Service policy, guarantee, etc. ..................................................rear cover
WARNING
This appliance can be used by children aged from 8 years and
above and persons with reduced physical, sensory or mental
capabilities or lack of experience or knowledge if they have been
given supervision or instruction concerning use of the appliance
in a safe way and understand the hazards involved. Children may
not play with the appliance. Cleaning and user maintenance shall
not be made by children without supervision.
To check the product suitability for commercial and multiple installations, please contact Triton’s
specication advisory service before installation.
Telephone:
Facsimile:
024 7637 2222
024 7632 4504
E mail:
technical@tritonshowers.co.uk
.
Power Shower Thermostatic
1 PLUMBING NOTES
1.1 All installations must comply with Water
Regulations or Water Bylaws.
1.2 Supply pipes must be flushed to clear
debris before connecting the shower unit.
1.3 DO NOT connect the shower unit to
the mains cold water supply as it would
damage the unit and also, the installation
would be in breach of Water Regulations.
1.4 DO NOT use excessive force when making
connections to the flexible hose or
showerhead – finger tight is sufficient.
1.5 ALL plumbing connections are to be
completed and water supplies turned on
BEFORE switching on the electricity supply.
The shower must not be operated dry
without water.
1.6 DO NOT solder pipes or fittings within
300 mm of the shower appliance, as heat
transfer can damage components.
1.7 When installed, the top of the shower unit
must be at least 75 mm lower than the
base of the cold water storage cistern to
prevent the pump being run dry without
water.
1.8 A dedicated cold water supply must be
taken directly from the cold water cistern
to the shower. This draw-off must be on
the opposite side of the cistern to the float
operated valve to reduce the risk of air
entering the unit.
1.9 The action of the pump is to increase the
flow rate. If the supply pipework cannot
handle the resulting flow rate then:
1.9.1 The anticipated flow rate may not
be achieved.
1.9.2 Air may be drawn into the hot
supply from the vent pipe causing
spluttering and temperature fluctuations at
the showerhead.
1.10 Fullway isolating valves MUST be fitted
on the hot and cold water supplies to
the shower as an independent means
of isolating the water supplies should
maintenance or servicing be necessary. DO
NOT use stop taps or ball-o-fix type valves
which restrict flow.
2 ELECTRICAL NOTES
2.1 The installation must comply with BS 7671
‘Requirements for electrical installations’
(IEE wiring regulations). Make sure the
incoming hot and cold water supplies to
the shower are adequately earth bonded.
2.2 DO NOT turn on the electrical supply
until the plumbing connections have been
completed. Only then can the electricity be
switched on in order to power the solenoid
to turn water on to the shower when
commissioning. The shower must not be
operated dry without water.
2.3 The mains supply must be 230/240V, at
50Hz, connected to the unit via a double
pole switched 3 Amp fused connection
unit (not supplied) with a minimum 3 mm
contact separation gap in each pole.
2.4 In accordance with ‘The Plugs and Sockets
etc. (Safety) Regulations 1994’, this unit
is intended to be permanently connected
to the fixed electrical wiring of the mains
system.
2.5 Fuses do not give personal protection
against electric shock.
2.6 A 30mA residual current device (RCD)
MUST be installed. This may be part of the
consumer unit or a separate unit.
1
Power Shower Thermostatic
INTRODUCTION
This book contains all the necessary fitting and
operating instructions for your Triton Power
Shower. Please read them carefully.
The shower installation must be carried out by
suitably competent person and in sequence of
this instruction book.
Care taken during the installation will ensure a
long and trouble free life from your shower
IMPORTANT: All plumbing connections must
be completed BEFORE making the electrical
connections.
Please read through the whole of this book
before beginning your installation.
IMPORTANT: The fittings on the pipe inlet
elbows are of the push-in type. The pipework
must be cut with a pipe cutter and all burrs
and rough edges removed from the end
of the tube. The fittings can be used with
copper and plastic pipe.
Where chrome plated pipe is used, remove
the first 25 mm of plating.
Note: The pump inside this product is rated
15 minutes on / 45 minutes off duty cycle.
SAFETY WARNINGS
a. DO NOT insert fingers into the push-in inlet
fittings. Doing so could cause injury.
b. Under no circumstances must this product
be connected to mains cold or hot water
supplies. Failure to comply will invalidate
the guarantee.
c. The shower MUST NOT be used if suspected
of being frozen.
d. The outlet of this appliance MUST NOT be
connected to any form of tap or fitting not
recommended by the manufacturer.
e. The showerhead cartridge MUST be cleaned
regularly to remove scale and debris.
f. This appliance MUST be earthed.
g. Switch off immediately at the isolating
switch if water ceases to flow during use.
h. DO NOT operate the shower outside the
guidelines laid out in ‘site requirements’.
