Traulsen TE036HT, TE048HT, TE060HT, TE065HT, TE072HT Service Manual

...
Page 1
Traulsen Refrigeration
SERVICE MANUAL #07
Instructions For The Troubleshooting
And Repair Of All Traulsen TE-Series
Refrigerated Equipment Stand Models
-NOTICE-
This Manual is prepared for the use of trained Authorized Traulsen Service Agents and should not be used by those not properly qualified. This manual is not intended to be all encompassing, but is written to supplement the formal training, on-the-job experience and other product knowledge acquired by Autho­rized Traulsen Service Agents. Before proceeding with any work, you should read, in its entirety, the repair procedure you wish to perform to determine if you have the necessary tools, instruments and skills required to perform the procedure. Procedures for which you do not have the necessary tools, instruments and skills should be performed only by a trained Authorized Traulsen Service Agent.
Reproduction or other use of this Manual, without the express written consent of Traulsen, is prohibited.
FORM NUMBER TR35896 - REVISED. 4/08
Page 2
TABLE OF CONTENTS
I. THE SERIAL TAG 1
II. GENERAL INFORMATION
a. Introduction 2 b. Model Designations 2 c. Wiring Diagrams 2 d. Installation - See Owner’s Manual 2 e. Cleaning 2 f. Tools 2 g. Refrigeration System Theory Of Operation 2 h. Air Flow Requirements 2 i. The Microprocessor Control 2 j. Control Locations 3 k. Specifications 3 l. Operating Data Chart 3
III. REMOVAL & REPLACEMENT OF PARTS
a. Louver Assembly 4 b. Evaporator Housing Cover 4 c. Removing The Drawer 4 d. Removing The Drawer Frame (slides) 4 e. Drawer Gaskets 5 f. Microprocessor Control 5 g. Condensate Drain Pan 5 h. Accessing Start Components 5
IV. REPLACING THE...
a. Condenser Fan Motor and/or Blade 6 b. Condenser Coil 7 c. Evaporator Fan 8 d. Evaporator Coil 9
IV. REPLACING THE... (contd)
f. Compressor 10
V. WIRING DIAGRAMS
a. 115V Refrigerator Models 11
VI. SERVICE PROCEDURES & ADJUSTMENTS
a. System Access 12 b. Sweat On Piercing Valves 12 c. Refrigerant Leak Check 12 d. Evacuating System 13 e. Charging System 13 f. System Clean-Up 14 g. Heater Test/Drawer Perimeter Heater 14
VII. ELECTRICAL OPERATION
a. Sequence Of Operation/Normal Operation 14 b. Sequence Of Operation/Defrost Mode 14 c. Component Function 15 d. Installation of Sensors 15
VIII. REPLACEMENT PARTS LISTING 16
IX. TROUBLESHOOTING 17
FORT WORTH, TX.
SERIAL MODEL VOLTS Hz PH
TOTAL CURRENT AMPS MINIMUM CIRCUIT AMPS MAXIMUM OVERCURRENT PROTECTION AMPS LIGHTS WATTS HEATERS AMPS
REFRIGERANT TYPE OZ DESIGN PRESSURE HIGH LOW
REFRIGERANT TYPE OZ DESIGN PRESSURE HIGH LOW
370-60294-00 REV (A)
I. THE SERIAL TAG
The serial tag is a permanently affixed sticker on which is recorded vital electrical and refrigeration data about your Traulsen product, as well as the model and serial number. This tag is located on the upper right interior wall of all TE-Series models.
READING THE SERIAL TAG
Serial = The permanent ID# of your Traulsen
Model = The model # of your Traulsen
Volts = Voltage
Hz = Cycle
PH = Phase
Total Current = Maximum amp draw
Minimum Circuit = Minimum circuit required
Lights = Light wattage
Heaters = Heater amperage
Refrigerant = Refrigerant type used
Design Pressure = High & low side operating
pressures and refrigerant charge
Agency Labels = Designates agency listings
-1-
Page 3
II. GENERAL INFORMATION
II. a - INTRODUCTION: This manual applies to the following Traulsen models only:
TE036HT, TE048HT, TE060HT, TE065HT, TE072HT TE084HT, TE096HT, TE110HT, TE125HT & TE139HT
II. b - MODEL DESIGNATIONS:
TE060HT
Position 1: TE = Traulsen Equipment Stand Position 2: 036 = 36” Long Model
048 = 48” Long Model 060 = 60” Long Model
Position 3: HT = Refrigerator
II. c - WIRING DIAGRAM: Refer to the wiring diagram for any service work performed on this unit. A copy is located on the unit when shipped. Should you require another copy, or a wiring diagram for an older production unit, please contact Traulsen Service at (800) 825-8220, and provide the model and serial number of the unit involved (this information is located on the serial tag, see page one).
II. g - REFN SYSTEM - THEORY OF OPERATION: The refrigeration system is the mechanism whereby heat is transferred from the cabinet to the outside air. It works under the principle that the heat moves from hot to cold as it tries to establish equilibrium.
