Tripp Lite SU120KX2 User Manual

PROTECT
YOUR INVESTMENT!
Completed and signed start-up forms
by Tripp Lite to activate your warranty.
SmartOnline™ 3-Phase UPS Systems
Input/Output: 220/380V, 230/400V or 240/415V AC, 3O, 4-wire + ground
Owner’s Manual
Model: SU120KX2
Not suitable for mobile applications.
1
2
3
4
5
6
7
8
9
10
11
12
13
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2012 Tripp Lite. All trademarks are the sole property of their respective owners.
1
12-212-93-3141.indb 1 12/28/2012 11:16:51 AM
14
Table of Contents
1
1 Introduction 3
2 Important Safety Instructions 4
2
3 Control Panel Features 6 4 Front and Rear Panel Features 7 5 Cabinet Installation 9
3
5-1 Preparation 9 5-2 Unpacking 9 5-3 Placement 10
6 Wiring 11
4
6-1 Wiring Warnings 11 6-2 Wiring Preparation 11 6-3 UPS System Terminal Block Diagram 12 6-4 External Battery Cabinet Wiring Diagrams 12
5
6-5 Electrical and Cable Data 13 6-6 External Battery Cabinet Wiring 14 6-7 AC Input/Output Wiring (Single UPS—SUS) 14 6-8 AC Input/Output Wiring (Parallel Configuration—2x MUS) 15
6
6-9 AC Input/Output Wiring (Parallel Configuration—4x MUS) 16
7 Operating Modes 17
7-1 Online (Normal) Mode (Single UPS—SUS) 17
7
7-2 Battery Backup Mode (Single UPS—SUS) 17 7-3 Auto Bypass Mode (Single UPS—SUS) 17 7-4 Manual Bypass Mode (Single UPS—SUS) 17 7-5 On-line (Normal) Mode (Parallel UPS—MUS) 18
8
7-6 Battery Backup Mode (Parallel UPS—MUS) 18 7-7 Auto Bypass Mode (Parallel UPS—MUS) 18 7-8 Manual Bypass Mode (Parallel UPS—MUS) 19 7-9 External Maintenance Bypass (Parallel UPS—MUS) 19
9
8 Start-Up, Shutdown and Bypass 20
8-1 Control Panel and Breaker Diagrams 20 8-2 Preliminary Checklist (Single UPS—SUS) 20 8-3 Standard Start-Up Procedure (Single UPS—SUS) 21
10
8-4 Battery Start-Up Procedure (Single UPS—SUS) 22 8-5 Manual Bypass Procedure (Single UPS—SUS) 22 8-6 Shutdown Procedure (Single UPS—SUS) 24 8-7 Preliminary Checklist (Parallel UPS—MUS) 24
11
8-8 Start-Up Procedure (Parallel UPS—MUS) 25 8-9 Shutdown Procedure (Parallel UPS—MUS) 26 8-10 Switching to Manual Bypass Mode from Normal Mode
(Parallel UPS—MUS) 27
12
8-11 Switching to Normal Mode from Manual Bypass Mode (Parallel UPS—MUS) 28
9 Power Module Status and Replacement 29
9-1 Power Module Features and Status 29 9-2 Preliminary Replacement Checklist 29 9-3 Replacement Procedure 29
10 Display and Configuration 30
10-1 Control Panel Diagram 30 10-2 Display Hierarchy 30 10-3 Default Display 31 10-3-1 Status Display 31 10-4 Main Menu 34 10-5 UPS Setup 36 10-5-1 Bypass Setup 37 10-5-2 Output Setup 38 10-5-3 Battery Setup 40 10-5-4 Charger Setup 43 10-5-5 Parallel Setup 44 10-5-6 Control & Test Setup 45 10-5-7 Local Setup 47 10-6 Maintenance 50
11 Communications 52
11-1 Communications Interfaces 52 11-2 SNMPWEBCARD Slot 52 11-3 Input Dry Contact Interface 52 11-4 Remote Emergency Power Off (EPO) Circuit Diagram 53 11-5 Auxiliary Dry Contact Input Circuit Diagram 53 11-6 External Battery Cabinet Temperature Inputs 53 11-7 External Battery Status Input 53 11-8 Output Dry Contact Interface Detail 54 11-9 Output Dry Contact Circuit Diagram 55 11-10 RS-232 Serial Port Circuit Diagram 55 11-11 Parallel Configuration Port 55
12 Specifications 56
12-1 UPS System Technical Specifications 56 12-2 UPS System Floor Loading Table 56
13 Storage and Service 57 14 Warranty 58
Español 59
Français 117
Русский 175
13
14
2
12-212-93-3141.indb 2 12/28/2012 11:16:51 AM
1 – Introduction
Tripp Lite’s SmartOnline 3-Phase KX2-Series UPS System (Model SU120KX2) is ideal for backing up and protecting data centers, telecommunications (VoIP), networks, industrial facilities, security/emergency systems and more.
1
Advanced Features:
• True on-line double conversion with superior IGBT inverter technology
• Low input current THDi allows 1:1 generator sizing for maximum efficiency and cost savings
• Internal N+1 power module redundancy
• Built-in parallel or hot standby redundancy capability for increased capacity or fault-tolerance
• Up to 120kVA capacity in compact footprint; up to 480kVA in parallel capacity configuration with 4 units
• High input power factor and high efficiency with low thermal loss and low noise
• Simplified, easy-to-repair, long-life, high-availability system design
• Redundant auxiliary power and control circuits within each power module and at the system level
• Single feed input design
• Supports external battery cabinets for extended battery backup runtime
• High-resolution LCD status screen simplifies operation and delivers detailed operational information, including system block diagrams
2
3
4
5
6
7
8
9
10
11
12
13
14
3
12-212-93-3141.indb 3 12/28/2012 11:16:51 AM
2 – Important Safety Instructions
1
SAVE THESE INSTRUCTIONS
All sections of this manual contains instructions and warnings that should be followed during the installation and operation of the UPS
2
systems described in this manual. Read all instructions thoroughly before attempting to move, install or operate the UPS systems described in this manual. Failure to comply may invalidate the warranty and cause property damage and/or personal injury.
Location Warnings
3
• Install the UPS system in a controlled indoor environment, away from moisture, temperature extremes, flammable liquids and gasses, conductive contaminants, dust and direct sunlight.
• Install the UPS system in a level, structurally sound location.
4
• The UPS system is extremely heavy; be extremely careful when moving or lifting the unit.
• Operate the UPS system at indoor temperatures between 32° F and 104° F (0° C and 40° C) only. For best results, maintain indoor temperatures
between 62° F and 84° F (17° C and 29° C).
• Leave adequate space around all sides of the UPS system for proper ventilation. Do not block, cover or insert objects into the external ventilation
5
openings of the cabinet.
• Do not place any object on the unit, especially containers of liquid.
• Do not mount the unit with its front or rear panel facing down (at any angle). Mounting in this manner will seriously inhibit the unit’s internal
cooling, eventually causing product damage not covered under warranty.
6
• Do not install the UPS system near magnetic storage media, as this may result in data corruption. Keep all recorded magnetic media a minimum of 60 cm (24 inches) away from the UPS system.
• Do not attempt to stack the UPS system. Attempting to stack the UPS system may cause permanent damage and create a potential for serious personal injury.
7
• The casters are designed for minor position adjustments within the final installation area only. The casters are not designed for moving the UPS system over longer distances.
• The casters are not designed to provide long-term support for the UPS system after final installation. Use the levelers to provide long-term support.
8
• When moving the UPS system, push from the front or rear, not from the sides.
• Do not attempt to unpack or move the UPS system without assistance.
Connection Warnings
9
• The power supply for the UPS system must be 3-phase rated in accordance with the equipment nameplate. It also must be suitably grounded and wired according to all applicable national and local electrical wiring standards, codes and regulations.