Replacement parts can be ordered from Triton
Customer Service. See ‘spare parts’ for details and part
numbers.
A 30mA residual current device (RCD) MUST
be installed in all UK 230V electric and
pumped shower circuits. This may be part of
the consumer unit or a separate unit.
2
Power Shower Thermostatic
MAIN COMPONENTS
1. Top pipe entry and cable entry
2. Terminal block
3. Cover screw fixing
4. Motor retaining bracket
5. Rear pipe entry and cable entry
6. Wall fixing holes
7. Pipe inlet elbow – top
(contains single check valves)
8. Filter cover – top
9.Pump
10. PCB housing
11. Setting adaptor
12. Temperature control valve
13. Solenoid
14. Filter cover - bottom
15. Pipe inlet elbow – bottom
(contains single check valves)
16. Outlet
17. Bottom pipe entry
SPECIFICATIONS
Hot water temperature
Maximum temperature 65°C.
BS 6700 recommends that the temperature of
stored water should never exceed 65°C. A stored
water temperature of 60°C is considered sufficient
to meet all normal requirements and will
minimise the effects of scale in hard water areas.
Temperature control
To obtain the maximum performance, this unit
should be installed, operated and maintained
as instructed in this book. The full performance
specification as below for the unit is achieved
with a blend set between 35°C – 40°C and
supplies of 15°C cold and 65°C hot with
nominally equal pressures.
1. The blended water temperature is maintained
within 2°C with a 10°C change in the hot
and cold water supply.
3
56 mm
Fig.1
86
mm
6
268
mm
10
1
3
4
2
5
6
7
8
9
13
6
6
3
16
206 mm
11
12
14
15
17
82 mm
2. The sensor effects a shut down to seepage in
about 2 seconds if the cold supply fails.
3. Shut down to seepage is achieved even if
the hot supply is only 12°C above the blend
temperature.
4. The blended water temperature is maintained
within 1°C when the pressure between inlet
and outlet is halved (defined as a pressure
loss ratio of 2:1) on either the hot or cold
side.
Maximum static inlet pressures
100 Kpa (1 bar) or 10m (supplies must be
gravity fed at nominally equal pressures).
Minimum static inlet pressure
0.75 Kpa (0.0075 bar) or 75mm (required to
prime the integral centrifugal pump).
Maximum supply head 10m.
3
Power Shower Thermostatic
Mains supply
Isolating
valve
Cold water cistern
Vent pipe tee
Isolating
valve
Hot supply
Hot water
cylinder
Drain
valve
Other hot water
draw-offs
Alternative
connection
Shower unit
Ring main
25 mm min
Isolating spur
(3A fused)
outside bathroom
Dedicated cold supply
10 m
max
75 mm
min
Isolating
valves
SITE REQUIREMENTS
Water
The installation must be in accordance with
Water Regulations/Bylaws and BS 6700.
For correct operation of this shower unit, both
hot and cold water supplies to the appliance
must be gravity fed, at nominally equal
pressures, from a cold water storage cistern and
a hot water storage cylinder.
The water circuit should be installed so that the
flow is not significantly affected by other taps
and appliances being operated elsewhere on the
premises.
Fig.2 shows a recommended installation where
the hot water supply for the shower is made
via a tee connection on the underside of the
horizontal section of pipework from the cylinder.
Alternatively, the connection can be taken from
the hot supply pipe to other outlets as long as it
is the first draw-off below the ventilation pipe tee.
Fig.3 illustrates all the incorrect connections that
must be avoided.
All pipework to the shower unit must be routed
where it remains below the level of water in
the cistern. In the case of horizontal sections
of pipework in lofts, it may be necessary to
fit automatic air vents at high points on the
supplies to remove the possibility of air locks.
For the operation of the shower only, it is
recommended that the cold water storage
cistern is capable of holding at least 114 litres
(25 gallons). Where other hot and cold outlets
are likely to be in use simultaneously, the storage
capacity should be increased to 228 litres (50
gallons) in accordance with BS 6700.
Do ensure compliance with the Water
Regulations/Bylaws.
DO NOT connect to a combination cylinder
unless there is a guaranteed 114 litre cold supply
to the cylinder as the shower can deliver up to
14 litres per minute. It is advisable to check that
4
Fig.2 (Diagrammatic view – not to scale)
Power Shower Thermostatic
the infill rate from the float operated valve meets
the output requirements..
It is recommended that there is a minimum
of approximately 114 litres (25 gallons) of hot
water storage per appliance.
The shower MUST NOT be connected to the
mains cold water supply.
DO NOT use jointing compounds.
