Highlights
750VA line interactive, extended-run tower UPS for networks
Maintains user selecable sine-wave 120, 110 or 100V nominal output
Simultaneous communications via SNMPWEBCARD slot, DB9 serial and HID
enabled USB ports
Free PowerAlert UPS monitoring software and cabling
Input: NEMA 5-15P (120V 15A) / Output: 8 NEMA 5-15R (120V)
2 year product warranty / $250,000 Ultimate Lifetime Insurance (USA, Puerto
Rico & Canada only)
Description
750VA line-interactive tower UPS system for server, networking and telecommunications equipment. Supports extended runtime with optional
BP24V28-2U and BP24V70-3U external battery packs. Compatible with 120V, 110V or 100V nominal voltage at 60Hz. Switches to battery-derived
AC output during power failures and extreme voltage variations. Line-interactive automatic voltage regulation (AVR) provides voltage boost during
brownouts and voltage cut during overvoltages to maintain regulated output during brownouts and overvoltages. Includes NEMA 5-15P input plug
and 8 NEMA 5-15R output receptacles. Network-grade AC surge and noise suppression. Network management via USB port, DB9 serial port and
SNMPWEBCARD slot. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows
and Mac OS X. Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via all 3 network interfaces at once.
Includes PowerAlert monitoring software and complete cabling. Features 3-stage load current monitoring and battery charge status, plus line power
and voltage boost/cut status LEDs. Dataline surge suppression protects dialup, DSL or network Ethernet connection. Audible alarm. Self-test. Field
replaceable, hot-swappable internal batteries and external battery packs. Attractive all-black color scheme. Two-year warranty and $250,000 connected equipment insurance
connected equipment insurance; extended warranty and service contracts available.
Applications
Ideal for the protection of network fileservers, internetworking gear, switches, hubs, POS terminals, VOIP telephony and traditional PBX switching systems, back office computer systems, ATM machines, informational/internet/commerce kiosks, remote unattended servers, web servers, database servers, security systems, card readers, security cameras and other sensitive electronic devices requiring clean, continuously-regulated output power.
Package Includes
SMART 750XLa UPS System PowerAlert Software CD-Rom USB and serial cabling User manual with warranty information
Features
SmartPro line-interactive UPS system is ideal for voice, data, medical and industrial networking applications Large internal batteries offer 27 minutes at half load (375VA/250W) and 10 minutes at full load (750VA/500w) Runtime is expandable with optional BP24V28-2U (limit 1) and BP24V70-3U (no limit) external battery packs
Line-interactive automatic voltage regulation (AVR) maintains selectable 120V, 110V or 100V nominal output during brownouts as low as 83V and overvoltages to 145V Network interfaces support simultaneous communications via built-in USB port, DB9 serial port and SNMPWEBCARD slot HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of additional servers over IP UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, timed inverter sutoff, activate self-test and output power control NEMA 5-15P input plug; 8 battery-supported NEMA 5-15R output receptacles Dataline surge suppression protects dialup, DSL or network Ethernet connection Front panel LEDs offer current monitoring, voltage regulation and battery charge level information UPS ships fully assembled in full compliance with DOT regulations; no time-consuming connection of internal batteries by user required 2-year warranty; $250,000 Ultimate Lifetime Insurance (USA & Canada only)
Specifications
SYSTEM OVERVIEW
Voltage compatibility 120V (110, 100V user selectable)
Frequency compatibility
60 Hz
OUTPUT
Output VA 750
Output watts 500
Output nominal voltage
120, 110, 100V AC
Output voltage regulation
LINE MODE: Sine wave line voltage 120V (+6%, -10%), 110V (+6%, -10%), 100V (+6%, -10%), BATTERY MODE: Sine wave output 120V, 110V, 100V (+/-5%)
Output frequency regulation
LINE MODE: Passes line frequency of +/-10% BATTERY MODE: Inverter output regulated to 60Hz (+/- 1Hz)
Outlet quantity / type 8 NEMA 5-15R
INPUT
Maximum input amps 5.4A (120V), 5.8A (110V), 6.4A (100V)
Input connection type NEMA 5-15P
Input cord length 6 ft.
Recommended Electrical Service
120V 15A
BATTERY
Full load runtime 10 minutes (500w) expandable
Half load runtime 27 minutes (250w) expandable
Expandable battery runtime
Runtime is expandable with BP24V28-2U (limit 1) or BP24V70-3U (multi-pack compatible)
DC system voltage 24VDC
Battery recharge rate 4.5 hour recharge to 90% (max)
Replacement Battery Cartridge
RBC24-SLT
VOLTAGE REGULATION
Voltage regulation description
Automatic Voltage Regulation (AVR) circuits maintain clean, regulated computer-grade 120, 110, 100V nominal output, without using battery power, during brownouts 95V (120V), 87V (110V), 83V (100V)
Overvoltage correction
Input voltages between 127 and 145V (120V), 116 and 133 (110V), 111 and 121 (100V) are reduced by 12%
Brownout correction Input voltages between 95 and 108 (120V), 87 and 99 (110V), 83 and 93 (100V) are boosted by 14%