Trane WCC030, WCC040, WCC050, WCC030FD00B, WCC040FD00B Product Data

...
50 Hz P ackage Heat Pump Units Product Data
Convertible Models
WCC030,040,050 30, 40, 50 MBh
IPB-99-7-EN-10-6-99
General Features
T-Top™ Corrosion Resistant Screws Powder Paint Water-Shed™ Base High Efficiency
Climatuff DuraT uff™ Plate Fin Coil Time Defrost Control Sloped Drain Pan 100% Foil Faced Insulation Easy Access
®
Compressor
Contents
Feature Summary 2 Features and Benefits 4
Standard Equipment 4
Impack Accessories 5 Optional Equipment 6 Selection Procedure 7
Model Number Nomenclature 7
General Data 8
English Units
WCC030FD00B 8 WCC040FD00B 8 WCC050FD00B 8
Metric Units
WCC030FD00B 9 WCC040FD00B 9 WCC050FD00B 9
IPB-99-7-EN-10-6-99 3
Perf ormance Data 10
Cooling English Units 10 Cooling Metric Units 11 Heating English Units 12 Heating Metric Units 13 Indoor Blower Performance 14
Optional Equipment 15 Controls 16 Field Wiring 17 Dimensions 20 Mechanical Specification Options 26
• High Efficiency
Impack performance is among the highest in the industry.
• Climatuff® Compressor
Protection against chemical, electrical, and mechanical stresses are built in for efficiency and a longer life. The compressor is backed by a 5-year limited warranty, with an optional warranty for 5 more years.
• Time Defrost Control
This is an electronic, time initiated, tempera­ture terminated defrost system that offers a choice of 50, 70, or 90 minute cycles. The time override limits the defrost cycle to 10 minutes.
• Convertibility
Impack units are easily converted from horizontal to downflow with the removal of one screw from each panel. Accordingly, the need to stock both dedicated horizontal and dedicated downflow models has been eliminated.
• Installation
The ease of installation and application flexibility exhibited through the design reduce both field time and material.
• Application
The low profile horizontal duct take-offs eliminate the need for expensive transition ducts in crawl space applications.
• Commonality
The common cabinet among the TCC’s, WCC’s, and YCC’s minimizes both the training of sales and service personnel and replacement parts inventory.
• Flexibility
A single curb fits the entire Impack line from
1.5 tons through 5 tons thereby providing great installation flexibility on shopping malls, factories, schools, and other commercial buildings where a mix-match of tonnages and utilities is desired.
Features and Benefits
Standard Equipment
• Water-Shed™ Base
Superior water integrity is accomplished with the Water-Shed™ base pan having elevated downflow openings and a perim­eter channel that prevents water from draining into the ductwork.
• Easy Access
All electrical components can be diagnosed and replaced with the removal of one panel that is attached with two screws.
• Service
All wiring is both numbered and color coded thereby reducing training and servicing costs related to circuit tracing and compo­nents replacements.
• Maintenance
A plug on the outdoor fan motor allows the top cover to be removed completely without the hassle of cumbersome wires. The unique service orifice ring allows the indoor fan motor/blower to be removed as a unit.
• Plate Fin Coil
Refrigeration coils are built with internally enhanced copper tubing for high efficiency with less coil area.
• Shipping
Unit dimensions were carefully selected to provide an attractive aspect ratio and for shipping and handling considerations.
• Good Neighbor
Most units can be installed flush with the residence or building thereby minimizing the ground space required. Blankets of insulation reduce blower noise and energy losses to the outside environments.
• Rooftop Mounting
The cabinets are physically smaller than most competitive models. This means less intrusive installations on residential rooftops where aesthetics are critical.
• Handling
The three-way wooden skid allows for easy loading between the wheel wells on pickup trucks for transporting to job sites.
• Structure
The units are lighter weight through the use of high technology components thereby reducing mounting structure requirements and difficulty when handling.
• Duct Flanges
Only Impack has downflow duct flanges for duct attachments that preserve the built-in water integrity.
• Corrosion
The drain pan is engineered material and eliminates the need for coatings and sealers to prevent sweating and corrosion. The heavy gauge, zinc-coated steel cabinet has a weather resistant enamel finish that stays attractive and protects your investment for years.
• Low Ambient Control
Zero degree ambient cooling is accom­plished with two kits. One for low cost installations when full tonnage is not needed. The other kit maintains head pressure and full capacity at zero degrees.
• Quality and Reliability Testing
We perform a 100% coil leak test at the factory. The evaporator and condenser coils are leak tested at the factory. The evaporator and condenser coils are leak tested at 200 psig and pressure tested to 450 psig respectively. In addition the Impack designs were rigorously rain tested at the factory to ensure water integrity. Shipping tests are performed to determine packaging requirements. Factory shake and drop tests are used as part of the package design process to help assure that the unit will arrive at the job site in top condition. Additionally, all components are inspected at the point of final assembly. Substandard parts and components are identified and rejected immediately. Every unit receives a 100% run test before leaving the production line to make sure it lives up to rigorous Trane® requirements. We at Trane test our designs at our factory and not on our customers!
4 IPB-99-7-EN-10-6-99
Impack Accessories
• Standard Thermostats
No special thermostats are needed with Impack units.
• Filter Frame Kit
The Impack filter frames accept standard filters and fit inside the unit. The frame kits function in either horizontal or downflow duct configurations.
• Coil Guard Kit
The guards are vinyl coated 1" x 3" wire grills. These grills will protect the coil from hail, kids with sticks as well as normal shipping and installation handling damage.
• UNI-CURB™
One universal curb fits all the Impack models. It ships knocked down. The curb design incorporates the popular locking tabs for quick and easy assembly. Full perimeter curbs are also available for all models.
• 25% Fresh Air Kit
The kit installs over the horizontal return air opening with six screws for downflow require­ments. It can be used on horizontal air flow applications by cutting a hole in the return air duct or in the unit filter access panel.
• Rectangular to Round Duct Kits
The adapter kit can be used in either horizontal or downflow applications.
• Low Ambient Kit
An EDC provides low ambient cooling to 0° F with some reduced capacity and protects the system against evaporator icing during other unusual cooling conditions.
• Fan Delay Relay Kit
This solid state kit is a time delay that keeps the indoor blower on for about ninety seconds and increases the SEER. It wires into the low voltage unit pigtails.
• High Static Motor Kit
Contains a higher torque indoor fan motor.
• Lifting Lug Kit
Four reusable lugs in each kit allow units to be easily lifted to rooftop installations. These lugs snap (no screws required) into slots in the unit drip lip channel.
• Start Kit
The kit mounts in the control box for those installations with specific conditions such as excessive voltage drop due to long wires. (This is a capacitor and start relay kit and is not a PTC device.) This kit can be a good specification buster!
IPB-99-7-EN-10-6-99 5
• Economizer
The economizer fits inside the unit with only the rain hood and barometric relief on the outside. Cabling (with polarized plugs) is shipped with the economizer. This cabling is easily routed to the control box where it terminates in low voltage pigtails. The economizer features a fully modulating low voltage motor eliminating the need for any high voltage wiring. The economizer must be used with the filter frame kit . . . no return air filter in the economizer kit. A dr y bulb sensor is shipped with the economizer. The economizer was not designed for use in horizontal applications. Heat pump applica­tions require a relay kit.
• Enthalpy Control Kit
For those applications specifying an econo­mizer with enthalpy control, this control can be used in place of the dry bulb sensor or, alternately, two enthalpy controls can be paired to provide differential enthalpy control.
• Single Power Entry Kit
The kit minimizes installation costs by reducing the load center circuit requirement and reducing the number of circuit pulls needed.
Optional Equipment
OPTIONAL EQUIPMENT FOR PACKAGE UNITS (Check mark [
Indoor Thermostats — 3H/2C Auto Changeover ............................................................................................................................... BAY28X153A [ ]
Roof Curb (Flat Roof) (WCC-F) 5 ................................................................................................................................................. BAYCURB030A [ ]
Roof Curb (Flat Roof) (WCC040-050F) ........................................................................................................................................ BAYCURB034A [ ]
0-25% Manual Fresh Air Damper (WCC030F) 2 ........................................................................................................................BAYDMPR040A [ ]
0-25% Manual Fresh Air Damper (WCC040,050F) 2 ................................................................................................................. BAYDMPR041A [ ]
12" Round Duct Adapter (2 per box) (WCC030F) ........................................................................................................................ BAYDUCT004A [ ]
14" Round Duct Adapter (1 per box) (WCC040,050F) ................................................................................................................. BAYDUCT005A [ ]
0-100% Mod. Economizer w/Baro. Relief (WCC030F) 12345 .............................................................................................. BAYECON054A [ ]
0-100% Mod. Economizer w/Baro. Relief (WCC040,050F) 12345 ....................................................................................... BAYECON055A [ ]
0-100% Horizontal Economizer 23 ............................................................................................................................................ BAYECON073A [ ]
Enthalpy Control (solid state) (WCC-F) 3 .....................................................................................................................................BAYENTH001A [ ]
Economizer Relay Kit (WCC-F) 1 .................................................................................................................................................BAYRLAY003A [ ]
Filter Frame (20x25x1" filter not incl.) WCC030F 2 .......................................................................................................................BAYFLTR012A [ ]
Filter Frame (3-10x25x1" filters not incl.) WCC040,050F 2 ..........................................................................................................BAYFLTR014A [ ]
Lifting Lug Kit (WCC-F) ........................................................................................................ ............................................................. BAYLlFT002A [ ]
Evaporator Defrost Control (Low Ambient Cool) Kit (WCC-F) 1 ................................................................................................. BAYLOAM011A [ ]
Condenser Coil Guard (WCC030F) .............................................................................................................................................. BAYGARD017A [ ]
Condenser Coil Guard (WCC040,050F) ....................................................................................................................................... BAYGARD022A [ ]
High Static Motor (WCC030F) (230/460) (3/4 hp) ........................................................................................................................ BAYHSMT043A [ ]
High Static Motor (WCC040,050F) (230/460) (1 hp) .................................................................................................................... BAYHSMT044A [ ]
Anti-Short Cycle Timer (WCC-F) ...................................................................................................................................................... BAYASCT001 [ ]
Indoor Fan Delay Kit (WCC-F) ............................................................................................................................................................ BAY24X045 [ ]
Notes:
1
Relay required with economizer on WCC-F models .