GENERAL INSTALLATION NOTES
1. DO NOT take risks with plumbing or
electrical equipment.
2. DO NOT install this unit in a position where
it could become frozen.
3. Isolate electrical and water supplies BEFORE
proceeding with installation work.
4. Shower control MUST be fed from a cold
water storage cistern and hot water cylinder
that provides nominally equal pressures.
5. The unit must be mounted onto the finished
wall surface (on top of tiles).
DO NOT tile up to the unit after fixing to
the wall.
6. If installing with rear inlet supplies, it is
recommended the supply pipework is sealed
to the wall so as to prevent water from
leaking back into the wall.
7. In solid wall installations, the supply
pipework should be housed within
ducting in order to allow some free lateral
movement when making connections and
to ensure compliance with requirements of
accessibility of pipes and pipe fittings.
Fig.4 shows a schematic wiring diagram of the
unit.
Fig.3 (Diagrammatic view
not to scale)
5
Power Shower Thermostatic
L E N
Potentiometer
Switch
Solenoid
Motor
Capacitor 2
RFI suppression coil
Capacitor 1
PCB
Thermal
fuse
Fig.4 (schematic view )
Fig.5
SITING OF THE SHOWER
WARNING!
The shower must not be positioned
where it will be subject to freezing
conditions.
IMPORTANT: If fitting to a tiled wall, always
mount the unit on the surface of the tiles.
NEVER tile up to the unit.
Refer to fig.5 for correct siting of the shower.
Position the unit vertically where it will NOT
be in direct contact with water from the
showerhead.
Note: Allow sufficient room between the ceiling
and the shower unit to access the top cover
screw.
Position the shower and showerhead on the wall
so that all controls can be comfortably reached
when using the shower.
The showerhead and riser rail can be positioned
either side of the shower unit.
Note: Water Regulations require the showerhead
be ‘constrained by a fixed or sliding attachment
so that it can only discharge water at a point
not less than 25 mm above the spill-over level
of the relevant bath, shower tray or other fixed
appliance’. The use of the supplied soap dish will
in most cases meet this requirement, but if the
showerhead can be placed within a bath, basin
or shower tray, then a device must be fitted to
prevent back-flow.
6
Power Shower Thermostatic
Maximum
temperature
stop
REMOVING THE COVER
To remove the cover, first pull off the cover trim
from the temperature control (fig.6) and undo
the retaining screw. Pull off the temperature
control.
This will reveal the maximum temperature stop
(fig.7). This should be left in position.
Note: If adjustment of the maximum
temperature stop is required, refer to section
’Adjusting the maximum temperature stop’.
Remove the two cover fixing screws – top and
bottom (fig.8).
Carefully lift the cover away from the backplate.
Lay aside the cover and screws until the unit is
fully installed.
Note: When removing the cover for future
maintenance purposes, be aware of the lead
connected to the PCB unit. Carefully pull off the
lead from the PCB.
DO NOT let the cover dangle by the lead.
PLUMBING CONNECTIONS
Plumbing to be carried out before wiring
Note: The outlet of the shower must not be
connected to anything other than the hose and
showerhead supplied.
DO NOT use jointing compounds on any pipe
fittings for the installation.
When connecting pipework avoid using tight
90° elbows. Swept or formed bends will give
optimum performance.
Isolate the mains water supply to the cold water
cistern. Drain the hot and cold pipes by opening
all taps.
The hot water supply can be taken from the hot
supply pipe from the cylinder. Make sure that it
is the first draw-off below the ventilation pipe
tee in order to minimise the effects of water
draw-off elsewhere in the house (see fig.2).
Note: There must not be any other draw-offs
between the take-off point and the shower.
A dedicated cold water supply must be taken
directly from the cold water cistern to the
shower. This draw-off must be positioned
25 mm below the cold feed connection to the
Fig.6
Fig.7
Fig.8
7
Power Shower Thermostatic
19 mm
26 mm
Cold
Hot
Area of
backplate
to remove
Wall
19 mm
34 mm
26 mm
Rear edge
of
backplate
Hot Cold
Wall
23.5 mm
Fig.10
Fig.9
Top
Rear
Bottom
hot water cylinder on the opposite side of the
cistern to the float operated valve (see fig.2).
This minimises air ingress into the pipework.
Plumbing options other than those outlined
in these fitting instructions could impair the
performance. For example, if hot and cold
connections are made after draw-off points
to other outlets, (eg. washing machine, taps,
etc.) it could result in unstable flows and
temperatures should other appliances operate at
the same time.
Run the hot and cold pipework to the shower
position, making sure that the pipework does
not rise above the level of water in the cold
cistern at any point to avoid air locks. Under
normal site conditions 15 mm pipework will be
adequate.