The microprocessor control signals a need for heat to be removed from the cabinet. The compressor begins by compressing the refrigerant gas as it is discharged. The high pressure refrigerant now circulates through the condenser, removing heat from the refrigerant and condensing it into a liquid. From there the refrigerant flows to the filter drier which removes all traces of moisture and particles from the system.
After the filter drier, the refrigerant passes through a “metering device.” Traulsen uses a capillary tube to regulate the flow of refrigerant into the evaporator coils.
In the evaporator coil, heat is transferred from the cabinet to the refrigerant, which changes from a cold liquid to a warm low pressure gas. When the desired cabinet air temperature has been reached, the microprocessor control shuts off the compressor.
II. d - INSTALLATION: Generally TE-Series refrigeration products are installed by the dealer, or others contracted by the dealer or owner. Detailed installation instructions are included along with each unit when shipped.
II. e - CLEANING: Detailed cleaning instructions are included with each unit, however special care MUST be given to the condenser coil. The condenser coil must be cleaned at a minimum of every six months. This can be done with a vacuum cleaner using a brush attachment, or a stiff brush or wisk broom. For more information please refer to Manual.
II. f - TOOL REQUIREMENTS: For most jobs a standard set of hand tools, a VOM and AC current tester, along with a temperature tester or thermometer are adequate. However in some cases the following additional tools may be required as well:
Section V.aof the TE-Series Owner’s
Refrigeration Guage Manifold
Refrigeration Reclaiming Equipment
Acetylene Torch
Anti-Static Grounding Kit (TL 84919)
Nitrogen Bottle With Gauges
Thin 5/16 Open End Wrench
Refrigerant Reclaim Unit
Fig. 1 - The Refrigeration System
II. h - AIR FLOW REQUIREMENTS: To assure optimum performance, the condensing unit of your Traulsen unit MUST have an adequate supply of air for cooling purposes. Therefore, the operating location must allow a minimum of 12clearance in front of the louvers to allow for unrestricted air flow to the condensing unit.
II. i - THE MICROPROCESSOR CONTROL: For detailed information on replacement, repair or adjustment of the INTELA-TRAUL® microprocessor control please refer to it’s service manual (form number TR35705).
-2-
Page 4
II. GENERAL INFORMATION (cont’d)
II. j - CONTROL LOCATION: On all TE-Series refrigerator models, the micro­processor control is located on the louver assembly. The louvers/refrigeration system are mounted standard on the left side, but as an option are available mounted on the right (see figure 2).
Fig. 2
Control Location
II. k -
OPERATING DATA CHART:
Refrigerated Models (cabinet temperature set at 38°F) Ambient 70°F 100°F
Suction Pressure 35 PSIG 50 PSIG Suction Temperature 3°F16°F Discharge Pressure 200 PSIG 295 PSIG Discharge Temperature 88°F115°F
II. l - SPECIFICATIONS:
TE-Series Refrigerated Equipment Stands
TE036 TE048 TE060 Horsepower 1/3 HP 1/3 HP 1/3 HP Condensing Unit - BTU/HR 2440 2440 2440 Condensing Unit Amp Draw 4.5 4.5 4.9 Fan, Lights, Etc. Amp Draw 0.6 0.6 1.1 Refrigerant R-404A R-404A R-404A Refrigerant Charge (oz.) 14.0 14.5 16.0
TE-Series Refrigerated Equipment Stands
TE065 TE072 TE084 Horsepower 1/3 HP 1/3 HP 1/3 HP Condensing Unit - BTU/HR 2440 2440 2440 Condensing Unit Amp Draw 4.9 4.9 4.9 Fan, Lights, Etc. Amp Draw 1.1 1.1 1.1 Refrigerant R-404A R-404A R-404A Refrigerant Charge (oz.) 16.5 16.5 17.0
TE-Series Refrigerated Equipment Stands
TE096 TE110 TE125 Horsepower 1/2 HP 1/2 HP 1/2 HP Condensing Unit - BTU/HR 4090 4090 4090 Condensing Unit Amp Draw 9.6 9.6 9.6 Fan, Lights, Etc. Amp Draw 1.5 1.5 1.5 Refrigerant R-404A R-404A R-404A Refrigerant Charge (oz.) 20.0 20.0 20.0
TE-Series Refrigerated Equipment Stands
TE139 Horsepower 1/2 HP Condensing Unit - BTU/HR 4090 Condensing Unit Amp Draw 9.6 Fan, Lights, Etc. Amp Draw 1.9 Refrigerant R-404A Refrigerant Charge (oz.) 21.0
-3-
Page 5
III. REMOVAL & REPLACEMENT OF BASIC PARTS
WARNING: DISCONNECT THE ELECTRICAL POWER TO THE MACHINE
AND FOLLOW LOCKOUT/TAGOUT PROCEDURES.
