Tripp-Lite SU1500RTXLCDN Data Sheet

SmartOnline 120V 1.5kVA 1.35kW Double­Conversion UPS, 2U Rack/Tower, Extended Run, WEBCARDLX Network Interface, LCD, USB, DB9
MODEL NUMBER: SU1500RTXLCDN
Protects connected mission-critical equipment against damage, downtime and data loss due to blackouts, brownouts, power surges and line noise. Pre-installed WEBCARDLX network interface permits remote UPS management, including reboots.
Description
Highlights
Zero transfer time suitable for advanced network applications
2% output voltage regulation in online and battery modes
Expandable runtime with optional external battery packs
Pre-installed WEBCARDLX network interface
14 min. runtime at half load; 4.2 min. at full load
Package Includes
SU1500RTXLCDN SmartOnline 120V 1.5kVA 1.35kW On-Line Double-Conversion UPS
Pre-installed WEBCARDLX network interface
USB cable
DB9 cable
EPO cable
Mounting hardware
Owner’s manual
Featuring six NEMA 5-15R outlets in two switchable numbered load banks, as well as a NEMA 5-15P input, the SU1500RTXLCDN has an internal battery that provides 14 minutes of support at half load and
4.2 minutes at full load. Adding external battery packs, such as BP48V24-2U (sold separately), provides extended runtime.
The Java-free HTML5-based WEBCARDLX interface enables full remote access for site power and UPS status monitoring, configuration, control and email notifications via secure web browser, SNMP, telnet or SSH. It supports 10/100 Mbps auto-sensing for optimum communication with an Ethernet network. Optional EnviroSense2 modules (sold separately) provide a variety of environmental monitoring capabilities. Protocols supported include HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet, SSH, FTP, DHCP and NTP.
EMI/RFI noise filtering improves your equipment’s performance and prevents damage. A 570-joule surge suppression rating protects your equipment from harmful power surges. With Tripp Lite’s free downloadable PowerAlert® software, the SU1500RTXLCDN enables safe unattended system shutdown and file saves in case of a prolonged power failure. An audible alarm indicates startup/shutdown, power
1 / 7
failure, low battery, overload and fault conditions.
Features
Protects Mission-Critical Rack-Mounted EquipmentProvides fully regulated sine wave AC output for
servers, network storage devices and telecom hardware+/-2% voltage regulation in online and battery modesSelectable 100/110/120/127V output voltage6 NEMA 5-15R outlets10 ft. power cord with NEMA 5­15P input570-joule surge suppression rating Reliable Battery Backup with Expandable RuntimeSupports half load for 14 min. and full load for 4.2 min.Zero transfer time suitable for advanced network applicationsExpandable runtime with optional external battery packs, such as Tripp Lite’s BP48V24-2UBattery independent restart ensures automatic UPS power-up after lengthy power outages, even with expired batteries Pre-Installed WEBCARDLX Network InterfaceAllows full remote access for power monitoring, configuration, control and email notifications via secure web browser, SNMP, telnet or SSHOptional EnviroSense2 sensors (sold separately) enable site monitoring of temperature, humidity and contact­closure status Switchable Numbered Load BanksOutlets are divided into 2 numbered load banks, each of which may be individually powered on and off remotely to reset or reboot connected equipment Interactive LCD ScreenReports detailed status information, including load, voltage and battery levelsOffers advanced configuration and setup options, including output voltage and operating mode EMI/RFI Line Noise FilteringRemoves electromagnetic and radio frequency interference that can disrupt or damage equipment’s performance
Audible AlarmIndicates startup/shutdown, power failure, low battery, overload and fault conditions Communications PortsUSB and DB9 ports enable data-saving unattended shutdown when used with
Tripp Lite’s PowerAlert software (available via free download at poweralert)EPO port supports emergency shutdown in large facilities Versatile Installation OptionsHardware included for 4-post mounting in 2U of EIA-standard 19 in. rackMounts on wall or 2-post rack with optional 2POSTRMKITWMMounts in upright tower position with optional 2-9USTAND
Specifications
OVERVIEW
UPC Code 037332192813 UPS Type On-Line
INPUT
Rated input current (Maximum Load) 12A Nominal Input Voltage(s) Supported 100V AC; 110V AC; 115V AC; 120V AC; 127V AC Nominal Input Voltage Description 120V factory default UPS Input Connection Type 5-15P Input Circuit Breakers 20A UPS Input Cord Length (ft.) 10 UPS Input Cord Length (m) 3.1 Recommended Electrical Service 15A 120V Input Phase Single-Phase
OUTPUT
Output Volt Amp Capacity (VA) 1500
2 / 7
Output kVA Capacity (kVA) 1.5 Output Watt Capacity (Watts) 1350 Output kW Capacity (kW) 1.35 Output Capacity Details ON LINE MODE: Maximum output capacity ratings is reduced to 1215 watts at 115V nominal and 1080 watts at
100V nominal; FREQUENCY REGULATION / CONVERSION MODE: Maximum output ratings are reduced in frequency regulation / conversion mode (127/120V 945 watts / 115V 850 watts / 110V 804 watts / 100V 756 watts)
OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150% load for 30 seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE
bypass limits) Power Factor 0.9 Crest Factor 3:1 Nominal Voltage Details 120V factory-default nominal voltage; Less than 3% THD for linear loads and less than 5% for non-linear computer
loads Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion Frequency Compatibility Details ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output
matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds
+/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz.
FREQUENCY REGULATION / CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency
input is 40 to 70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. BATTERY
MODE: Output is regulated to +/-0.05Hz. Output Voltage Regulation (Line
Mode) Output Voltage Regulation
(Economy Line Mode) Output Voltage Regulation (Battery
Mode)
+/- 2%
+/- 10%
+/- 3%
Load Management Receptacles Two switchable three-outlet 5-15R load banks Output AC Waveform (AC Mode) Pure Sine wave Output AC Waveform (Battery
Mode) Nominal Output Voltage(s)
Supported
Pure Sine wave
100V; 110V; 115V; 120V; 127V
Output Receptacles (6) 5-15R Individually Controllable Load Banks Yes
BATTERY
Full Load Runtime (min.) 4.2 min. (1350w) Half Load Runtime (min.) 14 min. (675w) Expandable Battery Runtime Extended runtime supported via optional external battery packs External Battery Pack Compatibility  <a class="productLink" href="// External-48V-2U-Rack-Tower-Battery-Pack-Enclosure-DC-
Cabling-select-UPS-Systems~BP48V24-2U">BP48V24-2U</a>  (limit 1);  <a class="productLink"
href="// External-48V-3U-Rack-Tower-Battery-Pack-Enclosure-DC-Cabling-select-UPS-
Systems~BP48V60RT-3U">BP48V60RT-3U</a>  (multi-pack compatible);  <a class="productLink"
href="// External-48V-2U-Rack-Tower-Battery-Pack-for-UPS-Systems~BP48V27-2US">BP48V27-
2US</a>  (multi-pack compatible) Expandable Runtime Description Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software, see
manual for details
3 / 7
Loading...
+ 4 hidden pages