SmartOnline 120V 1.5kVA 1.35kW DoubleConversion UPS, 2U Rack/Tower, Extended Run,
WEBCARDLX Network Interface, LCD, USB, DB9
MODEL NUMBER: SU1500RTXLCDN
Protects connected mission-critical equipment against damage, downtime and data loss due to blackouts,
brownouts, power surges and line noise. Pre-installed WEBCARDLX network interface permits remote
UPS management, including reboots.
Description
The SU1500RTXLCDN SmartOnline® 120V 1.5kVA 1.35kW On-Line Double-Conversion UPS provides
battery backup and AC power protection against blackouts, brownouts, power surges and line noise that
can damage electronics or destroy data. It converts AC input to DC power, and then converts DC to fully
regulated sine wave AC output with +/-2% voltage regulation in online and battery modes.
Highlights
●
Zero transfer time suitable for
advanced network applications
●
2% output voltage regulation in
online and battery modes
●
Expandable runtime with
optional external battery packs
●
Pre-installed WEBCARDLX
network interface
●
14 min. runtime at half load; 4.2
min. at full load
Package Includes
●
SU1500RTXLCDN SmartOnline
120V 1.5kVA 1.35kW On-Line
Double-Conversion UPS
●
Pre-installed WEBCARDLX
network interface
●
USB cable
●
DB9 cable
●
EPO cable
●
Mounting hardware
●
Owner’s manual
Featuring six NEMA 5-15R outlets in two switchable numbered load banks, as well as a NEMA 5-15P
input, the SU1500RTXLCDN has an internal battery that provides 14 minutes of support at half load and
4.2 minutes at full load. Adding external battery packs, such as BP48V24-2U (sold separately), provides
extended runtime.
The Java-free HTML5-based WEBCARDLX interface enables full remote access for site power and UPS
status monitoring, configuration, control and email notifications via secure web browser, SNMP, telnet or
SSH. It supports 10/100 Mbps auto-sensing for optimum communication with an Ethernet network.
Optional EnviroSense2 modules (sold separately) provide a variety of environmental monitoring
capabilities. Protocols supported include HTTP, HTTPS, SMTP, SNMPv1, SNMPv2, SNMPv3, telnet,
SSH, FTP, DHCP and NTP.
EMI/RFI noise filtering improves your equipment’s performance and prevents damage. A 570-joule surge
suppression rating protects your equipment from harmful power surges. With Tripp Lite’s free
downloadable PowerAlert® software, the SU1500RTXLCDN enables safe unattended system shutdown
and file saves in case of a prolonged power failure. An audible alarm indicates startup/shutdown, power
1 / 7
failure, low battery, overload and fault conditions.
Features
Protects Mission-Critical Rack-Mounted EquipmentProvides fully regulated sine wave AC output for
servers, network storage devices and telecom hardware+/-2% voltage regulation in online and battery
modesSelectable 100/110/120/127V output voltage6 NEMA 5-15R outlets10 ft. power cord with NEMA 515P input570-joule surge suppression rating
Reliable Battery Backup with Expandable RuntimeSupports half load for 14 min. and full load for 4.2
min.Zero transfer time suitable for advanced network applicationsExpandable runtime with optional
external battery packs, such as Tripp Lite’s BP48V24-2UBattery independent restart ensures automatic
UPS power-up after lengthy power outages, even with expired batteries
Pre-Installed WEBCARDLX Network InterfaceAllows full remote access for power monitoring,
configuration, control and email notifications via secure web browser, SNMP, telnet or SSHOptional
EnviroSense2 sensors (sold separately) enable site monitoring of temperature, humidity and contactclosure status
Switchable Numbered Load BanksOutlets are divided into 2 numbered load banks, each of which may
be individually powered on and off remotely to reset or reboot connected equipment
Interactive LCD ScreenReports detailed status information, including load, voltage and battery
levelsOffers advanced configuration and setup options, including output voltage and operating mode
EMI/RFI Line Noise FilteringRemoves electromagnetic and radio frequency interference that can disrupt
or damage equipment’s performance
Audible AlarmIndicates startup/shutdown, power failure, low battery, overload and fault conditions
Communications PortsUSB and DB9 ports enable data-saving unattended shutdown when used with
Tripp Lite’s PowerAlert software (available via free download at poweralert)EPO port
supports emergency shutdown in large facilities
Versatile Installation OptionsHardware included for 4-post mounting in 2U of EIA-standard 19 in.
rackMounts on wall or 2-post rack with optional 2POSTRMKITWMMounts in upright tower position with
optional 2-9USTAND
Specifications
OVERVIEW
UPC Code 037332192813
UPS Type On-Line
INPUT
Rated input current (Maximum Load) 12A
Nominal Input Voltage(s) Supported 100V AC; 110V AC; 115V AC; 120V AC; 127V AC
Nominal Input Voltage Description 120V factory default
UPS Input Connection Type 5-15P
Input Circuit Breakers 20A
UPS Input Cord Length (ft.) 10
UPS Input Cord Length (m) 3.1
Recommended Electrical Service 15A 120V
Input Phase Single-Phase
OUTPUT
Output Volt Amp Capacity (VA) 1500
2 / 7
Output kVA Capacity (kVA) 1.5
Output Watt Capacity (Watts) 1350
Output kW Capacity (kW) 1.35
Output Capacity Details ON LINE MODE: Maximum output capacity ratings is reduced to 1215 watts at 115V nominal and 1080 watts at
100V nominal; FREQUENCY REGULATION / CONVERSION MODE: Maximum output ratings are reduced in
frequency regulation / conversion mode (127/120V 945 watts / 115V 850 watts / 110V 804 watts / 100V 756 watts)
OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150%
load for 30 seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and
frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE
bypass limits)
Power Factor 0.9
Crest Factor 3:1
Nominal Voltage Details 120V factory-default nominal voltage; Less than 3% THD for linear loads and less than 5% for non-linear computer
loads
Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency Compatibility Details ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output
matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds
+/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz.
FREQUENCY REGULATION / CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency
input is 40 to 70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. BATTERY
MODE: Output is regulated to +/-0.05Hz.
Output Voltage Regulation (Line
Mode)
Output Voltage Regulation
(Economy Line Mode)
Output Voltage Regulation (Battery
Mode)
+/- 2%
+/- 10%
+/- 3%
Load Management Receptacles Two switchable three-outlet 5-15R load banks
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery
Mode)
Nominal Output Voltage(s)
Supported
Pure Sine wave
100V; 110V; 115V; 120V; 127V
Output Receptacles (6) 5-15R
Individually Controllable Load Banks Yes
BATTERY
Full Load Runtime (min.) 4.2 min. (1350w)
Half Load Runtime (min.) 14 min. (675w)
Expandable Battery Runtime Extended runtime supported via optional external battery packs
External Battery Pack Compatibility <a class="productLink" href="// External-48V-2U-Rack-Tower-Battery-Pack-Enclosure-DC-
Cabling-select-UPS-Systems~BP48V24-2U">BP48V24-2U</a> (limit 1); <a class="productLink"
href="// External-48V-3U-Rack-Tower-Battery-Pack-Enclosure-DC-Cabling-select-UPS-
Systems~BP48V60RT-3U">BP48V60RT-3U</a> (multi-pack compatible); <a class="productLink"
href="// External-48V-2U-Rack-Tower-Battery-Pack-for-UPS-Systems~BP48V27-2US">BP48V27-
2US</a> (multi-pack compatible)
Expandable Runtime Description Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software, see
manual for details
3 / 7