• The UPS system contains hazardous high voltages that have the potential to cause personal injury or death from electric shock.
• The UPS system has its own energy source (battery – internal and/or external). The output terminals may be live even when the UPS system is
10
11
12
not connected to an AC supply.
• If the UPS system receives power from a motor-powered AC generator, the generator must provide clean, filtered, computer-grade output.
• Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life
support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
• The UPS system is designed to power modern computer loads and associated peripheral devices. Do not use the UPS system to power pure inductive or capacitive loads.
• Input and output wiring should be performed by trained, qualified electricians only.
• Due to high leakage current, a proper earth ground connection is essential before connecting the AC supply.
• Isolate the UPS system before working on the circuit. An easily accessible disconnect device should be incorporated in the fixed wiring. The
disconnect device must disconnect all line conductors simultaneously when opened.
13
14
4
12-212-93-3141.indb 4 12/28/2012 11:16:52 AM
2 – Important Safety Instructions (continued)
Battery Warnings
• The UPS system does not require routine maintenance. There are no user-serviceable parts inside. Only qualified service personnel should open the access panels for any reason.
• Batteries present a risk of electrical shock and burns from high short-circuit current. Battery connection or replacement should be performed only by qualified service personnel, observing proper precautions. Turn off the UPS system before connecting or disconnecting internal batteries. Use tools with insulated handles. Do not open the batteries. Do not short or bridge the battery terminals with any object.
• Replace batteries with equivalent batteries available from Tripp Lite. Do not operate the UPS system without batteries.
• The batteries are recyclable. Refer to local codes for disposal requirements.
• Do not dispose of the batteries in a fire, mutilate the batteries or open the battery coverings.
• Battery fuses should be replaced by qualified service personnel only. Blown fuses must be replaced with the same number and type of fuses.
• Potentially lethal voltages exist within the UPS system as long as the battery supply is connected. Service and repair should be performed
by trained personnel only, while the UPS system is turned off or placed into bypass mode. Disconnect internal batteries (if present) before performing any service work by switching off the internal battery circuit breaker and removing the battery fuse(s). Disconnect external batteries (if present) by switching off the external battery cabinet breaker and disconnecting the external battery cabling from the UPS system.
• Do not connect or disconnect batteries when the UPS system is operating from the battery supply or when the unit is not in bypass mode.
• External batteries must be replaced by equivalent batteries available from Tripp Lite.
• Before connecting an external battery cabinet to the UPS system, read the external battery cabinet’s documentation. Use only external battery
cabinets that have been approved by Tripp Lite.
• If the UPS system remains off for an extended period of time, it should be turned on periodically to allow the batteries to recharge. The UPS system should be turned on and the batteries should be recharged at least one uninterrupted 24-hour period every 3 months. Failure to recharge the batteries periodically may cause irreversible battery damage.
1
2
3
4
5
6
Wiring Warnings
• See Section 6-1 for wiring warnings
7
8
9
10
11
12
13
14
5
12-212-93-3141.indb 5 12/28/2012 11:16:52 AM
3 – Control Panel Features
1
A E F G H I J KBCD
2
3
4
“NORMAL” LED: This green light illuminates to indicate that the UPS system is in online (normal) mode. The primary AC input supply is
A
present and within standard operating parameters.
“BATTERY” LED: This amber light illuminates when the UPS system is in battery backup mode, discharging the batteries to provide power
B
5
6
7
8
9
10
11
12
13
to connected equipment. An audible alarm will also sound.
“BYPASS” LED: This amber light illuminates when the UPS system is in bypass mode (auto bypass or manual bypass). Battery backup
C
power will not be available to connected equipment while the UPS system is in bypass mode, but connected equipment loads will be supported by the bypass (reserve) power source.
“FAULT” LED: This red light illuminates when any UPS system or input power fault occurs. Available diagnostic information will be
D
displayed on the LCD screen.
LCD Status Screen: This illuminated LCD status screen displays text and graphics to indicate a wide range of UPS system operating
E
conditions and diagnostic data. Note: The LCD backlight will turn off after 10 minutes of inactivity. Turn on the backlight by momentarily pressing the ON button or one of the scroll buttons.
“ESC” (Escape) Button: Press this button to return to the previous page or menu.
F G
Scroll Buttons ( and ): Press these buttons to move the cursor up or down and navigate the control panel menus and screens. These
buttons are also used for data entry in several screens.
Enter Button ( ): Press this button to select a menu item or confirm a setting change.
H
ON Button: Press and hold this button for 3 seconds to turn the UPS system’s inverter ON.
I
J
OFF Button: Press and hold this button for 3 seconds to turn the UPS system’s inverter OFF. If the UPS system is in online (normal) mode, it
will switch to auto bypass mode.
Note: Switching the inverter OFF does not stop the converter stage of the UPS and therefore, the connected battery is still charging as required.
Note: After switching the inverter OFF, if the battery circuit breaker or AC main input circuit breaker are opened and remain open for an extended period of time, the batteries should be recharged periodically. At a minimum, the batteries should be charged for an uninterrupted 24-hour period every 3 months to maintain their longest usable life. Failure to recharge the batteries may cause irreversible battery damage.
“EPO” (Emergency Power Off) Button: Press this button to turn the UPS system’s output OFF and also disable bypass output.
K
If the UPS system is in battery backup mode when the EPO button is activated:
• Main output and bypass output are turned off, the alarm sounds, fans shut down after approximately one minute, and control circuitry remains active.
• Releasing the EPO button (by pressing it again) turns off the UPS system completely, including the alarm and control circuit. Press the ON button for 3 seconds to restart the UPS system.
If the UPS system is in online (normal) mode when the EPO button is activated:
• Main output and bypass output are turned off, the alarm sounds, fans and control circuitry remain active.
• Releasing the EPO button (by pressing it again) turns off the alarm and places the UPS system in auto bypass mode. Press the ON button
for 3 seconds to return the UPS system to online (normal) mode.
See Section 10 – Display and Configuration for detailed information about the control panel’s menus and displays.
14
6
12-212-93-3141.indb 6 12/28/2012 11:16:53 AM
4 – Front and Rear Panel Features
A
B
1
2
3
4
5
6
D E C
G
H H
Front View
Control Panel: The control panel allows the operator to monitor and control the UPS system. See Section 3 – Control Panel Features for
A
more information.
B
Internal Power Modules: 20kVA internal power modules can be replaced in the field without powering down connected equipment loads.
The SU120KX2 contains 6 internal power modules capable of N+1 redundancy.
C
Output Circuit Breaker Switch (Q4): Controls AC output power.
D
Manual Bypass Circuit Breaker Switch (Q3): Controls AC input power to the UPS system during manual bypass operation.
E
Bypass Input Circuit Breaker Switch (Q2): Controls AC input power to the UPS system during auto bypass operation.
F
Main Input Circuit Breaker Switch (Q1): Controls AC input power to the UPS system during online (normal) operation.
G
Levelers: The levelers provide long-term support for the UPS system.
H
Casters: The casters are designed for small position adjustments within the final installation location only; they are not designed for moving
the UPS system over longer distances. The casters are not designed to provide long-term support for the UPS system after final installation. Use the levelers to provide long-term support.
F
G
7
8
9
10
11
12
13
14
7
12-212-93-3141.indb 7 12/28/2012 11:16:56 AM
4 – Front and Rear Panel Features (continued)
1
J
2
L
M K N
3
4
5
6
7
O
8
H
9
H
Levelers: The levelers provide long-term support for the UPS system.
I
Casters: The casters are designed for small position adjustments within the final installation location only; they are not designed for moving
10
11
12
13
14
the UPS system over longer distances. The casters are not designed to provide long-term support for the UPS system after final installation. Use the levelers to provide long-term support.
