Tripp Lite SMART700DV User Manual

WARRANTY
REGISTRATION
Register online today for a chance
to win a FREE Tripp Lite product!
www.tripplite.com/warranty
Intelligent, Line-Interactive UPS System
• 120V/230V Auto-Sensing Input, 120V Output
Owner’s Manual
SMART700DV
Not suitable for mobile applications.
Important Safety Instructions
Quick Installation
Optional Installation
Basic Operation
Storage and Service
Battery Replacement
Specifications
Warranty Registration
2
3
4
5
8
9
10
10
1111 W. 35th Street, Chicago, IL 60609 USA
Customer Support: (773) 869-1234 • www.tripplite.com
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during the installation, operation and storage of all Tripp Lite UPS Systems. Failure to heed these warnings will void your warranty.
UPS Location Warnings
• The UPS is heavy. Use caution when lifting it.
• Install your UPS indoors, away from excess moisture or heat, dust or direct sunlight.
• For best performance, the ambient temperature near your UPS should be between 0° C and 40° C (between 32° F and 104° F).
• Leave adequate space around all sides of the UPS for proper ventilation. Do not obstruct its vents or fan openings.
UPS Connection Warnings
• The UPS contains its own energy source (battery). The output terminals may be live even when the UPS is not connected to an AC supply.
• Connect your UPS to a properly grounded AC power outlet. Do not modify the UPS’s plug in a way that would eliminate the UPS's connection to ground. Do not use adapters that eliminate the UPS’s connection to ground.
• Do not plug your UPS into itself; this will damage the UPS and void your warranty.
• If you are connecting your UPS to a motor-powered AC generator, the generator must provide filtered, frequency-regulated computer-grade output. Connecting your UPS to a generator will void its Ultimate Lifetime Insurance.
Equipment Connection Warnings
• Do not use Tripp Lite UPS Systems for life support applications in which a malfunction or failure of a Tripp Lite UPS System could cause failure or significantly alter the performance of a life-support device.
• Do not connect surge suppressors or extension cords to the output of your UPS. This might overload the UPS and will void the surge suppressor and UPS warranties.
Battery Warnings
• Batteries can present a risk of electrical shock and burn from high short-circuit current. Observe proper precautions. Do not dispose of the batteries in a fire. Do not open the UPS or batteries. Do not short or bridge the battery terminals with any object. Unplug and turn off the UPS before performing battery replacement. Use tools with insulated handles. There are no user-serviceable parts inside the UPS. Battery replacement should be performed only by authorized service personnel using the same number and type of batteries (sealed Lead-Acid). The batteries are recyclable. Refer to your local codes for disposal requirements or in the USA only call 1-800-SAV-LEAD or 1-800-8-BATTERY (1-800-822-8837) or visit www.rbrc.com for recycling information. Tripp Lite offers a complete line of UPS System Replacement Battery Cartridges (R.B.C.). Visit Tripp Lite on the Web at www.tripplite.com to locate the specific replacement battery for your UPS.
• During hot-swap battery replacement, the UPS will not provide backup power in the event of a blackout or other power interruptions.
• Do not operate UPS without batteries.
2
Quick Installation
1
Plug the UPS into a wall outlet supplying either 120V or 230V (nominal) AC power.
Use the included detachable power cord. The IEC-320 end connects to the AC input receptacle on the rear of the UPS; the NEMA 5-15 end connects to the wall outlet.
To plug the UPS into a wall outlet that does not accept a NEMA 5-15 plug, simply replace the included power cord with a detachable cord from another piece of equipment, such as a computer. Then, use the includ­ed power cord to connect the equipment to the UPS.
NOTE! After you plug the UPS into a live AC outlet, the UPS (in “Standby” mode) will automatically charge its batteries,* but will not supply power to its outlets until it is turned ON (see Step 3 below).
* The BATTERY CHARGE LED will be the only LED illuminated.
2
Plug your equipment into the UPS.
NOTE! Your UPS is designed to support only elec­tronic equipment. You will overload the UPS if the total VA ratings for all the equipment you connect exceeds the UPS's Output Capacity (700VA). To find your equipment's VA ratings, look on their name­plates. If the equipment is listed in amps, multiply the number of amps by 120 to determine VA.
(Example: 1 amp × 120 = 120 VA). If you are unsure if you have overloaded
the UPS's outlets, see “OUTPUT LOAD LEVEL” LED description.
1
2
3
Turn the UPS ON.
3
Press and hold the “ON/OFF/STANDBY” button for one second. The alarm will beep once briefly after one second has passed. Release the button.
3
Optional Installation
These connections are optional. Your UPS will function properly without these connections.
USB and RS-232 Serial
1
Communications
Use the included USB cable (see ) and/or DB9 serial cable (see ) to connect the communication port on your equipment to the communication port of your UPS. Install on your equipment the Tripp Lite PowerAlert Software appropriate to your equipment’s operating system. Consult your PowerAlert manual for more information.
EPO Port Connection
2
This optional feature is only for those applications which require connection to a facility’s Emergency Power Off (EPO) circuit. When the UPS is connected to this circuit, it enables emergency shutdown of the UPS’s inverter.
Using the cable provided, connect the EPO port of your UPS (see ) to a user-supplied normally closed or normally open switch according to the circuit diagram (see ). The EPO port is not a phone line surge sup­pressor; do not connect a phone line to this port.
1b
2a
2b
1a
1a
1b
2a
4-5
2b
4