III. a - LOUVER ASSEMBLY/SYSTEM ACCESS: To remove the louver assembly first place your hands under the louver panel and lift this up off the bracket and then away from the cabinet face (see figure 3).
Fig. 3
To gain full access to the refrigeration system from the side, remove the cover by removing the bottom screws (see figures 4 & 5).
Fig. 4
Screw
Locations
EVAPORATOR HOUSING COVER:
III. b ­Remove the back cover by removing the four screws which secure this to the cabinet (see figure 6).
Fig. 6
Reverse the procedure when done to reinstall.
III. c -
REMOVING THE DRAWERS: Remove the drawer(s) from the drawer frame by lifting up on the drawer, and then pulling out.
III. d - REMOVING THE DRAWER FRAME: Once the drawer(s) have been removed, the drawer frame module can also be removed by loosening the front and back clamping knobs (2 of each), located on the cross-rail and liner locks (see figures 7 & 8). Slide the front cross-rail locks towards the center of the drawer frame module and allow the liner locks to drop down from the top of the liner.Pull the drawer frame module forward, tip forward and pull out. The entire frame assembly is now free to slide out of the cabinet.
Fig. 5
Side System
Access
When finished, lower the louver assembly into position and replace the side panel. Secure these in place using the previously removed screws.
Fig. 7
Fig. 8
-4-
Page 6
III. REMOVAL & REPLACEMENT OF BASIC PARTS (cont’d)
WARNING: DISCONNECT THE ELECTRICAL POWER TO THE MACHINE
AND FOLLOW LOCKOUT/TAGOUT PROCEDURES.
III. e - DRAWER GASKETS: To remove the gasket to be replaced, grasp it firmly by one corner and pull it out. Before attempting to install a new gasket, both the unit and the gasket itself must be at room temperature. Insert the four corners first by using a rubber mallet (or hammer with a block of wood). After the corners are properly inserted, work your way towards the center from both ends by gently hitting with a mallet until the gasket is completely seated in place (see figure 9 for gasket cross section).
Fig. 9
NOTE: The gasket may appear too large, but if it is installed as indicated above it will slip into place.
III. h - ACCESSING START COMPONENTS (cont’d):
Fig. 10
III. f - THE MICROPROCESSOR CONTROL: To remove the microprocessor controller from the unit in which it was installed, please refer to section “V” of your INTELA-TRAUL® Master Service Manual.
III. g - DRAIN PAN: To remove the drain pan, begin by removing the evaporator housing cover as outlined in section “III. c.Next, remove the screws and brackets which secure the drain pan, and remove the drain tube from the drain pan. Finish by sliding the drain pan out from under the coil.
Reverse the procedure to install.
III. h - ACCESSING START COMPONENTS: The start components are located behind the front louver, inside a metal tray.
To access the start components, first remove the louver assembly as shown in section III. a. Next loosen the top set screw (see figure 10). and remove the molex connection in the back of the box to gain access to the back set screw. Slide the electrical box out the font on its tracks.
Fig. 11
See figure 11 for component detail.
-5-
Page 7
IV. a - REPLACING THE CONDENSER FAN MOTOR AND/OR BLADE
STEP 1: Remove the louver assembly as outlined in
section III. a” to gain access through left side.
STEP 2: Remove the screws holding the fan motor
bracket to the compressor mounting base (see illustration 1).
STEP 3: Remove the blade from the motor shaft by
removing the nut (see illustration 2).
NOTE: Install the concave side of the fan blade toward the motor.
NOTE: If the blade is all that is being replaced, stop here and reverse procedure to install.
STEP 4: Remove the mounting bracket from the motor
(see illustration 3).
STEP 5: Disconnect the lead wires at the compressor
junction box.
STEP 6: Reverse the procedure to install.
STEP 7: Reconnect power to the unit.
WARNINGS:
1) DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AND FOLLOW LOCKOUT/TAGOUT PROCEDURES.
Illustration 01
STEP 8: Reset the microprocessor control defrost time
settings to the correct time of day.
\
Illustration 02
Illustration 03
-6-
Page 8
IV. b - REPLACING THE CONDENSER COIL
WARNINGS:
1) DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AND FOLLOW LOCKOUT/TAGOUT PROCEDURES.
2) THIS PROCEDURE REQUIRES THE USE OF REFRIG­ERANTS. BE CERTAIN THE WORK AREA IS WELL VENTILATED. SAFETY GOGGLES AND GLOVES SHALL BE WORN SINCE REFRIGERANTS MAY CAUSE BURNS TO THE SKIN.
STEP 1: Remove the louver assembly as outlined in
section III. a”.
STEP 2: Recover the refrigerant in the system
following the current EPA Guidelines for refrigerant recovery.
NOTE: The use of reclaiming equipment is required.
STEP 3: Disconnect the input and output lines to the
condenser coil at the soldered joints closest to the condenser.
STEP 4: Remove the four (4) screws which secure the
condenser coil to the mounting brackets (see illustration 1).
STEP 5: Remove the condenser coil.