Accessory Slot: Remove the cover panel to install a Tripp Lite SNMPWEBCARD accessory. The SNMPWEBCARD accessory provides an
J
Ethernet interface for the UPS system and enables remote monitoring and control via SNMP, Web browser or telnet. Visit www.tripplite.com for more information about the SNMPWEBCARD accessory.
K
RS-232 Serial Communications Port: This DB9 port connects the UPS system to compatible workstations or servers, enabling automatic
shutdown during extended blackouts and monitoring of operating and power conditions.
L
Parallel Configuration Port: These DB9 ports connect the UPS system to another UPS system, or chain of systems, of identical type and
capacity for use in a parallel configuration (up to 4 systems).*
*A pair of DIP switches are set to 1/On or 0/Off on each UPS, depending on the parallel configuration.
M
Input Dry Contact Interface: This interface receives dry contact signals that allow the UPS system to receive commands and monitor external battery conditions. See Section 11 - Communications for more information.
Output Dry Contact Interface: This interface allows the UPS system to send information via dry contact communications. See Section 11 –
N
Communications for more information.
Terminal Block Cover: Remove the terminal block cover to access the UPS system’s input, bypass input, external battery cabinet, output and
O
grounding connection terminals. Wiring conduits pass through the circular knockouts in the terminal block cover. See Section 6 – Wiring for more information, including a detailed diagram of the terminal block.
I I
Rear View
H
8
12-212-93-3141.indb 8 12/28/2012 11:17:05 AM
5 – Cabinet Installation
1
Read Section 2 – Important Safety Instructions Before Installation
5-1 Preparation
The UPS system must be installed in a structurally sound area with a level floor that is able to bear the weight of the UPS system, any external battery cabinet and other equipment that will be installed nearby. The installation site should also have a dedicated AC circuit available that is compatible with the UPS system’s input requirements. (See Section 12 – Specifications for details on input requirements and floor loading requirements.) Before unpacking the unit, you should transport the shipping container closer to the final installation site to minimize the distance you will need to move the unit after the protective shipping container has been removed. If you plan to store the UPS system for an extended period before installation, follow the instructions in Section 13 – Storage and Service. (Unpacking and storage instructions are also printed on the “Unpacking and Storage Instructions” sheet secured to the shipping container.) Warning: Do not attempt to unpack or move the UPS system
without assistance.
5-2 Unpacking
1
• Inspect the shipping container(s) for visible damage. If you determine that the unit has been damaged during shipping, contact Tripp Lite for assistance. Do not attempt to use the UPS system if it has been damaged or mishandled.
2
• Confirm that the shipping container is upright and use a screwdriver to remove its top panel, front panel and back panel. Also remove the plastic wrap and interior cushioning material. Confirm that the model name and rating at the rear of the cabinet match the unit you ordered. Examine the cabinet for any damaged or loosened parts. Confirm that the shipping container includes the accessories that ship with the unit.
The UPS system should include:
• AnRS-232serialcable
• Aparallelconfigurationcable
• AremoteEPOwiringconnector(2contacts)
• Adryinputcontactconnector(4contacts)
• Adryoutputcontactconnector(12contacts)
• SoftwareCD-ROM
If any of the package contents are missing or damaged, please
contact Tripp Lite for assistance.
3
• Confirm that the unit is stable, then remove the side panels from the shipping container.
1
2
3
4
5
6
7
8
9
10
11
2-3
• Remove the bolts from the shipping brackets securing the unit
4
to the pallet, then remove the shipping brackets from the UPS system. Warning: Be extremely careful, as the unit could shift
unexpectedly.
5
• Use several of the screws you removed in step 2 to attach the top panel of the shipping container to the front edge of the shipping pallet. The smooth surface of the panel should face upward so that it can be used as a ramp for rolling the unit off the shipping pallet. Do not attempt to use the top panel as a ramp if it is cracked or otherwise structurally damaged. Make sure the casters at the bottom of the unit are unlocked. Using extreme caution, slowly roll the unit down the ramp with the aid of several assistants.
12-212-93-3141.indb 9 12/28/2012 11:17:18 AM
4-5
9
12
13
14
5 – Cabinet Installation (continued)
1
5-3 Placement
• Use the casters to move the UPS system for a short distance over
1
2
3
4
5
6
7
8
9
a level, smooth, stable surface. Do not attempt to use the casters to move the UPS system over longer distances. The UPS system should be moved close to its final installation location inside its shipping container before it is unpacked from the shipping container. Use a mechanical device of sufficient capacity to move the shipping container. Warning: The UPS system could tip if it
is moved over an unstable surface. Be extremely careful when moving the UPS system. Push the UPS system from the front or rear, not from the sides.
2
• Position the UPS system in a structurally sound area with a level floor that is able to bear the weight of the UPS system, any external battery cabinets and other equipment that will be installed nearby. The installation site should also have a dedicated AC circuit available that is compatible with the UPS system’s input requirements. (See the Section 12 – Specifications for more information about input requirements and floor loading requirements.) The UPS system must be installed in a clean, secure environment with a relative humidity less than 90% (non­condensing). Operate the UPS system at indoor temperatures between 17° C and 29° C (62° F and 84° F). Prevent damage to cabling by using suitable protective conduits. In order to maintain proper airflow and service access, you must maintain the following clearances:
• At least 100 cm (39.4”) clearance in front of the UPS system.
• At least 50 cm (19.7”) clearance behind the UPS system.
• At least 50 cm (19.7”) clearance above the UPS system.
Warning: The cooling fans circulate air from front to back. Do not use any air conditioning or fan that blows air directly toward the rear of the UPS system.
• After moving the UPS system to its final location, lock the casters
3
A
and use the levelers B to stabilize the cabinet. Ensure that all
four levelers make firm contact with the floor.
1
50 cm (19.7 in.)
50 cm (19.7 in.)
100 cm (39.4 in.)
2
A
B
10
• Attach the balance supports on either side of UPS using 4 bolts.
4
Caution: The UPS system may topple over in unexpected circumstances if both balance supports are not properly installed.
3
11
4
• For emergency use, install a fire extinguisher rated for energized
5
12
electrical equipment fires (Class C rating or exact equivalent, with a non-conductive extinguishing agent) near the UPS system.
13
5
14
10
12-212-93-3141.indb 10 12/28/2012 11:17:21 AM
6 – Wiring
DANGER! LETHAL HIGH VOLTAGE HAZARD!
All wiring should be performed by a qualified electrician in accordance with the warnings in this manual, all applicable electrical and safety codes, and good wiring practices. Incorrect wiring may damage the UPS system severely and cause serious personal injury and property damage. Read Section 2 – Important Safety Instructions before proceeding.
1
2
6-1 Wiring Warnings
• De-energize all input and output power sources of the UPS system before installing cables or making electrical connections.
• Use flexible cable of sufficient length to permit UPS system servicing. The maximum cable length is 10 m (32.8 ft).
• Use ferrule caps to cover termination cables within mechanical lugs, or use compression lugs in order to prevent frayed ends from shorting on
the UPS system terminal block.
• Use cabling rated VW-1, FT-1 or better.
• Use cable sleeves and connector clamps.
• The neutral conductor must be the same size as the current conductors.
• Tighten all field wiring terminal connections with a torque of at least 3.95 N·m (35 in·lb); a torque of 11.8 N·m (100 in·lb) is required for the
“In”, “Out” and “Battery” bolt-screw terminals.
• Confirm that all cables are marked correctly according to their purpose, polarity, phase and diameter.
• If the UPS system’s input/output power source is wye-wye, then “Neutral” and “Ground” must not be re-bonded at the UPS.
• If the input power source has VNG>0, install a grounded wye secondary isolation transformer with a properly bonded neutral to ground before
the UPS system and input power source.