2
Must use filter frame when economizer/fresh air kit is used.
3
Dry bulb control standard with economizer.
2H/1C Auto ................................................................................................................................................... BAY28X138A [ ]
Prog. Setback Thermostat (WCC-F) ........................................................................................................... BAYSTAT024B [ ]
2 Stage Htg/Clg Thermostat (WCC-F) .......................................................................................................... BAYSTAT239 [ ]
Remote Sensor for Prog. Thermostat............................................................................................................ BAYSTAT021 [ ]
Fan Control Relay Kit (DPDT Relay (WCC-F) ...................................................................................... ........... BAY24X042 [ ]
5 or 7 Minute Delay Relay ............................................................................................................................. BAY41X171A [ ]
Locking Thermostat Cover (Thermostats) ....................................................................................................... BAY28X190 [ ]
Man. Prog. 2 Htg/1 Clg ................................................................................................................................... TAYSTAT500 [ ]
Man. Prog. 2 Htg/1 Clg ................................................................................................................................... TAYSTAT501 [ ]
Man. 2 Htg/1 Clg with Subbase..................................................................................................................... BAYSTAT240 [ ]
Outdoor Thermostat .................................................................................................................................... BAYSTAT033A [ ]
✓✓
] indicates accessories included).
✓✓
4
Ships knocked down.
5
Downflow only.
6 IPB-99-7-EN-10-6-99
123456789101112
WCC030FD00BA
PRODUCT TYPE
TC = Package Cooling WC = Package Heat Pumps
Selection Procedure
Model Number Nomenclature
PRODUCT SERVICE CHANGE
AIRFLOW CONFIGURATION
C = Convertible
NOMINAL NET COOLING CAPACITY
030 = 30 MBh 040 = 40 MBh 050 = 50 MBh
MAJOR DESIGN MODIFICATION
F = Impack
MINOR DESIGN MODIFICATION
FACTORY INSTALLED OPTIONS EXAMPLES:
0 = No factory installed options
AUXILIARY HEATING CAPACITY
Ø = No Auxiliary Heat (from Factory)
ELECTRICAL CHARACTERISTICS
D = 380-415V/3/50
IPB-99-7-EN-10-6-99 7
General Data English Units
MODEL RA TED VOL TS/PH/HZ A.R.I. RATING
RATINGS (COOLING)
BTUH INDOOR AIR FLOW (CFM)
POWER INPUT (kW) EER-95 (BTU/WATT-HR.) EER-82 NOISE RATING NO.
RATINGS (HEATING)
(HIGH TEMP.) BTUH - COP
POWER INPUT (kW)
(LOW TEMP.) BTUH - COP
POWER INPUT (kW) HSPF (BTU/WATT-HR.)
POWER CONNS. — V/PH/HZ
MIN. BRCH. CIR. AMPACITY FUSE SIZE - MAX.(AMPS) FUSE SIZE - RECMD. (AMPS)
COMPRESSOR
NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS L.R. AMPS BRCH. CIR. SELEC. CUR. AMPS
OUTDOOR COIL — TYPE
ROWS / F.P.I. F ACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT CONTROL
INDOOR COIL — TYPE
ROWS / F.P.I. F ACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT CONTROL DRAIN CONN. SIZE (IN.) DUCT CONNECTIONS
OUTDOOR FAN — TYPE
NO. USED / DIA. (IN.) TYPE DRIVE / NO. SPEEDS CFM @ 0.0 IN. W.G. NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS - L.R. AMPS
INDOOR FAN — TYPE
DIA. X WIDTH (IN.) NO. USED DRIVE / SPEEDS (NO.) CFM VS. IN. W.G. NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS - L.R. AMPS
FILTER — FURNISHED?
TYPE RECOMMENDED NO. - SIZE - THICKNESS
REFRIGERANT
CHARGE (LBS. OF R-22)
DIMENSIONS
CRATED (IN.) UNCRATED
WEIGHT
SHIPPING (LBS.) / NET (LBS.)
NOTES:
1
RATED IN ACCORDANCE WITH A.R.I. STANDARD 210/240.
2
CALCULATED IN ACCORDANCE WITH A.R.I. STANDARD 270.
3
CALCULATED IN ACCORDANCE WITH CURRENTLY PREVAILING NATL. ELECTRIC CODE.
4
STANDARD AIR - DRY COIL - OUTDOOR
1
6
2
1
6
3
4
5
WCC030FD00B
380-415/3/50
31000
1000
3.12
9.50
10.90
8.0
29600 - 3.12
2.78
15600 - 2.00
2.29
380-415/3/50
10.2 15 15
1 - 1
5.7 51
4.2
PLATE FIN
2 / 15
8.62
PLATE FIN
3 / 15
3.96
1 / 18
DIRECT / 1
2040
1 - 1/2
900
1.7 - 3.8
10 X 9
1
DIRECT / 2
1 - 1/3
900
1.1 - 2.6 NO
3 - 10 x 25
8.2 LBS.
406 / 366
®
CLIMATUFF 380-415/3/50
3/8 COPPER TXV BLEED
3/8 COPPER
ORIFICE - .071
3/4 FEMALE NPT
SEE OUTLINE DRAWING
PROPELLER
380-415/1/50
CENTRIFUGAL
SEE FAN PERFORMANCE TABLE
380-415/1/50
THROW AWAY
H X W X D
35-1/4 X 38 X 57
SEE OUTLINE DRAWING
WCC040FD00B
380-415/3/50
39600
1325
4.10
9.70
10.95
8.4
39400 - 3.18
3.66
20700 - 2.06
2.96
6.80
380-415/3/50
13.8 20 20
1 -
8.0 51
7.1
PLATE FIN
2 / 15
14.0 3/8
PLATE FIN
4 / 15
5.4 3/8
1 / 22
DIRECT / 1
2830
1 - 1/2
900
1.7 - 3.8
11.0 X 11.0 1
DIRECT / 2
1 - 3/4
900
2.1 - 4.8 NO
3 - 10 x 25
13.0 LBS
561 / 521
®
SEE OUTLINE DRAWING
SEE FAN PERFORMANCE TABLE
SEE OUTLINE DRAWING
CLIMATUFF 380-415/3/50
TXV BLEED
ORIFICE- .082
3/4 FEMALE
SEE OUTLINE DRAWING
PROPELLER
380-415/1/50
CENTRIFUGAL
SEE FAN PERFORMANCE TABLE
380-415/1/50
THROWAWAY
H X W X D
39-3/8 X 47 X 66
SEE OUTLINE DRAWING
5
STANDARD AIR - WET COIL - INDOOR
6
RATED IN ACCORDANCE WITH D.O.E. TEST PROCEDURE. HSPF IS AT THE MINIMUM DESIGN REQUIREMENT FOR REGION IV.
WCC050FD00B
380-415/3/50
51600
1675
5.53
9.35
11.15
8.4
53600 - 3.18
4.91
31300 - 2.16
4.21
6.80
380-415/3/50
16.3 25 25
1 -
9.8 71
10.0
PLATE FIN
2 / 15
14.0 3/8
PLATE FIN
4 / 15
5.4 3/8
1 / 22
DIRECT / 1
2830
1 - 1/2
900
1.7 - 3.8
11.0 X 11.0 1
DIRECT / 2
1 - 3/4
900
2.1 - 4.8 NO
3 - 10 x 25
12.0 LBS
579 / 539
®
CLIMATUFF 380-415/3/50
TXV BLEED
ORIFICE - .096
3/4 FEMALE
PROPELLER
380-415/1/50
CENTRIFUGAL
380-415/1/50
THROWAWAY
H X W X D
39-3/8 X 47 X 66
8 IPB-99-7-EN-10-6-99
General Data Metric Units
MODEL RA TED VOL TS/PH/HZ A.R.I. RATING
RATINGS (COOLING)
BTUH INDOOR AIR FLOW (CMH)
POWER INPUT (kW) EER-95 (BTU/WATT-HR.) EER-82 NOISE RATING NO.
RATINGS (HEATING)
(HIGH TEMP.) CAPACITY (WATTS) - COP
POWER INPUT (kW)
(LOW TEMP.) CAPACITY (WATTS) - COP
POWER INPUT (kW) HSPF (BTU/WATT-HR.)
POWER CONNS. — V/PH/HZ
MIN. BRCH. CIR. AMPACITY FUSE SIZE - MAX.(AMPS) FUSE SIZE - RECMD. (AMPS)
COMPRESSOR
NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS L.R. AMPS BRCH. CIR. SELEC. CUR. AMPS
OUTDOOR COIL — TYPE
ROWS / FINS PER MILLIMETER FACE AREA (SQ. M) TUBE SIZE (IN.) REFRIGERANT CONTROL
INDOOR COIL — TYPE
ROWS / FINS PER MILLIMETER FACE AREA (SQ. M) TUBE SIZE (IN.) REFRIGERANT CONTROL DRAIN CONN. SIZE (IN.) DUCT CONNECTIONS
OUTDOOR FAN — TYPE
NO. USED / DIA. (MM) TYPE DRIVE / NO. SPEEDS CMH @ 0.0 PASCALS NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS - L.R. AMPS
INDOOR FAN — TYPE
DIA. X WIDTH (MM) NO. USED DRIVE / SPEEDS (NO.) CMH VS. PASCALS NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS - L.R. AMPS
FILTER — FURNISHED?