Decide the position of the shower. Cut the
pipework to the dimensions relevant to the
chosen direction of water entry into the shower.
IMPORTANT: For rear entry only, the supplied
elbows must be used. For ease of installation,
the backplate area adjacent to the top pipe
inlet must be cut out, including the top left
wall fixing hole.
When fitting the elbows to incoming pipework,
ensure the elbow collets are fully engaged with
the pipe.
Dimensions are shown in fig.9 and fig.10.
Note: The pipe inlets are marked for hot and
cold connections – left-hand side for hot inlet on
bottom entry (fig.11), but right-hand side for
hot inlet on top or rear entry (fig.12).
IMPORTANT: The fittings on the inlet elbows
are the push-in type. The pipework must be
cut with a pipe cutter and all burrs and rough
edges removed from the end of the tube. The
fittings can be used with copper and plastic
pipe.
If using chrome plated copper pipe, remove
the first 25 mm of plating completely from
the connecting surfaces. If not completely
removed then the collet will not grip the pipe
and under pressure the pipe may be forced
out.
Note: Pipework must be clipped or fixed to the
wall so that it cannot be moved or removed
without the aid of a tool.
8
Power Shower Thermostatic
Bottom
(rising)
supply
Top
(falling)
or rearsupply
Hot
side
Hotside
Top
(falling)
or rear
supply
Hot
side
Blanking
plug
Splash guard
Note: The pipe inlets contain filters. These
should be periodically removed and cleaned
in order to maintain the performance of the
shower. See section ‘cleaning’ on how to access
the filters.
IMPORTANT: The inlets contain check valves,
so before completing the connection of the
water supplies to the shower flush out the
pipework to remove all swarf and system
debris that may cause damage to internal
parts. This can be achieved by connecting
a hose to the pipework and turning on the
water supplies long enough to clear the
debris to waste.
IMPORTANT: Two factory fitted blanking
plugs are fitted to the top pipe inlets. These
should be left in position if bottom pipe entry
is required.
For top or rear pipe entry, the two plugs
MUST be removed and refitted into the
bottom pipe inlets. Failure to fit the
blanking plugs will result in the unit working
erratically.
Insert the pipe removal tool supplied between
the flange of the plug and the grey collet and
lever the plug outward (fig.13). Whilst holding
back on the collet, pull out each plug by hand.
When refitting the plugs in the bottom pipe
inlets, make sure they are pushed fully home.
Note: The unit is supplied with a splash guard
(fig.14) to prevent water ingress when top
entry pipework is used. If fitting top entry
pipework, make sure the splash guard is
correctly fitted (fig.14) before replacing the
cover.
Fig.11
Fig.12
Fig.13
Fig.14
9
Power Shower Thermostatic
Remove shaded area
Cut out
for cable
3
Fig.15
Fig.16
Fig.17
FITTING THE SHOWER TO THE WALL
IMPORTANT: Before fitting the shower,
make sure the pipework is flushed out to
remove all debris, flux, etc.
For top pipe entry or top cable entry, remove
the relevant cut-outs by either breaking out or
by using a knife or junior hacksaw (fig.15).
If top entry for both pipe and cable is required,
then additionally remove the shaded area
(fig.15) by using a knife or junior hacksaw.
For bottom pipe entry, remove the cut-out and
break off the two circular parts (fig.16). Replace
the cut-out.
For rear pipe entry only, the supplied elbows
must be used with the necessary portion of
backplate cut away as shown in fig.9.
It will be necessary if rear cable entry is required,
for conduit or other routing of the electrical
cable to be completed before fixing the shower
to the wall.
Offer the backplate unit up to the completed
pipework and manoeuvre so that the end of the
pipes enter fully into the inlet fittings.
Mark positions for wall fixing holes using
backplate as template (fig.17). Note that four
fixing holes are provided but using only two
should be adequate for most site conditions.
Using the pipe removal tool supplied, push back
and hold the collets from the pipework (fig.18)
to disengage the pipework from the inlet elbows.
Remove unit from the wall.
Drill and plug the wall.
(An appropriate drill bit should be used. If the
wall is brick, plasterboard or a soft building block,
appropriate wall plugs and screws should be fitted).
Note: If fitting rising supplies to the unit, ensure
debris does not enter the pipes when drilling the
wall.
Offer the backplate unit up to the completed
pipework and manoeuvre so that the end of the
pipes enter fully into the inlet fittings.
Check the backplate is square and the fixing
holes are aligned then secure to the wall
(fig.17).
10
Power Shower Thermostatic
Terminal block
ELECTRICAL CONNECTIONS
WARNING!
This unit must be earthed. Isolate the
supply before starting.