• For equipment requiring a neutral connection to an IT power distribution system that requires neutral isolation upon disconnect, the disconnect device must be a four-pole device and must disconnect all line conductors and the neutral conductor. If a disconnect device interrupts the neutral conductor, it must simultaneously interrupt all line conductors.
• Allow the batteries to charge uninterrupted for 24 hours after the initial wiring connection and UPS startup.
• Observe proper polarity by connecting negative to negative, positive to positive and the center point of the battery string to the normal “N”
terminal. Do not bond the battery’s “N” terminal to the AC power “Neutral” or “Ground” as damage may result. Failure to observe proper polarity will damage the UPS system and create a serious risk of personal injury and property damage.
• Observe proper phase by connecting R to R, S to S, T to T and N to N. Source power phase rotation must be verified as RST before powering the UPS. Failure to observe proper phase will damage the UPS system and create a risk of personal injury and property damage.
3
4
5
6
7
8
6-2 Wiring Preparation
• De-energize all input and output (AC and DC) of the UPS system and external battery cabinet (if present).
• Mark all cables according to their correct purpose, polarity, phase and diameter.
• Review the diagrams in Section 6-3 and Section 6-4 to familiarize yourself with the terminal blocks.
• Consult the table in Section 6-5 to find the correct electrical input/output characteristics for the UPS system.
Note: If the UPS system’s input/output power source is wye-wye, then “Neutral” and “Ground” must not be re-bonded at the UPS. If the input power source has VNG>0, install an isolation transformer as part of the UPS input power source and bond “Neutral” and “Ground” together at the isolation transformer’s output.
9
10
11
12
13
14
11
12-212-93-3141.indb 11 12/28/2012 11:17:22 AM
6 – Wiring (continued)
1
6-3 UPS System Terminal Block Diagram
2
3
4
R RS ST TN NN
AC Input Battery Output
5
6-4 External Battery Cabinet Wiring Diagrams
6
7
8
+
Grounding Terminals
9
10
11
12
13
Battery and Circuit Breaker Diagram shown for illustration only; consult the battery cabinet’s documentation for exact specifications.
Notes:
• All internal wiring is UL-listed, MTW, 125C Hi-Flex cable.
• Terminal block is UL-recognized and rated for 600 VDC.
• Breaker is UL-listed and rated for 250 A, 600 VDC, 25 KAIC.
14
• Cabinets with breakers are shipped with the breaker in the off/open position.
• Battery arrangements shown are typical but may vary depending on cabinet and battery type.
12
12-212-93-3141.indb 12 12/28/2012 11:17:22 AM
6 – Wiring (continued)
6-4 External Battery Cabinet Wiring Diagrams (continued)
SU120KX2 schematic representation shown
External Battery Cabinets
10 Year Cabinet: 55AH, 78AH, 103AH, 140AH; 250A, 600VDC Circuit Breaker
1
2
3
4
5
6
6-5 Electrical and Cable Data
Model Input Output
SU120KX2
380Y/220V,
400Y/230V, or
415Y/240V AC, 3Ø,
4-wire + ground
380Y/220V,
400Y/230V, or
415Y/240V AC, 3Ø,
4-wire + ground
Input, Bypass and
Output Breaker Size
225A
Input, Reserve, Output and Battery Cable Size
120mm²
(4/0 AWG)
Battery Circuit
Breaker Fuse Size
250A
Battery
Cable Size
120mm²
(4/0 AWG)
7
8
9
10
11
12
13
14
13
12-212-93-3141.indb 13 12/28/2012 11:17:23 AM
6 – Wiring (continued)
1
6-6 External Battery Cabinet Wiring
Warning: External battery cabinets vary. Read the external battery cabinet’s documentation before attempting to connect it to the UPS
2
system. Use only external battery cabinets that have been approved by Tripp Lite.
Note: An external battery cabinet is required with model SU120KX2. Contact Tripp Lite for external battery cabinet ordering information.
• De-energize all input and output (AC and DC) of the UPS system and external battery cabinet, and confirm that the external battery cabinet
1
breaker switch is off. (If the UPS system has already been wired to an AC power source, see Section 8-6 for shutdown instructions.)
3
• Remove the terminal block covers from the UPS. Remove the front cover and conduit plates (if provided) of the external battery cabinet.
2 3
• Connect the positive (+), normal (N) and negative (-) UPS system connection terminals of the external battery cabinet to the corresponding positive (+), normal (N) and negative (-) external
4
5
6
7
8
9
battery connection terminals of the UPS system. See Section 6-3 and the external battery cabinet’s documentation for terminal block diagrams. See Section 6-4 for wiring diagrams. See Section
6-5 for cable size requirements. Cabling should be protected by
flexible conduit and routed through the appropriate knockouts in the terminal block cover. Warning: Observe proper polarity by
connecting negative to negative, positive to positive and center point of the battery string to normal “N”. Failure to observe proper polarity will damage the UPS system and create a risk of personal injury and property damage.
Note: Do not bond the battery “N” terminal to the AC power neutral or ground as damage may result.
4
• Connect the external battery cabinet’s grounding terminal UPS system’s corresponding grounding terminal (25 mm²) ground cable. Keep the ground cable connected at all times after installation.
5
• Connect the UPS system’s primary grounding terminal to your facility’s earth ground with a 4 AWG (25 mm²) minimum equipment grounding conductor (EGC) cable within the same conduit used in item 3 above. Keep the EGC cable connected at all times after installation.
• Replace the conduit landing cover of the external battery cabinet. If
6
you do not plan to wire the AC input/output of the UPS system at this time, replace the terminal block cover of the UPS system.
with a 4 AWG
B
A
to the
3
A
4
B
6-7 AC Input/Output Wiring (Single UPS—SUS)
1
• After de-energizing all input and output (AC and DC) of the UPS
10
system, remove the terminal block cover from the UPS system.
11
12
2
• Remove the UPS system’s front bezel to expose the circuit breakers. First, confirm that the main input circuit breaker switch
13
Q1
and the bypass input circuit breaker switch Second, confirm that the manual bypass circuit breaker switch is off. Third, confirm that the output circuit breaker switch off.
Q2
are both off.
14
Q4
1
Q3
is
2
14
Q4 Q2 Q1Q3
12-212-93-3141.indb 14 12/28/2012 11:17:25 AM
6 – Wiring (continued)
6-7 AC Input/Output Wiring (Single UPS—SUS) (continued)
3
• Connect the UPS system’s primary grounding terminal to your facility’s earth ground with a 4 AWG (25 mm²) minimum equipment grounding conductor cable. Keep the EGC cable connected at all times after installation.
4
• Confirm the phase of each cable, then connect the cables according to the UPS system terminal block diagram in
Section 6-3. See Section 6-5 for cable size requirements.
Cabling should be protected by flexible conduit and routed through the appropriate knockouts in the terminal block cover. Warning: Observe proper phase rotation
by connecting R to R, S to S, T to T and N to N. Failure to observe proper phase rotation will damage the UPS system and create a risk of personal injury and property damage.
5
• Replace the UPS system’s terminal block cover.
6-8 AC Input/Output Wiring: Parallel Configuration – 2x MUS (Multiple Unit System)
Parallel Configuration – MUS Warnings:
• The total cable length for each UPS must be within 10% of each of the other parallel-configured UPS in order to prevent
unbalanced load sharing between the individual UPS. (IP1 + OP1 = IP2 + OP2 = IP3 + OP3 = IP4 + OP4, minimum/maximum deviation must be < 10%).
• Parallel configurations are supported for 2, 3, or 4 UPS units only. Do not attempt to configure more than 4 UPS systems via
parallel configuration.
• Each UPS system to be parallel configured for either N+1 redundancy or capacity, must have the same rating, kVA capacity, and
system and power module level firmware version (see Section 10-6). Attempting to configure dissimilar UPS systems may be inhibited or may cause damage to the UPS systems and create a risk of personal injury and property damage.
