal should be extended as shown in fig. 3.8.
2) Dimension F:
This clearance may be reduced to 25 mm without affecting the performance of the boiler. However, in order to ensure that the condensate plume does not affect adjacent surfaces a clearance of 300 mm is pre ferred. For IE, recommendations are given in the cur­rent edition of IS 813.
Fig. 3.5
3.8 Air supply
Detailed recommendations for air supply are given in BS 5440: Part 2. It is not necessary to have an air vent in the room or internal space in which the boiler is installed.
3.8.1 Cupboard or compartment ventilation
The boilers are very high efficiency appliances. As a con­sequence the heat loss from the appliance casing during operation is very low. Compartment ventilation is requi­red if the flue used in not concentric and air is supplied from the room or compartment the boiler is installed in.
3.9 Electrical supply
A 230 V, ~ 50 Hz single phase electricity supply fused to 3 Amp. must be provided in accordance with the latest edition of BS7671 (IEE Wiring Regulations) and any other local regulations that may apply. In IE reference should be made to the current edition of the ETCI rules. The method of connection to the mains electricity supply must provide a means of completely isolating the boiler and its ancillary controls. Isolation is preferably by the use of a fused three pin plug and unswitched shuttered socket outlet, both complying with the requirements of BS 1363. Alternatively, a 3 Amp. fused doublepole switch with a 3 mm contact separation on both poles may be used.
This appliance must be earthed.
3.10 Guide to system requirements
3.10.1 Water circulation system
Detailed recommendations for the water circulation system are given in BS 6798 and BS 5449: Part 1 (for small bore and micro bore central heating systems). Pipework not forming part of the useful heating surface should be insulated to help prevent heat loss and possi­ble freezing, particularly where pipes are run through roof spaces and ventilated underfloor spaces. Draining taps must be located in accessible positions which per­mit the draining of the whole system including the boiler and the hot water system. Draining taps should be at least 1/2 in. BSP nominal size and be in accordance with BS 2879. The boiler is suitable for use with minibore or microbore systems. Copper tubing to BS 2871: Part 1 should be used for water carrying pipework. All capillary joints in all DHW pipework must be made with lead free solder. Particularly where a new boiler is to be fitted to an existing system, it is good practice that the system is thoroughly cleansed.
Attention!
To prevent the formation of deposits and pre-
vent serious damage to the appliance and system , cleansers must be used carefully and must be completely removed by thoroughly flushing the system. Cleansers should only be left in systems for a maximum of 24 hours.
balcony/eaves
flue extended to clear any overhang
flue adequately supported
gutter
11
General requirements 3
Instructions for installation and servicing ecoMAX 11
This cleansing must take place prior to the fitting of the new boiler and be in accordance with BS 7593. For advice on the application of system cleansers contact Sentinel, Betz Dearborn Ltd. Widnes, Cheshire, WA8 8UD. Tel: 0151 495 1861, or Fernox, Alpha Fry Technologies, Tandem House, Marlow Way, Croydon, CR0 4XS. Tel 0870 6015000
3.10.2 Filling and make up
The system can be filled via a separate filling point fit­ted at a convinient position on the heating circuit. The connection must be removed when filling is completed. Where local Water Authority regulation does not allow temporary connection, a sealed system filler pump with break tank must be used. The heating system will not be filled automatically from the domestic hot water side. (Alternative methods of filling sealed systems are given in BS 5449).
3.10.3 Pressure relief valve
A pressure relief valve is provided with the boiler. This safety device is required on all sealed C.H. systems and is preset at 3 bar and provided with a 15 mm compressi­on connection for a discharge pipe, which must be of no less than 15 mm in diameter. The pressure relief valve must not be used for draining purposes.
3.10.4 Pressure gauge
This is factory fitted to the boiler and indicates the pri­mary circuit pressure to facilitate filling and testing.