TYPE RECOMMENDED NO. - SIZE - THICKNESS
REFRIGERANT
CHARGE (KG OF R-22)
DIMENSIONS
CRATED (MM) UNCRATED
WEIGHT
SHIPPING (KG) / NET (KG)
NOTES:
1
RATED IN ACCORDANCE WITH A.R.I. STANDARD 210/240.
2
CALCULATED IN ACCORDANCE WITH A.R.I. STANDARD 270.
3
CALCULATED IN ACCORDANCE WITH CURRENTLY PREVAILING NATL. ELECTRIC CODE.
4
STANDARD AIR - DRY COIL - OUTDOOR
1
6
2
1
6
3
4
5
WCC030FD00B
380-415/3/50
9085 1690
3.12
9.50 / 10.00
10.90
8.0
8675 - 3.12
2.78
4572 - 2.00
2.29
6.80
380-415/3/50
10.2 15 15
CLIMATUFF
380-415/3/50
3/8 COPPER
3/8 COPPER
ORIFICE - .071
3/4 FEMALE NPT
SEE OUTLINE DRAWING
PROPELLER
380-415/1/50
CENTRIFUGAL
SEE F AN PERFORMANCE TABLE
380-415/1/50
THROWAWAY
H X W X D
895 X 965 X 1448
SEE OUTLINE DRAWING
®
1 - 1
5.7 51
4.2
PLATE FIN
2 / .591
.801
TXV BLEED
PLATE FIN
3 / .591
.368
1 / 457
DIRECT / 1
3448
1 - 1/2
900
1.7 - 3.8
254 X 229
1
DIRECT / 2
1 - 1/3
900
1.1 - 2.6 NO
3 - 254 x 635
3.72 KG
184 / 166
WCC040FD00B
380-415/3/50
11606
2240
4.10
9.70 / 10.00
10.95
8.4
11547 - 3.18
3.66
6067 - 2.06
2.96
6.80
380-415/3/50
13.8 20 20
CLIMATUFF
380-415/3/50
ORIFICE- .082
3/4 FEMALE
SEE OUTLINE DRAWING
PROPELLER
380-415/1/50
CENTRIFUGAL
SEE FAN PERFORMANCE TABLE
380-415/1/50
THROW AWAY
H X W X D
1000 X 1194 X 1676
SEE OUTLINE DRAWING
5
STANDARD AIR - WET COIL - INDOOR
6
RATED IN ACCORDANCE WITH D.O.E. TEST PROCEDURE. HSPF IS AT THE MINIMUM DESIGN REQUIREMENT FOR REGION IV.
®
1 -
8.0 51
7.1
PLATE FIN
2 / .591
1.30 3/8
TXV BLEED
PLATE FIN
4 / .591
.502
3/8
1 / 559
DIRECT / 1
4785
1 - 1/2
900
1.7 - 3.8
279 X 279
1
DIRECT / 2
1 - 3/4
900
2.1 - 4.8 NO
3 - 254 x 635
5.90 KG
254 / 236
SEE OUTLINE DRAWING
SEE FAN PERFORMANCE TABLE
1000 X 1194 X 1676
SEE OUTLINE DRAWING
WCC050FD00B
380-415/3/50
15122
2830
5.53
9.35 / 10.00
11.15
8.4
15709 - 3.18
4.91
9173 - 2.16
4.21
6.80
380-415/3/50
16.3 25 25
CLIMATUFF
380-415/3/50
ORIFICE - .096
3/4 FEMALE
PROPELLER
380-415/1/50
CENTRIFUGAL
380-415/1/50
THROWAWAY
H X W X D
®
1 -
9.8 71
10.0
PLATE FIN
2 / .591
1.30 3/8
TXV BLEED
PLATE FIN
4 / .591
.502
3/8
1 / 559
DIRECT / 1
4783
1 - 1/2
900
1.7 - 3.8
279 X 279
1
DIRECT / 2
1 - 3/4
900
2.1 - 4.8 NO
3 - 254 x 635
5.44 KG
263 / 244
IPB-99-7-EN-10-6-99 9
Performance Data Cooling English Units
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 72 74 76 78 80 KW
59 29.3 23.6 25.4 27.2 29.1 30.0* 2.29
85 63 31.5 20.1 21.9 23.7 25.5 27.3 2.37
67 33.8 16.2 18.0 19.8 21.6 23.4 2.44 71 36.2 12.3 14.1 15.9 17.7 19.5 2.52
59 28.6 23.3 25.1 26.9 28.7* 29.4* 2.41
90 63 30.8 19.8 21.6 23.4 25.2 27.0 2.48
67 33.0 15.9 17.7 19.5 21.3 23.1 2.56 71 35.3 11.9 13.7 15.5 17.3 19.1 2.64
59 27.9 23.0 24.8 26.6 28.2* 28.8* 2.53
95 63 30.0 19.5 21.3 23.1 24.9 26.7 2.60
67 32.2 15.6 17.4 19.2 21.0 22.8 2.67 71 34.4 11.6 13.4 15.2 17.0 18.8 2.75
59 27.0 22.6 24.4 26.2 27.5* 28.1* 2.65
100 63 29.0 19.1 20.9 22.7 24.5 26.3 2.72
67 31.1 15.2 17.0 18.8 20.6 22.4 2.79 71 33.3 11.2 13.0 14.8 16.6 18.4 2.86
59 26.2 22.2 24.1 25.9 26.7* 27.4* 2.77
105 63 28.1 18.7 20.5 22.3 24.1 25.9 2.84
67 30.1 14.8 16.6 18.4 20.2 22.0 2.91 71 32.2 10.8 12.6 14.4 16.2 18.0 2.98
59 24.4 21.5 23.3 24.7* 25.3* 25.9* 3.02
115 63 26.2 17.9 19.7 21.5 23.3 25.1 3.08
67 28.1 14.0 15.8 17.6 19.4 21.2 3.14 71 30.0 10.0 11.8 13.6 15.4 17.2 3.20
WCC040FD00B AT 1325 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 72 74 76 78 80 KW
59 37.1 30.9 33.4 35.9 37.7* 38.6* 2.60
85 63 40.0 25.9 28.5 31.0 33.5 36.1 2.68
67 42.9 20.5 23.1 25.6 28.1 30.7 2.75 71 46.0 15.0 17.6 20.1 22.6 25.1 2.84
59 36.5 30.6 33.1 35.7 37.2* 38.1* 2.73
90 63 39.3 25.7 28.2 30.7 33.3 35.8 2.81
67 42.2 20.3 22.8 25.3 27.9 30.4 2.89 71 45.2 14.8 17.3 19.8 22.4 24.9 2.97
59 35.9 30.4 32.9 35.4 36.7* 37.6* 2.87
95 63 38.6 25.4 28.0 30.5 33.0 35.5 2.95
67 41.5 20.0 22.5 25.1 27.6 30.1 3.02 71 44.5 14.5 17.0 19.6 22.1 24.6 3.10
59 34.9 29.9 32.5 35.0* 35.9* 36.8* 3.01
100 63 37.6 25.0 27.5 30.1 32.6 35.1 3.09
67 40.4 19.6 22.1 24.7 27.2 29.7 3.16 71 43.2 14.1 16.6 19.1 21.7 24.2 3.24
59 33.9 29.5 32.1 34.2* 35.1* 35.9* 3.16
105 63 36.5 24.6 27.1 29.6 32.2 34.7 3.23
67 39.2 19.2 21.7 24.2 26.8 29.3 3.30 71 42.0 13.7 16.2 18.7 21.3 23.8 3.37
59 32.0 28.7 31.3 32.6* 33.4* 34.2* 3.45
115 63 34.4 23.8 26.3 28.8 31.3 33.9 3.51
67 37.0 18.4 20.9 23.4 25.9 28.5 3.57 71 39.6 12.8 15.4 17.9 20.4 22.9 3.64
WCC030FD00B AT 1000 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
CORRECTION FA CTORS - OTHER AIRFLOWS
AIRFLOW 875 1125 TOTAL CAP. X0.98 X1.02 SENS. CAP. X0.94 X1.05 COMPR. KW X0.99 X1.01
GROSS CAPACITY = 32200 BTUH
AIRFLOW = 1000 CFM COMPRESSOR POWER = 2673 W ATTS I.D. FAN POWER = 340 WATTS O.D . FAN POWER = 250 WATTS E.E.R. = 9.50 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAP ACITY) TOTAL CAP ACITY,COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
AIRFLOW 1150 1500 TOTAL CAP. X0.98 X1.01 SENS. CAP. X0.94 X1.06 COMPR. KW X0.98 X1.02
GROSS CAPACITY = 41600 BTUH
AIRFLOW = 1325 CFM COMPRESSOR POWER = 3022 W ATTS I.D. FAN POWER = 560 WATTS O.D . FAN POWER = 500 WATTS E.E.R. = 9.70 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAP ACITY) TOTAL CAP ACITY,COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
(MULTIPLY OR ADD AS INDICATED)
VALUES AT 95/80/67 RATING CONDITIONS
SUCT. AND 3/8 LIQUID LINE
CORRECTION FA CTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
VALUES AT 95/80/67 RATING CONDITIONS
SUCT. AND 3/8 LIQUID LINE
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
WCC050FD00B AT 1675 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
D.B. W.B. CAP. 72 74 76 78 80 KW
59 47.9 40.4 43.6 46.9 48.7* 49.9* 4.22
85 63 51.3 34.0 37.3 40.5 43.7 47.0 4.35
67 55.0 27.0 30.3 33.5 36.8 40.0 4.48 71 58.8 19.9 23.2 26.4 29.6 32.9 4.61
59 47.3 40.2 43.4 46.7 48.3* 49.4* 4.17
90 63 50.8 33.8 37.1 40.3 43.5 46.8 4.29
