Tripp Lite BP240V7RT3U, SU10KRT3UPM, SU10KXFMR, SU6000XFMR, SU6000RT3UPM Owner's Manual

Owner’s Manual
1111 W. 35th Street • Chicago, IL 60609 USA
Customer Support: (773) 869-1234 • Application Services: (773) 869-1236
www.tripplite.com
Copyright ©2002 Tripp Lite. All rights reserved.
SmartOnline
Tower/Rackmount Power Protection
Tower/Rackmount UPS Systems
SU6000XFMR • SU10KXFMR
Tower/Rackmount Isolation Transformers
BP240V7RT3U • BP240V10RT3U
Tower/Rackmount Battery Packs
Important Safety Warnings
Mounting
Connection
Features
Operation
Service/Warranty and Insurance
Specifications
Español/Français/Deutsch
2
3
6
9
13
16
17
18/35/52
2
Important Safety Warnings
SAVE THESE INSTRUCTIONS. This manual contains important instructions and warnings that should be followed during the installation and maintenance of all Tripp Lite SmartOnline Rackmount UPS Systems and their batteries.
UPS Location Warnings
• Install your UPS indoors, away from excess moisture or heat, direct sunlight, dust and conductive contaminants.
• Install your UPS in a structurally sound area. Your UPS is extremely heavy; take care when moving and lifting the unit.
• Only operate your UPS at indoor temperatures between 32° F and 104° F (between 0° C and 40° C). For best results, keep indoor temperatures between 62° F and 84° F (between 17° C and 29° C).
• Leave adequate space around all sides of the UPS for proper ventilation: 12 in. (30 cm.) clearance at the rear; 4 in. (10 cm.) at sides and on top.
• Do not install the UPS near magnetic storage media, as this may result in data corruption.
UPS Connection Warnings
• The power supply for this unit must be single phase rated in accordance with the equipment nameplate. It also must be suitably grounded.
Equipment Connection Warnings
• Do not use Tripp Lite UPS Systems in life support applications in which a malfunction or failure of a Tripp Lite UPS System could cause failure or significantly alter the performance of a life support device.
• Connect your UPS’s and/or isolation transformer’s grounding terminal to a grounding electrode conductor.
• The UPS is connected to a DC energy source (battery). The output terminals may be live when the UPS is not connected to an AC supply.
Maintenance Warnings
• Your UPS, transformer and battery pack(s) do not require routine maintenance. Do not open them for any reason. There are no user-serviceable parts inside.
Battery Warnings
• Do not operate your UPS without connecting it to an external battery pack.
• Connect only Tripp Lite battery packs to your UPS’s external battery connector.
• The batteries in your battery pack are recyclable. Refer to local codes for disposal requirements, or if in the USA call 1-800-SAV-LEAD (1-800-728-5323) for complete recycling information. CAUTION: Do not dispose of the batteries in a fire, as this could cause the battery to explode.
• Because the batteries present a risk of electrical shock and burn from high short-circuit current, batteries should be changed only by trained service personnel observing proper precautions. Consult your battery pack manual before proceeding. Remove watches, rings, and other metal objects. Use tools with insulated handles. Wear rubber gloves and boots. Do not lay tools or metal parts on top of the batteries. Do not short or bridge the battery terminals with any object. Disconnect the charging source prior to connecting or disconnecting battery terminals. Determine if the batteries are inadvertently grounded. If inadvertently grounded, remove the source of the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance.
• Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes, and may be toxic.
• Fuses should be replaced only by factory authorized personnel. Blown fuses should be replaced only with fuses of the same number and type.
• Service and repair should be done only by trained personnel. During any service work to the UPS, it should be turned off or manually bypassed via the transformer (see pg. 6-7). Note that potentially lethal voltages exist within this unit as long as the battery supply is connected.
• Do not connect or disconnect battery pack(s) while the UPS is operating from the battery supply or when the transformer is not in bypass mode.
• During “hot-swap” battery pack replacement (when the transformer is on manual bypass and connected equipment is turned ON) your UPS will be unable to provide battery backup in the event of a blackout.
3
Mounting
1
Single Unit Installation
1
2
3
A
B
C
B
E
D
F
4
G
Connect the two segments of each shelf (A) using the included screws and nuts (B). Leave the screws slightly loose so that the shelves can be adjusted in the next step.
Adjust each shelf to fit your rack, then mount them in the lowest available space of your rack with the screws, nuts and washers provided (C). Note that the support ledges should face inward. Tighten the screws that connect the shelf segments (B).
Attach mounting ears (D) to the front mounting holes of your equipment (E) using the screws provided (F). The ears should face forward.
Using an assistant if necessary, lift yourequipment and slide it onto the mounting shelves. Attach your equipment to the rack by passing the screws, nuts and washers provided (G) through its mounting ears andinto the rack rails.
4
Your equipment may be rackmounted in 4-post rack enclosures using the included rack shelves and the following suggested mounting procedures, which should be used instead of the procedures described in your Owner's Manual (if any). These procedures are for common enclosure types and may not be appropriate for all rack enclosures. You must determine the fitness of rackmount hardware and procedures before mounting. If this hardware or these procedures are not suitable for your application, contact your rack enclosure's manufacturer for a solution.
