The SMART1500SLT SmartPro 120V 1.5kVA 900W Line-Interactive Sine Wave UPS provides battery backup and AC power protection against blackouts,
brownouts, power surges and line noise that can damage electronics or destroy data. Ideal for backing up VoIP systems, point-of-sale applications and
network closets, the SMART1500SLT switches to battery mode in milliseconds to keep your connected equipment running long enough to save files and shut
down safely with no data loss.
Featuring eight NEMA 5-15R outlets and a six-foot power cord with NEMA 5-15P input, the SMART1500SLT has an internal battery that provides 20 minutes
of support at half load and eight minutes at full load. Front-panel LEDs indicate line power, battery power, overload, voltage regulation and battery status. An
alarm sounds to indicate power failure and overload conditions.
Automatic voltage regulation(AVR) maintains selectable 100V, 110V or 120V nominal output over an input range of 95V to 145V without using battery power.
EMI/RFI noise filtering improves your equipment’s performance and prevents damage. A 690-joule surge suppression rating protects your equipment from
harmful power surges. With Tripp Lite’s included PowerAlert software, the SMART1500SLT enables safe unattended system shutdown and file saves in case of
a prolonged power failure. Adding an optional Network Management Card, such as Tripp Lite's SNMPWEBCARD, permits remote management of the UPS,
including reboots and activity logs.
Features
Protects Mission-Critical Equipment
Provides fully regulated AC output for VoIP systems, point-of-sale applications and network closets
Audible alarm signals loss of utility power or overload
8 NEMA 5-15R outlets
6 ft. power cord with NEMA 5-15P input
690-joule surge suppression rating
Reliable Battery Backup
Page 2
Supports half load up to 20 min. and full load up to 8 min.
Internal batteries designed for hot-swap field replacement
95% line-power efficiency rating saves money in energy costs
Cold-start capability enables turn-on in battery mode during blackouts
Automatic Voltage Regulation(AVR)
Maintains selected 100V, 110V or 120V nominal output over input range of 95V–145V without using battery power
EMI/RFI Line Noise Filtering
Removes electromagnetic and radio frequency interference that can disrupt or damage equipment’s performance
LED Indicators
Front-panel LEDs signal indicate line power, battery power, overload, voltage regulation and battery status
SNMP/Web Capability
Optional Network Management Card Options, such as Tripp Lite's SNMPWEBCARD, permits remote management of UPS, including reboots,
configuration, updates and activity logs
Communications Ports
USB and DB9 ports combine with included PowerAlert software to monitor operating conditions, monitor AC power, and enable safe unattended system
shutdown and file saves in case of a prolonged power failure
RJ45 Telephone/Ethernet Protection Jacks
Protect phone/DSL/fax/modem/Ethernet network against power surges
Specifications
OUTPUT
Output Volt Amp Capacity (VA)1500
Output kVA Capacity (kVA)1.5
Output Watt Capacity (Watts)900
Nominal Output Voltage(s)
Supported
Nominal Voltage Details120V default (voltage selection via back panel switches)
Frequency Compatibility50 / 60 Hz
Frequency Compatibility DetailsAutomatic frequency selection
Output Voltage Regulation (Line
Mode)
Output Voltage Regulation (Battery
Mode)
Output Receptacles(8) 5-15R
100V; 110V; 120V
-13%, + 15%
+/- 5%
Page 3
Output AC Waveform (AC Mode)Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load)10.1A (100V), 9.3A (110V), 8.6A (120V)
Nominal Input Voltage(s) Supported100V AC; 110V AC; 120V AC
UPS Input Connection Type5-15P
UPS Input Cord Length (ft.)6
UPS Input Cord Length (m)1.8
Recommended Electrical Service15A 120V
Input PhaseSingle-Phase
BATTERY
Full Load Runtime (min.)8 min. (900w)
Half Load Runtime (min.)20 min. (450w)
DC System Voltage (VDC)36
Battery Recharge Rate (Included
Batteries)
Internal UPS Replacement Battery
Cartridge
Battery AccessBattery access door
Battery Replacement DescriptionHot-swappable, user replaceable batteries
Expandable RuntimeNo
VOLTAGE REGULATION
Voltage Regulation Description
Overvoltage CorrectionVoltage reduction of 12% applies when input is 127 to 145 (120v), 116 to 133 (110v), 111 to 121 (100v)
Undervoltage CorrectionVoltage boost of 14% applies when input is 95 to 108 (120v), 87 to 99 (110v), 83 to 90 (100v)
USER INTERFACE, ALERTS & CONTROLS
Switches
Alarm Cancel OperationPower-fail alarm can be silenced using alarm-cancel switch
Audible AlarmAudible alarm indicates power failure and overload conditions
Less than 8 hours from 10% to 90% (typical, full load discharge)
RBC36-SLT
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 95 to 145 (120v),
87 to 133 (110v), 83 to 121 (100v)
2 Switches control off/on power status and alarm-cancel/self-test operation; rear panel protected switches support
nominal voltage selection
LED Indicators
Site Wiring Fault IndicationRear panel site wiring fault LED
Status LEDs indicate line power, battery power, AVR, overload and replace battery status - with a 3-LED level
meter for load and battery charge level
Page 4
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating690
UPS AC Suppression Response
Time
UPS Dataline Suppression1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
EMI / RFI AC Noise SuppressionYes
PHYSICAL
Primary Form FactorTower
UPS Power Module Dimensions
(hwd, in.)
UPS Power Module Dimensions
(hwd, cm)
UPS Power Module Weight (lbs.)45
UPS Power Module Weight (kg)20.4
UPS Shipping Dimensions (hwd / in.) 14 x 9.8 x 18.5
UPS Shipping Dimensions (hwd /
cm)
Shipping Weight (lbs.)49.2
Shipping Weight (kg)22.3
Cooling MethodFan
Instantaneous
10.2 x 6.8 x 13.2
26 x 17.1 x 33.7
35.6 x 24.8 x 47
UPS Housing MaterialSteel
ENVIRONMENTAL
Operating Temperature Range+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity0 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)161.1
Battery Mode BTU / Hr. (Full Load)498.1
AC Mode Efficiency Rating (100%
Load)
Audible NoiseAudible Noise < 50 dBA at Front Side 1 Meter
COMMUNICATIONS
Communications InterfaceUSB; DB9 Serial; Slot for SNMP/Web interface
Network Monitoring Port DescriptionSupports detailed monitoring of UPS and site power conditions
PowerAlert SoftwareIncluded
Communications CableUSB and DB9 cabling included
95%
Page 5
WatchDog CompatibilitySupports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer Time4-6 milliseconds
Low Voltage Transfer to Battery
Power (Setpoint)
High Voltage Transfer to Battery
Power (Setpoint)
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure)
High Availability UPS FeaturesHot swappable batteries
Green Energy-Saving FeaturesGreater than 95% efficiency - GREEN UPS
CERTIFICATIONS
UPS CertificationsTested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)
WARRANTY
Product Warranty Period (Worldwide) 2-year warranty, 3 year with registration. Note:
Connected Equipment Insurance
(U.S., Canada & Puerto Rico)
95V (120V), 87V (110V), 83V (100V)
145V (120V), 133V (110V), 121V (100V)
Cold-start operation supported