67 54.5 26.8 30.1 33.3 36.5 39.8 4.41 71 58.2 19.7 23.0 26.2 29.4 32.7 4.54
59 46.9 40.0 43.2 46.4 47.9* 49.0* 4.11
95 63 50.3 33.6 36.9 40.1 43.3 46.6 4.22
67 53.9 26.6 29.9 33.1 36.3 39.6 4.34 71 57.7 19.5 22.8 26.0 29.2 32.5 4.46
59 45.1 39.2 42.4 45.3* 46.5* 47.6* 4.28
100 63 48.5 32.8 36.1 39.3 42.6 45.8 4.39
67 51.9 25.9 29.1 32.3 35.6 38.8 4.51 71 55.6 18.8 22.0 25.2 28.5 31.7 4.63
59 43.4 38.4 41.7 44.0* 45.0* 46.1* 4.46
105 63 46.6 32.1 35.3 38.6 41.8 45.0 4.57
67 50.0 25.1 28.4 31.6 34.8 38.1 4.68 71 53.5 18.0 21.3 24.5 27.7 31.0 4.80
59 39.9 36.9 40.0* 41.1* 42.1* 43.1* 4.82
115 63 42.9 30.6 33.8 37.1 40.3 43.1* 4.92
67 46.0 23.6 26.9 30.1 33.3 36.6 5.03 71 49.3 16.6 19.8 23.0 26.3 29.5 5.13
CORRECTION FACTORS - OTHER AIRFLOWS
AIRFLOW 1450 1900 TOTAL CAP. X0.98 X1.01 SENS. CAP. X0.94 X1.06 COMPR. KW X0.99 X1.01
GROSS CAPACITY = 54000 BTUH
AIRFLOW = 1675 CFM COMPRESSOR POWER = 4339 W ATTS I.D. FAN POWER = 680 WATTS O.D . FAN POWER = 500 WATTS E.E.R. = 9.35 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAP ACITY) TOTAL CAP ACITY,COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
(MULTIPLY OR ADD AS INDICATED)
VALUES AT 95/80/67 RATING CONDITIONS
SUCT. AND 3/8 LIQUID LINE
10 IPB-99-7-EN-10-6-99
Performance Data Cooling Metric Units
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP . 22.2 23.3 24.4 25.6 26.7 KW
15.0 8.6 6.9 7.4 8.0 8.5 8.8* 2.3
29.4 17.2 9.2 5.9 6.4 6.9 7.5 8.0 2.4
19.4 9.9 4.7 5.3 5.8 6.3 6.9 2.4
21.7 10.6 3.6 4.1 4.7 5.2 5.7 2.5
15.0 8.4 6.8 7.4 7.9 8.4* 8.6* 2.4
32.2 17.2 9.0 5.8 6.3 6.9 7.4 7.9 2.5
19.4 9.7 4.7 5.2 5.7 6.2 6.8 2.6
21.7 10.3 3.5 4.0 4.5 5.1 5.6 2.6
15.0 8.2 6.7 7.3 7.8 8.3* 8.4* 2.5
35.0 17.2 8.8 5.7 6.2 6.8 7.3 7.8 2.6
19.4 9.4 4.6 5.1 5.6 6.2 6.7 2.7
21.7 10.1 3.4 3.9 4.5 5.0 5.5 2.8
15.0 7.9 6.6 7.1 7.7 8.1* 8.2* 2.7
37.8 17.2 8.5 5.6 6.1 6.7 7.2 7.7 2.7
19.4 9.1 4.5 5.0 5.5 6.0 6.6 2.8
21.7 9.8 3.3 3.8 4.3 4.9 5.4 2.9
15.0 7.7 6.5 7.1 7.6 7.8* 8.0* 2.8
40.6 17.2 8.2 5.5 6.0 6.5 7.1 7.6 2.8
19.4 8.8 4.3 4.9 5.4 5.9 6.4 2.9
21.7 9.4 3.2 3.7 4.2 4.7 5.3 3.0
15.0 7.1 6.3 6.8 7.2* 7.4* 7.6* 3.0
46.1 17.2 7.7 5.2 5.8 6.3 6.8 7.4 3.1
19.4 8.2 4.1 4.6 5.2 5.7 6.2 3.1
21.7 8.8 2.9 3.5 4.0 4.5 5.0 3.2
WCC040FD00B AT 2250 CMH (GROSS CAP ACITY IN KILOWATTS)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP . 22.2 23.3 24.4 25.6 26.7 KW
15.0 10.9 9.1 9.8 10.5 11.0* 11.3* 2.6
29.4 17.2 11.7 7.6 8.4 9.1 9.8 10.6 2.7
19.4 12.6 6.0 6.8 7.5 8.2 9.0 2.8
21.7 13.5 4.4 5.2 5.9 6.6 7.4 2.8
15.0 10.7 9.0 9.7 10.5 10.9* 11.2* 2.7
32.2 17.2 11.5 7.5 8.3 9.0 9.8 10.5 2.8
19.4 12.4 5.9 6.7 7.4 8.2 8.9 2.9
21.7 13.2 4.3 5.1 5.8 6.6 7.3 3.0
15.0 10.5 8.9 9.6 10.4 10.8* 11.0* 2.9
35.0 17.2 11.3 7.4 8.2 8.9 9.7 10.4 3.0
19.4 12.2 5.9 6.6 7.4 8.1 8.8 3.0
21.7 13.0 4.2 5.0 5.7 6.5 7.2 3.1
15.0 10.2 8.8 9.5 10.3* 10.5* 10.8* 3.0
37.8 17.2 11.0 7.3 8.1 8.8 9.6 10.3 3.1
19.4 11.8 5.7 6.5 7.2 8.0 8.7 3.2
21.7 12.7 4.1 4.9 5.6 6.4 7.1 3.2
15.0 9.9 8.6 9.4 10.0* 10.3* 10.5* 3.2
40.6 17.2 10.7 7.2 7.9 8.7 9.4 10.2 3.2
19.4 11.5 5.6 6.4 7.1 7.9 8.6 3.3
21.7 12.3 4.0 4.7 5.5 6.2 7.0 3.4
15.0 9.4 8.4 9.2 9.6* 9.8* 10.0* 3.5
46.1 17.2 10.1 7.0 7.7 8.4 9.2 9.9 3.5
19.4 10.8 5.4 6.1 6.9 7.6 8.4 3.6
21.7 11.6 3.8 4.5 5.2 6.0 6.7 3.6
WCC030FD00B AT 1698 CMH (GROSS CAP ACITY IN KILOWATTS)
CORRECTION FA CTORS - OTHER AIRFLOWS
AIRFLOW 1486 1910 TOTAL CAP. X0.98 X1.02 SENS. CAP. X0.94 X1.05 COMPR. KW X0.99 X1.01
GROSS CAP ACITY = 9435 KW
AIRFLOW = 1698 CMH COMPRESSOR POWER = 2673 W ATTS I.D. FAN POWER = 340 WATTS O.D . FAN POWER = 250 WATTS E.E.R. = 9.50 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN.
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAP ACITY) TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
AIRFLOW 1953 2547 TOTAL CAP. X0.98 X1.01 SENS. CAP. X0.94 X1.06 COMPR. KW X0.98 X1.02
GROSS CAP ACITY =12189 KW
AIRFLOW = 2250 CMH COMPRESSOR POWER = 3022 W ATTS I.D. FAN POWER = 560 WATTS O.D . FAN POWER = 500 WATTS E.E.R. = 9.70 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN.
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAP ACITY) TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
(MUL TIPLY OR ADD AS INDICATED)
VALUES AT ARI RATING CONDITIONS
SUCT. AND 3/8 IN. LIQUID LINES
CORRECTION FA CTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
VALUES AT ARI RATING CONDITIONS
SUCT. AND 3/8 IN. LIQUID LINES
O.D. I.D. TOTAL SENS. CAP. A T ENTERING D.B. TEMP. COMPR.
WCC050FD00B AT 2845 CMH (GROSS CAP ACITY IN KILOWATTS)
D.B. W.B. CAP . 22.2 23.3 24.4 25.6 26.7 KW
15.0 14.0 11.8 12.8 13.7 14.3* 14.6* 4.2
29.4 17.2 15.0 10.0 10.9 11.9 12.8 13.8 4.3
19.4 16.1 7.9 8.9 9.8 10.8 11.7 4.5
21.7 17.2 5.8 6.8 7.7 8.7 9.6 4.6
15.0 13.9 11.8 12.7 13.7 14.2* 14.5* 4.2
32.2 17.2 14.9 9.9 10.9 11.8 12.7 13.7 4.3
19.4 16.0 7.9 8.8 9.8 10.7 11.7 4.4
21.7 17.1 5.8 6.7 7.7 8.6 9.6 4.5
15.0 13.7 11.7 12.7 13.6 14.0* 14.4* 4.1
35.0 17.2 14.7 9.8 10.8 11.7 12.7 13.7 4.2
19.4 15.8 7.8 8.8 9.7 10.6 11.6 4.3
21.7 16.9 5.7 6.7 7.6 8.6 9.5 4.5
15.0 13.2 11.5 12.4 13.3* 13.6* 13.9* 4.3
37.8 17.2 14.2 9.6 10.6 11.5 12.5 13.4 4.4
19.4 15.2 7.6 8.5 9.5 10.4 11.4 4.5
21.7 16.3 5.5 6.4 7.4 8.4 9.3 4.6
15.0 12.7 11.3 12.2 12.9* 13.2* 13.5* 4.5
40.6 17.2 13.7 9.4 10.3 11.3 12.2 13.2 4.6
19.4 14.6 7.4 8.3 9.3 10.2 11.2 4.7
21.7 15.7 5.3 6.2 7.2 8.1 9.1 4.8
15.0 11.7 10.8 11.7* 12.0* 12.3* 12.6* 4.8
46.1 17.2 12.6 9.0 9.9 10.9 11.8 12.6* 4.9
19.4 13.5 6.9 7.9 8.8 9.8 10.7 5.0
21.7 14.4 4.9 5.8 6.7 7.7 8.6 5.1
IPB-99-7-EN-10-6-99 11
CORRECTION FA CTORS - OTHER AIRFLOWS
AIRFLOW 2462 3227 TOTAL CAP. X0.98 X1.01 SENS. CAP. X0.94 X1.06 COMPR. KW X0.99 X1.01
GROSS CAP ACITY =15822 KW
AIRFLOW = 2845 CMH COMPRESSOR POWER = 4339 W ATTS I.D. FAN POWER = 680 WATTS O.D . FAN POWER = 500 WATTS E.E.R. = 9.35 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN.