Mount one piece of equipment in a 4-post rack section using the Single Unit Installation procedure, or one piece of equipment in a 2-post rack using the 2-Post (Telecom) Installation procedure. If you have two UPSRMRII shelf kits and a sufficiently deep rack, you may mount two pieces of equipment in a 4-post rack section using the Back to Back Installation procedure.
2
3
4
Mounting
continued
Connect the shelved sections from two UPSRMRII kits (A) to the unshelved sections (B) using the included screws and nuts (C). Note: Two unshelved sections will be left over. Leave the screws slightly loose so that the shelves can be adjusted in the next step.
Adjust each shelf to fit your rack, then mount them in the lowest available space of your rack with with the screws, nuts and washers provided (D). Note that the support ledges should face inward. Tighten the screws that connect the shelf segments (C).
Attach mounting ears (E) to the front mounting holes of your equipment (F) using the screws provided (G). The ears should face forward.
Using an assistant if necessary, lift your equipment and slide it onto the mounting shelves. Attach your equipment to the rack by passing the screws, nuts and washers provided (H) through its mounting ears and into the rack rails.
2
3
4
D
C
F
E
H
G
2
3
4
1
B
C
A
Back-to-Back Installation
1
Mount the shelved sections (A) of your UPSRMRII kit on the back side of your rack. Mount them in the lowest available space of your rack with with the screws, nuts and washers provided (B). Note that the support ledges should face inward.
Attach mounting ears (C) to the front mounting holes of your equipment (D) using the screws provided (E). The ears should face backward.
Using an assistant if necessary, lift your equipment and slide it onto the mounting shelves. Attach your equipment to the rack by passing the screws, nuts and washers provided (F) through its mounting ears and into the rack rails.
5
1
2
3
A
D
C
F
B
E
2-Post (Telecom) Installation
1
2
Mounting
continued
3
Suggested Tower Mount Installation
The UPS system is shipped with two sets of plastic feet (A) and extensions (B) that can be used to tower mount the UPS, a battery pack, and either an isolation transformer or a second battery pack.
Adjust the feet to a width of 10.25 inches (26 cm) for a UPS and battery pack, or to a width of 15.375 inches (39 cm) for three units. Align the feet in your installation area, approximately 10 inches (26 cm) apart. Have one or more assistants help you place the units on their sides in the feet. The control panel of the UPS should be the UPS’s upper corner and face outward. If you are installing a transformer, place it between the UPS and its battery pack.
1
1
A
B
6
Features
Familiarize yourself with the location and function of the front and rear panel features before installing and operating your UPS.
UPS Front Panel Controls
The UPS Front Panel Controls can be rotated in its mounting to match your tower or rackmount installation. To rotate the controls, insert a flathead screwdriver into the Access Slots (12) and gently lever the controls out. Taking care not to excessively twist or pull the cables connecting the controls to the rest of the UPS, turn the controls to the desired orientation and reinsert them.
1. LCD DISPLAY: This backlit (16x2 character) dot matrix display indicates a wide range of UPS operating conditions and diagnostic data. It also displays UPS settings and options when the UPS is in setup mode.
2. ON/MUTE BUTTON: Press this button and hold it until you hear a beep to turn the UPS system’s inverter ON. If the UPS’s battery alarm is sounding, press this button to silence it.
3. SCROLL UP/EXIT SETUP BUTTON: This button allows you to browse through different options and power readings on the LCD display. Momentarily pressing it causes the LCD screen to display a different power reading (see “Normal Operation”, pg. 12). Pressing it and the “SCROLL DOWN” button together puts the UPS in setup mode, where this button is used to scroll through setup options and to exit setup mode.
4. SCROLL DOWN/SELECT BUTTON: This button allows you to browse through different options and power readings on the LCD display. Momentarily pressing it causes the LCD screen to display a different power reading (see “Operation”, pg. 12). Pressing it and the “SCROLL UP” button together puts the UPS in setup mode, where this button is used to select setup options.
5. OFF BUTTON: Press this button until you hear a beep to turn the UPS system’s inverter OFF.
6. O/P (OUTPUT) LED: This green light will illuminate to indicate your UPS is supplying AC power to connected equipment.
7. DC/AC (INVERTER) LED: This green light will illuminate to indicate the UPS’s DC/AC inverter is activated.
8. BYPASS LED: This green light will illuminate when the UPS is providing filtered mains power without engaging its converter or
inverter. If this LED is lit, connected equipment will not receive battery power in the event of a blackout.
9. AC/DC (Converter) LED: This green light will illuminate to indicate the UPS’s AC/DC converter is charging the connected battery pack(s).
10. BATTERY LED: This red light will illuminate when the UPS is discharging the battery to provide connected equipment with AC power. An alarm will sound which can be silenced by pressing the “ON/MUTE” button. This LED will remain lit after the alarm is silenced.
11. I/P (INPUT) LED: This green light will illuminate to indicate an AC input supply is present.
12. ACCESS SLOTS: To rotate the controls, insert a flathead screwdriver into these slots and gently lever the panel out. Taking care not
to excessively twist or yank the cables connecting the controls to the rest of the UPS, turn the controls to the desired orientation and reinsert them.
1
2 345
6879
10
11
12
12
Loading...
+ 11 hidden pages