STEP 6: Reverse the procedure to install the new
condenser coil.
STEP 7: Install a new drier.
Illustration 01
STEP 8: Charge the refrigeration system as outlined
under CHARGING SYSTEM in SERVICE PROCEDUES AND ADJUSTMENTS.
STEP 9: Reconnect power to the unit.
STEP 10: Reset the microprocessor control defrost time
settings to the correct time of the day.
-7-
Page 9
IV. c - REPLACING THE EVAPORATOR FAN
STEP 1: Begin by removing the back cover by first
removing the four screws which secure this to the cabinet (see illustration 1).
All evaporators and fans are located along the back wall of the cabinet and best accessed from the rear (see illustration 2).
STEP 2: Remove the holding rod and unhook the rod
from the other end. This evaporator fan can then be lifted away from the assembly (see illustration 3).
STEP 3: Disconnect the wires from the assembly.
STEP 4: Reverse the procedure to install the new
evaporator fan.
STEP 5: Reconnect power to the unit.
STEP 6: Reset the microprocessor control defrost time
settings to the correct time of the day.
WARNINGS:
1) DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AND FOLLOW LOCKOUT/TAGOUT PROCEDURES.
Illustration 01
Illustration 02
Illustration 03
-8-
Page 10
IV. d - REPLACING THE EVAPORATOR COIL
WARNINGS:
1) DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AND FOLLOW LOCKOUT/TAGOUT PROCEDURES.
2) THIS PROCEDURE REQUIRES THE USE OF REFRIG­ERANTS. BE CERTAIN THE WORK AREA IS WELL VENTILATED. SAFETY GOGGLES AND GLOVES SHALL BE WORN SINCE REFRIGERANTS MAY CAUSE BURNS TO THE SKIN.
STEP 1: Remove evaporator housing cover as outlined
in section III. b.
STEP 2: Recover the refrigerant in the system
following the current EPA Guidelines for refrigerant recovery.
NOTE: The use of reclaiming equipment is required.
STEP 3: Remove the screws which secure the
evaporator to the mounting brackets.
STEP 4: Disconnect the evaporator output line.
STEP 5: Unsolder the liquid line leading into the
capillary tube.
NOTE: When removing the capillary tube care must
be taken toheat protect. Heat sink or wrap a cold, dampcloth over the capillary tube to protect it from overheating.
NOTE: Inspect the end of the liquid line after
disassembly, it could become plugged with solder.
STEP 6: Remove the evaporator coil and capillary tube
from the unit.
STEP 7: Reverse the procedure to install the new
evaporator coil and capillary tube.
STEP 8: Install a new drier.
STEP 9: Charge the refrigeration system as outlined
under CHARGING SYSTEM in SERVICE PROCEDUES AND ADJUSTMENTS.
STEP 10: Reconnect power to the unit.
STEP 11: Reset the microprocessor control defrost time
settings to the correct time of day.
-9-
Page 11
IV. e - REPLACING THE COMPRESSOR
NOTE: Compressor models will vary with each cabinet model, but the basic removal instructions can be followed.
STEP 1: Recover the refrigerant in the system
following the current EPA Guidelines for refrigerant recovery.
NOTE: The use of reclaiming equipment is required.
STEP 2: Remove the compressor junction box cover.
STEP 3: Disconnect all wire leads coming into the
junction box.
STEP 4: Disconnect the discharge and suction lines to
the compressor (see illustration 1).
STEP 5: Remove the compressor which is secured by
either four (4) nuts or pins.
STEP 6: Install the new compressor and connect the
input and output lines.
STEP 7: Connect the lead wires at the junction box.
WARNINGS:
1) DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AND FOLLOW LOCKOUT/TAGOUT PROCEDURES.
2) THIS PROCEDURE REQUIRES THE USE OF REFRIG­ERANTS. BE CERTAIN THE WORK AREA IS WELL VENTILATED. SAFETY GOGGLES AND GLOVES SHALL BE WORN SINCE REFRIGERANTS MAY CAUSE BURNS TO THE SKIN.
STEP 8: Install a new drier.
STEP 9: Charge the refrigeration system as outlined
under CHARGING SYSTEM in SERVICE PROCEDUES AND ADJUSTMENTS.
STEP 10: Reconnect power to the unit.
STEP 11: Reset the microprocessor control defrost time
settings to the correct time of day.
Illustration 01
-10-
Page 12
V. WIRING DIAGRAM
-11-
Page 13
VI. SERVICE PROCEDURES & ADJUSTMENTS
WARNING: CERTAIN PROCEDURES IN THIS SECTION REQUIRE ELECTRICAL TEST OR MEASUREMENTS WHILE POWER IS APPLIED TO THE MACHINE. EXERCISE EXTREME CAUTION AT ALL TIMES. IF TEST POINTS ARE NOT EASILY ACCESSIBLE, DISCONNECT POWER, ATTACH TEST EQUIPMENT AND REAPPLY POWER TO TEST.
