UPS input
connection type
Hardwire
UPS input
connection
description
3 wire single phase input (L1, L2, G)
Recommended
Electrical Service
100A @ 200V-240V (L, N, PE), or 100A @ 200V, 208V, or 240V (L1, L2, G)
Phase Single-Phase
BATTERY
Full load runtime
(minutes)
5.5 minutes (14,400 watts)
Half load runtime
(minutes)
13.5 minutes (7200 watts)
Expandable battery
runtime
Runtime is expandable with external battery packs
External battery
pack compatibility
BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH; BP240V1407C-1PH
Expandable runtime
description
For best results, add external batteries in multiples of two so that both included 8kVA power modules have an equal
number and type of connected battery packs
DC system voltage
(VDC)
240
Battery recharge
rate (included
batteries)
Less than 8 hours from 10% to 90%
Battery replacement
description
Hot-swappable, user replaceable external battery packs
VOLTAGE REGULATION
Voltage regulation
description
2% output voltage regulation in standard online, double-conversion mode
Overvoltage
correction
Corrects overvoltages up to 300V
Undervoltage
correction
Corrects undervoltages as low as 100V
LEDS ALARMS & SWITCHES
LED Indicators 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD
screen offers additional information and control options
Front panel LCD
display
Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options;
LED/LCD panel rotates for viewing in rack/tower formats; LCD Display supports ENGLISH, FRENCH, GERMAN,
ITALIAN, SPANISH and PORTUGUESE (see manual)
Alarms Unique audible alarms for all major UPS, environmental and power conditions (see manual)
Alarm cancel
operation
Alarm cancel switch
Switches 2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and
execute scrolling LCD functions; bundled PDU includes bypass switch to enable hot-swap UPS power module
replacement
SURGE / NOISE SUPPRESSION
UPS AC
suppression
response time
Instantaneous