Tripp Lite SU10KRT3UHV User Manual

Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: SU10KRT3UHV
Highlights
10,000VA (10kVA) / 8,000W on-line 6U rack / tower UPS (3U Power Module +
3U Battery Pack)
Enhanced serial communications ports, SNMP/Web card slot and EPO jack
Maintains 200, 208, 220, 230 or 240V output +/-2% during brownouts to 156
and overvoltages to 276V
Internal fault tolerant auto bypass mode and detachable hardwired PDU with
manual bypass switch enables hot-swap UPS replacement without powering
off connected loads
Expandable runtime with optional battery packs
$250,000 Ultimate Lifetime Insurance (USA, Puerto Rico & Canada only)
Description
Tripp Lite 10,000VA (10kVA) SmartOnline Rack/Tower UPS. The SmartOnline SU10KRT3UHV on-line, double conversion UPS protects server,
networking or telecommunications equipment from blackouts, voltage fluctuations and surges in a compact tower/rackmount housing. In rack
configuration, power module and battery pack occupy only 3 rack spaces each (6U total). Upright tower placement of entire system supported with
included tower stands. Large capacity 10,000VA/8000W power module converts raw input AC to DC, then back to perfect sine wave AC output
within 2% of user-selectable 200/208/220/230/240V AC output voltages. Frequency regulation locks output power to 50/60Hz (+/-0.2 Hz), removing
harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types. Perfectly regulated,
continuous sine wave output with zero transfer time offers guaranteed compatibility with all equipment types. Hardwire input and output connections
support a variety of permanent or PDU style power connections. Detachable hardwired PDU with manual bypass switch enables hot-swap UPS
replacement without powering off connected loads. Battery support can be extended through the addition of optional external battery packs, sold
separately. Includes slot for internal SNMP/Web card, plus DB9 enhanced serial monitoring port for unattended shutdown, remote control and
monitoring of UPS system and power data.
Applications
Ideal for protection of critical 200/208/220/230/240V equipment in server rooms, internetworking closets and telecommunications systems in rackmount or tower applications. Common applications include corporate or departmental servers, workstations, hubs, routers, bridges, CAD/CAM workstations, concentrators, IP telephony and traditional PBX switching systems.
Package Includes
SU10KRT3UHV Rack-Tower UPS System with hardwire distribution module and 1 battery pack PowerAlert Software and cabling Mounting hardware for 4 post rack enclosures/tower stands Instruction manual with warranty information
Features
True on-line, double conversion UPS provides pure, sine wave AC output at all times World-wide compatibility with Euro 50Hz and High Voltage North American 60Hz power
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time Removes harmonic distortion, electrical impulses, frequency variations and other hard to solve power problems 10,000VA/8,000W power capacity with hardwire input/output connections Accepts input voltages between 156 and 276, regulating output within 2% of selectable 200/208/220/230/240V AC output Standard included 3U battery pack provides 10 minutes runtime at half load (5,000VA) and 4 minutes at full load (10,000VA) Expandable runtime with multiple external battery packs, sold separately Innovative design makes unit adaptable for rackmount, tower, or stacking applications Power module and battery pack require only 3 rack spaces each (6U total rack space usage) DB9 serial port for network interface; SNMP compatible Slot for optional SNMP/Web card (part# SNMPWEBCARD) PowerAlert unattended shutdown software and 6 ft. network cable included Fault tolerant auto-bypass maintians continuous utility output to connected equipment, even in cases where the UPS is overloaded or suffers an internal failure that requires service Detachable hardwired PDU with manual bypass switch enables hot-swap UPS replacement without powering off connected loads Diagnostic LEDs and LCD provide complete overview of operating conditions, UPS status and more Mounting hardware included Includes RJ11 EPO (emergency power off) port and interconnection cable 2 year manufacturers product warranty $250,000 Ultimate Lifetime connected equipment insurance
Specifications
SYSTEM OVERVIEW
Voltage compatibility 208V AC (200/208/220/230/240V)
Frequency compatibility
50/60Hz
OUTPUT
Output VA 10000
Output watts 8000
Output nominal voltage
208V AC (200/220/230/240V)
Output voltage regulation
Maintains pure sine wave output at all times, regulated within 2% of selected nominal output voltage, less than 5% total harmonic distortion
Output frequency regulation
Regulates line frequency to 50/60Hz +/- 0.05Hz
Outlet quantity / type Hardwire via detachable distribution module
INPUT
Maximum input amps 46.7A (200V), 44.9A (208V), 42.4A (220V), 40.6A (230V), 38.9A (240V) max.
Input connection type Hardwire via detachable distribution module
BATTERY
Full load runtime Included batteries — 4 min (10,000VA)
Half load runtime Included batteries — 10 min (5,000VA)
Expandable battery runtime
Supports extended runtime with optional external battery packs
DC system voltage 240V DC
Typical battery lifespan
3-6 years, depending on usage
Battery recharge rate Less than 8 hours to 90% (included battery set only)
VOLTAGE REGULATION
Voltage regulation description
On-line, double-conversion process allows this UPS to maintain output voltage within +/-2% of selected nominal voltage at all times
Overvoltage correction
Maintains continuous operation without using battery power during overvoltages to 276V AC, reducing output within 2% of selected nominal
Loading...