3.10.5 Expansion vessel
Vessel Volume [L] Initial system pressure (bar) 1.0 1.5 Pressure relief valve setting (bar) 3.0
Total water content of system litres 25 2.7 3.9 50 5.4 7.8 100 10.9 15.6 125 13.6 19.5 150 16.3 23.4 175 19.1 27.3 200 21.8 31.2 225 24.5 35.1 250 27.2 39.0 275 30.0 42.9 300 32.7 46.8 325 35.7 50.7 350 38.1 54.6 375 40.9 58.5 400 43.6 62.4 425 46.3 66.3 450 49.0 70.2 475 51.8 74.1 500 54.5 78.0 For system volumes other than those given above, multiply the system volume by the factor across 0.109 0.156
Table 3.3 Sizing of additional expansion vessel
ecoMAX 635 incorporates a 10 litre expansion vessel which is suitable for a sealed heating system with a maximum water content of 100 litres. If the nominal capacity of the built in expansion vessel is not sufficient for the heating system (for instance in case of modernization of old open systems) an additio­nal expansion vessel can be installed external to the boi­ler. It should be fitted in the return pipe as close as pos­sible to the boiler in accordance with BS 5449: Part 1. Guidance on the sizing of an additional expansion vessel is given in Table 3.3.
3.11 Pump specifications
3.11.1 Circulating pump
The ecoMAX 635 is fitted with a modulating circulating pump. The pump head available for the heating system is shown in figure 3.6.
Fig. 3.6 Pump specifications
3.11.2 System by–pass
An automatic system by–pass is included within the boi­ler. The boiler is suitable for use in systems with ther­mostatic radiator valves and no additional by–pass is required.
3.11.3 Venting
The boiler is fitted with an automatic air vent. Additional provision should be made to enable the heating system to be vented during filling and commissioning either by automatic air vents or manually.
3.12 Condensate trap
The boiler is fitted with a condensate trap incorporating a water trap of 75 mm.
400
300
200
100
0
0 200 400 600 800 1000 1200 1600
Lift
[
mbar
]
1800
Volumeflow [l/h
]
1900
1400
100 %
53 %
60 %
70 %
85 %
12
4 Boiler installation sequence
Instructions for installation and servicing ecoMAX12
4 Boiler installation sequence
4.1 General
Fig. 4.1
The boiler should be mounted on a flat and vertical area of wall of sufficient area for the boiler plus the required clearances for installation and servicing (fig. 3.8). These are shown on the installation template supplied with the boiler and are: – 5 mm either side of the boiler – 145 mm below the boiler – 205 mm* above the boiler when utilising the 100 mm
outside diameter flue
– 220 mm* above the boiler when utilising the 125 mm
outside diameter flue
– 500 mm in front of the boiler**
Note! If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with British Gas publication DM2 ‘Guide for gas installations in timber framed housing’.
4.1.1 Select position of boiler
Refer to section ‘Boiler location’ for information regarding siting the appliance. In general the boiler must be positioned such that:
• There is adequate space around the boiler for service and maintenance
• The boiler can be correctly flued, i.e. the flue terminal position is sited in accordance with these instructions and the air/flue duct can be installed in accordance with the flue installation instructions supplied.
• All necessary pipework can be connected, including the pressure relief valve and condensate drain.
** This clearance is only required to enable easier access to the boiler for
servicing and may be provided by an openable door, etc.
4.1.2 Unpack the boiler
To unpack the boiler, cut both plastic carton straps, open box and lift out the polystyrene top packing. Lift the cardbox box upwards.
Note! Care should be taken not to scratch the white surface of the boiler casing.
Packed in the boiler carton are the following:
• Boiler
• Flow and return central heating service valves
• Gas service valve
• Pressure relief valve
• Pre–formed copper pipework (for central heating flow and return, gas and pressure relief valve connections)
• Boiler installation template
• Boiler hanging bracket
• Fixing screws, wall plugs and washers
• Installation and user instructions
• Flue installation instructions
• Guarantee card and envelope
4.1.3 Using boiler template
Fix the paper template to the wall ensure that the template is vertical. The template shows: – The position of the fixing holes for the boiler
mounting bracket (1).
