Tripp Lite SU12000RT4U User Manual

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model Number: SU12000RT4U
Highlights
12kVA / 12,000VA / 8400W on-line double-conversion UPS
208/120V or 240/120V +/-3% output at 60Hz
8U Rack / Tower compatible; Hot-swappable power and battery modules
USB, RS232 & EPO ports; support for SNMP/WEB card options
Front panel LEDs with detailed LCD monitoring and control screen
Expandable runtime with optional external battery packs
Hardwire input (4 wire split phase); L6-30R, C19 & 5-15/20R outlets
Description
Tripp Lite 12kVA SmartOnline Hot-Swappable Modular Rack/Tower UPS offers 12,000 VA on-line, double-conversion UPS support for server, network and telecommunications equipment. Maintains battery-derived AC output during blackouts with active, full-time power conditioning. Fault-tolerant auto-bypass prevents unexpected service interruptions during overload or internal fault conditions. 4U power module and 4U external battery pack installs in 8 rack spaces (8U). Upright tower installation supported with optional accessories. Maintains full-time sine wave output within 3% of selectable 208/120 or 240/120V AC. Corrects brownouts and overvoltages from 65V to 140V (L-N). Expandable runtime with optional external battery packs. Converts raw input from AC to DC, then resynthesizes output power back to perfect sine wave AC output with enhanced protection from harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types. Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs. Network-grade AC surge and noise suppression. Network management interfaces include combination DB9 RS-232 enabled and dry contact serial port, enhanced USB port and SNMPWEBCARD slot. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Supports simultaneous detailed monitoring of equipment load levels, self-test data and utility power conditions via all 3 network interfaces. Includes PowerAlert monitoring software and complete cabling. Supports Emergency Power Off (EPO) via built-in interface. Front panel LEDs and LCD readout with scroll controls support visual monitoring of all major UPS functions. LED/LCD display panel easily rotates for viewing in rackmount or tower configurations. Split phase 4 conductor hardwire input and output supported. UPS supported outlets include two L6-30R, six C19 and 5 low voltage 5-15/20R. Output connections are mounted on a detachable backplate with manual bypass switch to enable hot-swappable UPS replacement without powering off connected equipment. External battery packs are field replaceable and hot swappable. Attractive all-black color scheme. $250,000
connected equipment insurance;
Package Includes
SU12000RT4UPM 4u UPS Power Module BP192V18-4U External battery pack SUPDMB16K Detachable PDU with manual bypass switch 4 post rackmount installation brackets
Features
True online, double-conversion UPS provides pure, full-time sine wave AC output free of surges, voltage fluctuations and line noise 12,000 VA / 8400 watt output power capacity with dual voltage output of 208/120 or 240/120V 4U high power density power module and 4U external battery pack supports rackmount installation in 8 rack spaces Dual conversion UPS actively converts raw input from AC to DC, then back to perfect sine wave AC output with enhanced protection from harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types Hardwire input terminals and output receptacles are mounted on a detachable back plate with manual bypass switch to enable hot-swappable UPS replacement without powering off connected equipment Provides perfectly regulated, sine wave output power free of line noise, transient surges and frequency variation for the most efficient operation of critical servers, networking and telecommunications equipment Maintains output within 3% of selected 208/120 or 240/120V nominal voltage during brownouts and overvoltages
Supports connected equipment during blackouts for 20/7 minutes at half/full load levels, runtime is further expandable with optional external BP192V18-4U battery packs Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual) Network interfaces support simultaneous communications via DB9 port, USB port and SNMPWEBCARD slot. DB9 port supports RS-232 and dry contact messaging. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of additional servers over IP Communications ports support on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, AC line frequency, timed inverter shutoff, activate self-test and output power control Built-in Emergency Power Off (EPO) interface with cable Includes 13 output receptacles (2 L6-30R, 6 C19, 5 NEMA 5-15/20R) plus hardwire output, all of which are available for simultaneous use Split phase, 4 conductor hardwire input connection (featured on included detachable PDU). Front panel LEDs and LCD readout with scroll button enables visual confirmation of all major UPS functions and current site electrical conditions Front panel switches enable power on/off control, self-test and alarm cancel functions Included adjustable mounting rails support installation in 4 post 19 inch rack enclosures Optional 2-9USTAND set of tower stands supports upright tower installation Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions $250,000 Ultimate Lifetime Insurance (USA, Puerto Rico and Canada only)
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
12000
Output kVA capacity (kVA)
12
Output Watt Capacity (watts)
8400
Output kW capacity 8.4
Output power factor 0.7
Output Capacity Details
12,000 VA (240V) / 10,395 VA (208V) / 8400 watts (208/240V)
Crest Factor 3:1
Nominal Output Voltage(s) Supported
120V; 208V; 240V
Nominal Voltage details
240/120V or 208/120V split phase output
Frequency compatibility
60 Hz
Output voltage regulation (line mode)
+/- 3%
Output voltage regulation (Economy line mode)
+/- 10%
Output voltage regulation (Battery mode)
+/- 3%
Built-in UPS output receptacles
5 5-15/20R outlet(s); 2 L6-30R outlet(s); 6 C19 outlet(s); Hardwire
Output circuit breaker 20A branch rated double pole breakers (x3) protect 2 C19 and 1 5-15/20R outlets each, 30A branch rated double
pole breakers (x2) protect 1 L6-30R outlet each, 20A single pole breakers (x2) protect one 5-15/20R outlet each
Output AC waveform (AC mode)
Sine wave
Output AC waveform (battery mode)
Pure Sine wave
INPUT
Rated input current (at maximum load)
50A
Nominal Input Voltage(s) Supported
208V AC / 120V AC (4 wire split single phase); 240V AC /120V AC (4 wire split single phase)
UPS input connection type
Hardwire
UPS input connection description
4 wire split-phase input (L1, L2, N, G)
Recommended Electrical Service
50A 208/240-120 Split Phase
Phase Single-Phase
BATTERY
Full load runtime (minutes)
7 min. (8400w)
Half load runtime (minutes)
20 min. (4200w)
Expandable battery runtime
Supports extended runtime with optional external battery packs
External battery pack compatibility
BP192V18-4U; BP192V557C-16K; BP192V787C-16K; BP192V1037C-16K; BP192V1407C-16K
DC system voltage (VDC)
192
Battery recharge rate (included batteries)
Less than 6 hours from 10% to 80%
Battery replacement description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation description
Online, double-conversion power conditioning
Overvoltage correction 3% output voltage regulation during overvoltages to 140 (measured L1-N : L2-N)
Undervoltage correction
3% output voltage regulation during undervoltages to 65 (measured L1-N : L2-N)
LEDS ALARMS & SWITCHES
LED Indicators 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD
screen offers additional information and control options
Alarms Unique audible alarms for all major UPS, environmental and power conditions (see manual)
Alarm cancel operation Alarm cancel switch
Loading...