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAP ACITY) TOTAL CAPACITY,COMP. KW AND APP. DEW PT. ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
(MUL TIPLY OR ADD AS INDICATED)
VALUES AT ARI RATING CONDITIONS
SUCT. AND 3/8 IN. LIQUID LINES
Performance Data Heating English Units
O.D. HEA TING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP .
F . 60 70 75 80 60 70 75 80
-18 7.94 7.70 7.57 7.45 1.62 1.69 1.72 1.75
-13 9.10 8.83 8.69 8.55 1.70 1.77 1.81 1.84
-8 10.3 9.95 9.80 9.64 1.78 1.86 1.90 1.93
-3 11.4 11.1 10.9 10.7 1.86 1.94 1.98 2.02 2 12.6 12.2 12.0 11.8 1.94 2.03 2.07 2.12 7 13.8 13.3 13.1 12.9 2.02 2.11 2.16 2.21
12 14.9 14.5 14.2 14.0 2.10 2.20 2.25 2.30 17 16.1 15.6 15.4 15.1 2.18 2.29 2.34 2.39 22 18.0 17.4 17.2 16.9 2.26 2.37 2.42 2.47 27 19.9 19.3 19.0 18.7 2.34 2.45 2.50 2.56 32 21.8 21.1 20.8 20.4 2.41 2.53 2.59 2.65 37 23.7 22.9 22.6 22.2 2.49 2.61 2.67 2.73 42 25.5 24.8 24.4 24.0 2.57 2.69 2.76 2.82 47 30.5 29.6 29.1 28.7 2.66 2.79 2.85 2.91 52 32.9 31.9 31.4 30.9 2.73 2.87 2.94 3.00 57 35.4 34.3 33.7 33.2 2.81 2.95 3.02 3.09 62 37.8 36.6 36.0 35.4 2.89 3.04 3.11 3.18 67 40.2 38.9 38.3 37.7 2.97 3.12 3.19 3.27 72 42.6 41.3 40.6 39.9 3.05 3.20 3.28 3.35
WCC040FD00B AT 1325 CFM
O.D . HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
F . 60 70 75 80 60 70 75 80
-18 10.5 10.2 10.1 9.97 2.27 2.36 2.40 2.45
-13 12.1 11.7 11.6 11.4 2.35 2.45 2.49 2.54
-8 13.6 13.2 13.1 12.9 2.43 2.53 2.58 2.64
-3 15.1 14.7 14.5 14.3 2.51 2.62 2.67 2.73 2 16.6 16.2 16.0 15.8 2.58 2.70 2.76 2.82 7 18.2 17.7 17.5 17.3 2.66 2.79 2.85 2.91
12 19.7 19.2 19.0 18.7 2.74 2.87 2.94 3.01 17 21.2 20.7 20.4 20.2 2.82 2.96 3.03 3.10 22 23.8 23.2 22.9 22.6 2.93 3.07 3.15 3.22 27 26.4 25.8 25.4 25.1 3.04 3.19 3.26 3.34 32 29.0 28.3 27.9 27.5 3.14 3.30 3.38 3.46 37 31.6 30.8 30.4 30.0 3.25 3.42 3.50 3.58 42 34.2 33.3 32.9 32.4 3.36 3.53 3.62 3.70 47 40.5 39.4 38.9 38.3 3.48 3.66 3.75 3.84 52 43.7 42.5 41.9 41.4 3.59 3.78 3.87 3.96 57 46.9 45.6 45.0 44.4 3.70 3.89 3.99 4.09 62 50.1 48.8 48.1 47.4 3.81 4.01 4.11 4.21 67 53.3 51.9 51.2 50.4 3.92 4.13 4.23 4.33 72 56.5 55.0 54.2 53.5 4.03 4.24 4.35 4.46
WCC030FD00B AT 1000 CFM
CORRECTION FA CTORS - OTHER AIRFLOWS
(VALUE AT 1000 CFM TIMES CORR. F A CTOR
AIRFLOW 870 1130 HEATING CAP. X0.98 X1.02 COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
AIRFLOW = 1000 CFM
HEATING CAP. (HIGH TEMP.) = 29600 BTUH HEATING CAP. (LOW TEMP.) = 15600 BTUH
COMPR. POWER (HIGH TEMP.) = 2195 WATTS COMPR. POWER (LOW TEMP.) = 1695 WATTS COEFF. OF PERF. (HIGH TEMP.) = 3.12 COEFF. OF PERF. (LOW TEMP.) = 2.00 OUTDOOR FAN PO WER = 250 WATTS INDOOR FAN PO WER = 340 WATTS NOTE:RATED WITH 25 FEET OF 7/8
AIRFLOW 1153 1497 HEATING CAP. X0.98 X1.01 COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
AIRFLOW = 1325 CFM
HEATING CAP. (HIGH TEMP.) = 39400 BTUH HEATING CAP. (LOW TEMP.) = 20700 BTUH
COMPR. POWER (HIGH TEMP.) = 2600 WATTS COMPR. POWER (LOW TEMP.) = 1900 WATTS COEFF. OF PERF. (HIGH TEMP.) = 3.18 COEFF. OF PERF. (LOW TEMP.) = 2.06 OUTDOOR FAN PO WER = 500 WATTS INDOOR FAN PO WER = 560 WATTS NOTE:RATED WITH 25 FEET OF 7/8
= VALUE AT NEW AIRFLOW)
70&47/43 (HIGH TEMP. POINT) 70&17/15 (LOW TEMP. POINT)
SUCTION AND 3/8 LIQUID LINE
CORRECTION FA CTORS - OTHER AIRFLOWS
(VALUE AT 1325 CFM TIMES CORR. F A CTOR
= VALUE AT NEW AIRFLOW)
70&47/43 (HIGH TEMP. POINT) 70&17/15 (LOW TEMP. POINT)
SUCTION AND 3/8 LIQUID LINE
O.D . HEATING CAPACITY (BTUH/1000) AT TOTAL POWER IN KILOWATTS AT
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
F . 60 70 75 80 60 70 75 80
-18 14.3 13.9 13.8 13.6 2.94 3.06 3.12 3.18
-13 16.8 16.4 16.2 16.0 3.09 3.23 3.30 3.36
-8 19.4 18.9 18.7 18.4 3.25 3.40 3.47 3.55
-3 21.9 21.4 21.1 20.8 3.41 3.57 3.65 3.73 2 24.5 23.9 23.6 23.3 3.57 3.74 3.82 3.91 7 27.0 26.3 26.0 25.7 3.72 3.91 4.00 4.09
12 29.5 28.8 28.5 28.1 3.88 4.08 4.17 4.27 17 32.1 31.3 30.9 30.5 4.04 4.25 4.35 4.45 22 33.9 33.1 32.7 32.3 4.08 4.29 4.39 4.50 27 35.8 34.9 34.5 34.0 4.12 4.33 4.44 4.54 32 37.7 36.7 36.2 35.8 4.16 4.37 4.48 4.59 37 39.5 38.5 38.0 37.5 4.20 4.42 4.53 4.63 42 41.4 40.3 39.8 39.3 4.24 4.46 4.57 4.68 47 55.0 53.6 52.9 52.2 4.69 4.94 5.06 5.19 52 58.8 57.3 56.6 55.8 4.80 5.06 5.18 5.31 57 62.6 61.0 60.2 59.4 4.91 5.17 5.30 5.43 62 66.5 64.8 63.9 63.0 5.02 5.29 5.42 5.55 67 70.3 68.5 67.6 66.7 5.13 5.40 5.54 5.68 72 74.1 72.2 71.2 70.3 5.24 5.52 5.66 5.80
WCC050FD00B AT 1675 CFM
12 IPB-99-7-EN-10-6-99
CORRECTION FA CTORS - OTHER AIRFLOWS
(VALUE AT 1675 CFM TIMES CORR. F A CTOR
AIRFLOW 1457 1893 HEATING CAP. X0.99 X1.01 COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
AIRFLOW = 1675 CFM
HEATING CAP. (HIGH TEMP.) = 53600 BTUH HEATING CAP. (LOW TEMP.) = 31300 BTUH
COMPR. POWER (HIGH TEMP.) = 3760 WATTS COMPR. POWER (LOW TEMP.) = 3065 WATTS COEFF. OF PERF. (HIGH TEMP.) = 3.18 COEFF. OF PERF. (LOW TEMP.) = 2.16 OUTDOOR FAN PO WER = 500 WATTS INDOOR FAN PO WER = 680 WATTS NOTE:RATED WITH 25 FEET OF 7/8
= VALUE AT NEW AIRFLOW)
70&47/43 (HIGH TEMP. POINT) 70&17/15 (LOW TEMP. POINT)
SUCTION AND 3/8 LIQUID LINE
Performance Data Heating Metric Units
O.D . HEATING CAP A CITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DR Y B ULB TEMP.