• Each UPS must have its parallel group set to 2 and a different “Parallel ID” that indicates the UPS systems are operating in
parallel (see Section 10-5-5 for more details).
• Follow the steps in Section 6-7, wiring the UPS systems as shown in the diagram
1
• Each UPS is shipped with (1) parallel configuration cable included. Connect each UPS parallel communication port(s) as shown and select
2
the correct position of the parallel port dip switches (either both ON (down) or both OFF (up) as shown in the diagram
R RS ST TN NN+–
AC Input Battery Output
Grounding Terminals
1
.
1
.
1
2
3
4
5
6
7
8
9
10
11
12
DASHED LINES INDICATE USER-SUPPLIED PARTS AND CABLES.
1
13
14
15
12-212-93-3141.indb 15 12/28/2012 11:17:25 AM
6 – Wiring (continued)
1
6-9 AC Input/Output Wiring: Parallel Configuration – 4x MUS (Multiple Unit System)
Parallel Configuration – MUS Warnings:
2
3
4
5
6
• The total cable length for each UPS must be within 10% of each of the other parallel-configured UPS in order to prevent unbalanced load sharing between the individual UPS. (IP1 + OP1 = IP2 + OP2 = IP3 + OP3 = IP4 + OP4, minimum/maximum deviation must be < 10%).
• Parallel configurations are supported for 2, 3, or 4 UPS units only. Do not attempt to configure more than 4 UPS systems via parallel configuration.
• Each UPS system to be parallel configured for either N+1 redundancy or capacity, must have the same rating, kVA capacity, and system and power module level firmware version (see Section 10-6). Attempting to configure dissimilar UPS systems may be inhibited or may cause damage to the UPS systems and create a risk of personal injury and property damage.
• Each UPS must have its parallel group set to 2 and a different “Parallel ID” that indicates the UPS systems are operating in parallel (see Section 10-5-5 for more details).
1
• Follow the steps in Section 6-7, wiring the UPS systems as shown in the diagram
• Each UPS is shipped with (1) parallel configuration cable included. Connect each UPS parallel communication port(s) as shown and select
2
the correct position of the parallel port dip switches (either both ON (down) or both OFF (up) as shown in the diagram
1
.
1
.
10
11
12
7
8
9
DASHED LINES INDICATE USER-SUPPLIED PARTS AND CABLES.
1
13
14
16
12-212-93-3141.indb 16 12/28/2012 11:17:26 AM
7 – Operating Modes
This section provides a basic description of the UPS system’s operating modes. The one-line diagrams used are schematic representations. For more information about switching between operating modes, refer to Section 8 – Start-Up, Shutdown and Bypass.
7-1 Online (Normal) Mode (Single UPS—SUS)
In online (normal) mode, the UPS system’s rectifier converts incoming AC utility power to DC power that charges the batteries and supplies the inverter. The inverter transforms the DC power to precision-regulated, pure sine wave AC power that supports the operation of connected equipment. This dual conversion technology isolates connected equipment from all power problems and ensures that connected equipment receives ideal power at all times.
1
2
3
4
7-2 Battery Backup Mode (Single UPS—SUS)
When a power outage or other extreme power event occurs, the UPS system automatically switches from normal mode to battery backup mode. The UPS system’s batteries (internal and/or external) provide emergency DC power to the inverter. The inverter transforms the DC power to precision-regulated, pure sine wave AC power that supports the operation of connected equipment.
7-3 Auto Bypass Mode (Single UPS—SUS)
If the inverter malfunctions due to excessive temperature, overload, output short circuit, abnormal voltage or battery problems, the inverter will shut down. If the UPS system detects a bypass (reserve) power source that conforms to normal parameters, then the UPS system automatically switches to auto bypass mode to continue supplying power to connected equipment. When all problems are eliminated, the UPS system switches back to online (normal) mode automatically.
7-4 Manual Bypass Mode (Single UPS—SUS)
If UPS system maintenance or repair is required, you can bypass the UPS system and enable bypass (reserve) power manually. After confirming that the bypass source is present (input AC available and Q3 open), transfer to manual bypass mode by first pressing the off button to stop the inverter. This transfers the UPS to static internal bypass. Next, switch the UPS system into manual bypass mode. (See Section 8-5 for complete manual bypass procedure.) The one-line diagram illustrates the system status and flow of power after the manual bypass procedure has been completed. This allows service technicians to perform maintenance or repair procedures without interrupting the flow of AC power to connected equipment. Warning: After switching to manual
bypass mode to perform selected maintenance or repair procedures, the UPS may require complete shutdown to affect those repairs. Use of an external 3-breaker maintenance bypass panel can facilitate this and still maintain AC power to the connected equipment.
3 PH, 4W + G
IN
POS, NEG, N + G
EXT BATT
CLOSED
5
6
7
OPEN
Q3
CLOSED
FB
Q2
CLOSED
Q1
6 X 20KVA MODULES
FB
STS
FB
CLOSED
Q4
PARALLEL
3 PH, 4W + G
PORTS
8
OUT
9
10
11
12
13
14
17
12-212-93-3141.indb 17 12/28/2012 11:17:27 AM
7 – Operating Modes (continued)
1
7-5 Online (Normal) Mode (Parallel UPS—MUS)
Parallel configuration provides UPS system redundancy or increased total capacity. Under parallel configuration, the
2
total load is shared by 2 to 4 UPS systems. If one of the UPS systems malfunctions, the total connected equipment load is supported by the remaining UPS systems. If the total load exceeds the capacity of the remaining UPS systems, the MUS
3
will switch all UPS units to auto bypass mode. The diagram illustrates the on-line mode for a 2x MUS.
4
7-6 Battery Backup Mode (Parallel UPS—MUS)
Similar to battery backup mode for a single UPS system (Section 7-2), except the total connected equipment load is
5
shared by the parallel UPS systems (2 to 4). The diagram illustrates the battery backup mode for a
2x MUS.
6
7
7-7 Auto Bypass Mode (Parallel UPS—MUS)
Similar to auto bypass mode for a single UPS system (Section 7-3), except with parallel UPS systems (2 to 4).
8
The diagram illustrates the auto bypass mode for a 2x MUS.
9
10
11
12
13
14
18
12-212-93-3141.indb 18 12/28/2012 11:17:28 AM
7 – Operating Modes (continued)
7-8 Manual Bypass Mode (Parallel UPS—MUS)
Similar to manual bypass mode for a single UPS system (Section 7-4), except with parallel UPS systems (2 to 4).
Note: All UPS systems must be switched into manual bypass mode.
The diagram illustrates the manual bypass mode for a 2x MUS.
7-9 External Maintenance Bypass Mode (Parallel UPS—MUS)
Utilizing the external parallel cabinet with system level maintenance bypass panel, the parallel UPS systems can be completely isolated for maintenance or repair procedures while the connected equipment remains powered.
Transfer to external maintenance bypass mode should only be accomplished once each individual UPS unit has been placed in auto or manual bypass first.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
19
12-212-93-3141.indb 19 12/28/2012 11:17:29 AM
8 – Start-Up, Shutdown and Bypass
1
Warning: The UPS system’s output voltage and frequency are set at 220/380V, 50Hz by default. If you require output voltage of 230/400V or 240/415V, or a frequency of 60Hz, you must change the UPS system’s output voltage and/or frequency by accessing the output setup menu described in Section 10-5-2. You must place the UPS system in bypass mode before changing the output voltage. Do not connect your
2
equipment to the UPS system’s output until you have set the proper parameters.