VI. a - SYSTEM ACCESS: All external indicators should be checked as part of system diagnosis before determining the refrigerant pressures. Improper access may expose the refrigerant to contaminates and non-condensables which will result in system failure.
VI. b - SWEAT-ON PIERCING VALVES: NOTE: Sweat-on piercing valves are used for system diagnostics, but may be left on after service is complete. They may be installed while the system is fully charged.
1) Place one piercing valve on the compressor process tube and one on the liquid line process tube. Follow the installation instructions provided by the manufacturer of the piercing valve.
2) When complete, follow the guidelines as outlined under LEAK CHECK and EVACUATING SYSTEM.
VI. c - REFRIGERANT LEAK CHECK: DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AT THE MAIN CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT BOX INDICATING THE CIRCUIT IS BEING SERVICED.
THIS PROCEDURE REQUIRES THE USE OF REFRIGERANTS. BE CERTAIN THE WORK AREA IS WELL VENTILATED. SAFETY GOGGLES AND GLOVES SHALL BE WORN SINCE REFRIGERANTS MAY CAUSE BURNS TO THE SKIN.
NOTE: The use of R-22 in small quantities is recommended as a trace gas for leak detection.
NOTE: This leak check procedure is to be used only after the refrigerant has been properly reclaimed.
1) Access the refrigeration system (note: see section V. a - SYSTEM ACCESS).
2) Attach gauge manifold set to the system, low side to process tube on the compressor and the high side to the process tube.
3) Connect refrigerant bottle to the center of gauge manifold and open the valve on the bottle. Bleed charging hose at the manifold gauge to remove air from the system.
4) Open valve on low side of gauge manifold and charge system with one ounce of R-22.
5) Close low side valve on gauge manifold and the valve on the refrigerant bottle.
6) Disconnect refrigerant bottle and connect nitrogen bottle.
VI. c - REFRIGERANT LEAK CHECK (cont’d): NOTE: The use of a nitrogen requlator is required.
7) Set output valve on nitrogen valve to 120 psi.
8) Open nitrogen bottle valve and low side gauge manifold valve. Allow pressure to equalize.
9) Shut off both valves and disconnect nitrogen bottle.
10) Use a leak detector or a thick soapy solution and check for leaks at all tubing connections.
A - If leaks are found, repair leaks and repeat process.
B - If no leaks are found, evacuate system as outlined in section “V. d - EVACUATING SYSTEM”).
11) Charge the system by weighing in the exact charge and check for proper operation.
VI. d - EVACUATING SYSTEM: Introduction - Refrigeration reclaiming equipment is required. Our goal in system evacuation is to remove all the non-condensables possible. No evacuation method will remove 100% of the moisture and air from within the refrigeration circuit. Because of this, guidelines and methods must be developed and adhered to ensuring only harmless amounts of contaminants remain in the system.
GUIDELINES WARNING - DO NOT PRESSURIZE SYSTEM ABOVE 150 PSIG. PRIOR TO EVACUATION OR DURING LEAK TEST PROCEDURES.
Use only a two stage vacuum pump (2 CFM or
greater) and electronic micron.
Evacuate from high and low sides of the system.
No chemical additive or alcohols are to be used to
dry up a system.
Blow down of system with DRY NITROGEN prior to
evacuation is acceptable and many times desirable. See System Clean-Up.
Evacuate to 200 microns.
PROCEDURE WARNING: DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AT THE MAIN CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT BOX INDICATING THE CIRCUIT IS BEING SERVICED.
WARNING: THIS PROCEDURE REQUIRES THE USE OF REFRIGERANTS. BE CERTAIN THE WORK AREA IS WELL VENTILATED. SAFETY GOGGLES AND GLOVES SHALL BE WORN SINCE REFRIGERANTS MAY CAUSE BURNS TO THE SKIN.
-12-
Page 14
VI. SERVICE PROCEDURES & ADJUSTMENTS (cont’d)
WARNING: CERTAIN PROCEDURES IN THIS SECTION REQUIRE ELECTRICAL TEST OR MEASUREMENTS WHILE POWER IS APPLIED TO THE MACHINE. EXERCISE EXTREME CAUTION AT ALL TIMES. IF TEST POINTS ARE NOT EASILY ACCESSIBLE, DISCONNECT POWER, ATTACH TEST EQUIPMENT AND REAPPLY POWER TO TEST.
VI. d - EVACUATING SYSTEM/GUIDELINES (contd):
1) Access the refrigeration system as outlined under SYSTEM ACCESS.
2) Connect low (blue) side of gauge manifold to schrader valve on compressor process line and high (red) side of gauge manifold to schrader valve on filter/drier process line.
3) Connect center line of gauge manifold to vacuum pump.
4) Turn vacuum pump on and open both sides of gauge manifold.
5) Pull a vacuum to 200 microns.
6) Break the vacuum with 3 psig of dry nitrogen.
7) Repeat steps 5 and 6.
8) Pull vacuum to 200 microns.
9) Charge system and check for proper operation.