The supply cable must conform to relevant
tables in current IEE regulations. In most cases
1 mm² twin and earth will be adequate.
The electrical rating of the shower is on the
rating label within the unit.
SWITCH OFF THE ELECTRICITY SUPPLY AT
THE MAINS.
Cable entry points are shown in fig.1. Conduit
entry can only be from the rear.
Route the cable into the shower, taking care to
avoid the area of the wall fixings and connect to
the terminal block (fig.19) as follows:
Earth cable to terminal marked E
Neutral cable to terminal marked N
Live cable to terminal marked L
IMPORTANT: Fully tighten the terminal block
screws and check that no cable insulation is
trapped under the screws.
Note: The supply cable earth conductor must
be sleeved.
The earth continuity conductor of the electrical
installation must be effectively connected
electrically to all exposed metal parts of other
appliances and services in the room in which the
shower is to be installed, to conform to current
IEE regulations.
Note: Fuses do not ensure user protection
against electric shock. In the interest of electrical
safety, all mains electric and pumped showers
should be fitted with a 30mA residual current
device (RCD). This may be part of the consumer
unit or a separate unit.
DO NOT switch on the electricity supply until
the water has been turned on to the unit and
connections have been tested for leaks.
IMPORTANT: The cover may be left off
initially only for commissioning.
Fig.18
Fig.19
11
Power Shower Thermostatic
Cold
Hot
Fig.20
Fig.21
COMMISSIONING
WARNING!
Before normal operation of the
shower, it is essential that the
commissioning and setup procedure
are correctly completed. Failure to do
so could cause the pump to run dry
without water and invalidate your
guarantee.
The first operation of the shower is intended to
flush out any remaining system debris and to
ensure water is purged through the unit. This
operation must be carried out with the flexible
hose screwed to the shower outlet but without
the showerhead attached.
Make sure the outlet of the flexible hose is
directed to waste.
Make sure the isolating valves controlling the
water supply to the unit are fully open.
Note: There is no need to fit the cover at
this stage but be aware of live parts when the
electricity is switched on temporarily.
Fit the temperature control onto the spindle
(fig.20).
Fig.22
WARNING!
Be aware of live parts in the unit
when the electricity is switched on.
DO NOT tamper with any parts and
DO NOT deviate from the following
instructions.
On the PCB, position the commissioning link on
the middle two pins (fig.21).
Switch on electric supply at isolating switch.
Water will begin to flow under gravity pressure.
In order to dispel air and to prime both supplies
to the shower unit, turn the temperature control
several times within its rotational limits. ONCE
RESISTANCE IS FELT, DO NOT FORCE THE
CONTROL FURTHER.
Note: The temperature control rotates less than
one complete turn (fig.22) – from 3 o’ clock
12
Power Shower Thermostatic
(cold) anti-clockwise to 6 o’ clock position (hot)
and vice versa. DO NOT force it beyond these
limits.
To stop the water flow, switch off the electricity
supply at the isolating switch.
Check for leaks in the pipework and remedy
if necessary. If rear entry has been used then
seal around pipes with mastic to prevent the
possibility of water entering the wall cavity. DO
NOT use plaster as this could cause difficulties if
maintenance is required at a later date.
Setup procedure
MAKE SURE THE ELECTRICITY TO THE UNIT IS
SWITCHED OFF.
Pull off the temperature control.
Remove the commissioning link from the PCB
(fig.23) and store safely for future use.
WARNING!
Once the unit has been commissioned,
turn off the electricity supply at
the mains before removing the
commissioning link.
Offer the cover to the unit. Make sure the
Start/Stop button is in the ‘off’ position - flush
with the cover. Attached to the flow control
potentiometer inside the cover is a 4-wire lead.
Fit the connector on the end of this lead to the
4 pins on the PCB (fig.24) – it can fit either
way.
Fig.23
Fig.24
Replacing the cover
Check the valve spindle is correctly positioned
before refitting the cover. See the section
‘Temperature control spindle setting’ for further
details.
Fit the cover, ensuring the connector is fitted
to the PCB and the wires are clear of the cover.
Secure with the top and bottom fixing screws
(fig.8).
Check the maximum temperature stop is still
in position. If not, refer to section ’Adjusting the
maximum temperature stop’.
WARNING
COVER RETAINING SCREWS
ONLY the SUPPLIED SCREWS should be
used. The use of none supplied screws WILL
invalidate product specications & warranty.
13
Power Shower Thermostatic
Fig.25
Fig.26
Groove
Drilled hole
Splined spindle
Valve housing
Replace the temperature control by push fitting
onto the splined spindle. When fitting the
temperature control, the pointer must relate to
the ‘5’ on the temperature scale when the cover
is fitted (fig.25). Refit the retaining screw and
push fit the cover trim back into place.