8-1 Control Panel and Breaker Diagrams
“NORMAL” LED
A
3
“BATTERY” LED
B
“BYPASS” LED
C
“FAULT” LED
D
4
LCD Status Screen
E F
“ESC” (Escape) Button
Scroll Buttons ( and )
G
Enter Button ( )
H
5
ON Button
I
OFF Button
J K
“EPO” (Emergency Power Off) Button
6
Main Input Circuit Breaker Switch
Q1
Bypass Input Circuit Breaker Switch
Q2
Manual Bypass Circuit Breaker Switch
Q3
Output Circuit Breaker Switch
Q4
7
A
B
C
D
1
Q4
Output Manual
2
Circuit Breaker Switches (UPS System Front Panel)
E
Control Panel
Q3
Bypass
G
Q2
Bypass
Input
F
I
J
H
Q1
Main Input
K
8-2 Preliminary Checklist (Single UPS—SUS)
• All circuit breaker switches should be off, including the breaker of the external battery cabinet.
8
• Confirm that no voltage potential exists between Neutral and Ground.
• Confirm that the input power source matches the rating (voltage, frequency and phase) of the UPS system.
Note: After start-up, the UPS system will perform a brief self-test and display the results on the LCD screen. After a successful self-test, the UPS system will provide AC power to the connected equipment load.
9
10
11
12
13
14
20
12-212-93-3141.indb 20 12/28/2012 11:17:30 AM
8 – Start-Up, Shutdown and Bypass (continued)
8-3 Standard Start-Up Procedure (Single UPS—SUS)
• With the external battery cabinet connected, switch on the circuit
1
breaker of the external battery cabinet.
1
2
3
2
• Confirm that the manual bypass circuit breaker switch Q3 is off.
• Switch on the bypass input breaker switch Q2 and then output
3
circuit breaker switch Q4. After a brief initialization process, the LCD screen will show “ON AUTO BYPASS”, the “BYPASS” LED will illuminate and UPS system output will be supplied by the input power source via the bypass path.
4
• Switch on the main input circuit breaker switch Q1. If the AC
input power source is normal, the UPS system is ready for start-up.
Note: In addition to the external battery cabinet breaker being turned on, the normal on-line running status of the four (4) circuit breakers is: Q1, Q2 and Q4 On (closed); Q3 Off (open). This is shown in the diagram 4 to the right.
1
4
5
Q3
Output Manual
2
Q4 Q2
Output Manual
3
Bypass
Bypass
Bypass
Input
Bypass
Input
Main Input
Main
Input
Q1
6
7
8
9
• Press the ON button A for 3 seconds (until you hear a beep), then
5
release the button. The inverter will activate and synchronize with the bypass source, then automatically switch from auto bypass mode to online (normal) mode. The “BYPASS” LED B will turn off and the “NORMAL” LED C will illuminate.
Output Manual
4
C
B
5
Bypass
Bypass
Input
A
Main
Input
10
11
12
13
14
21
12-212-93-3141.indb 21 12/28/2012 11:17:31 AM
8 – Start-Up, Shutdown and Bypass (continued)
1
8-4 Battery Start-Up Procedure (Single UPS—SUS)
Note: The battery must be at least partially charged for this operation to succeed.
2
• With the external battery cabinet connected, switch on the circuit
1
breaker of the external battery cabinet.
3
4
2
• Confirm that the main input circuit breaker switch Q1, bypass input circuit breaker switch Q2, manual bypass circuit breaker switch Q3 and output circuit breaker switch Q4 are all off.
5
6
3
• Press the ON button A for 3 seconds (until you hear a beep), then release the button. The inverter will activate and use stored DC battery power to supply AC power to the output circuit breaker.
7
The “BATTERY” LED
Warning: The output voltage and frequency must be set to the desired values PRIOR to applying UPS inverter output to the connected load (See Section 10-5-1).
B
will illuminate.
8
• After confirming output voltage and frequency are correct, turn on
4
output circuit breaker Q4 to supply battery-derived power to the connected equipment.
9
1
Q3Q4
Output
2
B
3
Q4
Manual
Bypass
Q2 Q1
Bypass
Input
A
Main Input
10
Output
4
Manual Bypass
Bypass
Input
Main Input
8-5 Manual Bypass Procedure (Single UPS—SUS)
Warning: Placing the UPS system in manual bypass will disable the inverter and power all loads from the manual bypass source path, but
11
the UPS system will still be energized. Before performing maintenance or repair on the UPS system, shut down and de-energize the UPS system completely by following the steps in Section 8-5. Although connected equipment loads will be powered through the bypass power path, they will not receive battery backup in the event of a utility power failure or out limits event.
To transfer the connected equipment load to Manual Bypass from NORMAL mode:
1
• With the UPS in NORMAL mode (green LED A ON, LCD
12
displays “Load Protected – On Line Mode”), stop the inverter by pressing and holding the red OFF (“O”) button B until the UPS beeps, then release the button and answer “YES” to the question “Transfer to Bypass Mode?”. The UPS should transfer to Bypass.
13
2
• Confirm the UPS is in BYPASS mode (amber Bypass LED C is ON; LCD displays “Load Unprotected – On Auto Bypass”). Do not proceed if it is not in BYPASS mode.
A
C
1
B
14
22
12-212-93-3141.indb 22 12/28/2012 11:17:32 AM
8 – Start-Up, Shutdown and Bypass (continued)
8-5 Manual Bypass Procedure (Single UPS—SUS) (continued)
3
• Turn OFF the MAIN INPUT circuit breaker Q1.
4
• Wait until the Power Module fans turn OFF (this may take a minute or two), then turn OFF the BATTERY BREAKER. Note:
The external battery cabinets will have the BATTERY BREAKER behind the front door/panel or elsewhere.
5
• Turn ON the MANUAL BYPASS circuit breaker Q3. The LCD will display “Load Unprotected – On Manual Bypass” and you will hear an audible alarm.
6
• Turn OFF the OUTPUT circuit breaker Q4.
7
• Turn OFF the BYPASS INPUT circuit breaker Q2. The unit’s LCD will go blank after a few seconds.
• The critical load is now supported by unconditioned utility power in manual bypass mode. In this mode, only the manual bypass path
8
3-8
(including manual bypass breaker Q3), the load terminals of the output breaker Q4] and the terminal block contain hazardous voltage, allowing qualified service personnel to perform maintenance or repair.
Note: Use of an external 3-breaker maintenance bypass panel is recommended if the connected equipment is to be powered during complete de-energized maintenance or repair/service procedures on the UPS system.
To transfer the critical load to NORMAL mode from Manual Bypass mode:
1
1. Confirm the UPS is in MANUAL BYPASS (the MANUAL BYPASS circuit breaker Q3 is ON; the OUTPUT Q4, BYPASS INPUT Q2 and MAIN INPUT Q1 circuit breakers are OFF).
2
2. Turn ON the BATTERY BREAKER. For the external battery cabinets, the BATTERY BREAKER will be behind the front door/ panel or elsewhere.
3. Turn ON the BYPASS INPUT circuit breaker Q2 (the amber
3
Bypass LED should come on and the LCD will display “Load
1
Unprotected-On Manual Bypass).
4. Confirm the amber BYPASS LED is ON. Do not proceed if it is
4
not ON.
5. Turn ON the OUTPUT circuit breaker Q4.
5
6
6. Turn OFF the MANUAL BYPASS circuit breaker Q3. The LCD will display “Load Unprotected-On Auto Bypass”.
7. Turn ON the MAIN INPUT circuit breaker Q1. The Power
7
3
Module fans will turn ON.
8. Press and hold the green ON button until the UPS beeps, then
8
release the button. The UPS will perform a self-test diagnostic and the LCD will display “Self Diagnosis”. After the UPS self-test is completed, the UPS will transfer to NORMAL mode (green LED ON and LCD displays “Load Protected-On Line Mode”).
9. Confirm there are no active alarms present (“!” on the display and
9
audible beeping). If an alarm is present, press the UP or DOWN arrows to display the active alarm. Correct the action as required.