VI. e - CHARGING SYSTEM: WARNING: DISCONNECT THE ELECTRICAL POWER TO THE MACHINE AT THE MAIN CIRCUIT BOX. PLACE A TAG ON THE CIRCUIT BOX INDICATING THE CIRCUIT IS BEING SERVICED.
WARNING: THIS PROCEDURE REQUIRES THE USE OF REFRIGERANTS. BE CERTAIN THE WORK AREA IS WELL VENTILATED. SAFETY GOGGLES AND GLOVES SHALL BE WORN SINCE REFRIGERANTS MAY CAUSE BURNS TO THE SKIN.
1) Access the refrigeration system.
2) Attach gauge manifold set to system, low side to process tube on the compressor and the high side to the process tube on the drier.
NOTE: See SYSTEM ACCESS.
3) Be sure the system is properly leak checked and evacuated before charging as outlined under “LEAK CHECK and EVACUATING SYSTEM.
4) Make certain both valves are closed on the gauge manifold. Open the valve on the bottle. Bleed charging hose at the manifold gauge to remove air.
NOTE: Initially charge system through high side to prevent liquid refrigerant from reaching compressor.
5) Open the high side gauge valve (red). Allow refrigerant to flow into the system until the nameplate charge is reached or until the high side will not accept any more refrigerant. At this point, shut the gauge and bottle valves.
6) Reconnect power to the unit and check for proper operation and high pressure leaks.
VI. e - CHARGING SYSTEM (cont’d):
7) Add the remaining amount of refrigeration charge through the low side with the compressor running.
8) Check for proper operation and leaks.
9) Disconnect power to the unit and replace any covers removed.
VI. f - SYSTEM CLEAN UP/INTRODUCTION: When a compressor burn-out or moisture infiltration is encountered, the service person must make the determination as to the degree of system contamina­tion. Normally a compressor burn-out will fit into one of three catagories:
CONTAINED - compressor oil not acidic, no oil dis coloration.
CONTAMINATED COMPRESSOR - oil acidic, discoloration of oil, contamination limited to compressor.
MASSIVE CONTAMINATION - contaminated oil and/or refrigerant pumped through system.
CONTAINED
1) Replacement of liquid line drier.
2) Install suction filter drier for clean up and then
remove it when service is complete. Usually within 48-hours.
3) Replacement of compressor.
4) Evacuation (to 200 microns).
5) Charge by weight.
CONTAMINATED COMPRESSOR The contaminated compressor requires the same procedure as the containedburn-out. Plus, the system must be flushed with nitrogen after the compressor and drier has been removed.
-13-
Page 15
VI. SERVICE PROCEDURES & ADJUSTMENTS (cont’d)
WARNING: CERTAIN PROCEDURES IN THIS SECTION REQUIRE ELECTRICAL TEST OR MEASUREMENTS WHILE POWER IS APPLIED TO THE MACHINE. EXERCISE EXTREME CAUTION AT ALL TIMES. IF TEST POINTS ARE NOT EASILY ACCESSIBLE, DISCONNECT POWER, ATTACH TEST EQUIPMENT AND REAPPLY POWER TO TEST.
VI. f - SYSTEM CLEAN UP/INTRODUCTION (cont’d):
MASSIVE CONTAMINATION The replacement compressor MUST NOT be installed until after system clean-up procedures have been completed.
1) Remove the burned-out compressor as outlined under COMPRESSOR in Section IV. f”.
2) Remove the capillary tube metering device.
3) Purge nitrogen through the high and low sides of system until moisture and contaminated oil has been removed from the remaining components of the system.
4) Reassemble refrigeration system and add a CW style liquid drier and a suction line drier.
5) Purge nitrogen through the high and low sides of system for 5 minutes.
6) Evacuate refrigeration as outlined under EVACUATING SYSTEMfor 30 minutes. Repeat nitrogen purge and evacuate two more times.
7) Charge system as outlined under CHARGING SYSTEM. Allow for the increased liquid capacity of the liquid line drier.
8) Reconnect power and check for proper operation.
9) Disconnect power and install any panels removed.
MASSIVE CONTAMINATION (contd):
10) Return between 24 and 48 hours to recover gas, replace liquid line drier with a CW style drier. Remove the suction drier, but do not replace.
11) Evacuate and charge system as outlined under “EVACUATING SYSTEM” and “CHARGING SYSTEM .
VI. g - HEATER TEST - DRAWER PERIMETER HEATER:
1) Access the heater wire around the drawer frame.
2) Plug the unit in and verify 120 volt supply to the heater.
3) The reading should be .25 amp.
VII. ELECTRICAL OPERATION
VII. a - NORMAL OPERATION:
1. Conditions a) Unit connected to correct voltage (check using a
volt meter). b) Microprocessor off cycle defrost settings correct. c) Condensing unit controlled by the microprocessor
control. d) Cabinet at desired temperature. e) Door perimeter heaters are powered 100% of the
time as preset by the factory (this can be adjusted
using the microprocessor control). f) Evaporator fan powered. g) Microprocessor control operating correctly.