Switch the electricity supply back on at the
mains. Make sure both water supplies are still
turned on.
Once the installation of the riser rail is complete,
the shower is ready for normal operation.
TEMPERATURE CONTROL SPINDLE
SETTING
Occasionally the spindle may need adjusting
when the temperature control and cover are
removed from the unit. To reset the spindle
to its correct alignment, please refer to the
following:
With the cover and control knob removed, use
your fingers to adjust the splined spindle. You
may see a possible combinations of either black
lines, or a drilled hole and groove. Whichever
combination the valve displays, rotate the
spindle until the marks on both the spindle and
the top of the valve housing line up (fig.26).
Refit the cover. When fitting the temperature
control, the pointer must relate to the ‘5’ on
the temperature scale when the cover is fitted
(fig.25).
Note: Incorrect positioning will result in
excessive cold bleed.
Black line
Black line
Splined spindle
Valve housing
14
Power Shower Thermostatic
Temperature
override
button
Flow
control
Temperature
override
button
OPERATING THE SHOWER
Make sure all plumbing and electrical supplies
are connected and switched on.
To start the shower, press the Start/Stop button
(fig.27).
Adjust the flow control (fig.28) until the flow
rate is satisfactory.
For maximum flow, turn the flow control fully
clockwise. For minimum flow, rotate the flow
control fully anti-clockwise.
To adjust the water temperature, rotate the
temperature control (fig.29). The temperature
is numbered for ease of use, ranging from ‘1’
– fully cold to ‘9’ – fully hot.
Once the preferred temperature is reached, no
further adjustment is required, providing the hot
and cold water supplies remain constant.
To stop the shower, press the Start/Stop button
once more. This stops the pump and water flow.
Unless the shower is to be used again
immediately, the shower should also be switched
off at the electricity isolating switch.
As a safety feature, the temperature control
has a built-in stop to prevent you accidentally
exceeding your highest desired temperature. If
adjustment is required see section ‘Adjusting the maximum temperature stop’.
To override this stop, press the button (fig.30)
while the control is up against the stop and turn
the control anti-clockwise to the higher settings
(pressing the button before the stop will not
operate the override mechanism even if the
control is turned with the button depressed).
To return to the normal temperature range just
turn the temperature control clockwise until it is
past the maximum temperature stop. Make sure
that the temperature control is in the normal
temperature range when the shower is switched
off. The stop comes in a factory set position
based on 65°C stored hot water temperature.
Note: As the flow control is adjusted it is quite
normal for the sound of the pump to alter in
pitch.
Fig.27
Fig.28
Fig.29
Fig.30
15
Power Shower Thermostatic
Maximum
temperature
stop
Increase stop position
Decrease stop position
Fig.31
Fig.32
ADJUSTING THE MAXIMUM
TEMPERATURE STOP
As a safety feature the shower has a built-in
maximum temperature stop to prevent you
accidentally exceeding your highest desired
temperature. This is set in the factory to provide
a maximum temperature based on the hot
and cold water supplies being 65°C and 15°C
respectively.
Procedure
Rotate the temperature control to setting ’5’ on
the temperature scale.
Remove the cover trim to gain access to the
retaining screw. Unscrew the retaining screw and
pull off the temperature control (fig.31).
Carefully pull off the maximum temperature
stop mechanism.
To increase the temperature stop setting,
reposition the mechanism anti-clockwise within
the arc of the grooves (fig.32).
To decrease the temperature stop setting,
reposition the mechanism clockwise within the
arc of the grooves (fig.32).
Replace the temperature control by push fitting
onto the spindle, making sure the pointer relates
to the ‘5’ on the temperature scale.
Refit the retaining screw and push the cover trim
into place.
IMPORTANT: Only adjust the maximum
temperature stop when the hot water is at its
usual storage temperature.
16
Power Shower Thermostatic
INSTRUCTIONS FOR INSTALLERS AND SERVICE ENGINEERS ONLY
CLEANING THE FILTERS
WARNING!
Switch off the electricity supply and
turn off both hot and cold water
supplies to the unit before proceeding
further.
To remove the unit cover first pull off the cover
trim from the temperature control and then
remove the retaining screw.
Pull off the temperature control.
Remove the two cover fixing screws – top and
bottom – and carefully lift the cover away from
the backplate.
Note: Be aware of the lead connected to the
PCB unit. Carefully pull off the lead from the
PCB. DO NOT let the cover dangle by the lead.
Remove the single retaining screw from either
the upper or lower filter cover (fig.33),
depending upon whether top/rear entry or
bottom entry is used.