10
10. Scroll through the Measure Menu and confirm all input and output power readings are within the recommended specifications.
11
11. If any problems are noted, contact your technical support personnel for further assistance.
12. The critical load is now supported by conditioned battery back-up power.
12
6
6 5 7 3
Q3 Q1Q4 Q2
Output Manual
Q4 Q3 Q2 Q1
Output Manual
Q2
Q3
Bypass
Bypass
Bypass
Input
Bypass
Input
5
7
Q4
Q1
Main
Input
Main
Input
1
2
3
4
5
6
7
8
9
10
11
12
13
14
23
12-212-93-3141.indb 23 12/28/2012 11:17:34 AM
8 – Start-Up, Shutdown and Bypass (continued)
1
8-6 Shutdown Procedure (Single UPS—SUS)
Warning: The UPS system shutdown procedure will eliminate the AC power output for all loads. Before shutdown, confirm that all loads
2
are turned off or place the UPS system in manual bypass mode (See Section 8-5) to keep loads powered by the bypass power path.
• If the UPS is in NORMAL mode (green LED A ON, LCD
1
displays “Load Protected-On Line Mode”), then you must stop the inverter by pressing and holding the OFF button B until the UPS
3
4
5
6
beeps, then release the button. The UPS will transfer to Bypass.
2
• Confirm the UPS is in BYPASS (amber Bypass LED C is ON; LCD displays “Load Unprotected-On Auto Bypass”). Do not proceed if it is not on BYPASS.
3
• Turn OFF the OUTPUT circuit breaker Q4.
• Turn OFF the MAIN INPUT circuit breaker Q1.
4 5
• Turn OFF the BYPASS UNIT circuit breaker Q2.
6
• Wait until the Power Module fans turn OFF and the LCD display goes blank (this may take a minute or two), then turn OFF the BATTERY BREAKER. The external battery cabinets will have the BATTERY BREAKER behind the front door/panel or elsewhere.
Note: If the UPS system remains off for an extended period of time, it should be turned on periodically to allow the batteries to recharge. The UPS system should be turned on and the batteries should be recharged at least one uninterrupted 24-hour period every 3 months. Failure to recharge the batteries periodically may cause irreversible battery damage.
1
2
Position of circuit breaker switches shown as in manual bypass mode.
A
C
3 5 4
Q3 Q1Q4 Q2
Output Manual
Bypass
Bypass
Input
B
Main Input
7
8-7 Preliminary Checklist (Parallel UPS—MUS)
Warning: Parallel configurations of two, three or four UPS systems (for N+1 redundancy or capacity) are allowed. Do not attempt to link more than four UPS systems via parallel configuration. All UPS systems must have the same rating, kVA capacity and power module level firmware version (See Section 10-6) for parallel UPS configuration. Attempting to link dissimilar UPS systems will damage the UPS
8
systems and create a serious risk of personal injury and property damage.
• All circuit breaker switches should be off, including the battery breakers of the external battery cabinets.
• Confirm that no voltage potential exists between Neutral and Ground.
9
10
• Confirm that the input power source matches the rating (voltage, frequency and phase) of the UPS systems.
• Each UPS must have its parallel group set to 2 and a different “Parallel ID” that indicates the UPS systems are running in parallel.
See Section 10-5-5 for more details.
Note: After start-up, the UPS systems will perform a brief self-test and display the results on the LCD screen. After a successful self-test, the UPS systems will provide AC power to the connected equipment load.
11
12
13
14
24
12-212-93-3141.indb 24 12/28/2012 11:17:35 AM
8 – Start-Up, Shutdown and Bypass (continued)
8-8 Start-Up Procedure (Parallel UPS—MUS)
• Connect the parallel configuration cable A (shipped with each
1
UPS) to the DB9 parallel configuration port B of each UPS system. Note: Before starting up the Parallel UPS system, ensure
that the “Parallel ID” is different for each UPS and parallel group is set to 2. See Section 10-5-5 for more details.
Refer to Section 6-8 or 6-9 for the appropriate settings of the parallel port DIP switches and parallel cable connections.
1
• With each UPS system’s external battery cabinet connected, switch
2
on the external battery cabinet circuit breaker switch of each battery cabinet.
2
3
• Confirm that the manual bypass breaker Q3 on each UPS system is off. Switch on the bypass input circuit breaker switch Q2 of each UPS system. After a brief initialization process, the LCD screen will show “ON AUTO BYPASS” and the “BYPASS” LED will illuminate.
B B
Q3
A
Q2
1
2
3
4
5
6
7
4
• Switch on the main input circuit breaker switch Q1 of each UPS system.
5
• Press the ON button A of one of the UPS systems for 3 seconds (until you hear a beep), then release the button. The inverter will activate and synchronize with the bypass source. Press the ON button for each of the other UPS systems for 3 seconds (until you hear a beep), then release the button. When the inverter of each UPS system is operating normally, they will automatically switch from auto bypass mode to on-line (normal) mode at the same time. The “BYPASS” LEDs B will turn off and the “NORMAL” LEDs
C
will illuminate.
6
• Check the output voltage of each UPS system. The phase voltage deviation between each UPS system should be less than 5V. If the phase deviation is within the acceptable range, switch on the output circuit breaker switch Q4 of each UPS system. Note: For more
information on checking the output voltage of each UPS system, see Section 10-4.
Output Manual
3
Bypass
Bypass
Input
Main Input
8
Q1
9
Output Manual
4
Bypass
C
B
Bypass
Input
Main
Input
A
10
11
5
12
Q4
13
Output Manual
6
Bypass
Bypass
Input
Main Input
14
25
12-212-93-3141.indb 25 12/28/2012 11:17:46 AM
8 – Start-Up, Shutdown and Bypass (continued)
1
8-9 Shutdown Procedure (Parallel UPS—MUS)
Warning: The UPS system shutdown procedure will eliminate the AC power output for all loads. Before shutdown, confirm that all loads
2
are turned off or place the UPS systems in manual bypass mode (See Section 8-10) to keep loads powered by the bypass power path.
1
• For the UPS system you wish to shut down, press the OFF button
A
for 3 seconds (until you hear a beep), then release the button.
If the other UPS systems can support the connected equipment
3
4
5
6
loads alone, the UPS system that was turned off will shut down its inverter and its LCD screens will read “LOAD NOT POWERED”. The other UPS system’s LCD screen will read “ONLINE MODE”. If the total connected equipment load is too large to be handled by the remaining UPS systems, all UPS systems will shut down their inverters and switch to bypass mode, and their LCD screens will read “ON AUTO BYPASS”.
Confirm the UPS you wish to shut down is in bypass mode (amber bypass LED B is on, LCD displays “ON AUTO BYPASS”).
2
• For the UPS system you wish to shut down, switch off the main input circuit breaker switch Q1, then switch off the output circuit breaker switch Q4.
B
1
A
Q1Q4
• For the UPS system you wish to shut down, switch off the bypass
3
7
input circuit breaker switch Q2.
8
4
• When the UPS system is completely shut down, the LCD screen
9
10
11
will be completely off. Wait until the power module fans power off and the LCD display goes blank (this may take a minute or two). Then, switch off the external battery cabinet circuit breaker switch of each battery cabinet connected to the UPS you wish to shut down.
Note: If the UPS system remains off for an extended period of time, it should be turned on periodically to allow the batteries to recharge. The UPS system should be turned on and the batteries should be recharged at least one uninterrupted 24-hour period every 3 months. Failure to recharge the batteries periodically may cause irreversible battery damage.
Output Manual
2
Output Manual
3
4
Bypass
Bypass
Bypass
Input
Q2
Bypass
Input
Main
Input
Main
Input
12
13
14
26
12-212-93-3141.indb 26 12/28/2012 11:17:47 AM
8 – Start-Up, Shutdown and Bypass (continued)
8-10 Switching to Manual Bypass Mode from Normal Mode Procedure (Parallel UPS—MUS)
Warning: When the UPS system is in manual bypass, the inverter shuts down. Connected equipment loads are powered by the bypass power path and will not receive battery backup during a utility power failure or out of limits event.