C. 23.3 31.7 35.8 40.0 23.3 31.7 35.8 40.0
-27.8 2.33 2.26 2.22 2.18 1.62 1.69 1.72 1.75
-25.0 2.67 2.59 2.55 2.51 1.70 1.77 1.81 1.84
-22.2 3.02 2.92 2.87 2.82 1.78 1.86 1.90 1.93
-19.4 3.34 3.25 3.19 3.14 1.86 1.94 1.98 2.02
-16.7 3.69 3.57 3.52 3.46 1.94 2.03 2.07 2.12
-13.9 4.04 3.90 3.84 3.78 2.02 2.11 2.16 2.21
-11.1 4.37 4.25 4.16 4.10 2.10 2.20 2.25 2.30
-8.3 4.72 4.57 4.51 4.42 2.18 2.29 2.34 2.39
-5.6 5.27 5.10 5.04 4.95 2.26 2.37 2.42 2.47
-2.8 5.83 5.65 5.57 5.48 2.34 2.45 2.50 2.56
0.0 6.39 6.18 6.09 5.98 2.41 2.53 2.59 2.65
2.8 6.94 6.71 6.62 6.50 2.49 2.61 2.67 2.73
5.6 7.47 7.27 7.15 7.03 2.57 2.69 2.76 2.82
8.3 8.94 8.67 8.53 8.41 2.66 2.79 2.85 2.91
11.1 9.64 9.35 9.20 9.05 2.73 2.87 2.94 3.00
13.9 10.37 10.05 9.87 9.73 2.81 2.95 3.02 3.09
16.7 11.08 10.72 10.55 10.37 2.89 3.04 3.11 3.18
19.4 11.78 11.40 11.22 11.05 2.97 3.12 3.19 3.27
22.2 12.48 12.10 11.90 11.69 3.05 3.20 3.28 3.35
WCC040FD00B AT 0.63 CUBIC METERS/SEC
O.D. HEATING CAP A CITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP .
C. 23.3 31.7 35.8 40.0 23.3 31.7 35.8 40.0
-27.8 3.08 2.99 2.96 2.92 2.27 2.36 2.40 2.45
-25.0 3.55 3.43 3.40 3.34 2.35 2.45 2.49 2.54
-22.2 3.98 3.87 3.84 3.78 2.43 2.53 2.58 2.64
-19.4 4.42 4.31 4.25 4.19 2.51 2.62 2.67 2.73
-16.7 4.86 4.75 4.69 4.63 2.58 2.70 2.76 2.82
-13.9 5.33 5.19 5.13 5.07 2.66 2.79 2.85 2.91
-11.1 5.77 5.63 5.57 5.48 2.74 2.87 2.94 3.01
-8.3 6.21 6.07 5.98 5.92 2.82 2.96 3.03 3.10
-5.6 6.97 6.80 6.71 6.62 2.93 3.07 3.15 3.22
-2.8 7.74 7.56 7.44 7.35 3.04 3.19 3.26 3.34
0.0 8.50 8.29 8.17 8.06 3.14 3.30 3.38 3.46
2.8 9.26 9.02 8.91 8.79 3.25 3.42 3.50 3.58
5.6 10.02 9.76 9.64 9.49 3.36 3.53 3.62 3.70
8.3 11.87 11.54 11.40 11.22 3.48 3.66 3.75 3.84
11.1 12.80 12.45 12.28 12.13 3.59 3.78 3.87 3.96
13.9 13.74 13.36 13.18 13.01 3.70 3.89 3.99 4.09
16.7 14.68 14.30 14.09 13.89 3.81 4.01 4.11 4.21
19.4 15.62 15.21 15.00 14.77 3.92 4.13 4.23 4.33
22.2 16.55 16.11 15.88 15.68 4.03 4.24 4.35 4.46
WCC030FD00B AT 0.47 CUBIC METERS/SEC
CORRECTION FA CTORS - OTHER AIRFLOWS
(VALUE AT 0.47 CMS TIMES CORR. F A CTOR
AIRFLOW 0.41 0.53 HEATING CAP. X0.98 X1.02 COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
AIRFLOW = 0.47 CMS
HEATING CAP. (HIGH TEMP.) = 8.67 KILOWATTS HEATING CAP. (LOW TEMP.) = 4.57 KILOWA TTS
COMPR. POWER (HIGH TEMP.) = 2195 WATTS COMPR. POWER (LO W TEMP.) = 1695 W ATTS COEFF. OF PERF. (HIGH TEMP.) = 3.12 COEFF. OF PERF. (LOW TEMP.) = 2.00 OUTDOOR FAN PO WER = 250 WATTS INDOOR FAN PO WER = 340 WATTS NOTE:RATED WITH 7.62 METERS OF 7/8
AIRFLOW 0.54 0.71 HEATING CAP. X0.98 X1.01 COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
AIRFLOW = 0.63 CMS
HEA TING CAP . (HIGH TEMP .) = 11.55 KILO WA TTS HEA TING CAP . (LO W TEMP.) = 6.07 KILOWA TTS
COMPR. POWER (HIGH TEMP.) = 2600 WATTS COMPR. POWER (LO W TEMP.) = 1900 W ATTS COEFF. OF PERF. (HIGH TEMP.) = 3.18 COEFF. OF PERF. (LOW TEMP.) = 2.06 OUTDOOR FAN PO WER = 500 WATTS INDOOR FAN PO WER = 560 WATTS NOTE:RATED WITH 7.62 METERS OF 7/8
= VALUE AT NEW AIRFLOW)
21&8/6 (HIGH TEMP. POINT) 21&(-8)/(-9) (LOW TEMP. POINT)
SUCTION AND 3/8 LIQUID LINE
CORRECTION FA CTORS - OTHER AIRFLOWS
(VALUE AT 0.63 CMS TIMES CORR. F A CTOR
= VALUE AT NEW AIRFLOW)
21&8/6 (HIGH TEMP. POINT) 21&(-8)/(-9) (LOW TEMP. POINT)
SUCTION AND 3/8 LIQUID LINE
O.D. HEA TING CAP A CITY IN KILOW A TTS A T TOTAL PO WER IN KILOW A TTS A T
TEMP . INDICA TED INDOOR DR Y BULB TEMP . INDICATED INDOOR DRY BULB TEMP .
C. 23.3 31.7 35.8 40.0 23.3 31.7 35.8 40.0
-27.8 4.19 4.07 4.04 3.98 2.94 3.06 3.12 3.18
-25.0 4.92 4.81 4.75 4.69 3.09 3.23 3.30 3.36
-22.2 5.68 5.54 5.48 5.39 3.25 3.40 3.47 3.55
-19.4 6.42 6.27 6.18 6.09 3.41 3.57 3.65 3.73
-16.7 7.18 7.00 6.91 6.83 3.57 3.74 3.82 3.91
-13.9 7.91 7.71 7.62 7.53 3.72 3.91 4.00 4.09
-11.1 8.64 8.44 8.35 8.23 3.88 4.08 4.17 4.27
-8.3 9.41 9.17 9.05 8.94 4.04 4.25 4.35 4.45
-5.6 9.93 9.70 9.58 9.46 4.08 4.29 4.39 4.50
-2.8 10.49 10.23 10.11 9.96 4.12 4.33 4.44 4.54
0.0 11.05 10.75 10.61 10.49 4.16 4.37 4.48 4.59
2.8 11.57 11.28 11.13 10.99 4.20 4.42 4.53 4.63
5.6 12.13 11.81 11.66 11.51 4.24 4.46 4.57 4.68
8.3 16.11 15.70 15.50 15.29 4.69 4.94 5.06 5.19
11.1 17.23 16.79 16.58 16.35 4.80 5.06 5.18 5.31
13.9 18.34 17.87 17.64 17.40 4.91 5.17 5.30 5.43
16.7 19.48 18.99 18.72 18.46 5.02 5.29 5.42 5.55
19.4 20.60 20.07 19.81 19.54 5.13 5.40 5.54 5.68
22.2 21.71 21.15 20.86 20.60 5.24 5.52 5.66 5.80
IPB-99-7-EN-10-6-99 13
WCC050FD00B A T 0.79 CUBIC METERS/SEC
CORRECTION FA CTORS - O THER AIRFLOWS
(VALUE AT 0.79 CMS TIMES CORR. F ACT OR
AIRFLOW 0.69 0.89 HEATING CAP. X0.99 X1.01 COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
21&8/6 (HIGH TEMP. POINT) 21&(-8)/(-9) (LOW TEMP. POINT)
AIRFLOW = 0.79 CMS
HEA TING CAP . (HIGH TEMP .) = 15.71 KILO WA TTS HEA TING CAP . (LO W TEMP.) = 9.17 KILOWA TTS
COMPR. POWER (HIGH TEMP.) = 3760 WATTS COMPR. POWER (LO W TEMP.) = 3065 W ATTS COEFF. OF PERF. (HIGH TEMP.) = 3.18 COEFF. OF PERF. (LOW TEMP.) = 2.16 OUTDOOR FAN PO WER = 500 WATTS INDOOR FAN PO WER = 680 WATTS NOTE:RATED WITH 7.62 METERS OF 7/8
= V ALUE A T NEW AIRFLO W)
SUCTION AND 3/8 LIQUID LINE
Performance Data
Indoor Blower Performances WCC030FD
Air Flow
CFM (CMH)
[2]
750 (1270) 0.58 (145) 220 0.17 0.43 (107) 218 0.17 790 (1335) 0.56 (140) 227 0.17 0.39 (97) 225 0.18 830 (1400) 0.53 (132) 234 0.18 0.34 (85) 231 0. 19 880 (1490) 0.50 (125) 241 0.1 9 0.28 (70) 239 0.20 920 (1554) 0.47 (117) 247 0.20 0.20 (50) 247 0.21
960 (1622) 0.44 (110) 254 0.20 0.10 (25) 254 — 1000 (1690) 0.40 (100) 260 0.21 — 1040 (1757) 0.36 ( 90) 267 0.21 — 1080 (1825) 0.32 (80) 274 0.22 — 1130 (1910) 0.26 (65) 281 0.23 — 1170 (1977) 0.21 (52) 287 0.24 — 1210 (2045) 0.13 (32) 293 0.24 — 1250 (2112) 0.05 (12) 300 0.25
High Speed [1] Low Speed
Press IN.