Pull off the filter cover.
Carefully hook out the filters together with ‘O’
rings. Thoroughly clean the filters and replace,
ensuring the ‘O’ rings are in position.
Refit the filter cover and secure with the screw.
Make sure the valve spindle is correctly aligned.
See section ‘Temperature control spindle setting’.
Offer the cover to the unit and replace the four
wire lead to the PCB. Secure the cover with the
top and bottom fixing screws.
Refit the temperature control. The pointer on
the temperature control should relate to setting
’5’ on the temperature scale.
Secure in place with the retaining screw and
push fit the cover trim into place.
Fig.33 Upper filter shown
17
Power Shower Thermostatic
SPARE PARTS
Ref. Description Part No.
1. Terminal block........................22001320
1
3
6
7
8
2
9
3
4
2. Plastic inlet elbow plug x1 .....7052140
3. Pump & motor assembly .......84000130
4. Link pin ..................................22009060
5. PCB unit .................................7073738
IMPORTANT: Switch OFF the electricity at the mains supply and remove the correct circuit
fuse before attempting any fault finding inside the unit.
Symptom Cause Action/Cure
1 Water too hot.
2 Water too cold.
3 Pump does not
operate.
1.1 Not enough cold water
flowing through shower.
1.2 Increase in the ambient
cold water temperature.
1.3 Cold inlet filter blocked
or check valve sticking.
1.4 Cold water supply
blocked or cut off.
2.1 Not enough hot water
flowing through shower.
2.2 Decrease in ambient
cold water temperature.
2.3 No hot water in the
storage cylinder.
2.4 Hot inlet filter blocked
or check valve sticking.
2.5 Hot water supply
blocked or otherwise cut off.
3.1 Interrupted power
supply.
3.2 Electrical malfunction.
3.3 Motor overheated.
3.4 Start/stop switch not
connected.
1.1.1 Turn the temperature control clockwise.
1.2.1 Turn the temperature control clockwise.
1.3.1 Remove filter and clean. If problem is with
check valve, contact Customer Service.
1.4.1 Isolate shower and consult a competent
plumber or contact Customer Service.
2.1.1 Turn temperature control anti-clockwise.
2.2.1 Turn temperature control anti-clockwise.
2.3.1 Turn shower off and wait for hot water
cylinder to reheat.
2.4.1 Remove filter and clean. If problem is with
check valve, contact Customer Service.
2.5.1 Turn shower off. Consult a competent
plumber or contact Customer Service.
3.1.1 Blown fuse. Check supply. Renew fuse. If it
fails again consult a competent electrician.
3.1.2 Power cut. Check other appliances and if
necessary, contact local Electricity Supply Co.
3.2.1 Consult a competent electrician or contact
Customer Service.
3.3.1 Thermal protection on motor has
operated. Allow appliance to cool and reset
itself. If it persists, contact Customer Service.
3.4.1 Remove cover and connect start/stop
switch.
Any maintenance or repair to the shower must be carried out by a suitably
competent person.
19
Power Shower Thermostatic
FAULT FINDING
Symptom Cause Action/Cure
4 Water does not
flow or is reduced.
5 Cross flow of
hot and cold water
into system.
6 Water dripping
from showerhead
when turned off.
7 Pump is noisy or
air lock in pump.
8 Unit running
erratically.
In the unlikely event of a fault occurring please contact Triton Customer service.
4.1 Water supplies cut off.
4.2 Shower blocked or air
in the system.
4.3 Showerhead blocked.
4.4 Blocked filters.
5.1 Dirt/debris in check
valves.
6.1 Debris in solenoid
valve.
6.2 Potentiometer faulty.
7.1 Air lock in pump.
7.2 Worn pump bearings.
8.1 Blanking plugs not
fitted into unused inlets.
DO NOT remove the shower from the installation.
4.1.1 Check water elsewhere in house and if
necessary contact the local Water Company.
4.2.1 Switch off shower and contact Customer
Service.
4.3.1 Clean showerhead.
4.4.1 Clean filters.
5.1.1 Isolate water to unit. Remove check valves.
Clean and replace.
6.1.1 Call Customer Service.
6.2.1 Call Customer Service.
7.1.1 Call Customer Service.
7.2.1 Replace pump.
8.1.1 Fit blanking plugs into unused inlets.
20
Power Shower Thermostatic
As a producer and a supplier of electric showers, Triton Showers is committed to the protection of the environment
Entry Points
Diagram Key:
3
Water Entry Points
Cable Entry Points
WEEE Directive – Policy Statement
via our own environmental policy and the compliance with the WEEE directive.
