12.6kW 3-Phase Metered PDU, 208V Outlets (36
C13 & 9 C19) Hubbell 50A CS8365C, 6 ft. (1.83 m)
Cord, 0U Vertical, TAA
MODEL NUMBER: PDU3MV6H50
Features
●
12.6kW 3 phase 208V Metered Power Distribution Unit / PDU
●
Set of 3 built-in current meters continuously report load current in amps for all 3 output phases
●
Attached Hubbell CS8365C 50A (3P+E) 208V 3 phase input plug with 6 ft. / 1.8m cord
●
0U, 70 in. / 178cm vertical form factor supports installation in 2 or 4 post equipment racks
●
45 total 208V outlets (36 C13, 9 C19) arranged in three breakered single phase output load banks
●
Included cord retention brackets keep vital network equipment plugged in and continuously powered
●
Toolless mounting supported in button-mount compatible racks, plus nut-and-bolt mounting brackets for
other mounting applications (set of 2 9mm buttons pre-installed, 2 9mm and 4 6mm spare buttons
included)
●
Federal Trade Agreements Act / TAA Compliant for GSA Schedule purchases
Highlights
●
Metered 12.6kW 3 Phase 208V
PDU; 70 in. / 178cm 0U vertical
rackmount
●
Reports load current per-phase
via set of 3 built-in current
meters
●
Hubbell CS8365C 50A (3P+E)
208V 3 phase input; 6-ft. (1.83
m) line cord
●
45 208V outlets total (36 C13, 9
C19)
●
Toolless button-mount
installation; cord retention
brackets included
●
Federal Trade Agreements Act /
TAA Compliant for GSA
Schedule purchases
Package Includes
●
Metered PDU with pre-installed
mounting buttons
●
Cord retention brackets
●
Spare installation buttons (2
9mm / 4 6mm)
●
Rack mounting brackets
●
Owner's manual
Specifications
OVERVIEW
UPC Code 037332163868
PDU Type Metered
INPUT
PDU Input Voltage 208V
Recommended Electrical Service Three-phase 50A 208V service
1 / 3
Maximum Input Amps 35
PDU Plug Type HUBBELL CS8365C 50A
Input Phase 3-Phase
Input Cord Length (ft.) 6
Input Cord Length (m) 1.83
OUTPUT
Output Capacity Details 12.6kVA (208V) total capacity; 20A max per breakered outlet bank; 16A max per C19 outlet; 12A max per C13 outlet
Frequency Compatibility 50 / 60 Hz
Output Receptacles (36) C13; (9) C19
Output Nominal Voltage 208V
Overload Protection 3 20A circuit breakers, 1 per outlet bank
USER INTERFACE, ALERTS & CONTROLS
Reported Load Segments Supports local monitoring of current for each output phase (20A balanced max per L1-L2, L2-L3 and L3-L1); Outlets
are color-coded and labeled for phase and load bank identification; L1-L2 feeds black outlets; L2-L3 feeds dark-gray
outlets; L3-L1 feeds light-gray outlets
Front Panel LCD Display Set of 3 digital current meters report current in amps for each output phase
Front Panel LEDs n/a
Switches n/a
PHYSICAL
Form Factors Supported Vertical rackmount installation supported with included mounting brackets; supports toolless mounting in button-
mount compatible racks
Material of Construction Metal
PDU Form Factor Vertical (0U)
Shipping Dimensions (hwd / cm) 15.24 x 25.40 x 196.34
Shipping Dimensions (hwd / in.) 6.00 x 10.00 x 77.30
Shipping Weight (kg) 9.71
Shipping Weight (lbs.) 21.40
Unit Dimensions (hwd / cm) 177.8 x 6.73 x 4.34
Unit Dimensions (hwd / in.) 70 x 2.65 x 1.71
Unit Weight (kg) 6.58
Unit Weight (lbs.) 14.5
ENVIRONMENTAL
Operating Temperature Range 0C ~ 40C (32F ~ 104F)
Storage Temperature Range -30°C to +60°C (-22°F to +140°F)
2 / 3