2. Cabinet temperature rises above set temperature. a) Microprocessor control initiates compressor
operation. b) Evaporator fan should be ON all the time.
3. Set temperature is met. a) Conditions return to those outlined in step 1.
VII. b - DEFROST MODE:
1. Conditions a) Unit operating in normal mode.
2. Defrost initiated by the microprocessor control (an off-cycle defrost should occur every 60-minutes).
3. Defrost terminated by either: 1) Evaporator Coil Temperature or 2) Maximum Set Time Interval.
4. Cabinet returns to normal operation.
a) Temperature controlled by the microprocessor
control.
b) Evaporator fan stays ON, evaporator coil will reach
desired temperature.
-14-
Page 16
VII. c - COMPONENT FUNCTION:
Compressor: Pumps refrigerant thru refrigeration system components and
Condenser Fan: Draws air across condenser coil to aid in removing heat from the
Evaporator Fan: Draws air from the cabinet and pulls the air thru the evaporator coil.
Start Capacitor: Stores electrical charge which helps start the compressor motor.
Run Capacitor: Helps keep the compressor motor running after starting.
Microprocessor Control: Performs the functions of the 1) defrost timer, 2) high limit switch,
Drawer Perimeter Heater: Heats drawer opening to prevent condensation from forming.
Contactor Relay: Controls voltage to compressor motors.
VII. ELECTRICAL OPERATION
compresses the low pressure vapor into high pressure vapor.
refrigerant and moves air across compressor to aid in cooling the compressor.
3) thermometer and 4) thermostat.
VII. d - INSTALLATION OF THE SENSORS:
There are two sensors used inside the cabinet. The first one is the Cabinet Sensor that is used to cycle the compressor on and off at the correct temperature. The cabinet sensor is mounted between the two coils just below the top of the cabinet thru the 1/2” holes in the back wall and the tip should be 1” inside the cabinet. Refer to the drawing below. The part number for the Cabinet Sensor is 337-60405-03.
Insert sensor inside the cabinet thru 1/2” holes in back wall
1” inside cabinet
The Evaporator Coil Sensor is to be mounted in the evaporator, in the center of the coil and fully inserted into the coil until only the wire is visible and then pinch the fins around the cable to hold it in place. The part number for the Evaporator Coil Sensor is 337-60406-03.
Fully insert probe into coil
The third sensor used is a Liquid Line Sensor. This sensor is to be installed on the liquid line as it comes out of the condenser coil. The part number for this sensor is 337-60407-01.
Attach sensor to the
liquid line using the
wrap
When the condensing temperature reaches 140°F or greater the control will display “CLN-FIL.” Should the condensing temperature increase to 160°F the compressor will automatically shut off. When the liquid line temperature drops below 140°F the compressor will restart and when the line temperature drops to 120°F the alarm will reset.
Center of Coil
.756 between 1 and 2nd hair bend
-15-
st
Page 17
VIII. REPLACEMENT PARTS LISTING
NOTE: Part numbers listed are for standard products as currently manufactured. For products manufactured
as other than standard, or for older production units, please contact the factory.
PART NO. NAME OF PART
SER-60536-00 4” High Caster w/o Lock SER-60536-01 4” High Caster with Lock
550-10053-00 Drawer Assembly 550-10057-00 Drawer Face 550-10059-00 Drawer Frame SER-60537-00 Drawer Frame Insert 341-60176-02 Drawer Gasket 344-60155-00 Drawer Roller
(all models except TE036HT, TE060HT, TE065HT, TE125HT &
550-10054-00 Drawer Assembly 550-10058-00 Drawer Face 550-10060-00 Drawer Frame SER-60537-01 Drawer Frame Insert 341-60176-03 Drawer Gasket 344-60155-00 Drawer Roller
550-10067-00 Drawer Assembly 550-10076-00 Drawer Face 550-10077-00 Drawer Frame SER-60537-03 Drawer Frame Insert 341-60176-04 Drawer Gasket 344-60155-00 Drawer Roller
550-10074-00 Drawer Assembly 550-10069-00 Drawer Face 550-10070-00 Drawer Frame SER-60537-02 Drawer Frame Insert 341-60176-01 Drawer Gasket 344-60155-00 Drawer Roller
CABINET SUPPORTS
DRAWER PARTS
(models TE036HT & TE065HT)
DRAWER PARTS
TE072HT)
DRAWER PARTS
(models TE060HT & TE125HT)
DRAWER PARTS
(model TE072HT only)
PART NO. NAME OF PART
COMPRESSORS 321-60225-00 For Models TE036HT thru TE084HT 321-60226-00 For Models TE096HT thru TE139HT