W.G.
(PA)
PWR
Watts
BHP
Press IN. W.G. (PA)
PWR
Watts
BHP
——————— ——————— ——————— ——————— ——————— ——————
[1] Factory setting at HI speed [2] Wet coil, no filter, no heater
Indoor Blower Performances WCC050FD
Air Flow
CFM (CMH)
[2]
1170 (1980) 0.73 (184) 431 0. 33 0.60 (150) 414 0.29 1210 (2050) 0.70 (175) 440 0.34 0. 55 ( 137) 423 0.29 1250 (2120) 0.67 (167) 450 0.35 0. 51 ( 127) 432 0.29 1290 (2180) 0.65 (163) 459 0.36 0. 47 ( 117) 442 0.28 1330 (2250) 0.63 (157) 469 0.38 0. 42 ( 105) 451 0.28 1380 (2340) 0.59 (148) 478 0.39 0.39 (97) 460 0.27 1420 (2400) 0.56 (140) 488 0.40 0.35 (87) 469 0.27 1460 (2470) 0.53 (132) 498 0.41 0.31 (77) 479 0.27 1500 (2540) 0.51 (127) 508 0.42 0.28 (70) 488 0.2 6 1540 (2600) 0.48 (120) 519 0.43 0.24 (60) 497 0.2 5 1580 (2670) 0.44 (110) 530 0.44 0.21 (52) 506 0.2 5 1630 (2760) 0.40 (100) 541 0.45 0.17 (42) 516 0.24 1670 (2830) 0.37 (92) 552 0.46 0.14 (35) 525 0.23 1710 (2890) 0.33 (83) 563 0.47 0.10 (25) 534 0.23 1750 (2960) 0.28 (70) 575 0.47 0.07 (17) 544 0.23 1790 (3025) 0.24 (60) 588 0.48 — 1830 (3090) 0.19 (45) 601 0.49 — 1880 (3180) 0.15 (37) 608 0.49 — 1920 (3250) 0.11 (27) 620 0.50 — 1960 (3315) 0.07 (17) 631 0.52
[1] Factory setting at HI speed [2] Wet coil, no filter, no heater
High Speed [1] Low Speed
Press IN. W.G. (PA)
PWR
Watts
BHP
Press IN. W.G. (PA)
PWR
Watts
BHP
Indoor Blower Performances WCC040FD
Air Flow
CFM (CMH)
[3]
1000 (1690) 0.69 (172) 356 0.27 1040 (1757) 0.67 (167) 365 0.27 1080 (1825) 0.64 (160) 373 0.28 1130 (1910) 0.60 (150) 381 0.28 1170 (1977) 0.73 (183) 431 0.3 3 0. 57 ( 142) 389 0.29 1210 (2045) 0.70 (175) 440 0.34 0.5 3 (1 32) 398 0.29 1250 (2112) 0.67 (167) 450 0.35 0.4 9 (1 22) 40 7 0.29 1290 (2180) 0.65 (162) 459 0.36 0.4 5 (1 12) 41 7 0.29 1330 (2247) 0.63 (157) 469 0.38 0.4 0 (1 00) 42 7 0.29 1380 (2332) 0.59 (147) 478 0.39 0.35 (87) 437 0.28 1420 (2400) 0.56 (140) 488 0.40 0.28 (70) 448 0.28 1460 (2467) 0.53 (132) 498 0.41 0.19 (47) 463 0.26 1500 (2535) 0.50 (125) 508 0.42 0.10 (25) 479 0.24 1540 (2602) 0.47 (117) 518 0.43 0.01 (2.5) 49 5 0.23 1580 (2670) 0.44 (110) 528 0.44 — 1630 (2755) 0.41 (102) 537 0.45 — 1670 (2825) 0.38 (95) 547 0.46 — 1710 (2890) 0.35 (87) 557 0.47
1750 (2958) [2] 0.31 (77) 567 0.48
[1] Factory setting at LO speed [2] Water Blow Off Unit
High Speed Low Speed [1]
Press IN.
W.G.
(PA)
PWR
BHP
Watts
[3] Wet coil, no filter, no heater
Press IN.
W.G. (PA )
PWR
Watts
BHP
14 IPB-99-7-EN-10-6-99
Optional Equipment
25% Manual Fresh Air Kit
T ypical Filter Frame
IPB-99-7-EN-10-6-99 15
Optional Equipment
Economizer and Rain Hood
(Downflow Applications)
ALL DIMENSIONS ARE IN INCHES (MM)
Thermostats
Two stages heating/cooling or one stage heating/cooling thermostats are available in either manual or automatic changeover.
Programmable Electronic Night Setback Thermostat
Heating setback and cooling setup with 7-day, 5-1-1 programming capability. Available in 2 heating/cooling or 1 heating/cooling versions with automatic changeover.
ECONOMIZER
MODEL
BA YEC ON054B WCC030F
BA YEC ON055B
APPLICATION
MODELS
WCC040F WCC050F20(500)21(533)26(660)
ABC D E FGH
20
16-5/8
(500)
(420)
Controls
Field Installed Control Options
Economizer Controls
The standard equipment offering is a fixed dry bulb changeover control. In addition to the standard offering, there are two other field installed control accessories.
Enthalpy Control
Replaces the dry bulb control with a solid state dry bulb and wet bulb changeover controller which has a fully adjustable set point. Enthalpy control offers a higher level of
23-1/2
22-9/16
(600)
energy savings potential than the standard dry bulb control due to the additional wet bulb sensing capability.
Differential Enthalpy
Replaces the standard dry bulb control with two enthalpy sensors that compare total heat content of the indoor air and outdoor air to determine the most efficient entering air source. This control option offers the highest level of energy efficiency available.
(575)
OMIT
8-5/8
22-1/4
(565)
26-1/8
(670)
25-1/8
(640)
32-1/8
(820)
(220)
12-1/8
(315)
From Dwg. 21D662389 Rev.1
1-1/2
(38)
1-3/4
(45)
16 IPB-99-7-EN-10-6-99
Field Wiring
WCC-F Heat Pump Models
NOTES:
1. FUSED DISCONNECT SIZE, POWER WIRING AND GROUNDING OF EQUIPMENT MUST COMPLY WITH CODES.
2. BE SURE POWER SUPPLY AGREES WITH EQUIPMENT AND HEATER NAMEPLATE.
3. LOW VOLTAGE WIRING TO BE 18 AWG MINIMUM CONDUCTOR.
4. SEE HEATER NAMEPLATE FOR CURRENT RATING OF HEATER USED.
5. SEE UNIT AND HEATER DIAGRAM FOR ELECTRICAL CONNECTION DETAILS.
6. IF ELECTRIC HEATER ACCESSORY IS NOT INSTALLED OMIT THE ELECTRIC HEATER, ASSOCIATED POWER WIRES AND THE ‘W’ AND ‘X2’ THERMOSTAT WIRES.
7. FIG. 3 DEMONSTRATES CONNECTION OF THE OUTDOOR THERMOSTAT ACCESSORY ONLY. FOR FURTHER UNIT CONNECTION DETAILS REFER TO THE OTHER FIGURES.
8. THE 41A(BR) WIRE IS FIRST STAGE ELECTRIC HEAT. IF THE ELECTRIC HEATER ACCESSORY HAS TWO HEATING STAGES THE 41C(BR) WIRE IS SECOND STAGE ELECTRIC HEAT.
9. WHEN THE BAYECON054A OR –055A ECONOMIZER IS INSTALLED THE BAYRLAY003 RELAY ACCESSORY KIT IS REQUIRED TO INTERFACE THE ECONOMIZER TO THE HEAT PUMP FOR PROPER SYSTEM OPERATION. WHEN THE BAYECON054B OR –055B OR 073A ECONOMIZER IS INSTALLED, THE BAYRLAY004A RELAY ACCESSORY KIT IS REQUIRED TO INTERFACE THE ECONOMIZER TO THE HEAT PUMP FOR PROPER SYSTEM OPERATION.
10. THE BAYSTAT033A OUTDOOR THERMOSTAT ACCESSORY KIT CONTAINS A THERMOSTAT AND A RELAY. THE RELAY IS NOT REQUIRED TO BE USED IN THIS APPLICATION.
IPB-99-7-EN-10-6-99 17
From Dwg. 21D756978
Field Wiring
Wiring Diagram for WCC030,040,050FD00B Units
continued on next page
18 IPB-99-7-EN-10-6-99
From Dwg. 21D756914 P03
Field Wiring
Wiring Diagram for WCC030,040,050FD00B Units
IPB-99-7-EN-10-6-99 19
From Dwg. 21D756914 P03
Dimensions
BAYCURB030A Roof Curb Outline With WCC030F Units
ALL DIMENSIONS ARE IN INCHES (MM)
MODEL NO.
WCC030F
WCC040F WCC050F
All dimensions are in inches (mm).
AIR DUCT
OPENINGS
SUPPLY 21 (533) 16-3/4 ( 425)
RETURN 21 (533) 21-1/8 (540)
SUPPLY 21 (533) 19 (483)
RETURN 21 (533) 22-1/8 (565)
Required Clearance for Unit Installation and Roof Penetration Hole Size Required
INSULATED DECK PANS ARE INCLUDED WITH THE BAYCURB038A ONLY.
