SmartOnline 208/240V 16kVA 14.4kW DoubleConversion UPS, N+1, 12U, Network Card Options, USB, DB9, Bypass, L6-30R, C19
MODEL NUMBER: SU16KRT
Description
Tripp Lite SU16KRT 16,000VA / 16kVA / 14,400 watt online, double-conversion UPS system offers complete power protection for critical server, network and telecommunications equipment in a 12U rack/tower configuration. This system delivers complete N+1 redundancy when used at loads up to 8kVA, and non-redundant operation at loads between 8 and 16kVA. Fault-tolerant auto-bypass prevents unexpected service interruptions during UPS overload or internal fault conditions. Included parallel PDU with manual bypass switching enables hot-swappable replacement of all major UPS system components in both N+1 and combined operating modes. Enhanced availability, fault tolerance and simple hot-swap replacement options make this UPS ideal for advanced networking applications in data centers, computer rooms, network closets and rugged industrial locations.
Features
●Tripp Lite SU16KRT 16kVA, 16,000VA / 14,400 watt on-line, double-conversion UPS system in 12U total rack/tower configuration
●Unique configuration offers 16kVA non-redundant operation and automatic N+1 redundancy at load levels of 8kVA and under
●Included Parallel PDU with manual bypass switch enables hot-swap replacement of power modules at any supported load level
●Hardwire input; 2 L6-30R and 8 C19 outlets
●Maintains full-time sine wave output within 2% of selectable 200/208/220/230/240V nominal
●Supports 50/60Hz operation for worldwide frequency compatibility
●Expandable runtime with optional external battery packs
●Compatible with Tripp Lite UPS management card options TLNETCARD, WEBCARDLX,
Highlights
●16kVA / 16,000VA / 14,400W on-line double-conversion UPS; 0.9 power factor
●200/208/220/230/240V 50/60Hz output
●Hot-swap power and battery modules, N+1 fault tolerance at loads up to 8kVA
●USB, RS232 & EPO ports; slot for network management card options
●Front panel LEDs with detailed LCD monitoring and control screen
●Expandable runtime with optional external battery packs
●Hardwire input (3 wire); L6-30R & C19 outlets
Package Includes
●Two SU8000RT3UPM UPS power modules
●Two BP240V10RT3U battery packs
●SUPDMB20K parallel PDU with Bypass switch
●4 post rackmount installation rails
●USB, DB9 & EPO cables
1 / 6
SNMPWEBCARD, MODBUSCARD and RELAYIOCARD (NOTE: Applications utilizing any supported network management card option, require the installation of two of the same model network card – install one card per included UPS power module)
●Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)
●Battery independent restart ensures automatic UPS power-up after lengthy power outages, even with expired batteries
●Intelligent battery management system with temperature-compensated charging extends battery life
●HID-compliant USB interface
●USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite's PowerAlert software, available via FREE download from www.tripplite.com/poweralert
●Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks (4 required)
●Optional 2-9USTAND supports upright tower placement (2 required)
●Supports Emergency Power Off (EPO) via built-in interface
●Front panel LEDs and LCD readout with scroll controls
●LED / LCD display panel rotates for viewing in rackmount or tower configurations
●External battery packs are field replaceable and hot swappable
●Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)
Specifications
OVERVIEW
UPC Code |
037332158222 |
|
|
UPS Type |
On-Line |
|
|
INPUT |
|
Rated input current (Maximum Load) |
92A (200V), 88.4A (208V), 76.6A (240V) |
|
|
Nominal Input Voltage(s) Supported |
200V AC; 208V AC; 240V AC |
|
|
UPS Input Connection Type |
Hardwire |
|
|
UPS Input Connection Description |
3 wire single phase input (L1, L2, G) |
|
|
Recommended Electrical Service |
100A @ 200V, 208V, or 240V (L1, L2, G) |
|
|
Input Phase |
Single-Phase |
|
|
OUTPUT |
|
Output Volt Amp Capacity (VA) |
16000 |
|
|
Output kVA Capacity (kVA) |
16 |
|
|
Output Watt Capacity (Watts) |
14400 |
|
|
2 / 6
Output kW Capacity (kW) |
14.4 |
|
|
|
|
Output Capacity Details |
Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30 |
|
|
seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power; |
|
|
Double conversion mode is automatically restored as load levels are reduced to 95% or less |
|
|
|
|
Power Factor |
0.9 |
|
|
|
|
Crest Factor |
3:1 |
|
|
|
|
Nominal Voltage Details |
Voltage selection via front panel LCD interface |
|
|
|
|
Frequency Compatibility |
50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion |
|
|
|
|
Frequency Compatibility Details |
Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to |
|
|
50Hz or 50Hz to 60Hz (no de-rating) |
|
|
|
|
Output Voltage Regulation (Line |
+/- 2% |
|
Mode) |
||
|
||
|
|
|
Output Voltage Regulation (Battery |
+/- 2% |
|
Mode) |
||
|
||
|
|
|
Output Circuit Breakers |
Two built-in 30A breakers protect one L6-30R outlet each; Eight built-in 20A breakers protect one C19 outlet each |
|
|
|
|
Output AC Waveform (AC Mode) |
Pure Sine wave |
|
|
|
|
Output AC Waveform (Battery |
Pure Sine wave |
|
Mode) |
||
|
||
|
|
|
Nominal Output Voltage(s) |
200V; 208V; 240V |
|
Supported |
||
|
||
|
|
|
Output Receptacles |
(2) L6-30R; (8) C19 |
|
|
|
|
Individually Controllable Load Banks |
No |
|
|
|
|
BATTERY |
|
|
Battery Type |
Valve Regulated Lead Acid (VRLA) |
|
|
|
|
Full Load Runtime (min.) |
5.5 minutes (14,400 watts) |
|
|
|
|
Half Load Runtime (min.) |
13.5 minutes (7200 watts) |
|
|
|
|
Expandable Battery Runtime |
Runtime is expandable with external battery packs |
|
|
|
|
Expandable Runtime |
Yes |
|
|
|
|
Expandable Runtime Description |
For best results, add external batteries in multiples of two so that both included 8kVA power modules have an equal |
|
|
number and type of connected battery packs |
|
|
|
|
External Battery Pack Compatibility |
<a class="productLink" href="//www.tripplite.com/external-240v-tower-battery-pack-tripp-lite-3-phase-ups- |
|
|
systems-3u~BP240V10RT3U">BP240V10RT3U</a> ; <a class="productLink" |
|
|
href="//www.tripplite.com/external-240v-battery-pack-select-tripp-lite-ups-systems-built-in-charger~BP240V787C- |
|
|
1PH">BP240V787C-1PH</a> |
|
|
|
|
DC System Voltage (VDC) |
240 |
|
|
|
|
Battery Recharge Rate (Included |
Less than 6 hours from 10% to 90% (typical, full load discharge) |
|
Batteries) |
||
|
||
|
|
|
Battery Replacement Description |
Hot-swappable, user replaceable external battery packs |
|
|
|
|
VOLTAGE REGULATION |
|
|
Voltage Regulation Description |
2% output voltage regulation in standard online, double-conversion mode |
|
|
|
3 / 6