– The position of the connections. – The position of the flue exit hole.
Mark the position of the hanging bracket fixing holes (1). Drill 2 holes Ø 8 mm for the hanging bracket.
Note! Use alternative fixing holes where necessary.
4.2 Rear flue exit
Mark the position of the air/flue duct and its circumfe­rence.
4.3 Other flue options
Flue instructions for other flue systems such as vertical RSF flues, flues run to the side of the boiler and the use of additional bends etc. are detailed in the flue installation instructions provided with the boiler. Remove the template from the wall and plug the drilled holes using the wallplugs supplied.
min
min 5
min 5
min 500**
min 145
205/220*
Fig. 4.2 Using Boiler template
4.4 Fitting the boiler hanging bracket
Fix the hanging bracket (2) to the wall using the screws supplied. (it may be necessary to use additional or alternative fixings to ensure adequate support).
Note! If the boiler is to be fitted in a timber framed building ensure that the bracket is secured to a substantial part of the timber frame capable of taking the weight of the boiler.
Fig. 4.3 Fitting the boiler
4.5 Install the flue system
Install the flue system (refer to separate air/flue duct installation instructions)
4.6 Fitting the boiler
• Lift the boiler (3) up to the wall so that it is slightly above the hanging bracket (1).
Note! Lift the boiler from either side at the bottom edge.
• Lower the boiler slowly onto the hanging bracket so that the cross member at the rear of the boiler fully engages onto the hanging bracket.
4.7 Removing the front case
To remove the front section of the case, proceed as follows:
• Loosen the screw (1) on the bottom of the unit.
• Push in the two retaining clips (2) on the bottom of the appliance until the case is released.
• Grasp the front case (3) by its bottom edge, pull it towards the front and remove it by lifting it off the unit.
85
50
240
75
75
23
50
3
1
2
Boiler casing
Minimum
Clearances
Reqd.
Flow
Gas in Return
Condensate
discharge
Minimum Clearances
Reqd.
Fixing holes and
Position for
optional
pre-instalation
connection
Flue hole
(80/125 mm
flue system)
Please use
the new
Boiler hanging
bracket
ecoMAX 635
13
Boiler installation sequence 4
Instructions for installation and servicing ecoMAX 13
14
3 General requirements
Instructions for installation and servicing ecoMAX14
Fig. 4.4 Removing/Refitting the case
4.8 Gas supply
Fig. 4.5 Fitting the gas connection
• Connect the compression gas service cock and 15 mm copper outlet tail as supplied with the appliance and tighten.
• Connect a gas supply pipe of not less than 15 mm dia­meter to the copper tail.
• Tighten all connections. (Ensure the gas supply pipe­work is adequately sized such that a 20 mbar gas pres­sure is available at the boiler inlet at full flow rate).
4.9 Central heating flow and return pipework
Fig. 4.6 Central heating flow and return pipework
Before connecting the heating circuit to the boiler, all pipework and radiators must be thoroughly flushed to remove any installation debris.
• Connect the central heating flow and return service valves to the appliance.
• Connect the 22 mm copper pipe tails to the service valves as shown in the illustration and tighten the nuts.
• Connect the central heating pipework to the flow and return tails.
Two additional tubes are supplied with the appliance for top connection of the flow and return pipework within the casing.
4.10 Pressure Relief Valve
A pressure relief valve is provided within the boiler card­board box and should be assembled as shown below. Connect a discharge pipe not less than 15 mm diameter to the outlet of this valve. The discharge pipework should be as short as possible and installed with a continuous fall away from the boiler. The pipe should terminate in a position which ensures that any discharge of water or steam from the valve can­not create a hazard to persons in or about the premises, or cause damage to any electrical components or exter­nal wiring, and the point of discharge should be clearly visible.
1
2
Loading...
+ 30 hidden pages