Triton Showers is fully registered with the Environment Agency under the following schemes:
Repic: Producers take-back scheme (PTS), registration number WEE/EJ3466QV
Valpak: Distributor take-back scheme (DTS), registration number 9659
All our electric products are labelled accordingly with the crossed out wheeled bin symbol. This indicates, for
disposal purposes at end of life, that these products must be taken to a recognised collection points, such as
local authority sites/local recycling centres; this will be free of any charges. Do not return to Triton Showers.
21
UK SERVICE POLICY
In the event of a product fault or complaint occurring, the following
procedure should be followed:
1. Telephone Customer Service on 02476 378495 having available,
your details including post code, the model number and power
rating of the product, together with the date of purchase and, where
applicable, details of the particular fault.
2. If required, the Customer Service Advisor will arrange
for a qualified engineer to call.
3.
All products attended to by a Triton service engineer must be installed
in full accordance with the Triton installation guide applicable to the
product. (Every product pack contains an installation guide, however, they can also be bought via our Customer Service Spares Department).
4.
Our engineer will require local parking and if a permit is required this
must be available to the engineer on arrival at the call.
5. It is essential that you or an appointed representative (who must
be over 18 years of age) is present for the duration of the service
engineer's visit. If the product is in guarantee you must produce proof
of purchase.
6.
Where a call under the terms of guarantee has been booked and
the failure is not product related (i.e. scaling and furring, incorrect
water pressure, pressure relief device operation or electrical/plumbing
installation fault) a charge will be made. A charge will also be issued
if nobody is at home when the service engineer calls or adequate
parking/permit is not available.
7.
If the product is no longer covered by the guarantee an up front fixed
fee will be charged before the site visit.
8. Should proof of purchase not be available on an “in-guarantee” call,
or should the service engineer find that the product is no longer
under guarantee, the engineer will charge the same fixed price and
the customer will be expected to pay the engineer before he leaves.
If payment is not made on the day an administration charge will be
added to the fixed charge.
9.
If a debt is outstanding from a previous visit, or from any other Triton
purchase, Triton reserves the right to withhold service until the debt
has been settled.
10.
Triton takes the health, safety and wellbeing of its employees very
seriously and expects customers to treat all staff members with respect.
Should any employee feel threatened or receive abuse, either verbally
or physically, Triton reserves the right to withhold service and will
support the employee with a legal prosecution.
Replacement Parts Policy
Availability: It is the policy of the manufacturer to maintain parts
availability for the duration of production and a period of five years
thereafter, in accordance with industry standards.
Spare parts are available via our website, www.tritonshowers.co.uk,
or by telephoning Triton Customer Service Spares Department.
Payment should be made by credit/debit card (excluding American
Express or Diners Card). Payment can also be made by pre-payment
of a pro forma invoice by cheque or money order.
Telephone orders are based on information given during of the call.
Before contacting Triton, please verify your requirements
using the information contained in the supplied user guide.
Triton cannot accept liability for incorrect part identification.
TRITON STANDARD GUARANTEE
With the exception of accessories, Triton guarantee the
product against all manufacturing defects for a period of
1 year (for domestic use only) from the date of purchase,
provided that it has been installed by a competent person in
full accordance with the fitting instructions.
All accessories such as shower heads, hoses and riser rails
carry a 1 year parts only guarantee against manufacturing
defects.
Any part found to be defective during this guarantee period
we undertake to repair or replace at our option without
charge so long as it has been properly maintained and
operated in accordance with the operating instructions, and
has not been subject to misuse or damage. This product
must not be taken apart, modified or repaired except by a
person authorised by Triton. This guarantee applies only to
products installed within the United Kingdom and does not
apply to products used commercially. This guarantee does
not affect your statutory rights.
What is not covered:
1. Breakdown due to: a) use other than domestic use by
you or your resident family; b) wilful act or neglect;
c) any malfunction resulting from the incorrect use or
quality of electricity, gas or water or incorrect setting
of controls; d) failure to install in accordance with this
installation guide
2. Claims for missing parts once the product has been
installed.
3. Repair costs for damage caused by foreign objects or
substances.
4. Total loss of the product due to non-availability of parts.
5. Compensation for loss of use of the product or
consequential loss of any kind.
6. Call out charges where no fault has been found with the
appliance.
7. The cost of repair or replacement of pressure relief
devices, showerheads, hoses, riser rails and/or wall
brackets, isolating switches, electrical cable, fuses and/or
circuit breakers or any other accessories installed at the
same time.
8. The cost of routine maintenance, adjustments, overhaul
modifications or loss or damage arising therefrom,
including the cost of repairing damage, breakdown,
malfunction caused by corrosion, furring,
. Call out charges where the water supply cannot be
9
isolated, this includes consequential losses arising from
unserviceable supply valves.