34
(865)
21
(533)
1
(38)
1
/
(790)
2
31
1
(38)
1
(38)
1
/
2
1
/
2
ABCD
ALL DIMENSIONS ARE IN INCHES (MM)
A
SUPPLY
1
/
4
(108)
1
53
/
(1350)
1
/
8
50
(1275)
B
D
RETURN
2
1
1
(38)
C
/
2
1
/
1
(38)
8
(38)
2
1
1
/
2
This member used on WCC030F models only
8
(200)
1
/
2
1
(38)
34
(865)
8
(222)
13
/16
(2.1)
14
3
/4
(355)
11/4
(32)
From Dwg. 21C729942
SERVICE CLEARANCE & PENETRATION DIMENSIONS
MODEL NO. A B C D E F
42"
30"
*12"
30"
WCC030F WCC040F
WCC050F
* 18" (457) WITH 25% FRESH AIR ACCESSORY 30" (762) WITH ECONOMIZER
(1067)
42"
(1067)
(762)
30"
(762)
(305)
*12"
(305)
(762)
36"
(915)
44"
(1117)
50"
(1270)
25"
(635)
25"
(635)
From Dwg. 21C662039
20 IPB-99-7-EN-10-6-99
BAYCURB034A Roof Curb Outline With WCC040,050F Units
MODEL NO.
WCC040F WCC050F
All dimensions are in inches (mm).
AIR DUCT
OPENINGS
SUPPLY
RETURN
ABC
21
(533)19(482)
21
(533)
22-1/8
(565)
Dimensions
ALL DIMENSIONS ARE IN INCHES (MM)
1
1
/
11/
(38)
2
(32)
A
SUPPLY
4
43
(1090)
12
(305)
1
62
/
16
(1575)
11/
2
(38)
1
/2 (114)
A
RETURN
13
/
16
(21)
4
C
B
11/
2
(38)
7
17
(450)
40
(1015)
/
8
1
/
1
(38)
1
(38)
From Dwg. 21C662034
14
(355)
2
1
/
2
Required Clearance for Unit Installation and Roof Penetration Hole Size Required
SERVICE CLEARANCE DIMENSIONS
MODEL NO. A B C D
WCC040F WCC050F
* 18" (457) WITH 25% FRESH AIR ACCESSORY 30" (762) WITH ECONOMIZER
42"
(1070)
30"
(815)
*6"
(150)
36"
(915)
ALL DIMENSIONS ARE IN INCHES (MM)
50"
(1270)
25"
(635)
From Dwg. 21C662039
IPB-99-7-EN-10-6-99 21
Dimensions
Field Fabricated (Side X Side) Ducts — WCC030-050F Units
Installed from Above Mounting Curb
ALL DIMENSIONS ARE IN INCHES (MM)
P.V .C. Rubber Gasket Position on B AYCURB030A for Unit Placement — WCC030-050F Units
NOTES:
1. OVERLAP AND POSITION JOINTS IN P.V.C. RUBBER GASKET.
2. AIR SEALS – APPLY P.V.C. RUBBER LAST TO INSURE THERE IS ADEQUATE P.V.C. FOR THE WATER SEAL.
3. USE TYPICAL SEALING METHODS TO PREVENT AIR DUCT LEAKAGE AT CURB-DUCT JOINT.
ALL DIMENSIONS ARE IN INCHES (MM)
22 IPB-99-7-EN-10-6-99
Dimensions
WCC030-050F OUTLINE DRA WING — Fr ont
ALL DIMENSIONS ARE IN INCHES (MM)
CABINET
SIZE
"B"
"D"
"D"
IPB-99-7-EN-10-6-99 23
MODEL BAYCURB "A" "B" "C" "D" "E" "F" "G" "H"
WCC030F 030A WCC040F
WCC050F WCC040F
WCC050F
030A 034A
14-1/8
(360)
14-13/16
(380)
14-13/16
(380)
16-5/8
(425)36(915)34(865)
21
(535)45(1145)34(865)
21
(533)45(1145)43(1092)
29-3/16
(740)
33-3/8
(850)
33-3/8
(850)
13-3/4
(350)
13-3/4
(350)
13-3/4
(350)
——
10-1/8
(261)
——
From Dwg. 21D661772
9-7/8 (251)
Dimensions
WCC030-050F OUTLINE DRA WING — Fr ont
ALL DIMENSIONS ARE IN INCHES (MM)
MODELABCDE F
WCC030F WCC040F
WCC050F
55-1/4 (1405)
64-5/16
(1634)45(1145)
36
(915)
29-3/16
(740)
33-3/8
(850)
12-15/16
(330)
14-13/16
(375)
4-7/8 (122)
4-7/8 (122)
24 IPB-99-7-EN-10-6-99
KNOCKOUTS FOR 3/4" (20) AND 1-1/4" (32 ) CONDUI T
KNOCKOUTS FOR 3/4" (20) AND 1-1/2" (38 ) CONDUI T
From Dwg. 21D729945 Rev. 5
13/8
(35)
Dimensions
WCC030-050F OUTLINE DRAWING — Rear
ALL DIMENSIONS ARE IN INCHES (MM)
MODEL
WCC030F WCC040F WCC050F
1
/4 (6)
1
/2 (12)
CORNER WEIGHT LBS (KG)
W1 W2 W3 W4
94
(43)73(33)80(36) 126
104
(57)
(47)
131
108
(59)
(49)
127 (58)
132 (60)
104 (47)
153 (70)
159 (72)
UNIT
WEIGHT
LBS (KG)
318
(144)
486
(220)
504
(229)
11/8
(30)
CONDENSATE DRAIN FOR 3/4" (19) FEMALE NPT
3 (75)
3
/4 (19)
5
(16)
/8
3
(19)
/4
ABC D E F G H J K LMNP
55-1/4 (1400)36(915)
64-5/16
(1634)45(1145)
29-3/16
(750)
33-3/8
(846)
18-9/16
(470)
21-1/16
(535)
11-1/16
(280)
15-1/16
(385)
6-9/16
(170)
4-15/16
(120)
6-13/16
(170)17(430)
9-1/8
21-15/16
(230)
(550)
18-13/16
(465)24(610)
24-3/4
(628)29(736)
24-3/4
(628)29(736)
17-1/2
(445)10(250)3(75)
20
(500)14(350)
3-1/2
(90)
4-7/16
(115)
8-5/16
(210)
From Dwg. 21D729988 Rev. 10
IPB-99-7-EN-10-6-99 25
Mechanical Specification Options
General
The units shall be horizontal airflow as shipped and convertible to downflow. All units shall be factory assembled, piped, internally wired and fully charged with R-22. Units shall be UL listed and carry a UL label. All units shall be factory run tested to check cooling operation, fan and blower rotation and control sequence. Units shall be designed to operate at ambient temperatures between 115°F and 55°F in cooling as manufactured. Cooling performance shall be rated in accordance with ARI standards.
Unit Casing
All components shall be mounted in a weather-resistant steel cabinet with an enamel finish. Access panels shall be provided for unit controls and indoor coil and fans. Indoor air section compartment shall be completely insulated with fireproof, perma­nent, odorless glass fiber material. Knockouts shall be provided for utility and control connections. Drain connections shall be provided to accommodate indoor water runoff.
Compressor
The compressor shall be a hermetically sealed, high efficiency Climatuff® compressor. Internal overcurrent and over temperature protection, internal pressure relief shall be standard. Crankcase heaters shall be standard on all three phase models.
Refrigeration System
All units shall have capillary tube refrigerant control. Service pressure tap ports, and a refrigerant line filter dryer shall be standard.
Indoor and Outdoor Coils
Coils shall be internally finned or smooth bore 3/8" copper tubes mechanically bonded to configured aluminum plate fin as standard. Evaporator coil leak and pressure tested to 200 psig; condenser coil tested to 450 psig.
Indoor Fan
The indoor fan shall be a forward curved, centrifugal-type fan with a multiple-speed, direct drive motor. Motor is permanently lubricated and shall have built-in overload protection.
Outdoor Fan
One, direct-drive, statically and dynamically balanced propeller fan shall be used in a draw-through vertical discharge configuration. Permanently lubricated weather proof motor shall have built-in thermal overload protection.
System Controls
System controls include condenser fan, evaporator fan and compressor contactors.
Accessories Roof Curb — The roof curb shall be designed
to mate with the unit and provide support and complete weathertight installation when properly installed. Adhesive back polyure­thane sealing strips shall be provided to ensure an airtight seal between supply and return openings of the curb and unit. The roof curb design allows field fabricated ductwork to be connected directly to the curb. Curb ships knocked down for field assembly, and includes factory-installed wood nailer strips.
Fully Modulating Economizer — This accessory shall be field installed and be composed of the following items: 0-100% fresh air damper, damper drive motor, fixed dry bulb enthalpy control, and low voltage pigtails for electrical connections. Solid state enthalpy or differential enthalpy control is optional. Economizer operations shall be controlled by the preset position of the enthalpy control. A barometric relief damper shall be standard with the economizer and provide a pressure operated damper that shall be gravity closing and prohibit entrance of outside air on equipment “off” cycle.
Manual Outside Air Dampers — Rain hood and screen shall be field installed. Suitable for up to 25% outside air.
Anti-Short Cycle Timer — Timed off device that ensures a minimum of five minutes off between compressor cycles.
Control Options Standard Indoor Thermostats — T wo stage
heating/cooling or one stage heating/cooling thermostats shall be available in either manual or automatic changeover.
Programmable Electronic Night Setback Thermostat — Programmable electronic
thermostat shall provide heating setback and cooling setup with 7-day, programming capability. 1H/1C or 2H/2C models available.
26 IPB-99-7-EN-10-6-99
Notes
IPB-99-7-EN-10-6-99 27
The Trane Company
Trane International Unitary Systems 1789 Chaussée de Wa vre 1160 Brussels Belgium www.trane.com
An American Standard Company
File Number P.I. Supersedes Stocking Location
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design and specifications without notice.
IPB-99-7-EN-10-6-99 IPB-92-6 P.I.-L