• For the first UPS system you wish to transfer to manual bypass
1
mode, press the OFF button A for 3 seconds (until you hear a beep), then release the button. If the other UPS systems can support the connected equipment loads, the UPS system that was turned off will shut down its inverter and its LCD screen will read “LOAD NOT POWERED”. All other UPS systems’ LCD screens will read “ONLINE MODE”. If the total connected equipment load is too large to be handled by the remaining UPS systems, all UPS systems will shut down their inverters and switch to bypass mode, and their LCD screens will read “ON AUTO BYPASS”. Repeat step 1 for each UPS system you wish to transfer to manual bypass mode.
Confirm that all UPS systems are in auto bypass mode.
2
• Switch off the main input circuit breaker switch Q1 of each UPS system.
1
A
Q1
1
2
3
4
5
3
• Switch on the manual bypass input circuit breaker switch Q3 of each UPS system. The bypass power path will power the loads and all LCD screens will read “ON MANUAL BYPASS”.
4
• Switch off the bypass input circuit breaker switch Q2 and the output circuit breaker switch Q4 of each UPS system. Wait for the power module fans and the LCD screen to turn off completely (this may take a minute or two).
5
• Switch off the external battery cabinet circuit breaker switch of each battery cabinet.
Output
2
Manual
Bypass
Q3
Bypass
Input
Main
Input
6
7
Output
3
Manual Bypass
Bypass
Input
Main
Input
8
Q2Q4
9
Output
4
Manual Bypass
Bypass
Input
Main
Input
10
11
6
• In this mode, only the manual bypass path (including the manual
5
12
bypass circuit breaker Q3), the load terminals of the output circuit breaker switch Q4 and the terminal block B contain hazardous voltage, allowing qualified service personnel to perform maintenance or repair. Note: Qualified service personnel may
Q4 Q3
B
13
prefer to de-energize the UPS systems completely, depending on local codes and the nature of the maintenance or repair. Use of a parallel cabinet with system level maintenance bypass is recommended.
12-212-93-3141.indb 27 12/28/2012 11:17:51 AM
27
6
14
8 – Start-Up, Shutdown and Bypass (continued)
1
8-11 Switching to Normal Mode from Manual Bypass Mode (Parallel UPS—MUS)
• If the UPS systems have external battery cabinets connected,
1
2
3
4
5
switch on the external battery cabinet circuit breaker switch of each battery cabinet for each UPS.
2
• Switch on the bypass input circuit breaker switch Q2 and the output circuit breaker switch Q4 of each UPS system.
1
Q2Q4
6
• Confirm that all UPS systems are in manual bypass mode, then
3
switch off the manual bypass input circuit breaker switch Q3 of each UPS system. The LCD screen will read “ON AUTO BYPASS”.
7
8
• Switch on the main input circuit breaker switch Q1 of each UPS
4
system.
9
• Press the ON button A of the first UPS system for 3 seconds (until
5
10
you hear a beep), then release the button. Press the ON button for each of the remaining UPS system for 3 seconds (until you hear a beep), then release the button. When the inverters of all UPS systems are operating normally, they will switch to on-line
11
(normal) mode at the same time.
Output Manual
2
Output
3
Output
4
Bypass
Q3
Manual Bypass
Manual
Bypass
Bypass
Input
Bypass
Input
Bypass
Input
Main Input
Main
Input
Q1
Main Input
A
5
12
13
14
28
12-212-93-3141.indb 28 12/28/2012 11:17:51 AM
9 – Power Module Status and Replacement
Warning: Only authorized Tripp Lite service technicians with knowledge and operational training of this equipment should install, repair or remove any system components, including power modules. Only power modules with the same firmware versions may be placed within the same UPS system frame. Verify power module firmware version before replacement. Permanent power module removal or addition can only be performed by Tripp Lite authorized service technicians.
9-1 Power Module Features and Status
1
2
Each Power Module features an LED indicator to inform the user of its status.
LED Indicator Statuses
“ON”—The power module is active and functioning properly. “FLASHING”—The power module has failed and is offline. “OFF”—When the locking latch is in “UNLOCKED” ( ) position, the
power module is inactive.
When the locking latch is in “LOCKED” ( ) position and the
main power is on, the power module has failed.
9-2 Preliminary Replacement Checklist
• BeforeremovingaPowerModule,ensurethattheremainingPowerModulescansupporttheconnectedload.
• VerifythatthePowerModuleneedsserviceorreplacementviaitsindividualLEDstatusindicator.
• DonotattempttoremovePowerModulesbyyourself.PowerModulesweigh30kg(66lb)andrequireatleasttwopeopleforproperhandling.
• PowerModulescanbereplacedinanyUPSOperatingMode.Itisnotnecessarytopowerloadsofforleavethemunprotected.Note: UPS must
be able to support load without the Power Modules to be replaced. If the UPS cannot handle the load once the Power Module is deactivated, an overload will occur and the UPS will shut down.
• Replacepowermoduleswithsamefirmwareversiononly.
9-3 Replacement Procedure
To Remove Power Module
1. Remove the bezel cover of the Power Module you wish to
1
replace. Verify that there is a fault through the individual LED status and UPS LCD screen.
2. Deactivate the Power Module by turning the spring-activated
2
knob of the locking latch counter-clockwise until it pops out. Move the locking latch to “UNLOCKED” ( )
3
3. Use a screwdriver to remove the screws on either side of the Power Module (total of 4).
4
4. With one person on either side of the Power Module, pull out and lift the module from the UPS frame.
To Replace Power Module:
5
Verify power module replacement has the same firmware version
(as labeled).
With one person on either side of the repaired or new Power
6
Module, lift and align the Power Module into the appropriate slot on the UPS. Slide the Power Module in until it is fully inside the unit and seated flush with its brackets.
Use a screwdriver to fasten the screws on either side of the Power
7
Module (total of 4).
8
Move the locking latch to “LOCKED” ( ) position and turn
clockwise until it pops in. Power Module will activate.
9
Verify that the Power Module is activated via the status LED and
UPS LCD screen before replacing the bezel cover.
3
4
5
6
7
8
9
10
11
12
13
14
29
12-212-93-3141.indb 29 12/28/2012 11:17:53 AM
10 – Display and Configuration
1
10-1 Control Panel Diagram
“NORMAL” (Green) LED: Illuminated when the UPS input
A
2
3
4
5
6
power is normal.
B
“BATTERY” (Amber) LED: Illuminated when the UPS is in Battery Backup mode.
“BYPASS” (Amber) LED: Illuminated when the UPS is in
C
Manual Bypass mode.
D
“FAULT” (Red) LED: Illuminated when any fault occurs.
E
LCD Status Display: Multi-language display.
F
“ESC” (Escape) Button: Escape/Page Up.
G
Scroll Buttons ( and ): Scroll cursor Up or Down.
H
Enter Button ( ): Confirm settings.
I
ON Button: Press and hold for 3 seconds to start up the UPS (turns Inverter ON).
J
OFF Button: Press and hold for 3 seconds to power OFF the UPS (turns Inverter OFF).
K
“EPO” (Emergency Power Off) Button: Pressing the EPO button will completely remove power from the UPS output.
E
A
B
C
D
Control Panel
F
I
G
J
H
K
10-2 Display Hierarchy
The Tripp Lite SU120KX2 UPS features a user-friendly LCD screen to show messages and display UPS Status screens.
7
8
9
10
11
12
13
14
30
12-212-93-3141.indb 30 12/28/2012 11:17:58 AM
Loading...
+ 202 hidden pages