MISC. SYSTEM COMPONENTS 323-60088-00 Suction Heat Exchange Evap 9” Coil 350-10000-00 Suction Heat Exchange Evap 18” Coil 322-60048-00 Evaporator Coil 9” 322-60050-01 Evaporator Coil 18” 325-60103-00 Liquid Line Drier 325-60144-00 Condenser Fan Motor Assembly 325-60145-00 Evaporator Fan Motor Assembly 325-60135-00 Condenser Fan Blade 338-60050-00 Condenser Fan Motor 701-61119-00 Spring Rod 9” Evaporator Coil 701-61119-01 Spring Rod 18” Evaporator Coil 337-60360-01 Compressor Relay
MISC. CABINET PARTS 337-60346-00 ON/OFF Power Switch 509-50118-00 Marine Top for TE036HT 509-50118-01 Marine Top for TE048HT 509-50118-02 Marine Top for TE060HT 509-50118-03 Marine Top for TE065HT 509-50118-04 Marine Top for TE072HT 509-50118-05 Marine Top for TE084HT 509-50118-06 Marine Top for TE096HT 509-50118-07 Marine Top for TE110HT 509-50118-08 Marine Top for TE125HT 509-50118-09 Marine Top for TE139HT
LOUVER PANELS 500-70075-00 For System on Left 500-70075-01 For System on Right
CONTROL PARTS 337-60403-00 Control Head 337-60405-03 Cabinet Temp Sensor 337-60406-03 Coil Temp Sensor 337-60407-01 Liquid Line Sensor 337-60317-00 Relay Module
-16-
Page 18
IX. TROUBLESHOOTING
WARNING: CERTAIN PROCEDURES IN THIS SECTION REQUIRE ELECTRICAL AND REFRIGERA-
TION SYSTEM TEST OR MEASUREMENTS WHILE POWER IS APPLIED TO THE MACHINE. EXER­CISE EXTREME CAUTION AT ALL TIMES. IF TEST POINTS ARE NOT EASILY ACCESSIBLE, DISCON­NECT POWER, ATTACH TEST EQUIPMENT AND REAPPLY POWER TO TEST.
Compressor will not run, compressor has no current draw. 1. Main circuit breaker open.
Compressor will not run, current draw and trips overload. 1. Low voltage.
Compressor short cycles on overload. 1. Low voltage.
Compressor short cycles. 1. Improper air flow over evaporator coil.
Continuous unit operation. 1. Loss of refrigerant.
Compressor run time lengthy. 1. Partial loss of refrigerant.
Low suction pressure. 1. Capillary tube restricted.
High head pressure. 1. Improper air flow across condenser.
Will not defrost or inadequate defrost. 1. Defrost heater malfunction.
Coil icing. 1. Number of defrost cycles too few.
The cabinet & coil sensors show high temperature. 1. Sensor needs rreplacing (place sensor tip and
2. Compressor overload tripped.
3. Cabinet temperature satisfied.
4. Wired wrong or faulty connection.
5. INTELA-TRAUL
6. Start component malfunction.
7. Compressor motor windings open.
2. Start component malfunction.
3. Compressor windings shorted.
4. Locked rotor.
5. Excessive discharge pressure.
2. Low refrigerant charge.
3. Dirty condenser coil and/or filter.
4. Wired wrong or faulty connection.
5. Condenser fan inoperative.
6. Run capacitor malfunction.
7. Start component malfunction.
8. INTELA-TRAUL® control malfunction1.
9. High head pressure.
2. Low ambient conditions.
3. INTELA-TRAUL® control malfunction1.
4. Bad sensors.
5. Temp differential set too close.
2. Excessive drawer openings.
3. INTELA-TRAUL® control malfunction1.
4. Broken compressor valves.
5. Very dirty condenser and/or filter.
6. Check the “DL,” if higher than 160F
2. High ambient conditions.
3. Dirty condenser coil or improper air flow over condenser coil.
4. Excessive product load.
5. Excessive drawer openings.
6. Drawer gasket requires replacement.
7. INTELA-TRAUL® control malfunction1.
8. Contaminates in refrigeration system.
9. Compressor valve leakage.
10. Inadequate defrost cycle.
2. Drier plugged.
3. Loss of refrigerant.
4. Poor air flow.
5. Iced evaporator coil.
2. High ambient conditions.
3. Overcharge of refrigerant.
4. Air in system.
5. Dirty condenser coil.
2. Wired wrong or faulty connection.
3. Cabinet air leak.
4. Coil sensor failure.
5. INTELA-TRAUL® control malfunction1.
2. Defrost duration too short.
3. Cabinet air leak.
4. Drain tube plugged.
5. Defrost heater not working.
6. Non-frozen product put into cabinet.
7. Coil sensor failure.
thermometer in ice water. Change sensor ir readings differ, or if sensor displays -40 02 266).
®
control malfunction1.
-17-
Page 19
-18-
Page 20
For More Information On The Proper Installation, Use and Maintenance Of Traulsen Refrigerated Equipment Stand Models, Please Refer To The Following Materials Available From Your Local Hobart/Traulsen Sales & Service Location:
INTELA-TRAUL Master Service Manual - Form Number TR35705